These publications can help you install the air
conditioner or heat pump. You can usually find these
at your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ..................... ANSI/NFPA 70
Standard for the Installation ............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ...................... ACCA Manual J or
Winter and Summer Manual N
Air Conditioning
Low Pressure, Low Velocity ............ ACCA Manual D or
Duct System Design Manual Q
Winter and Summer Air Conditioning
FOR MORE INFORMATION, CONTACT THESE
PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration,
and Air Conditioning Engineers, Inc.
Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manual 2100-603B
Page 3 of 44
Q-TEC Series General Information
Q-TEC MODEL NOMENCLATURE
Q36 H 2DA 10 X X X X X X
MODEL
NUMBER
Q-TEC™
CAPACITY
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
VENTILATION OPTIONS
X - Barometric Fresh Air Damper (Standard)
B - Blank-off Plate
V - Commercial Ventilator - Motorized w/Exhaust Spring Return
P - Commercial Ventilator - Motorized w/Exhaust Power Return
R - Energy Recovery Ventilator w/Independent Intake & Exhaust Control
These electric heaters are available in 230/208V units only.
These electric heaters are available in 480V units only.
At 240V At 208V At 480V At 460V
1-Ph
Amps
3-Ph
Amps
BTUHKW
1-Ph
Amps
3-Ph
Amps
BTUHKW
3-Ph
Amps
BTUHKW
3-Ph
Amps
BTUH
Manual 2100-603B
Page 4 of 44
TABLE 2 – ELECTRICAL SPECIFICATIONS
No.
Field
Power
Circuits
1
1
3
1
3
1
3
1
3
1
3
1
3
1
1 or 2
1
1
1
1
1
1
1
1
1 or 2
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1 or 2
1
1
1
1
1
1
1
1
1
1 or 2
1 or 2
1 or 2
1
1
1
1
1
1
Minimum
Circuit
Ampacity
22
47
72
17
35
44
10
19
23
25
50
75
18
37
45
55
12
21
25
30
31
56
81
83
25
43
52
53
12
21
26
27
34
59
84
84
25
43
52
53
13
22
26
27
38
63
88
88
29
47
56
56
15
24
28
28
45
70
95
95
31
58
58
17
31
31
MODEL
Q24H2DA0Z
A05
A10
Q24H2DB0Z
B06
B09
Q24H2DC0Z
C06
C09
Q30H2DA0Z
A05
A10
Q30H2DB0Z
B06
B09
B12
Q30H2DC0Z
C06
C09
C12
Q36H2DA0Z
A05
A10
A15
Q36H2DB0Z
B06
B09
B15
Q36H2DC0Z
C06
C09
C15
Q42H2DA0Z
A05
A10
A15
Q42H2DB0Z
B06
B09
B15
Q42H2DC0Z
C06
C09
C15
Q48H2DA0Z
A05
A10
A15
Q48H2DB0Z
B06
B09
B15
Q48H2DC0Z
C06
C09
C15
Q60H2DA0Z
A05
A10
A15
Q60H2DB0Z
B09
B15
Q60H2DC0Z
C09
C15
Rated
Volts &
Phase
230/208-
230/208-
460-3
230/208-
230/208-
460-3
230/208-
230/208-
460-3
230/208-
230/208-
460-3
230/208-
230/208-
460-3
230/208-
230/208-
460-3
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest
revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to
Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
Maximum KW that can operate with heat pump on is 10KW. Other 5KW energizes during emergency heating only.
Maximum KW that can operate with heat pump on is 9KW. Other 6KW energizes during emergency heating only.
NOTE: Reference Form 7960-582 for dehumidification model performance information.
Single CircuitDual Circuit
Maximum
External
Fuse or Ckt.
Brkr.
30
50
80
20
35
45
15
20
25
35
50
80
25
40
45
60
15
25
25
30
45
60
90
90
30
50
60
60
15
25
30
30
50
60
90
90
35
50
60
60
15
25
30
30
50
70
90
90
40
50
60
60
20
25
30
30
60
90
100
100
45
60
60
25
35
35
Field
Power
Wire Size
10
8
4
12
8
8
14
12
10
8
8
4
10
8
8
6
14
10
10
10
8
6
4
4
10
8
6
6
14
10
10
10
8
6
4
4
8
8
6
6
14
10
10
10
8
6
3
3
8
8
6
6
12
10
10
10
8
4
3
3
8
6
6
10
8
8
Minimum
Ground
Wire
10
10
8225030501081010
12
10
10
14
12
10
10
10
8255030501081010
10
10
10
10
14
10
10
10
10
10
8
8
10
10
10
10
14
10
10
10
10
10
8
8
10
10
10
10
14
10
10
10
10
8
8
8
10
10
10
10
12
10
10
10
10
8
8
8
10
10
10
10
10
10
Circuit
Ampacity
Ckt. A Ckt. B Ckt. ACkt. B Ckt. A Ckt. BCkt. A Ckt. B
31335050454550
34345050454550
38
38
38
45
45
45
25
50
50
25
50
50
Maximum
External Fuse or
Ckt. Breaker
50
50
50
25
50
50
50
50
60
25
60
50
60
50
Field Power
Wire Size
8
8
8
8
10
8
8
8
10
8
8
8
8
8
8
8
8
8
8
8
Ground
Wire Size
101010
101010
10
10
10
10
10
10
Manual 2100-603B
Page 5 of 44
10
10
10
10
10
10
10
10
FIGURE 1
Q24H2D
UNIT DIMENSIONS
Q30H2D
Q36H2D
Q42H2D
Q48H2D
Q60H2D
Manual 2100-603B
Page 6 of 44
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. The
skid must remain attached to the unit until the unit is
ready for installation. If damage is found, the receiving
party must contact the last carrier immediately,
preferably in writing, requesting inspection by the
carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
This unit is heavy and requires more than one
person to handle and remove from the skid.
Check unit wheels to ensure that wheels are
locked before removing from skid. Extreme
caution must be taken to prevent injury to
personnel and damage to the unit.
FIGURE 2
AIR SEAL UNDER Q-TEC UNIT
Air Seal
It is recommended that the unit not be removed from
the skid with a forklift since the air seal under the unit
could be damaged. See Figure 2.
The shipping brackets on each side of the unit must be
removed and discarded. See Figure 3-A. The return
air grille panel can be removed to provide a place to
hold the unit. The unit can be slid forward on the skid
until the front wheels hang over the edge of the skid.
FIGURE 3
REMOVAL OF UNIT FROM SKID
See Figure 3-B. The unit can be tipped forward and
slid down the edge of the skid until the front wheels
touch the ground. See Figure 3-C. The wheels will
not roll. They are shipped from the factory locked so
they will not roll. The back of the skid will have to be
held down to keep it from tipping up. The skid can be
slid out from under the unit. The unit can then be set
upright.
Hold Skid
Down
A Shipping BracketsB Front Wheels Over Edge
C Front Wheels On Floor
Manual 2100-603B
Page 7 of 44
HANDLING UNIT AFTER REMOVAL
FROM SKID
WARNING
Exercise extreme caution when pushing the
unit on the rollers. Handle and push from the
lower 1/3 of the unit. Insure that debris is not
on the oor where the unit is to be moved on
the rollers. Failure to do so could result in the
unit tipping over and causing bodily injury and/
or damage to the unit.
See Figure 4. The blade of the appliance cart should
be slid under the wheels of the unit. The strap of the
appliance cart should be placed around the unit and
strapped tightly. Help will be required to tip the unit
back onto the cart. The unit can be leaned far enough
back to be rolled through the door. Be careful when
setting the unit back up to keep from damaging the
unit.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The unit will have to be turned sideways and removed
from the skid to fit through a 36" doorway. If the door
height allows, the unit can be slid sideways through the
door.
If the unit can not be slid through the door, then the
unit will have to be put on a cart and tipped down
to roll through the door. It is recommended that an
appliance cart by used with a strap to hold the unit on
the cart. The wheels of the unit must be locked. If the
wheels were allowed to roll, the unit could roll off the
cart. The unit should always be carted from the left side. This is the side where the compressor is located.
FIGURE 4
UNIT ON APPLIANCE CART
Q-TEC UNIT
(Right Side)
STRAP
The unit is designed for use with or without duct work.
For use without duct work, Plenum Box QPB42 is
recommended.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Start
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any
national and/or local codes in any way. Authorities
having jurisdiction should be consulted before the
installation is made. See Page 3 for information on
codes and standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with
the Standards of the National Fire Protection Systems
of Other Than Residence Type, NFPA No. 90A, and
Residence Type Warm Air Heating and Air Conditioning
Systems, NFPA No. 90B. Where local regulations are
at a variance with instructions, installer should adhere
to local codes.
APPLIANCE
CART
COMPRESSOR
Manual 2100-603B
Page 8 of 44
MINIMUM INSTALLATION HEIGHT
The minimum installation height of the unit with a
Free Blow Plenum is 8 ft. 6 in. This provides enough
clearance for the plenum to be removed. See Figure 5.
The minimum installation height for ducted
applications is 8 ft. 4½ in. This provides enough
clearance to install the duct work. See Figure 6.
FIGURE 5
INSTALLATION WITH DUCT FREE PLENUM
FIGURE 6
DUCTED APPLICATION
Manual 2100-603B
Page 9 of 44
DUCT WORK
Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit. All duct work must be properly sized
for the design airflow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is
an excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should
be properly insulated in order to both conserve energy
and prevent condensation or moisture damage. When
duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect
the duct work to the equipment in order to keep the
noise transmission to a minimum.
The Q-TEC series heat pump has provision to attach a
supply air duct to the top of the unit. Duct connection
size is 12 inches x 20 inches. The duct work is field
supplied and must be attached in a manner to allow
for ease of removal when it becomes necessary to slide
the unit out from the wall for service. See Figure 7 for
suggested attachment method.
FIGURE 7
SUPPLY DUCT CONNECTIONS
For hot water coil option a QPBHWxx-F for free blow or
QPBHWxx-D for ducted airflow is used.
When used with a ducted supply, a QCX Cabinet
Extension can be used to conceal the duct work above
the unit to the ceiling. This extends 20" above the unit
for a total height above the floor of 10'-7/8". The unit
is equipped with a variable speed indoor blower motor
which increases in speed with an increase in duct
static pressure. The unit will therefore deliver proper
rated airflow up to the maximum ESP shown in Table 9.
However, for quiet operation of the air system, the duct
static should be kept as low as practical, within the
guidelines of good duct design.
FILTERS
Two 1-inch throw away filters [(1) 16x16 and (1)
16x20] are supplied with each unit. The filters slide
into filter brackets. Refer to Figure 8.
The filters are serviced from the inside of the building
by opening the hinged door. This door is attached by
one torx screw and one locking latch.
The internal filter brackets are adjustable to
accommodate 2-inch filters. The tabs for the 1-inch
filters must be bent down to allow the 2-inch filters to
slide in place.
SUPPLY DUCT
TO BE FIELD
SUPPLIED
ATTACHMENT
SCREWS TO
BE FIELD
SUPPLIED
ROOM SIDE OF
Q-TEC UNIT
DUCT FLANGE
PROVIDED WITH
UNIT
NOTE: Unit cabinet, supply air duct and duct free
plenum are approved for “0” clearance to
combustible material.
The Q-TEC series heat pumps are designed for use with
free return (non-ducted) and either free blow with the
use of QPB Plenum Box or a duct supply air system.
The QPB and QPBHW Plenum Box mounts on top
of the unit and has both vertically and horizontally
adjustable louvers on the front discharge grille.
FILTERS
RETURN AIR
GRILLE
FIGURE 8
FILTER LOCATION
Manual 2100-603B
Page 10 of 44
FRESH AIR INTAKE
This unit is equipped with a fresh air damper assembly.
The damper blade is locked in the closed position
when the unit is shipped from the factory. To allow
the damper to operate remove the two plastic locking
pins, one on each end of the blade. This will allow
for maximum fresh airflow. The damper blade will
now open when the indoor blower is operating. If less
than maximum fresh airflow is required, reinsert the
plastic pins to limit damper blade opening to desired
level. Two extra pins are provided (taped to the inside
of the assembly) which may be used to hold the blade
in some position other than minimum or maximum
position. This fresh air assembly is located in the
rear of the unit and to gain access to make these
adjustments remove the air filter service door.
All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets are based upon the fresh
air blank-off plate in place and is recommended for
maximum energy efficiency.
The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.
The rear drain can be used with wall thickness of up to
10 inches where a water trap can be installed between
the unit and the interior wall. See Figure 10. The trap
cannot extend beyond the edge of the unit or it will
interfere with the wall mounting bracket. The drain
can be routed through the floor or through the wall. If
the drain is routed through the wall, the drain line must
be positioned such that it will not interfere with the
sleeve flange or the grille. See Figure 11. If the drain
is to be routed through an unconditioned space, it must
be protected from freezing.
OPTIONAL REAR DRAIN KITS
Optional Rear Drain Kit, Bard Model QCDS48A, is also
available for these products. The optional rear drain kit
offers multiple benefits that include the following:
• Allows unit to be rolled away from the sleeve
without having to disconnect any hard plumbing
connections.
• Allows indoor coil condensate to be easily
connected to Rear Drain Box while bypassing the
outdoor coil drain pan. This aids in minimizing
the potential for biological growth to occur by
minimizing the standing water and exposing it to
warm temperatures.
For details on energy recovery ventilation see separate
section.
SERVICE LIGHT
The unit is equipped with a service light, which signals
the user that service is required. The light is located
in the upper control panel and is visible only when the
hinged service/filter access door is open.
The Service Unit light indicates that the unit has
been shut off by a high or low pressure device. This
indicates that the unit needs to be serviced.
CONDENSATE DRAIN
There are two drain connections on the unit. The rear
drain is the primary drain, and is located on the right
lower rear panel of the unit. The optional side drain is
located on the bottom right side of the unit. The side
drain is shipped with a plug installed.
The side drain requires a water trap for proper
drainage. See Figure 9. The drain can be routed
through the floor or through the wall. If the drain is to
be routed through an unconditioned space, it must be
protected from freezing. The drain line must be able
to be removed from the unit if it is necessary to remove
the unit from the wall. When the side drain is used,
the plug must be removed and installed in the rear
drain outlet.
See Figures 12A, 12B, 12C and 12D.
The drain box permanently mounts onto the wall sleeve
and is then either piped directly outdoors, or can be
piped vertically. The Q-TEC unit is then equipped with
fittings on the rear of the unit that slide into the drain
box as it is wheeled towards the wall sleeve.
NOTE: On models equipped with a refrigerant
subcooler in the lower drain pan may experience a
2-3% decrease in cooling performance and efficiency
when the indoor condensate is routed around the
outdoor coil drain pan/subcooler assembly. Unit
rated performance and efficiency are with the indoor
condensate routed to the outdoor coil pan.
There is also a heated version of the rear drain box
available (Model #QCDS48H) for installation in
northern climates where freezing may occur.
NOTE:Additional circuit needed for drain heater.
Manual 2100-603B
Page 11 of 44
FIGURE 9
OPTIONAL SIDE DRAIN (SIDE VIEW)
Q-TEC UNIT
FIGURE 10
STANDARD REAR DRAIN
FIGURE 11
REAR DRAIN (TOP VIEW)
DRAIN LINE
SLEEVE
WATER
TRAP
WALL (MAXIMUM
10" FOR REAR
DRAIN)
COUPLINGS NOT
SHOWN BUT
RECOMMENDED
FOR EASE OF
REMOVABILITY
FOR SERVICE.
WALL
BRACKET
UNIT
Manual 2100-603B
Page 12 of 44
MIS-2469
DRAIN BOX
WALL SLEEVE
OVERFLOW TUBE
CAULK AROUND TUBE
FIGURE 12A
Manual 2100-603B
Page 13 of 44
SUPPLIED WITH DRAIN BOX KIT
3/4" PLASTIC PIPE NIPPLE
HORIZONTAL TO FLOOR)
(TIGHTEN THREADS SO TEE IS
THREADS)
(APPLY TEFLON TAPE TO
REAR DRAIN CONNECTION IN
Q/Tec PRODUCT
1/2" SLIP X 1/2" SLIP X 3/4" NPT
TEE SUPPLIED WITH DRAIN BOX KIT
PLUG INSTALLED IN
SIDE Q/Tec DRAIN
MIS-2470
FIGURE 12B
Manual 2100-603B
Page 14 of 44
IMPORTANT!
REMOVE KNOCK-OUT FOR
INDOOR DRAIN HOSE CONNECTOR
MIS-2471
FIGURE 12C
(If Used)
Manual 2100-603B
Page 15 of 44
MIS-2472
DRAIN HOSE FROM INDOOR
DRAIN PAN.
MOVE HOSE FROM ATTACHMENT IN
LOWER DRAIN PAN AND SLIDE ONTO
DRAIN BOX BARB FITTING, SECURING
WITH SUPPLIED CLAMP IF OUTDOOR
PAN IS BYPASSED. ( WILL REDUCE RISK
OF ALGAE GROWTH IN THE OUTDOOR
PAN BUT AT A SLIGHT COOLING
PERFORMANCE REDUCTION OF 2-3% )
FIGURE 12D
Manual 2100-603B
Page 16 of 44
Washer
Sleeve
Stud
MIS-2689
Nut
Lower Control Panel
Condenser
Door (Removed)
Return Grille
BOTTOM
TRIM PIECE
BOTTOM TRIM
EXTENSION
FIGURE 13A
UNIT MOUNTING
SIDE TRIM
(2 PCS.)
SIDE TRIM
(2 PCS.)
MOUNTING
BRACKET
ENLARGED VIEW OF MOUNTING
BRACKET SHOWING SLEEVE TO
CABINET ATTACHMENT
MOUNTING BRACKET
WALL
SLEEVE
#8 SCREW
PROVIDED
(LIGHT COLOR)
CABINET
SIDE PANEL
#10 HEX
HEAD SCREW
PROVIDED
FIGURE 13B
UNIT MOUNTING
Manual 2100-603B
Page 17 of 44
INSTALLATION
MOUNTING THE UNIT
When installing a Q-TEC unit near an interior wall on
the left side, a minimum of 8 inches is required; 12
inches is preferred.
When installing a Q-TEC unit near an interior wall on
the right side, a minimum of 18 inches is required as
additional space is required to connect the side drain.
If the rear condensate drain kit QCDS48 is used the
minimum can be reduced to 8 inches.
This clearance is required to allow for the attachment of
the unit to the sleeve and side trim pieces to the wall.
This unit is to be secured to the wall sleeve with
mounting brackets provided. The unit itself, the supply
duct and the free blow plenum are suitable of “0”
clearance to combustible material.
Following are the steps for mounting the Q-TEC.
For reference see Figure 13A for external mounting
bracket or 13B for internal bolt secured bracket
(recommended).
1. Attach mounting brackets to the wall sleeve with
screws provided. Either use external mounting
bracket (Fig. 13A) or internal bolt bracket (Fig. 13B).
2. Position the unit in front of the sleeve with the
condenser section toward the sleeve.
3. Remove the locking screws from the wheels. Refer
to Figure 14.
4. Roll the unit into the sleeve. Make sure to check
both sides of the unit as it is being rolled to keep it
centered in the sleeve. Also check the alignment
to the mounting brackets. This unit must be level
from side to side. If adjustments are necessary,
shim up under the rollers with sheets of steel or
any substance that is not affected by moisture.
5. Make sure the gasket on the rear of the unit is
touching the sleeve across the top and down both
sides. This is a rain water seal.
6. Secure the mounting brackets to the unit with
screws provided, #10 hex head sheet metal screws
(Figure 13A) or use nut and washer to secure
sleeve (Figure 13B).
7. Bottom trim extensions are provided for use when
wall is less than 14 inches but greater than 10.5
inches. Secure to wall with screws (not provided).
8. Attach the bottom trim piece to the unit with the
screws provided (dark colored).
9. Position side trim pieces to wall and attach with
field supplied screws. There are two long pieces
and two short pieces supplied. The long pieces
are to enclose the gap behind the unit. The
short pieces are to fill the gap behind the cabinet
extension or the free blow plenum box. They may
be cut to suit your ceiling height or overlap the unit
side trim. There is sufficient length to trim up to a
10'2" ceiling.
NOTE: If the exterior wall thickness is between 5
inches to 10.5 inches, a side trim extension
piece kit, model QSTX42, is available.
REMOVE SCREWS FROM WHEELS
BEFORE ROLLING INTO PLACE
Manual 2100-603B
Page 18 of 44
FIGURE 14
REMOVING LOCKING SCREWS FROM WHEELS
WIRING – MAIN POWER
Refer to the unit rating plate and/or Table 2 for wire
sizing information and maximum fuse or circuit breaker
size. Each unit is marked with a “Minimum Circuit
Ampacity”. This means that the field wiring used must
be sized to carry that amount of current. Depending
on the installed KW of electric heat, there may be
two field power circuits required. If this is the case,
the unit serial plate will so indicate. All models are
suitable only for connection with copper wire. Each
unit and/or wiring diagram will be marked “Use
Copper Conductors Only”. These instructions MUST BE adhered to. Refer to the National Electrical Code
(NEC) for complete current carrying capacity data on
the various insulation grades of wiring material. All
wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper)
for all models, including the most commonly used heater
sizes. Also shown are the number of field power circuits
required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or circuit breaker that is to be used with
the equipment. The correct size must be used for
proper circuit protection, and also to assure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.
See “Start Up” section for information on three phase
scroll compressor start-ups.
FIGURE 15
COMPONENT LOCATION
SIDE FIELD WIRE
ELECTRIC
HEATERS
UNIT
MOUNTED
THERMOSTAT
LOCATION
DEHUMIDIFICATION
CONTROL
(OPTIONAL)
ENTRANCE
REMOTE
THERMOSTAT
TERMINAL
BLOCK
INDOOR
BLOWER
CIRCUIT
BREAKER PANEL
& CONTROLS
The field wiring connections are located behind the
top and hinged panel in the circuit breaker panel. See
Figure 15.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 PHASE AND 3 PHASE EQUIPMENT
DUAL PRIMARY VOLTAGE TRANSFORMERS
All equipment leaves the factory wired on 240V tap.
For 208V operation, reconnect from 240V to 208V tap.
The acceptable operating voltage range for the 240 and
208V taps are as noted in Table 3.
TABLE 3
OPERATING VOLTAGE RANGE
TAPRANGE
240V253 – 216
208V220 – 187
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
OPTIONAL CLIMATE CONTROLS
SEQUENCE OF OPERATION
The standard Climate Control Option X is a remote
thermostat connection terminal block. See Figure
17 or Figure 18 for wiring diagram. Compatible
thermostats are listed in Table 4.
The Climate Control Option E is an electronic,
programmable thermostat with humidistat. The
subbase of the thermostat is factory wired to the front
panel of the unit. See Figure 19 for wiring diagram.
Compatible for use with Energy Recovery Ventilator.
This unit has a refrigerant reheat circuit that is
controlled by a 3 way valve.
When the humidity is above the setpoint of the
humidistat, the compressor circuit and the 3 way valve
are energized and the evaporator airflow is reduced.
The 3 way valve directs hot discharge gas into a
separate desuperheating condenser circuit that reheats
the conditioned air before it is delivered to the room.
When the humidistat is satisfied, the system switches
back to normal air conditioning mode.
If the thermostat calls for cooling during
dehumidification mode, the call for cooling takes
precedence over the dehumidification and the unit will
cool until the thermostat is satisfied. Once the call for
cooling is satisfied, the unit may continue to dehumidify.
LOWER
CONTROL
PANEL
If the thermostat calls for heat when the unit is in
the dehumidification mode, the electric heaters will
energize and the evaporator airflow will return to the
heating airflow. When the thermostat is satisfied, the
electric heaters will turn off and the airflow will be
reduced and the system will continue to dehumidify
until humidistat is satisfied.
Manual 2100-603B
Page 19 of 44
If the unit is running in heat pump mode and the
humidistat calls for dehumidification, the
dehumidification mode takes precedence over the heat
pump heating mode. The unit will not return to the
heating mode until 2nd stage heating is called for.
The Climate Control Option I is an electronic,
programmable thermostat with humidistat and a CO
controller. The subbase of the thermostat and CO
2
2
controller are factory wired to the front panel of the
unit. See Figure 20 for wiring diagram. This unit has a
refrigerant reheat circuit that is controlled by a 3 way valve.
When the humidity is above the setpoint of the
humidistat, the compressor circuit and the 3 way valve
are energized and the evaporator airflow is reduced. The
3 way valve directs hot discharge gas into a separate
desuperheating condenser circuit that reheats the
conditioned air before it is delivered to the room. When
the humidistat is satisfied, the system switches back to
normal air conditioning mode.
If the thermostat calls for cooling during dehumidification
mode, the call for cooling takes precedence over the
dehumidification and the unit will cool until the thermostat
is satisfied. Once the call for cooling is satisfied, the unit
may continue to dehumidify.
If the thermostat calls for heat when the unit is in the
dehumidification mode, the electric heaters will energize and
the evaporator airflow will return to the heating airflow. When
the thermostat is satisfied, the electric heaters will turn off
and the airflow will be reduced and the system will continue
to dehumidify until humidistat is satisfied.
If the unit is running in heat pump mode and the
humidistat calls for dehumidification, the
dehumidification mode takes precedence over the heat
pump heating mode. The unit will not return to the
heating mode until 2nd stage heating is called for.
The CO
ID blower when the room CO
Default CO
controller will energize the vent option and the
2
set point is 950 ppm. See Figure 24.
2
levels rise over set level.
2
The Climate Control Option J & K are an electronic,
programmable thermostat, humidistat and CO
. controller
2
"J" model only) with BACnet, MS/TP or Ethernet
connections.
When the humidity is above the setpoint of the humidistat,
the compressor circuit and the 3-way valve are energized
and the evaporator airflow is reduced. The 3-way valve
directs hot discharge gas into a separate desuperheating
condenser circuit that reheats the conditioned air before it is
delivered to the room. When the humidistat is satisfied, the
system switches back to normal air conditioning mode.
If the thermostat calls for cooling during dehumidification
mode, the call for cooling takes precedence over the
dehumidification and the unit will cool until the thermostat
is satisfied. Once the call for cooling is satisfied, the unit
may continue to dehumidify.
If the thermostat calls for heat when the unit is in the
dehumidification mode, the electric heaters will energize
and the evaporator airflow will return to the heating airflow.
When the thermostat is satisfied, the electric heaters will
turn off and the airflow will be reduced and the system will
continue to dehumidify until humidistat is satisfied.
If the unit is running in heat pump mode and the
humidstat calls for dehumidification, the dehumidification
mode takes precedence over the heat pump heating mode.
The unit will not return to the heating mode until 2nd
stage heating is called for.
Option J (Models only) the CO
sensor in the controller
2
will energize the vent option and the ID blower when the
room CO
levels rise over set level. Default CO2 set point
2
is 1000 ppm.
NOTE: On option X, field provided means to control
ventilation must be used if any of the motorized
ventilation options are installed.
LOW VOLTAGE CONNECTIONS
FOR DDC CONTROL
Fan Only Energize G
Cooling Mode Energize Y, G
Heat Pump Heating Energize Y, G, B
2nd State Heating Energize G, W2, Y, B
(if employed)
Ventilation Energize G, O1
Dehumidication Energize 4
Emergency Heat Energize B, W2, E, G
LOW VOLTAGE CONNECTIONS
These units use a grounded 24 volt AC low voltage circuit.
The “R” terminal is the hot terminal and the “C” terminal
is grounded.
“G” terminal or pin 6 of P2 is the fan input. If the climate
control option is abandoned and connections are made
directly to P2 pin 6 of P2 must be energized for proper
operation.
“Y1” terminal or pin 7 of P2 is the compressor input.
“W1” terminal or pin 8 of P2 is the fist stage heat.
“R” terminal or pin 10 of P2 is 24 VAC hot.
“C” terminal or pin 11 of P2 is 24 VAC grounded.
Terminal “1” or pin 4 of P2 is the dehumidification circuit.
Terminal “2” or pin 12 of P2 is the dehumidification
circuit. A contact must connect terminals 1 and 2.
“W2” terminal or pin 9 of P2 is second stage heat (if
equipped). If the unit is equipped with an optional
hot water coil plenum box or electric heat these will be
energized by this terminal.
“F” terminal of pin 5 of P2 is the ventilation input. This
terminal energizes any factory installed ventilation option.
NOTE: For total and proper control using DDC, a total
of 7 controlled outputs are required (6 if no ventilation
system is installed). For proper system operation under
Emergency Heat conditions where the compressor needs to
be deactivated, the B-W2-E outputs need to be energized.
Manual 2100-603B
Page 20 of 44
Removing the Y (compressor) signal alone turns the
compressor off, but does not activate the additional
circuitry embedded in the heat pump for proper and
complete operation.
CAUTION
Do not plug in or unplug blower motor
connectors while the power is on.
Failure to do so may result in motor failure.
WALL THERMOSTATS & CONTROLS
ThermostatPredominant Features
8403-067
8403-060
(1120-445)
CSB9E-THO
CSB9E-THOC
Carbon Dioxide Sensor with LCD for
Sensor Readings
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover
with Humidity Contol
BacNet MS/TP or Ethernet Connection
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover
with CO
BacNet MS/TP or Ethernet Connection
GENERAL
This unit is equipped with a variable speed ECM motor.
The motor is designed to maintain rated airflow up to
the maximum static allowed. It is important that the
blower motor plugs are not plugged in or unplugged
while the power is on. Failure to remove power prior
to unplugging or plugging in the motor could result in
motor failure.
TABLE 4
& Humidity Contol
2
FIGURE 16
MIS-1285
Manual 2100-603B
Page 21 of 44
12345
FACTORY INSTALLED JUMPER
"J" CS9BE-THO
"K" CS9BE-THOC
Plug #2
FIGURE 17
REMOTE THERMOSTAT WIRING DIAGRAM
“X” THERMOSTAT OPTION
8
9
7
6
10
11
12
Black
Red/Yellow
L
Relay Logic Board
Purple/White
L
E1
Orange
Brown/White
E1
BK
G1
RV
Freeze
Protect Tstat
Blue
Brown
Yellow
TWV
W
Bard Part #8408-038
YO
A1
Red/White
A2
W2
Pink
RAT
G
3
2
Return Air
Thermostat
Red/WhiteRed/White
Y
D
R
B
Black/White
C
Black/White
4102-063 B
Plug #4
Black/White
Red/White
123
Red/White
Black/White
6
5
W1/E
Red
Red/Yellow
E
W1/E
D
4
Purple/White
Purple/White
4
D/YO
A
Brown/White
6
5
Brown/White
O1
A
SC
Orange
Orange
G
G
G
Blue
Yellow
7
Yellow
Y
Y1
Y1
Y1
SC
Brown
8
9
101112
Blue
Brown
Red/White
Black/White
L
W1
1
SC
W2
W2
W2
R
C
RCL
R
C
L
Term. Block
Low Voltage
8403-060
Thermostat
1
B
O/B
B
Manual 2100-603B
Page 22 of 44
Dehumidification WiringDiagram
art #8403-067
FIGURE 18
REMOTE THERMOSTAT WIRING DIAGRAM
“X” THERMOSTAT OPTION & DEMAND VENTILATION
9
8
12345
Plug #2
7
6
11
10
12
Black
Red/Yellow
Brown/White
Purple/White
L
E1
L
E1
Relay Logic Board
G1
Orange
Freeze
BK
RV
Protect Tstat
Blue
Brown
Yellow
YO
TWV
W
A1
Bard Part #8408-038
Red/White
Pink
Y
A2
RAT
D
G
W2
3
2
Thermostat
Return Air
Red/White
R
B
C
Red/White
Black/White
MIS-2690 D
Black/White
AndDemand Ventilation
With"X" ThermostatOption
Red/White
3
2
1
Optional
24 VAC
CO2 Controller
Bard P
CO2-OUT
465
TEMP-OUT
Black/White
Red/White
12345
Plug #4
Red/White
Black/White
6
Red
Purple/White
Brown/White
Blue
Yellow
Orange
7
6
Yellow
Purple/White
D/YO
Orange
Brown/White
4
Y
G
O1
A
Y1
G
Y1
Red/Yellow
5
E
W1/E
Brown
9
8
Blue
B
O/B
10
11
12
Brown
Red/White
Black/White
L
R
C
W2
W1
R
C
W2
Term. Block
Low Voltage
8403-060
L
Thermostat
FACTORY INSTALLED JUMPER
1
Manual 2100-603B
Page 23 of 44
4102-064
B
Thermostat
RAT
C
R
E1
BK
TWV
YO
A2
Y
Purple/White
L
L
E1
G1
RV
W
A1
W2
G
D
Relay Logic Board
Thermostat
Plug #2
Pink
Red/White
Brown
Blue
Yellow
Orange
Brown/White
Purple/White
Black/White
Brown
Blue
Yellow
Orange
Brown/White
Purple/White
Red
Red/White
Red/WhiteRed/White
Black/White
Black/White
Black
Red/Yellow
Plug #4
2
3
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
Return Air
Protect Tstat
Bard Part #8408-038
L
C
R
W2
B
W1/E
G
A
Y1
Red/Yellow
Brown/White
Orange
Yellow
Blue
Brown
Red/White
Black/White
Freeze
8403-060
D/YO
FIGURE 19
“E” THERMOSTAT OPTION
UNIT MOUNTED THERMOSTAT WIRING DIAGRAM
Manual 2100-603B
Page 24 of 44
FIGURE 20
With"I" ThermostatOption
WiringDiagram
UNIT MOUNTED THERMOSTAT WIRING DIAGRAM
“I” THERMOSTAT OPTION
CO Controller
2
Bard Part #8403-067
2
1
24 VAC
2
CO2-OUT
TEMP-OUT
3
4
5
Red/White
1
6
8403-060
Thermostat
W1/E
D/YO
G
Y1
W2
4
Red/Yellow
Purple/White
A
Orange
Yellow
B
R
C
L
Blue
Brown
Red/White
Black/White
Brown/White
Red/White
Black/White
Plug #4
3
1
2
3
4
5
6
7
8
9
10
11
12
4102-066 C
Manual 2100-603B
Page 25 of 44
SC
SC
SC
Black/White
RAT
C
R
E1
BK
TWV
YO
A2
Y
B
L
L
E1
G1
RV
W
A1
W2
G
D
4102-079
Thermostat
Plug #2
Pink
Red/White
Brown
Blue
Yellow
Orange
Brown/White
Purple/White
Black/White
Brown
Blue
Yellow
Orange
Brown/White
Purple/White
Red
Red/White
Red/WhiteRed/White
Black/White
Black/White
Black
Red/Yellow
Plug #4
2
3
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
Relay Logic Board
Purple/White
12
Bard Part #8408-038
L
C
R
W2
B
W1/E
G
A
Y1
Red/Yellow
Brown/White
Orange
Yellow
Blue
Brown
Red/White
Return Air
Protect Tstat
K" CS9BE-THOC
Freeze
"J" CS9BE-THO"
D
FIGURE 21
“J” OR “K” THERMOSTAT OPTION
UNIT MOUNTED THERMOSTAT WIRING DIAGRAM
Manual 2100-603B
Page 26 of 44
START UP
THESE UNITS REQUIRE R-410A
REFRIGERANT AND POLYOL
ESTER OIL.
GENERAL
1. Use separate service equipment to avoid cross
contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800
psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-
125.
5. R-410A is nearly azeotropic - similar to R-22 and
R-12. Although nearly azeotropic, charge with
liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot
withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming
potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb
moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used - even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with
small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard
Manufacturing recommends reclaiming, evacuating
(see criteria above), and charging to the nameplate
charge. If done correctly, topping off the system
charge can be done without problems.
With R-410A, there are no significant changes in the
refrigerant composition during multiple leaks and
recharges. R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound
or single component refrigerant). The remaining
refrigerant charge, in the system, may be used after
leaks have occurred and then “top-off” the charge by
utilizing the pressure charts on the inner control panel
cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it
must come out of the charging cylinder/tank as a liquid
to avoid any fractionation, and to insure optimal system
performance. Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.
WARNING
Failure to conform to these practices
could lead to damage, injury or death.
SAFETY PRACTICES
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses. Polyol Ester oils
can be irritating to the skin, and liquid refrigerant
will freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become flammable.
4. Do not inhale R-410A – the vapor attacks
the nervous system, creating dizziness, loss
of coordination and slurred speech. Cardiac
irregularities, unconsciousness and ultimate death
can result from breathing this concentration.
5. Do not burn R-410A. This decomposition
produces hazardous vapors. Evacuate the area if
exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct
sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands significantly
at warmer temperatures. Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.
Manual 2100-603B
Page 27 of 44
DESCRIPTION OF STANDARD
EQUIPMENT
Solid State Electronic Heat Pump Control
Provides efficient 30-minute defrost cycle. A
thermistor sensor and speed up terminal for service
along with a 10- minute defrost override are standard
on the electronic heat pump control.
High Pressure Switch
Provides refrigerant circuit high pressure protection.
Includes lockout circuit that is resettable from room
thermostat.
Compressor Control Module
Provides short cycle protection for the compressor
which extends compressor life, as well as high and low
pressure switch monitoring and alarm functions.
Service Lights
One service light indicates when service is required.
• Check System – detects high or low pressure
switch operation for compressor protection.
OPTIONAL CFM (Q36H2D, Q42H2D,
Q48H2D AND Q60H2D ONLY)
These units are shipped from the factory set to operate
at the optional CFM level shown in Table 9. This
provides lower operating sound levels for non-ducted,
free discharge applications. This CFM level will reduce
the system capacity performance by approximately 2%
at the same energy efficiency.
Rated CFM is required for ducted applications for
maximum performance rating. To obtain full CFM on
these models, connect jumper wire as follows:
1. Disconnect all power to the unit. Failure to do so
may result in damage to the motor.
2. Open return air service panel
3. Open inner control panel cover
4. Locate low voltage terminal strip. There is a pink
jumper wire with both ends attached to terminal
marked “G2”. Move one end of this jumper to
terminal “Y”.
5. Reverse steps to reassemble.
IMPORTANT INSTALLER NOTE
For improved start-up performance, wash the indoor
coil with a dishwasher detergent.
PHASE MONITOR
All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two
LEDs. If the Y signal is present at the phase monitor
and phases are correct the green LED will light and the
compressor contactor is allowed to energize.
If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION
Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.
However, three phase compressors will rotate in either
direction depending upon phasing of the power.
Since there is a 50-50 chance of connecting power
in such a way as to cause rotation in the reverse
direction, verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time
the equipment is put into service. If improper rotation
is corrected at this time there will be no negative impact
on the durability of the compressor. However, reverse
operation for even one hour may have a negative impact
on the bearing due to oil pump out.
All three phase scroll compressors used in the Q-TEC
series are wired identically internally. As a result, once
the correct phasing is determined for a specific system
or installation, connecting properly phased power
leads to the same Fusite terminal should maintain
proper rotation direction. The direction of rotation of
the motor may be changed by reversing any two line
connections to the unit.
Manual 2100-603B
Page 28 of 44
SERVICE HINTS
1. Caution user to maintain clean air filters at all
times. Also, not to needlessly close off supply air
registers. This may reduce airflow through the
system, which shortens equipment service life as
well as increasing operating costs and noise levels.
2. Switching to heating cycle at 75°F or higher
outside temperature may cause a nuisance trip
of the remote reset high pressure switch. Turn
thermostat off, then on to reset the high pressure
switch.
3. The heat pump wall thermostats perform multiple
functions. Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.
4. Check all power fuses or circuit breakers to be sure
they are the correct rating.
5. Periodic cleaning of the outdoor coil to permit full
and unrestricted airflow circulation is essential.
6. Some service requires the need to remove the
unit from the wall including replacement of the
indoor coil and/or the outdoor coil. Also servicing
the outdoor fan motor or fan blade will require
removing the unit from the wall if the unit is
installed at a height that is not easily accessible
from the outside of the building.
In order to remove the unit from the wall the
following procedure must be used:
a. Turn off power to the unit at the remote
location. Some units may have more than one
power supply.
b. Disconnect field wiring at unit terminal block
and remove from unit.
c. Disconnect condensate drain.
d. Remove the lower skirting around the unit.
7. Annual maintenance is required to ensure that all
of the systems are functioning properly.
a. Check to make sure that the drains are not
obstructed in any way.
b. Remove any debris in the condenser section of
the unit.
c. Inspect and clean mist eliminator as described
below.
d. Inspect and wash outdoor coil as necessary.
MIST ELIMINATOR SERVICE
A mist eliminator is supplied with the wall sleeve. The
mist eliminator is constructed of an aluminum frame
and mesh. The mist eliminator is located in the top
section of the wall sleeve and can be removed from the
inside of the building without removing the unit from
the wall. This requires that the ventilation package
must be removed.
It is recommended that the mist eliminator be
inspected annually and serviced as required. The mist
eliminator can be inspected from the outside of the
building by looking through the outdoor grille. The
mist eliminator can be serviced from the outside by
using a vacuum cleaner. The outdoor grille must be
removed. Use the vacuum to remove dirt and debris
from the surface of the mist eliminator. If additional
cleaning is required, the mist eliminator will have to be
removed from the sleeve.
The ventilation package will have to be removed to gain
access to the mist eliminator. If the blank off plate
option is used, it is not necessary to service the mist
eliminator. The steps necessary to remove each of the
vent options are listed below.
The mist eliminator can be cleaned by washing with
soap and water. The excess water should be shaken off
the mist eliminator before it is reinstalled.
e. Remove wall mounting brackets from wall on
each side of the unit.
f. If unit is attached to duct work, remove upper
cabinet extension by removing the top center
screw only from the cabinet side panel.
g. Remove screws that attach the duct work to
the unit flanges.
This unit is equipped with four rollers mounted
to the base. For ease of pulling unit out from
the wall, you may want to remove the bottom
service door which requires removal of the
return air panel, and grip the front flange of
the base pan then pull straight out.
Manual 2100-603B
Page 29 of 44
VENT OPTIONS
BAROMETRIC FRESH AIR DAMPER (Standard)
Before starting, make sure the power has been turned
off. The return air grille panel must be removed. The
fresh air damper assembly can be seen on the back of
the unit. See Figure 22.
1. The fresh air damper is attached to the back of the
unit with one screw on either side of the assembly.
Both of the screws must be removed.
2. Once the mounting screws are removed, tilt the
assembly down and lift it out.
The mist eliminator can be seen through the opening.
The mist eliminator must be raised up and the bottom
can be pulled toward the front of the unit.
COMMERCIAL ROOM VENTILATOR (Option)
Before starting, make sure the power has been turned
off. The return air grille panel must be removed. The
commercial room ventilator (CRV) can be seen after the
panel has been removed. The CRV must be removed to
gain access to the mist eliminator.
1. The two mounting screws in the front of the CRV
must be removed.
2. The power connectors for the CRV (located on
the right side of the unit) must be disconnected.
Squeeze the tabs on the sides of the connector and
pull straight out. Unplug both of the connectors.
3. Slide the CRV straight out of the unit.
The mist eliminator can be seen through the opening
in the back of the unit. The mist eliminator must be
raised up and the bottom can be pulled toward the
front of the unit and removed.
Q-TEC ENERGY RECOVERY VENTILATOR (Option)
Before starting, make sure that the power has been
turned off. The return air grille panel must be
removed. The energy recovery ventilator (QERV) can be
seen after the panel has been removed. To gain access
to the mist eliminator, the QERV must be removed.
See Figure 23.
1. The front fill plate of the QERV must be removed.
There is one screw on either side of the plate.
Remove these screws and remove the plate.
2. On either side of the QERV there are mounting
screws that hold the QERV in place. Remove both
of these screws.
3. Underneath the heat recovery cassette there is a
power connector for the lower blower assembly. To
disconnect this plug, the tabs on both sides of the
plug must be squeezed to release the plug. While
squeezing the tabs, pull the plug out of the socket.
4. The QERV is plugged into the unit in the right
side of the unit. Both of these plugs must be
disconnected to remove the QERV. Squeeze the
tabs on the sides of the connector and pull straight
out.
5. Slide the QERV assembly straight out of the unit,
being careful not to let the cassette slide out of the
QERV.
The mist eliminator can be seen through the opening
in the back of the unit. The mist eliminator must be
raised up and the bottom can be pulled toward the
front of the unit and removed.
Manual 2100-603B
Page 30 of 44
FIGURE 22
FRESH AIR DAMPER REMOVAL
MOUNTING SCREW
Manual 2100-603B
Page 31 of 44
FIGURE 23
QERV REMOVAL
MOUNTING SCREWS
POWER
CONNECTORS
LOWER BLOWER
ASSEMBLY POWER
CONNECTOR
FRONT FILL
Manual 2100-603B
Page 32 of 44
SEQUENCE OF OPERATION
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED
Settings RecommendedDefault
RON10001000
ROF950950
DSPCCT
UNIUSUS
COLNot Used
COHNot Used
TOLNot Used
TOHNot Used
BAR
See Instrution with Controller
For High Altitude Installations
CALUsed for Field Calibration
MIS-3326
Cooling – Circuit R-Y makes the thermostat pull in
the compressor contactor starting the compressor
and outdoor motor. The G (indoor motor) circuit
is automatically completed on any call for cooling
operation, or can be energized by manual fan switch on
subbase for constant air circulation.
Heating – A 24V solenoid coil on the reversing valve
controls heating cycle operation. Two thermostat options,
one allowing “Auto” change over from cycle to cycle
and the other constantly energizing solenoid coil during
heating season and thus eliminating pressure equalization
noise except during defrost, are to be used on “Auto”
option, a circuit is completed for R-W1 and R-Y on each
heating “on” cycle, energizing reversing valve solenoid
and pulling in compressor contactor starting compressor
and outdoor motor. R-G also makes starting indoor
blower motor. Heat pump heating cycle now in operation.
The second option has no “Auto” change over position,
but instead energizes the reversing valve solenoid
constantly whenever the system switch on subbase
is placed in “Heat” position, the “B” terminal being
constantly energized from R. A thermostat demand
for heat completes R-Y circuit, pulling in compressor
contactor starting compressor and outdoor motor. R-G
also make starting indoor blower motor.
Reheat Circuit – There is a small capillary tube inserted
between the reheat coil return line and suction line
that will prevent liquid from accumulating in the reheat
coil when it is inactive. This drain does not affect the
normal operation of the system.
There is a check valve located in the reheat coil
return line. It has a soft spring to hold the ball on the
seat. This will make the method of checking the ball
freedom with a magnet difficult. Refer to Figures 25
and 26 for the location of the check valve and drain
back capillary.
When the system is operating in the dehumidification
mode, the suction pressure will be reduced by 4 to 8 psig
and the discharge pressure will be reduced by 19 to 22
psig.
Return Air Thermostat – In dehumidification mode if
the return air temperature is lower than 65°, the return
air thermostat closes and brings on stage one electric
heat to maintain 65°.
High/Low Pressure Control provides protection for the
compressor. In the event system pressures go above
600 PSI or below 15 PSI in either cooling or heating
mode the compressor will be stopped. This will
activate the red light located in the control panel. The
lockout circuit will hold compressor off line. When the
system problem is corrected, the unit operation can be
restored by turning of the main power supply off and
then back on, or reset the room thermostat. The low
pressure control has a bypass to eliminate nuisance
lockout on cold start up.
The bypass timer should be set to 120 seconds. This
is to assure there is no nuisance tripping of the lowpressure control during startup in heating mode under
cold weather conditions.
FIGURE 24 – CO2 CONTROLLER (FACTORY SET TO 950 PPM)
Manual 2100-603B
Page 33 of 44
REFRIGERANT TUBE SCHEMATIC FOR
REHEAT COIL
Figure 25 shows the refrigerant gas flow through the reheat
coil during the dehumidification mode.
When the unit is in standard cooling (Figure 26) or heating
mode, the reheat coil is inactive.
FIGURE 25
Q-TEC DEHUMIDIFICATION MODE CIRCUIT DIAGRAM
Manual 2100-603B
Page 34 of 44
FIGURE 26
Q-TEC COOLING MODE CIRCUIT DIAGRAM
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on
all units so that the system operating pressures can
be observed. Pressure curves can be found later in
the manual covering all models on both cooling and
heating cycles. It is imperative to match the correct
pressure curve to the unit by model number. Upper
and lower service doors must be attached to obtain
proper reading.
This unit employs high-flow Coremax valves instead of
the typical Shrader type valves.
WARNING! Do NOT use a Schrader valve core removal
tool with these valves. Use of such a tool could result
in eye injuries or refrigerant burns!
To change a Coremax valve without first removing the
refrigerant, a special tool is required which can be
obtained at www.fastestinc.com/en/SCCA07H. See the
replacement parts manual for replacement core part
numbers.
Manual 2100-603B
Page 35 of 44
DEFROST CYCLE
The defrost cycle is controlled by temperature and time
on the solid state heat pump control.
When the outdoor temperature is in the lower
40°F temperature range or colder, the outdoor coil
temperature is 32°F or below. This coil temperature
is sensed by the coil temperature sensor mounted near
the bottom of the outdoor coil. Once coil temperature
reaches 30°F or below, the coil temperature sensor
sends a signal to the control logic of the heat pump
control and the defrost timer will start accumulating
run time.
After 30, 60 or 90 minutes of heat pump operation at
30°F or below, the heat pump control will place the
system in the defrost mode.
During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57°F, the
coil temperature sensor will send a signal to the heat
pump control which will return the system to heating
operations automatically.
If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 8 minutes.
The heat pump defrost control board has an option of
30, 60 or 90-minute setting. By default, this unit is
shipped from the factory with the defrost time on the
30 minute pin. If circumstances require a change
to another time, remove the wire from the 30-minute
terminal and reconnect to the desired terminal. Refer
to Figure 27.
There is a cycle speed up jumper on the control. This
can be used for testing purposes to reduce the time
between defrost cycle operation without waiting for
time to elapse.
Use a small screwdriver or other metallic object, or
another ¼ inch QC, to short between the SPEEDUP
terminals to accelerate the HPC timer and initiate
defrost.
Be careful not to touch any other terminals with the
instrument used to short the SPEEDUP terminals.
It may take up to 10 seconds with the SPEEDUP
terminals shorted for the speedup to be completed and
the defrost cycle to start.
There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.
By placing a jumper across the SEN JMP terminals
(a ¼ inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out & will
activate the timing circuit. This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.
In order to terminate the defrost test the SEN JMP
jumper must be removed. If left in place too long, the
compressor could stop due to the high pressure control
opening because of high pressure condition created
by operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.
There is also a 5-minute compressor time delay
function built into the HPC. This is to protect the
compressor from short cycling conditions. The board’s
LED will have a fast blink rate when in the compressor
time delay. In some instances, it is helpful to the
service technician to override or speed up this timing
period, and shorting out the SPEEDUP terminals for a
few seconds can do this.
Low Pressure Switch Bypass Operation– The control
has a selectable (SW1) low pressure switch bypass set
up to ignore the low pressure switch input during the
first (30, 60, 120 or 180 seconds) of “Y” operation.
After this period expires, the control will then monitor
the low pressure switch input normally to make sure
that the switch is closed during “Y” operation.
High Pressure Switch Operation– The control has a
built-in lockout system that allows the unit to have the
high pressure switch trip up to two times in one hour
and only encounter a “soft” lockout. A “soft” lockout
shuts the compressor off and waits for the pressure
switch to reset, which at that point then allows the
compressor to be restarted as long as the 5-minute
short cycle timer has run out. If the high pressure
switch trips a third time within one hour, the unit is in
“hard” lockout indicating something is certainly wrong
and it will not restart itself.
As soon as the defrost cycle kicks in, remove the
shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and
run through the 1-minute minimum defrost length
sequence in a matter of seconds and will automatically
terminate the defrost sequence.
Code "1", go to Step #6; Code "2", go to Step#7; Fast Blink, go to Step #5
Check for proper operation; if still needed, go back to Step #1.
Yes = go to Step #10; No = go to Step #11
Yes = go to Step #12; No = go to Step #13
Check thermostat wiring, incorrect phase of unit (see section on Phase Monitor), and finally unit wiring.
Check across fan relay on heat pump control. (Com-NC)
Replace heat pump control.
Check for 24V between RV-C and B-C.
1. Check control circuit wiring.
2. Replace heat pump control.
Check for open or shorted coil.
Replace solenoid coil.
Disconnect temperature sensor from board and jumper across "SPEEDUP" terminals and "SEN
JMP" terminals. This should cause the unit to go through a defrost cycle within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
Jumper across "SPEEDUP" terminal.
This should cause the unit to come out of defrost within one minute.
1. If unit comes out of defrost cycle, replace temperature sensor.
2. If unit does not come out of defrost cycle, replace heat pump control.
LED Blink Codes
Manual 2100-603B
Page 38 of 44
CHECKING TEMPERATURE SENSOR
1. Disconnect temperature sensor from board and
from outdoor coil.
2. Use an ohmmeter to measure the resistance of the
sensor. Also use ohmmeter to check for short or
open.
3. Check resistance reading to chart of resistance use
sensor ambient temperature. (Tolerance of part is
±10%.)
TABLE 6
TEMPERATURE (F) VS RESISTANCE (R) OF TEMPERATURE SENSOR
FRFRFRFR
-25.019687113.05698553.01937489.07507
-24.019009914.05528452.01886790.07334
-23.018358515.05364053.01837591.07165
-22.017731816.05205154.01798992.07000
-21.017128917.05051455.01743493.06840
-20.016548718.04902856.01698494.06683
-19.015990419.04759057.01654795.06531
-18.015452920.04620058.01612296.06383
-17.014935521.04485559.01571097.06239
-16.014437422.04355460.01531098.06098
-15.013957623.04229561.01492199.05961
-14.013495624.04107762.014544100.05827
-13.013050625.03989863.014177101.05697
-12.012621926.03875764.013820102.05570
-11.012208927.03765265.013474103.05446
-10.011810828.03658366.013137104.05326
-9.011427229.03554867.012810105.05208
-8.011057530.03454568.012492106.05094
-7.010701031.03357469.012183107.04982
-6.010357432.03263470.011883108.04873
-5.010026033.03172371.011591109.04767
-4.09706434.03084072.011307110.04663
-3.09398135.02998673.011031111.04562
-2.09100836.02915774.010762112.04464
-1.08813937.02835575.010501113.04367
0.08537138.02757776.010247114.04274
1.08269939.02682377.010000115.04182
2.08012140.02609278.09760116.04093
3.07763241.02538379.09526117.04006
4.07523042.02469680.09299118.03921
5.07291043.02403081.09077119.03838
6.07067044.02338482.08862120.03757
7.06850745.02275883.08653121.03678
8.06641846.02215084.08449122.03601
9.06439947.02156185.08250123.03526
10.06244948.02098986.08057124.03452
11.06056549.02043587.07869
12.05874550.01989688.07686
4. If sensor resistance reads very low, then sensor is
shorted and will not allow proper operation of the
heat pump control.
5. If sensor is out of tolerance, shorted, open, or
reads very low ohms, it should be replaced.
Manual 2100-603B
Page 39 of 44
TROUBLESHOOTING ECM™ MOTORS
CAUTION:
Disconnect power from unit before removing or replacing
connectors, or servicing motor. To avoid electric shock
from the motor’s capacitors, disconnect power and wait at
least 5 minutes before opening motor.
Symptom Cause/Procedure
Motor rocks slightly • This is normal start-up for ECM
when starting
Motor won’t start • Check blower turns by hand
• No movement
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
(G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
• Perform Moisture Check
• Motor rocks, • Check for loose or compliant motor mount
but won’t start
• Perform motor/control replacement check
Motor oscillates up • It is normal for motor to oscillate with no
& down while being load on shaft
tested off of blower
Motor starts, but
runs erratically
• Varies up and down • Check line voltage for variation or “sag”
or intermittent • Check low voltage connections
(G, Y, W, R, C) at motor, unseated pins in
motor harness connectors
• Check “Bk” for erratic CFM command (in
variable-speed applications)
• Check out system controls, Thermostat
• Perform Moisture Check
• “Hunts” or “puffs” at • Does removing panel or filter reduce
high CFM (speed) “puffing”?
- Reduce restriction
- Reduce max airflow
• Stays at low CFM • Check low voltage (Thermostat) wires and
despite system call connections
for cool or heat CFM • Verify fan is not in delay mode; wait until
delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check
• Stays at high CFM • “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
complete
• Perform motor/control replacement check
• Blower won’t shut off •
Check for Triac switched thermostat or solid state relay
Excessive noise• Determine if it’s air noise, cabinet, duct or motor noise; interview customer, if necessary
• Air noise • High static creating high blower speed?
- Is airflow set properly?
- Does removing filter cause blower to slow
down? Check filter
- Use low-pressure drop filter
- Check/correct duct restrictions
• Check power at motor
• Make sure blower wheel is tight on shaft
Current leakage from controls into G, Y or W?
Symptom Cause/Procedure
• Noisy blower or cabinet • Check for loose blower housing, panels, etc.
• High static creating high blower speed?
- Check for air whistling through seams in
ducts, cabinets or panels
- Check for cabinet/duct deformation
• “Hunts” or “puffs” at • Does removing panel or filter reduce
high CFM (speed)
- Reduce restriction
- Reduce max. airflow
Evidence of Moisture
• Motor failure or • Replace motor and
malfunction has occurred
and moisture is present
• Evidence of moisture • Perform Moisture Check
present inside air mover
“puffing”?
Perform Moisture Check
Do Don’t
• Check out motor, controls, • Automatically assume the motor is bad.
wiring and connections
thoroughly before replacing
motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
water can’t get in positions
- Install “drip loops”
• Use authorized motor and • Replace one motor or control model # with
model #’s for replacement another (unless an authorized replacement)
• Keep static pressure to a • Use high pressure drop filters; some have
minimum: H20 drop!
- Recommend high • Use restricted returns
efficiency, low static filters
- Recommend keeping filters
clean.
- Design ductwork for min.
static, max. comfort
- Look for and recommend
ductwork improvement,
where necessary
• Size the equipment wisely • Oversize system, then compensate with low
airflow
• Check orientation before • Plug in power connector backwards
inserting motor connectors • Force plugs
Moisture Check
• Connectors are oriented “down” (or as recommended by equipment
manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airflow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet
Comfort Check
• Check proper airflow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?
½"
Manual 2100-603B
Page 40 of 44
™
MOTORS CONT’D.
8b. IF REPLACING AN ECM 2.3 CONTROLWITH AN ECM 2.3CONTROL, the plastic tab and shorter through-bolts are not needed. Thecontrol can be oriented in two positions 180° apart. MAKE SURE THEORIENTATION YOU SELECT FOR REPLACING THECONTROL ASSURES THE CONTROL'S CABLE CONNECTORSWILL BE LOCATED DOWNWARD IN THE APPLICATION SOTHAT WATER CANNOT RUN DOWN THE CABLES AND INTOTHE CONTROL.Simply orient the new control to the motor's endshield,
insert bolts, and tighten. DO NOT OVERTIGHTEN THE BOLTS.
8c. IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0
CONTROL (It is recommended that ECM 2.3 controls be used for allreplacements), the new control must be attached to the motor using
throughboltsidenticaltothoseremovedwiththeoriginalcontrol.DONOT OVERTIGHTEN THE BOLTS.
9.Reinstall the blower/motor assembly into the HVAC equipment.
Follow the manufacturer's suggested procedures.
10. Plug the 16-pin control plug into the motor. The plug is keyed.
Make sure the connector is properly seated and latched.
11. Plug the 5-pin power connector into the motor. Even though theplug is keyed, OBSERVE THE PROPER ORIENTATION. DO NOTFORCE THE CONNECTOR.It plugs in very easily when properlyoriented. REVERSING THIS PLUG WILL CAUSE IMMEDIATE
FAILURE OF THE CONTROL MODULE.
12.
Final installation check. Make sure the motor is installed as follows:a.Unit is as far INTO the blower housing as possible.b.Belly bands are not on the control module or covering vent holes.c.Motor connectors should be oriented between the 4 o’clock and 8
o’clock positions when the blower is positioned in its finallocation and orientation.
d.Add a drip loop to the cables so that water cannot enter the motor
by draining down the cables. Refer to Figure 26.
The installation is now complete. Reapply the AC power to the HVACequipment and verify that the new motor control module is workingproperly. Follow the manufacturer's procedures for disposition of the oldcontrol module.
Replacing ECM Control Module
To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:
1. You MUST have the correct replacement module. The controls
are factory programmed for specific operating modes. Even though
they look alike, different modules may have completely different
functionality.
USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.
2. Begin by removing AC power from the furnace or air handler
being serviced. DO NOT WORK ON THE MOTOR WITH AC POWER APPLIED. To avoid electric shock from the motor’s capacitors,
disconnect power and wait at least 5 minutes before opening motor.
3. It is usually not necessary to remove the motor from the blower
assembly. However, it is recommended that the whole blower
assembly, with the motor, be removed from the furnace/air handler.
(Follow the manufacturer’s procedures). Unplug the two cable
connectors to the motor. There are latches on each connector. DO NOT PULL ON THE WIRES. The plugs remove easily when properly
released.
4. Locate the two standard ¼" hex head bolts at the rear of the
control housing (at the back end of the control opposite the shaft
end). Refer to Figure 28. Remove these two bolts from the
motor and control assembly while holding the motor in a way that
will prevent the motor or control from falling when the bolts are
removed. If an ECM2.0 control is being replaced (recognized by an
aluminum casting rather that a deep-drawn black steel can housing
the electronics), remove only the hex-head bolts. DO NOT REMOVE
THE TORX-HEAD SCREWS.
5. The control module is now free of mechanical attachment to the
motor endshield but is still connected by a plug and three wires
inside the control. Carefully rotate the control to gain access to the
plug at the control end of the wires. With thumb and forefinger,
reach the latch holding the plug to the control and release it by
squeezing the latch tab and the opposite side of the connector
plug and gently pulling the plug out of the connector socket in the
control. DO NOT PULL ON THE WIRES. GRIP THE PLUG ONLY.
6. The control module is now completely detached from the motor.
Verify with a standard ohmmeter that the resistance from each
motor lead (in the motor plug just removed) to the motor shell is
>100K ohms. Refer to Figure 29. (Measure to unpainted motor
end plate.) If any motor lead fails this test, do not proceed to
install the control module. THE MOTOR IS DEFECTIVE AND MUST BE REPLACED. Installing the new control module will cause it to
fail also.
7. Verify that the replacement control is correct for your
application. Refer to the manufacturer's authorized replacement
list. USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION. Orient the control module so
that the 3-wire motor plug can be inserted into the socket in the
control. Carefully insert the plug and press it into the socket until
it latches. A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED.
Finish installing the replacement control per one of the
three following paragraphs, 8a, 8b or 8c.
8a. IF REPLACING AN ECM 2.0 CONTROL (control in cast
aluminum can with air vents on the back of the can) WITH AN ECM
2.3 CONTROL (control containing black potting for water protection
in black deep-drawn steel case with no vents in the bottom of the
can), locate the two through-bolts and plastic tab that are packed
with the replacement control. Insert the plastic tab into the slot at
the perimeter of the open end of the can so that the pin is located
on the inside of the perimeter of the can. Rotate the can so that
the tab inserts into the tab locater hole in the endshield of the
motor. Using the two through-bolts provided with the replacement
control, reattach the can to the motor.
THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN THE
BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0 CONTROL
AND MUST BE USED IF SECURE ATTACHMENT OF THE
CONTROL TO THE MOTOR IS TO BE ACHIEVED.
DO NOT OVERTIGHTEN THE BOLTS.
8b. IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 2.3
CONTROL, the plastic tab and shorter through-bolts are not needed. The control can be oriented in two positions 180° apart. MAKE
SURE THE ORIENTATION YOU SELECT FOR REPLACING THE
CONTROL ASSURES THE CONTROL'S CABLE CONNECTORS WILL
BE LOCATED DOWNWARD IN THE APPLICATION SO THAT WATER
CANNOT RUN DOWN THE CABLES AND INTO THE CONTROL.
Simply orient the new control to the motor's endshield, insert bolts,
and tighten. DO NOT OVERTIGHTEN THE BOLTS.
8c. IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0
CONTROL (It is recommended that ECM 2.3 controls be used for all
replacements), the new control must be attached to the motor using
through bolts identical to those removed with the original control. DO
NOT OVERTIGHTEN THE BOLTS.
9. Reinstall the blower/motor assembly into the HVAC equipment.
Follow the manufacturer's suggested procedures.
10. Plug the 16-pin control plug into the motor. The plug is keyed.
Make sure the connector is properly seated and latched.
11. Plug the 5-pin power connector into the motor. Even though
the plug is keyed, OBSERVE THE PROPER ORIENTATION. DO NOT FORCE THE CONNECTOR. It plugs in very easily when properly
oriented. REVERSING THIS PLUG WILL CAUSE IMMEDIATE
FAILURE OF THE CONTROL MODULE.
12. Final installation check. Make sure the motor is installed as
follows:
a. Unit is as far INTO the blower housing as possible.
b. Belly bands are not on the control module or covering vent
holes.
c. Motor connectors should be oriented between the 4 o’clock
and 8 o’clock positions when the blower is positioned in its
final location and orientation.
d. Add a drip loop to the cables so that water cannot enter the
motor by draining down the cables. Refer to Figure 30.
The installation is now complete. Reapply the AC power to the HVAC
equipment and verify that the new motor control module is working
properly. Follow the manufacturer's procedures for disposition of the
old control module.
Only remove
Hex Head Bolts
ECM 2.0
Note:
Use the shorter
bolts and
alignment pin
supplied when
replacing an
ECM 2.0
control.
Figure 28Figure 29
Figure 24
Figure 3
Control Disassembly
Motor Connector
(3-pin)
ECM
2.3/2.5
Push until
Latch Seats
Over Ramp
From Motor
Circuit
Board
Power Connector
(5-pin)
Hex-head Screws
Motor
Motor Connector
(3-pin)
Control Connector
(16-pin)
Back of
Control
Figure 25
Figure 4
Winding Test
Motor OK when
R > 100k ohm
Figure 30
Figure 26
Figure 5
Drip Loop
Connector Orientation
Between 4 and 8 o'clock
Drip Loop
Manual 2100-603B
Page 41 of 44
FAN BLADE SETTING DIMENSIONS
Any service work requiring removal or adjustment in the
fan and/or motor area will require that the dimensions
in Table 7 be checked and blade adjusted in or out of
the motor shaft accordingly.
R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efficiency ratings were determined by testing with
this refrigerant charge quantity. Reference Table 8.
FIGURE 31
FAN BLADE SETTING
TABLE 7
FAN BLADE DIMENSIONS
MODEL
All
Q**H2D
Models
DIMENSION A
(INCHES)
.750
The following pressure tables show nominal
pressures for the units. Since many installation
specific situations can affect the pressure readings,
this information should only be used by certified
technicians as a guide for evaluating proper system
performance. They shall not be used to adjust charge.
If charge is in doubt, reclaim, evacuate and recharge
the unit to the serial plate charge.
TABLE 8
SUBCOOLING AT LIQUID LINE
MODEL
RATED
CFM
Q24H2D80023 - 2522 - 24
Q30H2D100023 - 2523 - 25
Q36H2D120019 - 2117 - 19
Q42H2D120016 - 1815 - 17
Q48H2D140019 - 2119 - 21
Q60H2D155022 - 2422 - 24
95°F OD
TEMPERATURE
82°F OD
TEMPERATURE
TABLE 9
INDOOR BLOWER PERFORMANCE
Model
Q24H2D o.100.5800N/A800700800
Q30H2D.150.81000N/A10009101000
Q36H2D.150.812001000100011751000
Q42H2D.150.812001000100011751000
Q48H2D.150.814001100110011751250
Q60H2D.200.515501250110014001250
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjust itself to maintain
Maximum ESP (inches WC) shown is with 1" thick disposable filter (reduced by .2 for 2" filter).
Rated CFM for ducted applications – required for maximum performance rating. To obtain full CFM on models Q36H2D, Q42H2D, Q48H2D and
Q60H2D connect the pink jumper wire (provided) to terminal #G2 and #Y on the low voltage terminal block located in the circuit breaker box.
Optional CFM – the unit is shipped from the factory set to operate at the optional CFM level shown. This provides lower operating sound levels
for non-ducted, free discharge applications. This reduces system capacity performance by approximately 2% at the same energy efficiency.
Continuous fan CFM is the total air being circulated during continuous fan mode.
Indoor airflow during periods of high humidity when system is operating under control of optional humidistat for maximum humidity reduction.
o Model Q24H2D – when operating on 2nd stage heating the indoor air will increase to 1000 CFM.
Rated
ESP
approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at both
230/208 or 460 volts.
Max. ESP
Rated CFM
Optional
CFM
Continuous
CFM
CFM @
Max. ESP
Dehum.
CFM
Manual 2100-603B
Page 42 of 44
TABLE 10
COOLING PRESSURE
(ALL TEMPERATURES IN DEGREES F)
MODEL
Q24H2
Q30H2
Q36H2
Q42H2
Q48H2
Q60H2
RETURN
AIR
TEMP.
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
75 DB
62 WB
80 DB
67 WB
85 DB
72 WB
PRESSURE
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
AIR TEMPERATURE ENTERING OUTDOOR COIL
75°80°85°90°95°100°105°110°115°
122
369
130
378
135
391
122
360
131
369
136
382
122
367
130
376
135
389
118
372
126
382
130
395
119
372
127
382
131
395
108
378
115
388
119
402
121
378
129
388
134
402
123
377
132
387
137
401
124
390
133
400
138
414
121
394
129
404
134
418
122
394
130
404
135
418
109
395
117
405
121
419
121
391
129
401
134
415
124
398
133
408
138
422
128
413
137
424
142
439
123
416
132
427
137
442
124
417
133
428
138
443
111
413
119
424
123
439
121
407
129
417
134
432
126
419
135
430
140
445
130
437
139
448
144
464
125
440
134
451
139
467
127
442
136
453
141
469
114
435
122
446
126
462
122
426
130
437
135
452
128
444
137
455
142
471
133
460
142
472
147
489
128
465
137
477
142
494
130
467
139
479
144
496
116
458
124
470
128
486
122
449
131
460
136
476
130
470
139
482
144
499
135
485
144
497
149
514
130
491
139
504
144
522
132
493
141
506
146
524
119
485
127
497
131
514
123
474
132
486
137
503
132
498
141
511
146
529
137
508
146
521
151
539
132
520
141
533
146
552
134
522
143
535
148
554
121
513
129
526
134
544
125
503
134
516
139
534
134
528
143
542
148
561
137
533
147
547
152
566
134
549
143
563
148
583
135
550
144
564
149
584
123
544
132
558
137
578
128
535
137
549
142
568
136
561
145
575
150
595
138
558
148
572
153
592
136
579
145
594
150
615
136
580
145
595
150
616
126
577
135
592
140
613
Low side pressure ± 4 psig
High side pressure ± 10 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the
system, the charge should be removed, system evacuated and recharged to serial plate instructions.
75°F outdoor temperature condenser fan motor is running on low speed.
When the system is operating in the dehumidification mode, the suction pressure will be reduced by 4 to 8 psig and the discharge
pressure will be reduced by 19 to 22 psig.
Manual 2100-603B
Page 43 of 44
TABLE 11
HEATING PRESSURE
(ALL TEMPERATURES IN DEGREES F)
RETURN
MODEL
AIR
TEMP.
Q24H2D70
Q30H2D70
Q36H2D70
Q42H2D70
Q48H2D70
Q60H2D70
PRESSURE
Low Side
High Side35273422844929556307623186932976340833518936296374
Low Side
High Side33278402904730354315613276734074352813648837795389
Low Side
High Side33266402754728553295603056731574325803348734494354
Low Side
High Side2926536275422864929656306633177032777337833479035897368
Low Side
High Side3126837280442915130258314643257133678348853599237098382
Low Side
High Side2225730270372824429552308593206633373346813588837195384
05101520253035404550556065
AIR TEMPERATURE ENTERING OUTDOOR COIL
103
385
102
401
100
364
110
396
109
414
107
374
104
378
105
393
103
396
116
407
116
426
114
384
111
389
112
404
110
409
TABLE 12
DEHUMIDIFICATION RELAY LOGIC BOARD
Inputs to BoardOutputs From Board
NOTESGYBW2E1A1DRAT G1 BKYORVWE1A2 TWV
Cooling Mode Unoccupied1XXXXXXX
Cooling Mode Occupied1XXXXX
123
418
122
438
121
393
117
399
119
416
117
422
1st Stage Heating Occupied2XXXXXXXXX
1st Stage Heating Unoccupied2XXXXXXX
2nd Stage Heating Occupied3XXXXXXXXXXX
2nd Stage Heating Unoccupied3XXXXXXXXX
Emergency HeatXXXXXX
Dehumidification Occupied4XXXXXX
Dehumidification Unoccupied4X5555
Dehumidification w/RAT ClosedXXXXXXX
Fan Only OccupiedXXXX
Fan Only UnoccupiedXX
NOTES:
1. Cooling takes precedence over dehumidification. A cooling call will cancel dehumidification.
2. Dehumidification takes precedence over first stage heating.
3. A second stage heating call cancels dehumidification.
4. The relay logic board has a jumper on it to choose between full-time dehumidification and occupied dehumidification only. With
the jumper in the 1-2 position dehumidification is available full-time. With the jumper in the 2-3 position dehumidification is
available only when the room is occupied. The room is considered occupied when the A1 terminal is energized.
5. These outputs will be energized if the jumper is in the full time dehumidification position. They will be off if the jumper is in the
occupied dehumidification only position.
Manual 2100-603B
Page 44 of 44
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.