Bard PA13601-A, PA13601-B, PA13421-A, PA13481-B, PA13421-B, PA13481-A, Single Package Air Conditioners PA13421-A User Manual

593.98 Kb
Loading...

INSTALLATION INSTRUCTIONS

SINGLE PACKAGE

AIR CONDITIONERS

MODELS

PA13241-A

PA13361-A

PA13421-A

PA13481-A

PA13601-A

PA13301-A PA13361-B PA13421-B PA13481-B PA13601-B

Bard Manufacturing Company

Manual :

2100-467

Bryan, Ohio 43506

Supersedes:

NEW

Since 1914 . . . Moving ahead just as planned

File:

Volume II Tab 10

Date:

03-03-06

 

© Copyright 2006

Manual

2100-467

Page

1 of 23

CONTENTS

Getting Other Informations and Publications

........ 3

General Instructions

 

Important ................................................................

4

Shipping Damage ....................................................

4

General ................................................................

4

Field Installed Heater Packages (Optional) .............

4

Installation

 

Location ................................................................

9

Slab Mounting..........................................................

9

Typical Installations .........................................

9 & 12

Condensate Drain Trap .........................................

12

Air Filters ..............................................................

12

Wiring – Main Power .............................................

13

Wiring – 24V Low Voltage Control Circuit .............

13

Transformer Taps ...................................................

13

Thermostats ...........................................................

13

Figures

 

 

Figure 1

Unit Dimensions ......................................

8

Figure 2

Slab Mounting at Ground Level ............

10

Figure 3

Airflow and Service Access

 

 

Clearances ............................................

10

Figure 4

Elevated Mounting Platform ...................

11

Figure 5

Condensate Drain Trap .........................

12

Figure 6

Low Voltage Wiring ...............................

14

Figure 7

Low Ambient Control Wiring .................

17

Figure 8

Fan Blade Setting .................................

18

Figure 9

Brazing Diagram ...................................

19

Figure 10 Control Disassembly .............................

21

Figure 11

Winding Test .........................................

21

Figure 12

Drip Loop ..............................................

21

Start Up and Operation

 

General ..............................................................

15

Topping Off System Charge...................................

15

Safety Practices.....................................................

15

Start Up Notes .......................................................

15

Three Phase Scroll Compressor Start Up

 

Information.............................................................

16

Sequence of Operation..........................................

16

Indoor Blower Motor ..............................................

16

Compressor Control Module ..........................

16 & 17

Adjustments ...........................................................

17

Low Ambient Control .............................................

17

Service and Troubleshooting

 

Service Hints .........................................................

18

Pressure Service Ports ..........................................

18

Refrigerant Charge ................................................

18

Fan Blade Settings ................................................

18

Suction and Discharge Tube Brazing ....................

19

Troubleshooting ECM Blower Motors .............

20-21

Pressure Tables .............................................

22 & 23

Tables

 

 

Table 1

Rated CFM & ESP ..................................

4

Table 2

Electrical Specifications ..........................

5

Table 3

Opt. Field Installed Heater Packages .....

6

Table 4

Opt. Field Installed Elec. Heater .............

7

Table 5

Filter Requirements & Sizes .................

12

Table 6

Thermostat Wire Size ...........................

13

Table 7

Wall Thermostat and Subbase

 

 

Combinations ........................................

13

Table 8

Refrigerant Charge ...............................

18

Table 9

Fan Blade Setting Dimensions..............

18

Table 10

Indoor Blower Performance ..................

18

Table 11

Pressure Table ......................................

22

Table 12

Pressure Table ......................................

23

Manual

2100-467

Page

2 of 23

Getting Other Information and Publications

These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.

National Electrical Code ......................

ANSI/NFPA 70

Standard for the Installation ..............

ANSI/NFPA 90A

of Air Conditioning and

 

Ventilating Systems

 

Standard for Warm Air ......................

ANSI/NFPA 90B

Heating and Air

 

Conditioning Systems

 

Load Calculation for ............................

ACCA Manual J

Residential Winter and

 

Summer Air Conditioning

 

Duct Design for Residential ..............

ACCA Manual D

Winter and Summer Air

Conditioning and Equipment Selection

FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:

ACCA

Air Conditioning Contractors of America

 

1712 New Hampshire Ave. N.W.

 

Washington, DC 20009

 

Telephone: (202) 483-9370

 

Fax: (202) 234-4721

ANSI

American National Standards Institute

 

11 West Street, 13th Floor

 

New York, NY 10036

 

Telephone: (212) 642-4900

 

Fax: (212) 302-1286

ASHRAE American Society of Heating, Refrigerating,

and Air Conditioning Engineers, Inc.

1791 Tullie Circle, N.E.

Atlanta, GA 30329-2305

Telephone: (404) 636-8400

Fax: (404) 321-5478

NFPA

National Fire Protection Association

 

Batterymarch Park

 

P.O. Box 9101

 

Quincy, MA 02269-9901

 

Telephone: (800) 344-3555

 

Fax: (617) 984-7057

Manual

2100-467

Page

3 of 23

GENERAL INSTRUCTIONS

IMPORTANT

The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return ducts, must be properly sized for the design air flow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

FIELD INSTALLED HEATER PACKAGES (OPTIONAL)

These packaged air conditioners are manufactured without supplementary electric heaters. Supplementary heaters are available for simple, fast field installation.

A separate power circuit is required for the supplementary heaters.

IMPORTANT: Refer to Table 1 when designing duct work for maximum available static pressure with heater installed.

Refer to data shown in Table 3 and 4 for proper application information on all available heater combinations and what units they can be used with. It also shows the applicable circuit ampacities, fuse size, and wire size for each heater combination.

GENERAL

The refrigerant system is completely assembled and charged. All internal wiring is complete.

The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.

These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.

These instructions and any instructions packaged with any separate equipment required to make up the entire system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made.

TABLE 1

RATED CFM AND EXTERNAL STATIC

PRESSURE (ESP)

Model

Rated

Recommended

Rated

Max.

No.

CFM

Airflow Range

ESP

ESP

 

 

 

 

 

PA13241

800

Note

0.18

0.50

 

 

 

 

 

PA13301

1000

Note

0.23

0.50

 

 

 

 

 

PA13361

1100

Note

0.23

0.50

 

 

 

 

 

PA13421

1400

Note

0.23

0.50

 

 

 

 

 

PA13481

1550

Note

0.28

0.50

 

 

 

 

 

PA13601

1650

Note

0.28

0.50

 

 

 

 

 

NOTE: ECM motors provide rated CFM up to 0.50 ESP

Manual

2100-467

Page

4 of 23

Page

Manual

23 of 5

467-2100

TABLE 2

ELECTRICAL SPECIFICATIONS

Model

PA13241-A

PA13301-A

PA13361-A

PA13361-B

PA13421-A

PA13421-B

PA13481-A

PA13481-B

PA13601-A

PA13601-B

 

 

 

 

 

 

 

 

 

 

 

Electric Rating –

230/208-60-1

230/208-60-1

230/208-60-1

230/208-60-3

230/208-60-1

230/208-60-3

230/208-60-1

230/208-60-3

230/208-60-1

230/208-60-3

60 Hz – Circuit A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range

197 - 253

197 - 253

197 - 253

187 - 253

197 - 253

187 - 253

197 - 253

187 - 253

197 - 253

187 - 253

 

 

 

 

 

 

 

 

 

 

 

Minimum Circuit Ampacity

15

18

24

17

31

23

34

24

38

26

 

 

 

 

 

 

 

 

 

 

 

BCSC

9

11

15

10

21

15

22

14

26

16

 

 

 

 

 

 

 

 

 

 

 

Field Wire Size *

12

10

8

12

10

10

8

10

8

10

 

 

 

 

 

 

 

 

 

 

 

Ground Wire Size

12

10

8

12

10

10

8

10

8

10

 

 

 

 

 

 

 

 

 

 

 

Delay Fuse – Max. **

20

25

35

30

50

40

55

40

60

40

 

 

 

 

 

 

 

 

 

 

 

Total unit Amps – 230/208

10.8/11.8

13.3/14.8

16.4/18.4

17.0/13.3

16.2/18.1

14.1/15.4

23.0/24.7

16.9/18.0

25.3/28.9

17.7/19.9

 

 

 

 

 

 

 

 

 

 

 

Compressor – Circuit A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Type

Recip.

Recip.

Recip.

Recip.

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

 

 

 

 

 

 

 

 

 

 

 

Volts

230/208

230/208

230/208

230/208

230/208

230/208

230/208

230/208

230/208

230/208

 

 

 

 

 

 

 

 

 

 

 

Rated Load Amps

7.5/8.5

9.5/11

12/14

7.6/8.9

11.8/13.7

8.3/9.6

17/18.7

10.9/12

19.3/22.9

11.7/13.9

 

 

 

 

 

 

 

 

 

 

 

Lock Rotor Amps

48/48

57/57

74/74

75/75

115/115

115/115

117/117

83.1/83.1

134/134

110/110

 

 

 

 

 

 

 

 

 

 

 

Fan Motor and Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor – HP/RPM

1/6 - 825

1/6 - 825

1/6 - 825

1/6 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

1/4 - 825

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

1.1

1.1

1.1

1.1

1.5

1.5

1.5

1.5

1.5

1.5

 

 

 

 

 

 

 

 

 

 

 

Fan – Dia./CFM

24"/2700

24"/2600

24"/2600

24"/

24"/3400

24"/3400

24"/3400

24"/3400

24"/3400

24"/3400

 

 

 

 

 

 

 

 

 

 

 

Motor and Evaporator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor – HP/RPM *

1/3 - VS

1/2 - VS

1/2 - VS

1/2 - VS

1/2 - VS

1/2 - VS

3/4 - VS

3/4 - VS

3/4 - VS

3/4 - VS

 

 

 

 

 

 

 

 

 

 

 

Blower Motor – Amps

2.2

2.7

3.3

3.3

4.3

4.3

4.5

4.5

4.7

4.7

 

 

 

 

 

 

 

 

 

 

 

CFM Cooling & ESP

 

 

 

 

1400/.23

1400/.23

1500/.28

1500/.28

1700/.28

1700/.28

 

 

 

 

 

 

 

 

 

 

 

Charge (R-410 oz.)

75

85

120

120

160

160

160

160

160

160

 

 

 

 

 

 

 

 

 

 

 

Shipping Weight (pounds)

300

300

350

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* VS = Variable Speed Programmable Motor

Page

Manual

23 of 6

467-2100

TABLE 3

OPTIONAL FIELD INSTALLED HEATER PACKAGES

ONLY TO BE USED WITH THE MODELS INDICATED

Heater Package

Volts &

 

 

 

 

 

 

 

 

 

 

Model

Phase

PA13241-A

PA13301-A

PA13361-A

PA13361-B

PA13421-A

PA13421-B

PA13481-A

PA13481-B

PA13601-A

PA13601-B

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A05

240/208-1

X

X

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A10

240/208-1

X

X

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A15

240/208-1

 

X

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-B09

240/208-3

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-B15

240/208-3

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A05

240/208-1

 

 

 

 

X

 

X

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A10

240/208-1

 

 

 

 

X

 

X

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A15

240/208-1

 

 

 

 

X

 

X

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-B09

240/208-3

 

 

 

 

 

X

 

X

 

X

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-B15

240/208-3

 

 

 

 

 

X

 

X

 

X

 

 

 

 

 

 

 

 

 

 

 

 

Page

Manual

23 of 7

467-2100

TABLE 4

OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLE

 

 

Htr. KW & Capacity

Htr. KW & Capacity

 

 

 

 

Circuit B

 

 

 

 

@ 240 Volts

@ 208 Volts

 

Heater

 

 

 

 

Heater

 

240/208V

 

 

 

 

 

Unit Volts

 

 

 

 

Internal

 

 

 

 

 

 

 

 

 

 

3

1

2

2

Package

Phases

 

 

 

 

Htr.

Circuit

 

 

 

 

 

No. Field

Min.

Max. Over

Field

 

Model No.

KW

BTUH

KW

BTUH

Amps

 

 

Breaker

Circuits

Circuit

Current

Power

Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ampacity

Protection

Wiring

Wire Size

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A05

240/208-1

5

17,100

3.75

12,800

20.8/18.1

 

1

26/23

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A10

240/208-1

10

34,100

7.50

26,000

41.6/36.2

30/60

1

53/46

60/50

6/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A15

240/208-1

15

51,200

11.25

38,400

62.5/54.1

 

1

79/68

80/70

4/4

8

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A05

240/208-1

5

17,100

3.75

12,800

20.8/18.1

 

1

26/23

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A10

240/208-1

10

34,100

7.50

26,000

41.6/36.2

30/60

1

53/46

60/50

6/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A15

240/208-1

15

51,200

11.25

38,400

62.5/54.1

 

1

79/68

80/70

4/4

8

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-B09

240/208-3

9

30,700

6.75

23,000

21.7/18.7

None

1

28/24

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-B15

240/208-3

15

51,200

11.25

38,400

36.2/31.2

1

46/39

50/40

8/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-B09

240/208-3

9

30,700

6.75

23,000

21.7/18.7

None

1

28/24

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-B15

240/208-3

15

51,200

11.25

38,400

36.2/31.2

1

46/39

50/40

8/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1Maximum size of the time delay fuse or HACR circuit breaker for protection of field wiring devices.

2Based on wire suitable for 75°C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based on 75°C copper wire. All wiring must conform to the National Electric Code and all local codes.

3These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all existing local codes.