INSTALLATION INSTRUCTIONS
SINGLE PACKAGE
AIR CONDITIONERS
MODELS
PA13241-A PA13301-A PA13361-A PA13361-B PA13421-A PA13421-B PA13481-A PA13481-B PA13601-A PA13601-B
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914 . . . Moving ahead just as planned
Manual : 2100-467 Supersedes: NEW File: Volume II Tab 10 Date: 03-03-06
© Copyright 2006
Manual 2100-467 Page 1 of 23
CONTENTS
Getting Other Informations and Publications ........ 3
General Instructions
Important ................................................................ 4
Shipping Damage .................................................... 4
General ................................................................ 4
Field Installed Heater Packages (Optional) ............. 4
Installation
Location ................................................................ 9
Slab Mounting .......................................................... 9
Typical Installations ......................................... 9 & 12
Condensate Drain Trap ......................................... 12
Air Filters .............................................................. 12
Wiring – Main Power ............................................. 13
Wiring – 24V Low Voltage Control Circuit ............. 13
Transformer Taps ................................................... 13
Thermostats ........................................................... 13
Figures
Figure 1 Unit Dimensions ...................................... 8
Figure 2 Slab Mounting at Ground Level ............ 10
Figure 3 Airflow and Service Access
Clearances ............................................ 10
Figure 4 Elevated Mounting Platform ...................11
Figure 5 Condensate Drain Trap ......................... 12
Figure 6 Low Voltage Wiring ............................... 14
Figure 7 Low Ambient Control Wiring ................. 17
Figure 8 Fan Blade Setting ................................. 18
Figure 9 Brazing Diagram ................................... 19
Figure 10 Control Disassembly ............................. 21
Figure 11 Winding Test ......................................... 21
Figure 12 Drip Loop .............................................. 21
Start Up and Operation
General .............................................................. 15
Topping Off System Charge ................................... 15
Safety Practices..................................................... 15
Start Up Notes ....................................................... 15
Three Phase Scroll Compressor Start Up
Information ............................................................. 16
Sequence of Operation .......................................... 16
Indoor Blower Motor .............................................. 16
Compressor Control Module .......................... 16 & 17
Adjustments ........................................................... 17
Low Ambient Control ............................................. 17
Service and Troubleshooting
Service Hints ......................................................... 18
Pressure Service Ports .......................................... 18
Refrigerant Charge ................................................ 18
Fan Blade Settings ................................................ 18
Suction and Discharge Tube Brazing .................... 19
Troubleshooting ECM Blower Motors ............. 20-21
Pressure Tables ............................................. 22 & 23
Tables
Table 1 Rated CFM & ESP .................................. 4
Table 2 Electrical Specifications .......................... 5
Table 3 Opt. Field Installed Heater Packages ..... 6
Table 4 Opt. Field Installed Elec. Heater ............. 7
Table 5 Filter Requirements & Sizes ................. 12
Table 6 Thermostat Wire Size ........................... 13
Table 7 Wall Thermostat and Subbase
Combinations ........................................ 13
Table 8 Refrigerant Charge ............................... 18
Table 9 Fan Blade Setting Dimensions.............. 18
Table 10 Indoor Blower Performance .................. 18
Table 11 Pressure Table ...................................... 22
Table 12 Pressure Table ...................................... 23
Manual 2100-467 Page 2 of 23
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ............................ACCA Manual J
Residential Winter and Summer Air Conditioning
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
Duct Design for Residential .............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-467 Page 3 of 23
GENERAL INSTRUCTIONS
IMPORTANT
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return ducts, must be properly sized for the design air flow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
FIELD INSTALLED HEATER PACKAGES (OPTIONAL)
These packaged air conditioners are manufactured without supplementary electric heaters. Supplementary heaters are available for simple, fast field installation.
A separate power circuit is required for the supplementary heaters.
IMPORTANT: Refer to Table 1 when designing duct work for maximum available static pressure with heater installed.
Refer to data shown in Table 3 and 4 for proper application information on all available heater combinations and what units they can be used with. It also shows the applicable circuit ampacities, fuse size, and wire size for each heater combination.
TABLE 1
RATED CFM AND EXTERNAL STATIC
PRESSURE (ESP)
ledoM
.oN
14231AP 10331AP0001 16331AP 12431AP 18431AP 10631AP
detaR
MFC
008
0011 0041 0551 0561
dednemmoceR
egnaRwolfriA
etoN etoN etoN etoN etoN etoN
detaR
PSE
81.005.0
32.005.0
32.005.0
32.005.0
82.005.0
82.005.0
PSE
.xaM
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made.
Manual 2100-467 Page 4 of 23
NOTE: ECM motors provide rated CFM up to 0.50 ESP
TABLE 2
ELECTRICAL SPECIFICATIONS
1-06-802/0321-06-802/0321-06-802/0323-06-802/0321-06-802/0323-06-802/0321-06-802/0323-06-802/0321-06-802/0323-06-802/032
resnednoCdnarotoMnaF
yticapmAtiucriCmuminiM51814271133243428362
egnaRegatloVgnitarepO352-791352-791352-791352-781352-791352-781352-791352-781352-791352-781
AtiucriCzH06
gnitaRcirtcelE
ledoMA-14231APA-10331APA-16331APB-16331APA-12431APB-12431APA-18431APB-18431APA-10631APB-10631AP
*
eziSeriWdnuorG21018210101801801
eziSeriWdleiF21018210101801801
CSCB9115101125122416261
802/032spmAtinulatoT8.11/8.018.41/3.314.81/4.613.31/0.711.81/2.614.51/1.417.42/0.320.81/9.619.82/3.529.91/7.71
AtiucriCrosserpmoC
**.xaMesuFyaleD02525303050455040604
epyTrosserpmoC.piceR.piceR.piceR.piceRllorcSllorcSllorcSllorcSllorcSllorcS
spmAdaoLdetaR5.8/5.711/5.941/219.8/6.77.31/8.116.9/3.87.81/7121/9.019.22/3.919.31/7.11
spmArotoRkcoL84/8475/7547/4757/57511/511511/511711/7111.38/1.38431/431011/011
stloV802/032802/032802/032802/032802/032802/032802/032802/032802/032802/032
MPR/PHrotoMnaF528-6/1528-6/1528-6/1528-6/1528-4/1528-4/1528-4/1528-4/1528-4/1528-4/1
spmArotoMnaF1.11.11.11.15.15.15.15.15.15.1
MFC/.aiDnaF0072/"420062/"420062/"42/"420043/"420043/"420043/"420043/"420043/"420043/"42
*MPR/PHrotoMrewolBSV-3/1SV-2/1SV-2/1SV-2/1SV-2/1SV-2/1SV-4/3SV-4/3SV-4/3SV-4/3
rotaropavEdnarotoM
spmArotoMrewolB2.27.23.33.33.43.45.45.47.47.4
PSE&gnilooCMFC 32./004132./004182./005182./005182./007182./0071
)sdnuop(thgieWgnippihS003003053053
).zo014-R(egrahC5758021021061061061061061061
* VS = Variable Speed Programmable Motor
Manual 2100-467 Page 5 of 23
XX
TABLE 3
OPTIONAL FIELD INSTALLED HEATER PACKAGES
ONLY TO BE USED WITH THE MODELS INDICATED
Manual 2100-467 Page 6 of 23
esahPA-14231APA-10331APA-16331APB-16331APA-12431APB-12431APA-18431APB-18431APA-10631APB-10631AP
&stloV
egakcaPretaeH
50A-313PHE1-802/042 XXX
ledoM
51A-313PHE1-802/042XX
90B-313PHE3-802/042X
0
1A-313PHE1-802/042 XXX
51B-313PHE3-802/042X
0
51A-315PHE1-802/042XXX
90B-315PHE3-802/042 XXX
50A-315PHE1-802/042X
1A-315PHE1-802/042XXX
51B-315PHE3-802/042 XXX
eziSeriW
dnuorG
2
rewoP
gniriW
dleiF
2
revO.xaM
noitcetorP
BtiucriC
tnerruC
1
yticapmA
tiucriC
.niM
3
dleiF.oN
stiucriC
lanretnI
rekaerB
tiucriC
retaeH
64 /3505/068/601
132/6252/0301/0101
132/6252/0301/0101
06/03
/9707/084/48
06/03
93 /6404/058/801
142/8252/0301/0101
enoN
93 /6404/058/801
142/8252/0301/0101
enoN
V802/042
spmA
.rtH
TABLE 4
yticapaC&WK.rtH
stloV802@
yticapaC&WK.rtH
OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLE
stloV042@
00 1,7157.3008,211.81/8.02
00 1,7157.3008,211.81/8.02
WKHUTBWKHUTB
stloVtinU
sesahP
01A-313PHE1-802/04201001,4305.7000,622.63/6.141
.oNledoM
egakcaP
retaeH
50A-313PHE1-802/0425
51A-313PHE1-802/04251002,1552.11004,831.45/5.26186/9707/084/48
01A-315PHE1-802/04201001,4305.7000,622.63/6.14164/3505/068/601
50A-315PHE1-802/0425
90B-313PHE3-802/0429007,0357.6000,327.81/7.12
51A-315PHE1-802/04251002,1552.11004,831.45/5.26186
conductor wires in accordance with the National Electrical Code and all existing local codes.
90B-315PHE3-802/0429007,0357.6000,327.81/7.12
51B-313PHE3-802/04251002,1552.11004,832.13/2.631
51B-315PHE3-802/04251002,1552.11004,832.13/2.631
conform to the National Electric Code and all local codes.
1 Maximum size of the time delay fuse or HACR circuit breaker for protection of field wiring devices.
2 Based on wire suitable for 75°C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based on 75°C copper wire. All wiring must
conductor sizing.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and
Manual 2100-467 Page 7 of 23