T able 1 1 Pressure T able - Cooling ....................... 18
T able 12 Pressure Table - Heating....................... 18
Getting Other Information and Publications
These publications can help you install the air conditioner or
heat pump. You can usually find these at your local library
or purchase them directly from the publisher. Be sure to
consult current edition of each standard.
National Electrical Code ........................... ANSI/NFPA 70
Standard for the Installation...................... ANSI/NFPA 90A
of Air Conditioning and
Ventilating Systems
Standard for Warm Air .............................ANSI/NFPA 90B
Heating and Air
Conditioning Systems
Load Calculation for .................................ACCA Manual J
Residential Winter and
Summer Air Conditioning
Duct Design for Residential......................ACCA Manual D
Winter and Summer Air Conditioning
and Equipment Selection
For more information, contact these
publishers:
ACCA — Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSI — American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE — American Society of Heating
Refrigerating, and
Maximum time delay fuse or HACR type circuit breaker. HACR type not applicable to 460 volt.
Q
75 degree C cooper wire size, basic unit only.
R
TABLE 2
OPTIONAL FIELD INSTALLED HEATER PACKAGES
ONLY TO BE USED WITH THE HEAT PUMP MODELS INDICATED
R
dleiF
rewoP
gniriW
R
dnuorG
eziSeriW
egakcaPretaeH
.oNledoM
50A-CP3HE
01A-BP3HE
01A-CP3HE
51A-CP3HE
90B-BP3HE
51B-BP3HE
dnastloV
esahP4221HP0321HP6321HPB-6321HP
X
1/042
X
X
X
X
X
X
X
3/042
X
X
TABLE 3
OPTIONAL FIELD-INSTALLED ELECTRIC HEATER TABLE
&WK.rtH
yticapaC
@
retaeH
ledoM.gkP
.oN
01A-BP3HE
50A-CP3HE
01A-CP3HE
51A-CP3HE
90B-BP3HE
51B-BP3HE
Q
R
S
stloVtinU
esahP
1-802/04201001,4305.7000,627.1413506601
1-802/042
5
1-802/042
01
1-802/042
51
3-802/042
9
3-802/042
51
Time delay fuses or “HACR” type circuit breakers must be used for 60 and smaller sizes. Standard fuses
or circuit breakers are suitable for sizes 70 and larger. 480V circuit breakers are not “HACR” type.
Based on wire suitable for 75° C. Other wiring materials must be rated for marked “Minimum Circuit
Ampacity” or greater.
Based upon T able 250-95 of N.E.C. 1993. See electrical data for basic heat pump for Circuit A wiring
specification requirements.
ro(V042
fiV084
)elbacilppa
@
001,71
001,43
002,15
007,03
002,15
&WK.rtH
@
yticapaC
stloV802
57.3
05.7
52.11
57.6
52.11
008,21
000,62
004,83
000,32
004,83
V042
saV084ro
elbacilppa
spmA.rtH
8.02
7.14
5.2606/03
7.12
2.63
retaeH
.oN
lanretnI
dleiF
sesuF
.stkC
1
1
1
1
1
muminiM
tiucriC
yticapmA
62
35
97
82
64
Q
BtiucriC
R
mumixaM
tnerrucrevO
noitcetorP
03
06
08
03
05
6
4
8
S
dleiF
rewoP
gniriW
01
01
dnuorG
eriW
eziSWKHUTBWKHUTB
01
01
8
01
01
IMPORTANT:While this electrical data is presented as a guide, it is important to electrically connect properly size fuses
and conductor wires in accordance with the National Electrical Code and all existing local codes.
Manual 2100-344
Page2
GENERAL INSTRUCTIONS
IMPORTANT
The equipment covered in this manual is to be installed by
trained, experienced service and installation technicians.
Any heat pump is more critical of proper operating charge
and an adequate duct system than a straight air conditioning
unit. All duct work, supply and return ducts, must be
properly sized for the design air flow requirement of the
equipment. ACCA is an excellent guide to proper sizing.
All duct work or portions thereof not in the conditioned
space should be properly insulated in order to both conserve
energy and prevent condensation or moisture damage.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for
external signs of shipping damage. If damage is found, the
receiving party must contact the last carrier immediately,
preferably in writing, requesting inspection by the carrier’s
agent.
GENERAL
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the electrical
wiring connections to the unit.
These instructions and any instructions packaged with any
separate equipment required to make up the entire heat
pump system should be carefully read before beginning the
installation. Note particularly “Starting Procedure” and any
tags and/or labels attached to the equipment.
FIELD INSTALLED HEATER PACKAGES
(OPTIONAL)
These packaged heat pumps are manufactured without
supplementary electric heaters. Supplementary heaters
EH3P series (to fit PH1224, PH1230, and PH1236) are
available for simple, fast, field installation.
A separate field power circuit is required for the
supplementary heaters.
IMPORTANT:Refer to Table 4 when designing duct
work for maximum available static
pressure with heater installed.
Refer to the electrical data shown on pages 2 and 3 for
proper application information on all available heater
combinations and what units they can be used with. It also
shows the applicable circuit ampacities, fuse size, and wire
size for each heater combination.
Refer to the installation instructions packed with the heater
for details on how to insert it into the basic unit.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made.
Manual 2100-344
Page3
MIS-1177
FIGURE 1
PREFABRICATED ROOF CURB SPECIFICATIONS
HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP, WELDED/LEAKPROOF
*Duct Sizing Information
Return Air Dimension “C” is lengthSupply Air Dimension “C” is length
Return Air Dimension “H” is widthSupply Sir Dimension “J” is width
FIGURE 2
FIELD FABRICATED CURBING
dooHfooR
ledoM
dooHfooR
ledoM
tinU
ledoM
gninoitidnoCriA
stinU
,0321HP,4221HP
6321HP
E
4221HP
63EHR
0321HP
14
6321HP
MIS-1178
Manual 2100-344
Page4
INSTALLATION
LOCATION
GENERAL
The unit must be located outside, or in a well ventilated
area. It must not be in the space being heated or cooled. A
sound absorbing material should be considered if the unit is
to be installed in such a position or location that might cause
transmission of sound or vibration to the living area or
adjacent buildings.
SLAB MOUNTING
In areas where winter temperatures DO NOT go below
32° F for periods over twelve hours, the unit may be slab
mounted at grade level. When installing unit at grade level,
install on a concrete slab at least four inches above finished
grade level. Slab should have a slope tolerance away from
the building structure of at lease 1/4 inch per foot, while
being level from side to side. This will prevent ice buildup
under the unit during defrost cycles. Place slab in a location
where runoff water from higher ground will not collect
around unit. See Figure 3.
A minimum of 18 inches should be provided between the
coil inlet and any building surfaces. Provide at least four
feet between coil outlet and any building wall, fences or
other vertical structures. Provide a minimum of three feet
clearance on the service access side of the unit. See
Figure 4
ROOF MOUNTING
When a unit is installed in areas where low ambient
temperatures or strong winter winds exist, it should be
placed so prevailing winter winds are not in direct line with
the heat pump coil. If this is not possible, a wind barrier
should be constructed. Place barrier 24 inches from the coil
inlet side of the unit and in the direction of prevailing winds.
Size barrier at least the same height and width as the unit.
This may be necessary on ground level installations, also.
See Figure 5.
WINTER INSTALLATION BELOW 32°F
In areas where winter conditions go below 32°F for
extended periods, the unit must be elevated above the
mounting surface to prevent snowfall or defrost ice
accumulation from interfering with the operation of the unit.
A minimum of twelve inch elevation is recommended, while
greater elevation may be required for areas of high snow
accumulation. Poured concrete, steel framework, brick,
cement block, etc., can be utilized to construct a suitable
raised mounting platform. See Figure 6.
DUCT WORK
Refer to Tables 4, 5 and 5A when designing duct work for
maximum static pressure available with the specific model
and heater package being installed. Unit duct work is
suitable for 0” clearance to combustible materials.
TYPICAL INSTALLATIONS
1.
ROOF MOUNTED
sturdy base on the roof of the building. Return air to the
unit is brought through a single return grille (grilles with
built-in filters are best since they enable easy access for
filter changing). Return air ducts are attached to the
lower section of the front panel. Supply air is brought
from the unit to attic duct work or to a furred down hall.
Supply air duct is attached to the top of the front panel.
CAUTION: All outdoor duct work must be thoroughly
insulated and weatherproofed. All attic duct work
must be thoroughly insulated. Two inch thick
insulation with suitable vapor barrier is
recommended for both outdoor and attic runs.
In roof top installation, as in all installations, the heat
pump must be level from side to side. However, the unit
should have a pitch along the length to assure complete
external drainage of precipitation and of defrost
condensate.
CRAWL SPACE
2.
space must be well insulated and provided with a vapor
barrier. In addition, the crawl space must be thoroughly
ventilated and provided with a good vapor barrier as a
ground cover. It is most desirable to install the unit
outdoors rather than inside the crawl space, so that it
will be readily accessible for service. In addition, it is
necessary to dispose of the condensate from the outdoor
coil on the heating cycle, and this is virtually impossible
with the unit installed inside the crawl space.
3.
SLAB MOUNTED AT GROUND LEVEL
type installation is ideal for homes with a slab floor
construction where a roof mounted unit is not desired.
The supply and return duct work can be run through a
furred closet space.
4.
THROUGH THE WALL
requires a suitable framework to be fabricated capable of
withstanding the unit weight. Normally the unit will be
insulated so as to minimize supply and return duct work.
5.
OTHER INSTALLATIONS
installations are possible with the packaged heat pump.
No matter what the installation, always consider the
following facts:
A. Insure that the discharge air is not obstructed in any
way so as to cause operation difficulties.
B. The indoor coil drain pan is equipped with a
coupling that must be piped through a condensate
drain trap to a suitable drain.
C. Always mount the unit is such a position that it may
be easily reached for servicing and maintenance.
D. Insure that the unit is clear so that proper air flow
over the outdoor coil will be maintained.
If this unit is operated in cooling below a 65° outdoor
ambient temperature, the installation of low ambient
controls (CMA-6) to unit is required.
– The unit is mounted on a
– Duct work installed in crawl
– This
– This type installation
– Many other
Manual 2100-344
Page5
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.