Bard PH1230, PH1236, PH1224 User Manual

Page 1
INST ALLA TION INSTRUCTIONS
SINGLE P ACKAGE
HEA T PUMPS
MODELS
PH1224 PH1230 PH1236
Since 1914...Moving ahead, just as planned.
Manual : 2100-344 File: Volume II Tab 11 Date: 08-21-98
© Copyright 1998
Page 2
Contents
Getting Other Informations and Publications ........ 1
General Instructions................................................. 3
Important ................................................................ 3
Shipping Damage .................................................... 3
General ................................................................ 3
Field-Installed Heater Packages (Optional).............. 3
Installation................................................................. 5
Location ................................................................ 5
Typical Installations .................................................. 5
Condensate Drain Trap............................................ 8
Air Filters ................................................................ 8
Wiring – Main Power................................................ 9
Wiring – 24V Low Voltage Control Circuit................ 9
Thermostats........................................................... 10
Thermostat Indicator Lamps ...................................1 1
Emergency Heat Position .......................................1 1
Transformer Taps....................................................1 1
Compressor Cut-Off Thermostat and Outdoor
Thermostat Wiring ..................................................11
Start Up and Operation .......................................... 12
Three Phase Scroll Compressor Start Up
Information............................................................. 12
Sequence of Operation.......................................... 12
Defrost Cycle ......................................................... 12
Start Up Notes ....................................................... 12
Service and Troubleshooting ................................ 14
Service Hints.......................................................... 14
Pressure Service Ports .......................................... 14
Refrigerant Charge ................................................ 14
Fan Blade Settings................................................. 14
Solid State Heat Pump Control
Troubleshooting Procedure.................................... 14
Troubleshooting Guide ........................................... 15
Checking T emperature Sensor Check Out............. 16
Temperature vs. Resistance of
Temperature Sensor Chart..................................... 16
Suction and Discharge Tube Brazing..................... 17
Pressure T ables ..................................................... 18
Wiring Diagrams ............................................. 19 - 21
Figures
Figure 1 Prefabricated Rood Curb
Specifications .......................................... 4
Figure 2 Field Fabricated Curbing......................... 4
Figure 3 Elevated Mounting Platforms .................. 6
Figure 4 Airflow and Service Access
Clearances .............................................. 6
Figure 5 Roof Top Application ............................... 7
Figure 6 Slab Mounting at Ground Level ............... 7
Figure 7 Condensate Drain Trap ........................... 8
Figure 8 Low Voltage Wiring ................................. 9
Figure 9 Compressor Cut-Off Thermostat
Wiring (5 and 10 KW) ............................11
Figure 10 Compressor Cut-Off Thermostat
Wiring )15 KW ONLY) ...........................11
Figure 11 Heat Pump Control Board..................... 13
Figure 12 Fan Blade Setting Dimensions .............. 14
Figure 13 Brazing Diagram ................................... 17
Tables
Table 1 Electrical Data......................................... 2
T able 2 Optional Field Installed Heater
Packages ................................................ 2
T able 3 Optional Field Installed Heater Table....... 2
Table 4 Rated CFM and Rated ESP.................... 3
Table 5 Air Filter Area and Size ........................... 8
Table 6 Thermostat Wire Size ............................. 9
Table 7 Heat Pump Thermostats ....................... 10
Table 8 V olts, KW and Phase - Compressor
Cut-Off Wiring (5 and 10 KW)...............11
Table 9 V olts, KW and Phase - Compressor
Cut-Off Wiring (15 KW ONLY0 .............11
Table 10 Refrigerant Charge ............................... 14
T able 1 1 Pressure T able - Cooling ....................... 18
T able 12 Pressure Table - Heating....................... 18
Page 3
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ........................... ANSI/NFPA 70
Standard for the Installation...................... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air .............................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for .................................ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential......................ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating, and
Air Conditioning Engineers, Incorporated
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
Commercial Low Pressure, ....................... ACCA Manual Q
Low Velocity Duct System Design
Load Calculation For Commercial ............ACCA Manual N
Summer and Winter Air Conditioning
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-344 Page 1
Page 4
TABLE 1
ELECTRICAL DATA
Q
mumixaM
lanretxE
detaR
&stloV
ledoM
sesahP
gnitarepO
egatloV
egnaR
mumixaM
spmAtinU
rosesuF
.krB.tkC
A.tkCA.tkCA.tkCA.tkC
muminiM
tiucriC
yticapmA
4221HP1-802/032352-7914.4152810101 0321HP1-802/032352-7917.7103220101 6321HP1-802/032352-7918.12047288
B-6321HP3-802/032352-7916.5152910101
Maximum time delay fuse or HACR type circuit breaker. HACR type not applicable to 460 volt.
Q
75 degree C cooper wire size, basic unit only.
R
TABLE 2
OPTIONAL FIELD INSTALLED HEATER PACKAGES
ONLY TO BE USED WITH THE HEAT PUMP MODELS INDICATED
R
dleiF
rewoP
gniriW
R
dnuorG
eziSeriW
egakcaPretaeH
.oNledoM 50A-CP3HE
01A-BP3HE 01A-CP3HE 51A-CP3HE
90B-BP3HE 51B-BP3HE
dnastloV
esahP4221HP0321HP6321HPB-6321HP
X
1/042
X
X X
X
X X
X
3/042
X X
TABLE 3
OPTIONAL FIELD-INSTALLED ELECTRIC HEATER TABLE
&WK.rtH
yticapaC
@
retaeH
ledoM.gkP
.oN
01A-BP3HE 50A-CP3HE
01A-CP3HE 51A-CP3HE
90B-BP3HE 51B-BP3HE
Q
R
S
stloVtinU
esahP
1-802/04201001,4305.7000,627.1413506601 1-802/042
5
1-802/042
01
1-802/042
51
3-802/042
9
3-802/042
51
Time delay fuses or HACR type circuit breakers must be used for 60 and smaller sizes. Standard fuses or circuit breakers are suitable for sizes 70 and larger. 480V circuit breakers are not “HACR” type.
Based on wire suitable for 75° C. Other wiring materials must be rated for marked Minimum Circuit Ampacity or greater.
Based upon T able 250-95 of N.E.C. 1993. See electrical data for basic heat pump for Circuit A wiring specification requirements.
ro(V042
fiV084
)elbacilppa
@
001,71 001,43 002,15
007,03 002,15
&WK.rtH
@
yticapaC
stloV802
57.3
05.7
52.11
57.6
52.11
008,21 000,62 004,83
000,32 004,83
V042
saV084ro elbacilppa
spmA.rtH
8.02
7.14
5.2606/03
7.12
2.63
retaeH
.oN
lanretnI
dleiF
sesuF
.stkC
1 1 1
1 1
muminiM tiucriC
yticapmA
62 35 97
82 64
Q
BtiucriC
R
mumixaM
tnerrucrevO
noitcetorP
03 06 08
03 05
6 4
8
S
dleiF
rewoP
gniriW
01
01
dnuorG eriW eziSWKHUTBWKHUTB
01 01
8
01 01
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly size fuses
and conductor wires in accordance with the National Electrical Code and all existing local codes.
Manual 2100-344 Page 2
Page 5
GENERAL INSTRUCTIONS
IMPORTANT
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work, supply and return ducts, must be properly sized for the design air flow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
FIELD INSTALLED HEATER PACKAGES (OPTIONAL)
These packaged heat pumps are manufactured without supplementary electric heaters. Supplementary heaters EH3P series (to fit PH1224, PH1230, and PH1236) are available for simple, fast, field installation.
A separate field power circuit is required for the supplementary heaters.
IMPORTANT: Refer to Table 4 when designing duct
work for maximum available static pressure with heater installed.
Refer to the electrical data shown on pages 2 and 3 for proper application information on all available heater combinations and what units they can be used with. It also shows the applicable circuit ampacities, fuse size, and wire size for each heater combination.
Refer to the installation instructions packed with the heater for details on how to insert it into the basic unit.
TABLE 4
RATED CFM AND
EXTERNAL STATIC PRESSURE (ESP)
WET COIL (COOLING)
detaR
ledoM
4221HP00802.MFC088-086 0321HP000103.MFC0011-577 6321HP001102.MFC0121-577
MFC
detaR
PSE
dednemmoceR
egnaRwolFriA
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made.
Manual 2100-344 Page 3
Page 6
MIS-1177
FIGURE 1
PREFABRICATED ROOF CURB SPECIFICATIONS
HEAVY GAUGE GALVANIZED WITH WOOD NAILING STRIP, WELDED/LEAKPROOF
ONE PIECE CONSTRUCTION – READY TO INSTALL
CURB AND ROOF DETAILS
fooR
bruCAB*CDEF *J*H
300-24098/3-084/1-044/1-738/3-838/3-53244/3-418/1-9106EHR
*Duct Sizing Information Return Air Dimension “C” is length Supply Air Dimension “C” is length Return Air Dimension “H” is width Supply Sir Dimension “J” is width
FIGURE 2
FIELD FABRICATED CURBING
dooHfooR
ledoM
dooHfooR
ledoM
tinU
ledoM
gninoitidnoCriA
stinU
,0321HP,4221HP
6321HP
E
4221HP
63EHR
0321HP
14
6321HP
MIS-1178
Manual 2100-344 Page 4
Page 7
INSTALLATION
LOCATION
GENERAL
The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the living area or adjacent buildings.
SLAB MOUNTING
In areas where winter temperatures DO NOT go below 32° F for periods over twelve hours, the unit may be slab mounted at grade level. When installing unit at grade level, install on a concrete slab at least four inches above finished grade level. Slab should have a slope tolerance away from the building structure of at lease 1/4 inch per foot, while being level from side to side. This will prevent ice buildup under the unit during defrost cycles. Place slab in a location where runoff water from higher ground will not collect around unit. See Figure 3.
A minimum of 18 inches should be provided between the coil inlet and any building surfaces. Provide at least four feet between coil outlet and any building wall, fences or other vertical structures. Provide a minimum of three feet clearance on the service access side of the unit. See Figure 4
ROOF MOUNTING
When a unit is installed in areas where low ambient temperatures or strong winter winds exist, it should be placed so prevailing winter winds are not in direct line with the heat pump coil. If this is not possible, a wind barrier should be constructed. Place barrier 24 inches from the coil inlet side of the unit and in the direction of prevailing winds. Size barrier at least the same height and width as the unit. This may be necessary on ground level installations, also. See Figure 5.
WINTER INSTALLATION BELOW 32°F
In areas where winter conditions go below 32°F for extended periods, the unit must be elevated above the mounting surface to prevent snowfall or defrost ice accumulation from interfering with the operation of the unit. A minimum of twelve inch elevation is recommended, while greater elevation may be required for areas of high snow accumulation. Poured concrete, steel framework, brick, cement block, etc., can be utilized to construct a suitable raised mounting platform. See Figure 6.
DUCT WORK
Refer to Tables 4, 5 and 5A when designing duct work for maximum static pressure available with the specific model and heater package being installed. Unit duct work is suitable for 0” clearance to combustible materials.
TYPICAL INSTALLATIONS
1.
ROOF MOUNTED
sturdy base on the roof of the building. Return air to the unit is brought through a single return grille (grilles with built-in filters are best since they enable easy access for filter changing). Return air ducts are attached to the lower section of the front panel. Supply air is brought from the unit to attic duct work or to a furred down hall. Supply air duct is attached to the top of the front panel.
CAUTION: All outdoor duct work must be thoroughly
insulated and weatherproofed. All attic duct work must be thoroughly insulated. Two inch thick insulation with suitable vapor barrier is recommended for both outdoor and attic runs.
In roof top installation, as in all installations, the heat pump must be level from side to side. However, the unit should have a pitch along the length to assure complete external drainage of precipitation and of defrost condensate.
CRAWL SPACE
2. space must be well insulated and provided with a vapor barrier. In addition, the crawl space must be thoroughly ventilated and provided with a good vapor barrier as a ground cover. It is most desirable to install the unit outdoors rather than inside the crawl space, so that it will be readily accessible for service. In addition, it is necessary to dispose of the condensate from the outdoor coil on the heating cycle, and this is virtually impossible with the unit installed inside the crawl space.
3.
SLAB MOUNTED AT GROUND LEVEL
type installation is ideal for homes with a slab floor construction where a roof mounted unit is not desired. The supply and return duct work can be run through a furred closet space.
4.
THROUGH THE WALL
requires a suitable framework to be fabricated capable of withstanding the unit weight. Normally the unit will be insulated so as to minimize supply and return duct work.
5.
OTHER INSTALLATIONS
installations are possible with the packaged heat pump. No matter what the installation, always consider the following facts:
A. Insure that the discharge air is not obstructed in any
way so as to cause operation difficulties.
B. The indoor coil drain pan is equipped with a
coupling that must be piped through a condensate drain trap to a suitable drain.
C. Always mount the unit is such a position that it may
be easily reached for servicing and maintenance.
D. Insure that the unit is clear so that proper air flow
over the outdoor coil will be maintained.
If this unit is operated in cooling below a 65° outdoor ambient temperature, the installation of low ambient controls (CMA-6) to unit is required.
– The unit is mounted on a
– Duct work installed in crawl
This
– This type installation
– Many other
Manual 2100-344 Page 5
Page 8
FIGURE 3
ELEVATED MOUNTING PLATFORMS
MIS-1183
FIGURE 4
AIRFLOW and SERVICE ACCESS CLEARANCES
Manual 2100-344 Page 6
MIS-1185
Page 9
FIGURE 5
ROOF TOP APPLICATION
(May also be required for ground level installations.)
MIS-1176
FIGURE 6
SLAB MOUNTING AT GROUND LEVEL
(Above 32° F Outside Temperature)
MIS-1184
Manual 2100-344 Page 7
Page 10
CONDENSATE DRAIN TRAP
It is very important to provide a trap in the condensate drain line to allow a positive liquid seal in the line and assure correct drainage from the coil condensate pan.
Install condensate drain trap shown in Figure 7. Use drain connection size or larger. Do not operate unit without trap. Unit must be level or slightly inclined toward drain. With a trap installed on a unit located in an unconditioned area, water in the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes.
AIR FILTERS
Air filters for the return air side of the system are not provided as part of the various types of applications for these models, and must be field supplied and installed as part of the final installation.
maintained for proper operation. If this is not done, excessive energy use, poor performance, and multiple service problems will result. It is impossible to oversize air filters. Generous sizing will result in cleaner air and coils as well as lower operating costs and extend the time between required changes. Table 6 shows minimum filter areas and recommended filter sizes. Actual filter sizes can vary with the installation due to single or multiple returns utilizing a filter/grille arrangement or being placed immediately ahead of the indoor coil face in the return air duct.
TABLE 5
retliFmuminiM
ledoM
4221HP 0321HP 6321HP
saerA
sehcnierauqs264
)teeferauqs12.3(
dednemmoceR
eziS
1x8/5-03x51
Prior thought should be given to return air location and placement of the air filter(s). The air filter(s) must be of adequate size and readily accessible to the operator of the equipment. Filters must be adequate in size and properly
CONDENSATE DRAIN TRAP
NOTE: If roof hood accessory is to be used, information on air filters may be found under that heading in this manual. Air filters are supplied as part of that package.
FIGURE 7
Manual 2100-344 Page 8
MIS-136
Page 11
remrofsnarT
AV
ALF
eriW
eguaG
htgneLmumixaM
teeFnI
553.202 81 61 41 21
54 06
001 061
052
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical Data” on pages 2.) All models are suitable for connection with copper wire only. These instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.
The electrical specifications on page 2 lists fuse and wire sizes (75° F copper) for all models including the most commonly used heater sizes.
The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.
WIRING – 24V LOW VOLTAGE CONTROL CIRCUIT
Ten (10 ) wires should be run from thermostat subbase to the 24V terminal board in the unit. A ten conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8.
FIGURE 8 – LOW VOLTAGE WIRING
MIS-1187
TABLE 6 – THERMOSTAT WIRE SIZE
Manual 2100-344 Page 9
Page 12
THERMOSTATS
See specific wiring information for the different models, heater KWs, and voltages.
TABLE 7
HEAT PUMP THERMOSTATS
TATSOMREHTESABBUSNOITPIRCSED
540-3048
)1671A148T(
710-3048
)9211R478T(
810-3048
)4201N478T(
240-3048
)0701G1158T(
430-3048
)08-49F1(
720-3048
)17-29F1(
fotraP
tatsomrehT
900-4048
1811L476Q
010-4048
1621F476Q
fotraP
tatsomrehT
fotraP
tatsomrehT
fotraP
tatsomrehT
taeHmE-kcehC:spmaLgnitacidnI
taeHmE-kcehC:spmaLgnitacidnI
revoegnahclaunamrocitamotuA
revoegnahclaunaM;blubyruceM;taehegats2,loocegats1
looC-ffO-taeH-taeHmE:hctiwSmetsyS;nO-otuA:hctiwSnaF
taeHxuA-taeHmE-kcehC:spmaLgnitacidnI
revoegnahclaunaM;blubyrucreM;taehegats2,loocegats1
looC-ffO-taeH-taeHmE:hctiwSmetsyS;nO-otuA:hctiwSnaF
revoegnahcotuA;blubyrucreM;taehegats2,loocegats1
xuA-flaM-pmuP-remE:spmaLgnitacidnI
xuA-flaM-pmuP-remE:spmaLgnitacidnI
Q
R
looC-otuA-taeH-taeHmE-ffO:hctiwSmetsyS;nO-otuA:hctiwSnaF
)deriuqeryrettabon(elbammargorp-nonlatigiD;taehegats2,loocegats1
taeH/looCrootuA-taeHmE-ffO:hctiwSmetsyS;nO-otuA:hctiwSnaF
taeHxuA-taeHmE:noitacidnIyalpsiDkcehC:spmaLgnitacidnI
pukcabyrettaB;)yad7(elbammargorplatigiD;taehegats2,loocegats2
sruoh42repdoirepkcab-tes/pu-tes1;revoegnahclaunamrocitamotuA
yrevocerygrenerorezimonoceroflanimretnoitalitnevelbammargorP
taeH/looCrootuA-taeHmE-ffO:hctiwSmetsyS;nO-otuA:hctiwSnaF
pukcabyrettaB;)yad2/yad5(elbammarforplatigiD;taehegats3,loocegats2
sruoh42repsdoirepkcab-tes/spu-tes4:revoegnahclaunamrocitamotuA
taeH/looCrootuA-taeHmE-ffO:hctiwSmetsyS;nO-otuA:hctiwSnaF
No automatic changeover position – must be manually placed in heat or cool. Reversing valve remains energized
Q
at all times system switch is in heat position (except during defrost cycle). No pressure equalization noise when thermostat is satisfied on either heating or cooling.
Allows thermostat to control both heating and cooling operation when set in AUTO position. Reversing valve de-
R
energizes at end of each ON heating cycle.
Manual 2100-344 Page 10
Page 13
THERMOSTAT INDICATOR LAMPS
The red lamp marked “EM. HT.” comes on and stays on whenever the system switch is placed in Em. Ht. position. The green lamp marked “Check” will come on if there is any problem that prevents the compressor from running when it is supposed to be.
COMPRESSOR CUTOFF THERMOSTAT WIRING (5 and 10 KW)
FIGURE 9
UNIT 24V TERMINAL BOARD
EMERGENCY HEAT POSITION
The operator of the equipment must manually place the system switch in this position. This is done when there is a known problem with the outdoor section, or when the green “Check” lamp comes on indicating a problem.
TRANSFORMER TAPS
230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
TAP RANGE 240 253 – 216 208 220 – 187
NOTE: The voltage should be measured at the field power
connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
COMPRESSOR CUTOFF THERMOSTAT and OUTDOOR THERMOSTAT WIRING
Heat pump compressor operation at outdoor temperatures below 0° F are neither desirable nor advantageous in terms of efficiency. Since most equipment at time of manufacture is not designated for any specific destination of the county and most of the equipment is installed in areas not approaching the lower outdoor temperature range, the compressor cutoffs are not factory installed.
Outdoor thermostats are available to hold off various banks of electric heat until needed as determined by outdoor temperature. The set point of either type of thermostat is variable with geographic region and sizing of the heating equipment to the structure. Utilization of the Heating Application Data and the heat loss calculation of the building are useful in determining the correct set points.
REMOVE FACTORY JUMPER Y-Y1
MIS-1188
ledoMWKstloVesahP
4221HP01,5,00321 0321HP01,5,00321 6321HP01,5,00321
OUTDOOR THERMOSTAT USED AS COMPRESSOR CUTOFF
TABLE 8
5 and 10 KW
COMPRESSOR CUTOFF THERMOSTAT WIRING (15 KW ONLY)
FIGURE 10
UNIT 24V TERMINAL BOARD
REMOVE FACTORY JUMPER Y-Y1
MIS-1189
OUTDOOR THERMOSTAT USED AS COMPRESSOR CUTOFF
TABLE 9
15 KW ONLY
ledoMWKstloVesahP
0321HP510321 6321HP510321
Manual 2100-344 Page 11
Page 14
START UP AND OPERATION
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION
Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, verification of proper rotation must be made. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as, substantially reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time the equipment is put into service. If improper rotation is
corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for over one hour may have a negative impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for several minutes the compressor’s internal protector will trip.
All three phase ZR*3 compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminals should maintain proper rotation direction.
The direction of rotation of the motor may be changed by reversing any two line connections to the unit.
SEQUENCE OF OPERATION
COOLING
compressor contactor starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation, or can be energized by manual fan switch on subbase for constant air circulation.
HEATING
controls heating cycle operation. Two thermostat options, one allowing “AUTO” changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season and thus eliminating pressure equalization noise except during defrost, are to be used. On “AUTO” option, a circuit is completed from R-W1 and R-Y on each heating “On” cycle energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second energizes
– Circuit R-Y makes at thermostat pulling in
– A 24V solenoid coil on reversing valve
the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A thermostat demand for heat completes R-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.
DEFROST CYCLE
The defrost cycle is controlled by temperature and time on the solid state heat pump control.
When the outdoor temperature is in the lower 40° F temperature range or colder, the outdoor coil temperature is 32°F or below. This temperature is sensed by the coil sensor mounted near the bottom of the outdoor coil. Once the coil temperature reaches 32°F or below, the coil sensor sends a signal to the control logic of the heat pump control and defrost timer will start.
After 60 (90 or 30) minutes at 32°F or below, the heat pump control will place the system in the defrost mode.
During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57° F, the coil sensor will send a signal to the heat pump control which will return the system to heating operations automatically.
If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 10 minutes.
There are three settings on the heat pump control -- 30 minutes, 60 minutes, and 90 minutes. Most models are shipped wired on the 60 minutes setting for greatest operating economy. If special circumstances require a change to another time, remove wire connected to terminal 60 and reconnect to desired terminal. (See Figure 11.)
There is a cycle speed up jumper on the control. This can be used to reduce the time between defrost cycle operation without waiting for time to elapse.
There is an initial defrost (sen jmp) jumper on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature. This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.
START UP NOTES
For improved start up performance, wash the indoor coil with dishwasher detergent
Manual 2100-344 Page 12
Page 15
FIGURE 11
HEAT PUMP CONTROL BOARD
MIS-1191
Manual 2100-344 Page 13
Page 16
SERVICE AND TROUBLESHOOTING
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system which shortens equipment service life as well as increasing operating costs.
2. Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the manual reset high pressure switch.
3. The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired operating mode before trying to diagnose any reported service problems.
4. Check all power fuses or circuit breakers to be sure that they are the correct rating.
5. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found in Tables 11 and 12 in this manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressure table to the unit by model number.
FIGURE 12
FAN BLADE SETTING DIMENSIONS
ledoMAnoisnemiD
4221HP 0321HP 6321HP
MIS-1190
"00.1 "57. "57.
SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE
1. Turn on AC power supply to indoor and outdoor units.
2. Turn thermostat blower switch to fan on. The indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)
REFRIGERANT CHARGE
The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 10.
TABLE 10
FeergeD59
detaR
ledoM
4221HP 0321HP 6321HP
The above suction line temperatures are based upon 80° F dry bulb/67° F wet bulb (50% RH) temperature and rated airflow across the evaporator during cooling cycle.
wolfriA
008
0001 0011
DO
erutarepmeT
65-65 65-65 25-05
FeergeD28
DO
erutarepmeT
26-16 06-85 45-25
FAN BLADE SETTINGS
Shown in Figure 12 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions in Figure 12 be checked and blade adjusted in or out on the motor shaft accordingly.
3. Turn thermostat blower switch to Auto position. Indoor blower should stop.
4. Set system switch to heat or cool. Adjust thermostat to call for heat or cool. The indoor blower, compressor, and outdoor fan should start.
NOTE: If there is no power to 24 volt transformer, the
compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.
Manual 2100-344 Page 14
Page 17
TROUBLE SHOOTING GUIDE
motpmySsesuaCelbissoPkcehCottahWriapeRrokcehCotwoH
rotcatnocrosserpmoC
ezigrenetonseod
)gniloocrognitaeh(
noitcetorp
evitcefed
rotomroodtuonaF
nurtonseod
gnitaehrognilooc(
)tsorfedgnirudtpecxe
evitcefed
seodevlavgnisreveR
ezigreneton
)ylnognitaeh(
evitcefed
otniogtonlliwtinU
tsorfed
)ylnognitaeh(
tuoemoctonlliwtinU
tsorfedfo
)ylnognitaeh(
evitcefed
evitcefedrotoMdetrohsroneporofkcehC
evitcefedlioc
.evitcefed
gniriwtiucriclitnoCtinutanoitcennocRrofkcehC
tuokcolrosserpmoCneewtebV42rofkcehC.1
elcyctrohsrosserpmoC
lortnocpmuptaeH
evitcefedrotcatnoCdetrohsroneporofkcehC
evitcefedroticapacrotoM.gnitarroticapackcehC
lortnocpmuptaeH
dionelosevlovgnisreveR
lortnocpmuptaeH
rorosneserutarepmeT
lortnocpmuptaeh
rorosneserutarepmeT
lortnocpmuptaeh
taehrewopottinuroodtuootnoitcennocRnuR
.C-Rneewtebtlov42dna
lortnocpmuptaehnoC-1L
hgihssorcakcehC.2
.hctiwserusserp
C-CCneewtebV42rofkcehC
pmuptaehnoC-Ydna
.lortnoc
elbissoprehtollakcehC
.560-0012launaM.sesuac
.gnidniwlioc
.gnidniwrotom
detrohsroneporofkcehC
.roticapac
noyalernafssorcakcehC
)CN-moC(.lortnocpmuptaeh
detrohsroneporofkcehC
.lioc
C-VRneewtebV42rofkcehC
.C-Bdna
erutarepmettcennocsiD
dnadraobmorfrosnes
pudeepsssorcarepmuj
pmujnesdnaslanimret
esuacdluohssihT.slanimret
ahguorhtogottinueht
enonihtiwelcyctsorfed
.etunim
pudeepsssorcarepmuJ
esuacdluohssihT.slanimret
tsorfedfotuoemocottinueht
.etunimenonihtiw
.lortnocpmup
ffotatsomrehtnrut,C-1LneewtebegatlovonfI.1
.hctiwserusserphgihteserotniaganodna
,tesertonlliwdnaneposihctiwserusserphgihfI.2
.hctiwserusserphgihecalper
pudeepsrepmuj,C-CCneewtebegatlovonfI
dluohsrewopsdnoces01nihtiwdna,lanimret
repmujpudeepsevomeR.C-CCneewtebraeppa
.sdnoces01retfa
.lortnocpmuptaehecalpeR
.rotcatnocecalpeR
.rotomecalpeR
.roticapacecalpeR
.lortnocpmuptaehecalpeR
.liocdionelosecalpeR
.gniriwtiucriclortnockcehC.1
lortnocpmuptaehecalpeR.2
ecalper,elcyctsorfedhguorhtseogtinufI.1
.rosneserutarepmet
ecalper,elcyctsorfedhguorhtogtonseodtinufI.2
.lortnocpmuptaeh
ecalper,elcyctsorfedfotuosemoctinufI.1
.rosneserutarepmet
,elcyctsorfedfotuoemoctonseodtinufI.2
.lortnocpmuptaehecalper
Manual 2100-344 Page 15
Page 18
CHECKING TEMPERATURE SENSOR CHECK OUT
1. Disconnect temperature sensor from board and from outdoor coil.
2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
TEMPERATURE F vs RESISTANCE R OF TEMPERATURE SENSOR
FR FR FR FR
0.52-1786910.51046350.55434710.591356
0.42-9900910.61150250.65489610.693836
0.32-5853810.71415050.75745610.799326
0.22-8137710.81820940.85221610.898906
0.12-9821710.91095740.95017510.991695
0.02-7845610.02002640.06013510.0017285
0.91-4099510.12558440.16129410.1017965
0.81-9254510.22455340.26445410.2010755
0.71-5539410.32592240.36771410.3016445
0.61-4734410.42770140.46028310.4016235
0.51-6759310.52898930.56474310.5018025
0.41-6594310.62757830.66731310.5014905
0.31-6050310.72256730.76018210.7012894
0.21-9126210.82385630.86294210.8013784
0.11-9802210.92845530.96381210.9017674
0.01-8018110.03545430.07388110.0113664
0.9-2724110.13475330.17195110.1112654
0.8-5750110.23436230.27703110.2114644
0.7-0107010.33327130.37130110.3117634
0.6-4753010.43048030.47267010.4114724
0.5-0620010.53689920.57105010.5112814
0.4-460790.63751920.67742010.6113904
0.3-189390.73553820.77000010.7116004
0.2-800190.83775720.8706790.8111293
0.1-931880.93328620.9762590.9118383
0.0173580.04290620.0899290.0217573
0.1996280.14383520.1877090.1218763
0.2121080.24696420.2826880.2211063
0.3236770.34030420.3835680.3216253
0.4032570.44483320.4894480.4212543
0.5019270.54857220.580528
0.6076070.64051220.687508
0.7705860.74165120.789687
0.8814660.84989020.886867
0.9993460.94534020.987057
0.01944260.05698910.094337
0.11565060.15473910.195617
0.21547850.25768810.290007
0.31589650.35573810.390486
0.41482550.45898710.493866
3. Check resistance reading to chart of resistance; use sensor ambient temperature. (Tolerance of part is ± 10%.)
4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control.
5. If sensor is out of tolerance, shorted, open, or reads very low ohms then it should be replaced.
Manual 2100-344 Page 16
Page 19
SUCTION AND DISCHARGE TUBE BRAZING
Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used.
To disconnect: heat joint Areas 2 and 3 slowly and
uniformly until braze material softens and the tube can be pulled out of suction fitting. (See Figure 10.)
BRAZING DIAGRAM
To connect:
Recommended brazing materials: silfos with
minimum 5% silver or silver braze material with
flux. – Reinsert tube into fitting. – Heat tube uniformly in Area 1 moving slowly to
Area 2. When joint reaches brazing temperature,
apply brazing material. (See Figure 10.) – Heat joint uniformly around the circumference to
flow braze material completely around the joint. – Slowly move torch into Area 3 to draw braze
material into joint. (See Figure 10.) – Do not overheat joint.
FIGURE 13
MIS-1179
Manual 2100-344 Page 17
Page 20
COOLING
PRESSURE TABLES
TABLE 11
Air T emperature Entering Outdoor Coil Degrees F
riAnruteR
ledoM
4221HP
0321HP
6321HP
erutarepmeTerusserP5708580959001501011511
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
BD.ged57 BW.ged26
BD.ged08 BW.ged76
BD.ged58 BW.ged27
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
37
57
67
87
97
08
18
28
191
502
912
432
152
762
582
303
87
08
691
012
18
38
302
712
37
57
802
222
87
08
312
822
18
38
022
632
27
47
112
522
77
97
612 08
28
422
932
18
38
48
88
78
88
522
042
752
472
292
48
68
78
98
09
332
842
662
482
203
67
87
97
97
732
452
072
882
703
18
38
48
58
78
342
062
772
592
513
48
68
78
88
09
252
962
782
503
623
57
77
87
242
852
672
08
28
38
132
842
562
382
38
58
68
752
472
392
97
08
492
413
48
68
203
223
78
98
313
333
113 19
223
18
28 623
88 433
19
643
18
333 78
243 09
453
38 323
98
133
29 343
48 643
09 553
39 763
28 553
88 463
19
773
TABLE 12
HEATING
Air T emperature Entering Outdoor Coil Degrees F
nruteR
ledoM
4221HPged07
0321HPged07
6321HPged07
Low side pressure ± 2 PSIG High side pressure ± 5 PSIG
T ables are based upon rated CFM (airflow across the evaporator coil and should be found under section titled Refrigerant Charge elsewhere in manual. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated, and recharged to serial plate instructions.
pmeTriA
.
erusserP
05 015171025203530454740555
ediSwoL
22
42
72
03
13
33
73
14
54
05
65
ediShgiH
471
281
091
891
102
502
312
122
922
732
542
ediSwoL
12
32
52
82
92
13
43
83
34
84
35
ediShgiH
761
071
471
871
971
281
781
291
791
302
012
ediSwoL
42
52
62
82
82
03
33
73
24
74
35
ediShgiH
491
591
791
102
202
502
112
812
622
532
642
85
26
86
842
352
162
55
95
56
312
712
422
65
06
86
052
752
072
Manual 2100-344 Page 18
Page 21
Wiring Diagram (4098-123) printed
from CAD to get size needed
Manual 2100-344 Page 19
Page 22
Wiring Diagram (4098-124) printed
from CAD to get size needed
Manual 2100-344 Page 20
Page 23
Wiring Diagram (4098-211) printed
from CAD to get size needed
Manual 2100-344 Page 21
Loading...