conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code .......................ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for W arm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ...............ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
FOr mOre InFOrmatIOn, cOntact
these PublIshers:
ACCA Air Conditioning Contractors of America1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSI American National Standards Institute11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPA National Fire Protection AssociationBatterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manual 2100-467K
Page 3 of 24
General InstructIOns
ImPOrtant
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians. All duct work, supply and return
ducts, must be properly sized for the design airow
requirement of the equipment. ACCA is an excellent
guide to proper sizing. All duct work or portions
thereof not in the conditioned space should be properly
insulated in order to both conserve energy and prevent
condensation or moisture damage.
shIPPInG DamaGe
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
General
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
system should be carefully read before beginning the
installation. Note particularly “Starting Procedure” and
any tags and/or labels attached to the equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation
is made.
FIelD InstalleD heater PacKaGes
(OPtIOnal)
These packaged air conditioners are manufactured
without supplementary electric heaters. Supplementary
heaters are available for simple, fast eld installation.
A separate power circuit is required for the
supplementary heaters.
IMPORTANT: Refer to Table 1 when designing duct
work for maximum available static pressure with heater
installed.
Refer to data shown in Table 3 and 4 for proper
application information on all available heater
combinations and what units they can be used with. It
also shows the applicable circuit ampacities, fuse size,
and wire size for each heater combination.
conform to the National Electric Code and all local codes.
Based on wire suitable for 75°C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based on 75°C copper wire. All wiring must
conductor sizing.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and
Manual 2100-467K
Page 7 of 24
FIGure 1a
Return opening
Drain access
Supply opening
High voltage knockout
Low voltage knockout
access door
Control panel door
Heater package access panel
Compressor
Heater package knockout
A
E
C
D
L
W
B
F
Condenser air
Condenser air
intake grille
intake grille
access door
Blower motor
Condenser fan
G
47 11/16"
H
Unit Dimension Chart
MIS-2142 A
ACBCH (height) L (length) W (width)DEFG
PA/PH1324,1330,13365.87532.87513.87532.87526.2553.2538.12523.251.1251.37535.625
PA/PH1342,1348,13609.87537.87515.87537.87533.2555.2542.37530.251.52.37538.125
The unit must be located outside, or in a well ventilated
area. It must not be in the space being heated or cooled.
A sound absorbing material should be considered if the
unit is to be installed in such a position or location that
might cause transmission of sound or vibration to the
living area or adjacent buildings.
slab mOuntInG
A minimum of 24 inches should be provided between
the coil inlet and any building surfaces. Provide a
minimum of three feet clearance on the service access
side of the unit. See Figure 2.
tYPIcal InstallatIOns
1. rOOF mOunteD – The unit is mounted on a
sturdy base on the roof of the building. Return
air to the unit is brought through a single return
grille (grilles with built-in lters are best since they
enable easy access for lter changing). Return air
ducts are attached to the lower section of the front
panel. Supply air is brought from the unit to attic
duct work or to a furred down hall. Supply air duct
is attached to the top of the front panel.
In roof top installation, as in all installations, the
air conditioner must be level from side to side.
However, the unit should have a pitch along the
length to assure complete external drainage of
precipitation and of defrost condensate.
2.
craWl sPace – Duct work installed in crawl
space must be well insulated and provided with a
vapor barrier. In addition, the crawl space must
be thoroughly ventilated and provided with a good
vapor barrier as a ground cover. It is most desirable
to install the unit will be outdoors rather than inside
the crawl space, so that it will be readily accessible
for service.
3. slab mOunteD at GrOunD leVel – This
type installation is ideal for homes with a slab
oor construction where a roof mounted unit is not
desired. The supply and return duct work can be
run through a furred closet space.
4. thrOuGh the Wall – This type installation
requires a suitable framework to be fabricated
capable of withstanding the unit weight. Normally
the unit will be insulated so as to minimize supply
and return duct work.
CAUTION: All outdoor duct work must be
thoroughly insulated and weatherproofed. All
attic duct work must be thoroughly insulated.
Two inch thick insulation with suitable vapor
barrier is recommended for both outdoor and
attic runs.
Manual 2100-467K
Page 10 of 24
36" min.
24" min.
24" min.
The distance between
1 inch clearance
Access
Air Inlet
Comp-
Nearest Structure
Air Inlet
Supply and Return Ducts
Nearest Structure
Nearest Structure
Building
Control Panel
Access
Control Panel
Access
Heater Package
Access
Blower Service
and
ressor
Blower Motor
Heater Package
Blower
Compressor
from top.
units only).
Condenser fan
and motor access
above fan.
Leave 60" min.
Side
View
View
Top
between duct and
any combustible
material if distance
between outside
wall and unit is less
than 3 feet (needed
on electric heat
MIS-2143 A
Mounting Slab
Ground Level
Package Unit
Supply Duct
from building
Return Duct
requirements.
outside wall and unit
Air Outlet
varies with installation
1/4 inch per foot
slope away
Building
FIGure 2
slab mOuntInG at GrOunD leVel
FIGure 3
aIrFlOW anD serVIce access clearances
Manual 2100-467K
Page 11 of 24
FIGure 4
Both legs must rest
on surface of platform
32°F or lower climate
12" min. if in
48" min.
48" min.
32°F or lower climate
12" min. if in
on surface of platform
Both legs must rest
Platform can be as
shown or solid
Poured concrete,
brick, or block
Metal frame
MIS-2144 A
eleVateD mOuntInG PlatFOrm
*
* AS REqUIRED
Manual 2100-467K
Page 12 of 24
*
5. Other InstallatIOns – Many other
installations are possible with the packaged air
conditioner. No matter what the installation, always
consider the following facts:
A. Insure that the discharge air is not obstructed in
any way so as to cause operation difculties.
B. The indoor coil drain pan is equipped with a
coupling that must be piped through a condensate drain trap to a suitable drain.
C. Always mount the unit is such a position that it
may be easily reached for servicing and
maintenance.
D. Insure that the unit is clear so that proper air
ow over the outdoor coil will be maintained.
If this unit is operated in cooling below a 55° outdoor
ambient temperature, the installation of low ambient
controls (CMA-28) to unit is required.
Prior thought should be given to return air location and
placement of the air lter(s). The air lter(s) must be
of adequate size and readily accessible to the operator
of the equipment. Filters must be adequate in size and
properly maintained for proper operation. If this is
not done, excessive energy use, poor performance, and
multiple service problems will result. It is impossible to oversize air lters. Generous sizing will result in
cleaner air and coils as well as lower operating costs
and extend the time between required changes. Table
5 shows minimum lter areas and recommended lter
sizes. Actual lter sizes can vary with the installation
due to single or multiple returns utilizing a lter/grille
arrangement or being placed immediately ahead of the
indoor coil face in the return air duct.
table 5
FIlter requIrements & sIzes
cOnDensate DraIn traP
It is very important to provide a trap in the condensate
drain line to allow a positive liquid seal in the line and
assure correct drainage from the coil condensate pan.
Install condensate drain trap shown in Figure 8. Use
drain connection size or larger. Do not operate unit
without trap. Unit must be level or slightly inclined
toward drain. With a trap installed on a unit located in
an unconditioned area, water in the trap may freeze. It
is recommended that the trap material be of a type that
will allow for expansion of water when it freezes.
aIr FIlters
Air lters for the return air side of the system are not
provided as part of these models, and must be eld
supplied and installed as part of the nal installation.
cOnDensate DraIn traP
NOTE: If roof hood accessory is to be used,
FIGure 5
model no.
PA1324
PA1330
PA1336
PA1342
PA1348
PA1360
minimum Filter
Free area
403 Square Inches
(2.8 Square Feet)
473 Square Inches
(3.3 Square Feet)
recommended size
information on air lters may be found under
that heading in this manual. Air lters are
supplied as part of that package.
minimum
(2) 14 x 20 x 1
(2) 16 x 20 x 1
Manual 2100-467K
Page 13 of 24
WIrInG – maIn POWer
Refer to the unit rating plate for wire sizing information
and maximum fuse size. Each outdoor unit is marked
with a “Minimum Circuit Ampacity”. This means that
the eld wiring used must be sized to carry that amount
of current. If eld installed heaters are added to the
basic unit, a second separate power supply circuit will
be required. The heater rating plate located adjacent
to the basic unit rating plate will show the appropriate
circuit ampacity fuse size, etc. (Also see “Electrical
Specications” on pages 5 & 7.) All models are
suitable for connection with copper wire only. These
instructions must be adhered to. Refer to the National
Electrical Code for complete current carrying capacity
data on the various insulation grades of wiring material.
The electrical specications list fuse and wire sizes
(75°F copper) for all models including the most
commonly used heater sizes.
The unit rating plate lists a “Maximum Time Delay
Fuse” or “HACR” type circuit breaker that is to be used
with the equipment. The correct size must be used for
proper circuit protection and also to assure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor.
WIrInG – 24V lOW VOltaGe cOntrOl
cIrcuIt
Five (5) wires should be run from thermostat subbase
to the 24V terminal board in the unit. A ve conductor,
18 gauge copper, color-coded thermostat cable is
recommended. The connection points are shown in
Figure 6.
table 6
thermOstat WIre sIze
transformer
Va
552.3
Fla
Wire
Gauge
20
18
16
14
12
maximum
Distance
In Feet
45
60
100
160
250
transFOrmer taPs
230/208V, 1 phase and 3 phase equipment employ dual
primary voltage transformers. All equipment leaves
the factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
taPranGe 240 253 – 216
208 220 – 187
NOTE: The voltage should be measured at the eld
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
thermOstats
See specic wiring information for the different models, heater KWs, and voltages on unit and heating wiring
diagrams.
table 7
Wall thermOstats
thermostatPredominant Features
8403-058
(TH5220D1151)
8403-060
(1120-445)
IMPORTANT NOTE: Only the thermostats as shown above will work with this equipment. The thermostats and
correct operation can be assured only by proper selection and application of these parts.
These units require R-410A refrigerant and Polyol Ester
oil.
General:
1. Use separate service equipment to avoid cross
contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and
R-12. Although nearly azeotropic, charge with
liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot
withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming
potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly
absorb moisture and strongly hold this moisture in
the oil.
10. A liquid line dryer must be used - even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with
small amount of nitrogen when inserting plugs.
tOPPInG OFF sYstem charGe
If a leak has occurred in the system, Bard
Manufacturing recommends reclaiming, evacuating
(see criteria above), and charging to the nameplate
charge. Topping off the system charge can be done
without problems.
With R-410A, there are no signicant changes in the
refrigerant composition during multiple leaks and
recharges. R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound
or single component refrigerant). The remaining
refrigerant charge, in the system, may be used after
leaks have occurred and then “top-off” the charge by
utilizing the pressure charts on the inner control panel
cover as a guideline.
REMEMBER: When adding R-410A refrigerant,
it must come out of the charging cylinder/tank as a
liquid to avoid any fractionation, and to insure optimal
system performance. Refer to instructions for the
cylinder that is being utilized for proper method of
liquid extraction.
saFetY PractIces:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can
be irritating to the skin, and liquid refrigerant will
freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become ammable.
4. Do not inhale R-410A – the vapor attacks the
nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death
can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if
exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never ll cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct
sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands signicantly
at warmer temperatures. Once a cylinder or line is
full of liquid, any further rise in temperature will
cause it to burst.
start uP nOtes
For improved start up performance, wash the indoor
coil with dishwasher detergent.
Manual 2100-467K
Page 16 of 24
start uP anD OPeratIOn
three Phase scrOll cOmPressOr
start uP InFOrmatIOn
All units with three phase scroll compressors are
equipped with a three phase line monitor to prevent
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two
LED’s. If the “Y” signal is present at the phase monitor
and phases are correct, the green LED will light.
If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.
If a fault condition occurs, reverse tow of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
sequence OF OPeratIOn
blOWer OnlY – When the “Fan” switch on the
room thermostat is placed in the “On” position (circuit
R-G makes), the blower will energize and run until the
“Fan” switch is placed back into the “Auto” position.
This will allow for constant air circulation at a lower
airow during times when the unit is not in operation
for cooling or heating.
cOOlInG – On a call for cooling from the room
thermostat (circuit R-Y makes), the blower will
energize (circuit R-G is automatic when R-Y makes) as
well as the compressor, and outdoor fan motor. Note
that if the “Fan” switch on the room thermostat is in the
“On” position and the blower is already in operation,
then the motor will ramp up to the required speed for
cooling.
heatInG (1st stage) – On a call for heating
from the room thermostat (circuit R-W1 makes), the
blower will energize (circuit R-G is automatic when
R-W1 makes). This will place the system into heating
operation to maintain the thermostat set temperature.
Note that if the “Fan” switch on the room thermostat
is in the “On” position and the blower is already in
operation, then the motor will ramp up to the required
speed for heating.
InDOOr blOWer mOtOr
These models feature a variable speed (ECM) motor
providing high efciency, low sound levels and soft
start capabilities. The motor is self adjusting to provide
the proper airow rate at duct static pressures up to
0.50" WC without user adjustment or wiring changes.
On command from the wall thermostat the motor will
start slowly and ramp up to full speed over a period of
10-15 seconds.
When the thermostat is satised the blower will operate
for approximately 1 minute, and then slow down and
stop.
cOmPressOr cOntrOl mODule
The compressor control is an anti-short cycle/lockout
timer with high and low pressure switch monitoring and
alarm output.
aDJustable DelaY-On-maKe anD breaK
tImer
On a call for compressor operation the delay-on-make
period begins which will be 10% of the delay-on-break setting. When the delay-on-make is complete
and the high pressure switch (and low pressure switch
if employed) is closed, the compressor contactor is
energized. Upon shutdown, the delay-on-break timer
starts and prevents restart until the delay-on-break and
delay-on-make periods have expired.
hIGh Pressure sWItch anD lOcKOut
sequence (standard Feature)
If the high pressure switch opens, the compressor
contactor will de-energize immediately. The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delayon-make time has expired. If the high pressure switch
opens again in this same operating cycle the unit will
go into manual lockout condition and the alarm circuit
will energize. Recycling the wall thermostat resets the
manual lockout.
heatInG (2nd stage) – If the operation of the 1st
Stage electric heaters will not maintain the set room
temperature, then the thermostat will call for additional
heat to help maintain the set temperature. On a call
for second stage heating from the room thermostat
(circuit R-W2 makes), additional electric heaters will
be energized if installed.
Manual 2100-467K
Page 17 of 24
lOW Pressure sWItch, bYPass, anD
lOcKOut sequence (standard Feature)
lOW ambIent cOntrOl
If the low pressure switch opens for more that 120
seconds, the compressor contactor will de-energize
and go into a soft lockout. Regardless the state of the
low pressure switch, the contactor will reenergize after
the delay-on-make time delay has expired. If the low
pressure switch remains open or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm circuit will energize. Recycling
the wall thermostat resets the manual lockout.
alarm OutPut
Alarm terminal is output connection for applications
where alarm signal is desired. This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.
NOTE: Both high and low pressure switch controls
are inherently automatic reset devices. The
high pressure switch and low pressure switch
cut out and cut in settings are xed by specic
air conditioner or heat pump unit model. The
lockout features, both soft and manual, are a
function of the Compressor Control Module.
aDJustments
Optional Low Ambient Control
An optional low ambient control is available for both
factory and eld installed options. The low ambient
control is to be applied to the PA13 Series models when
operation below 55° outdoor conditions are anticipated.
Without this device, the evaporating pressure would fall
off, and the indoor coil would ice over.
The fan cycling control cycles the fan motor on, once
the liquid refrigerant pressure reaches 350 psig, and
off, once it has dropped to 225 psig. It will continue to
cycle between these parameters depending on outdoor
temperatures and the load/stage of the system.
This cycling maintains a minimum liquid pressure
affecting the minimum suction pressure. This effect
insures an evaporating temperature that is slightly above
the point of ice formation on the evaporator.
This eld installed option is Bard Part #CMA-28. See
Figure 7.
FIGure 7
lOW ambIent cOntrOl WIrInG
aDJust able Dela Y-On-maKe anD
elaY-On-breaK tImer
D
The potentiometer is used to select Delay-on-Break
time from 30 seconds to 5 minutes. Delay-onMake (DOM) timing on power-up and after power
interruptions is equal to 2 minutes plus 10% of Delayon-Break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (160 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
Manual 2100-467K
Page 18 of 24
serVIce anD trOubleshOOtInG
serVIce hInts
1. Caution homeowner to maintain clean air lters at
all times. Also, not to needlessly close off supply
and return air registers. This reduces airow
through the system which shortens equipment
service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure
that they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full
and unrestricted airow circulation is essential.
Pressure serVIce POrts
High and low pressure service ports are installed on
all units so that the system operating pressures can be
observed. Pressure tables can be found later in this
manual covering all models on cooling cycle. It is
imperative to match the correct pressure table to the
unit by model number.
r-410a
reFrIGerant charGe
Fan blaDe settInGs
Shown in Figure 8 are the correct fan blade setting
dimensions for proper air delivery across the outdoor
coil.
Any service work requiring removal or adjustment
in the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.
FIGure 8
Fan blaDe settInG
3¼"
MD-1417BC
This unit was charged at the factory with the quantity
of refrigerant listed on the serial plate. AHRI capacity
and efciency ratings were determined by testing with
this refrigerant charge quantity.
The following pressure tables show nominal
pressures for the units. Since many installation
specic situations can affect the pressure readings,
this information should only be used by certied
technicians as a guide for evaluating proper system
performance. They shall not be used to adjust charge.
If charge is in doubt, reclaim, evacuate and recharge
the unit to the serial plate charge.
2 Continuous CFM is the total air being circulated during continuous (manual fan) mode.
3 Will occur automatically with a call for “Y” for cooling mode operation.
4 Will occur automatically with a call for “W1” for heating mode operation.
Compliant Scroll compressors have copper plated
steel suction and discharge tubes. These tubes are far
more rugged and less prone to leaks than copper tubes
used on other compressors. Due to different thermal
properties of steel and copper, brazing procedures may
have to be changed from those commonly used.
• To disconnect: heat joint Areas 2 and 3 slowly and
uniformly until braze material softens and the tube
can be pulled out of suction tting. (See Figure 9.)
• To connect:
– Recommended brazing materials: silfos with
minimum 5% silver or silver braze material with
ux.
brazInG DIaGram
– Reinsert tube into tting.
– Heat tube uniformly in Area 1 moving sl owly to
Area 2. When joint reaches brazing temperature, apply brazing material. (See
Figure 9)
2.Ifthesystemisexcessivelynoisy,doesnotappeartochangespeeds in response to a demand (Heat, Cool, Other), or is havingsymptoms during the cycle such as tripping limit or freezing coil,checkthefollowing:
a.Wait for programmed delays to time out.b.Ensure that the motors control inputs are wired to the factory
suppliedwiringdiagramtoinsuremotorisgettingpropercontrol signals and sequencing.
c.Remove the filter and check that all dampers, registers, and
grillesareopen andfreeflowing.Ifremovingthe filterscorrects the problem, clean or replace with a less restrictivefilter. Also check and clean the blower wheel or coil asnecessary.
d.Check the external static pressure (total of both supply and
voltage checks in the next section below, then continue withthe“Model X13 Communication Diagnostics”.
If the Motor is Not Running
1.Check for proper high voltage and ground at the (L/L1) (G) (N/L2) connections at the motor (see Figure 10). Correct any voltageissues before proceeding to the next step. The X13 Motor is voltagespecific.Onlythecorrectvoltageshouldbeappliedtothepropermotor.Inputvoltagewithinplusorminus10%ofthenominal230VAC is acceptable.
2.If the motor has proper high voltage and ground at the (L/L1)(G) (N/L2) connections, then continue with the “Model X13Communication Diagnostics”.
1. It is normal for the motor to rock back and forth on start up. Do
not replace the motor if this is the only problem identied.
2. If the system is excessively noisy, does not appear to change
speeds in response to a demand (Heat, Cool, Other), or is having
symptoms during the cycle such as tripping limit or freezing coil, check
the following:
a. Wait for programmed delays to time out.
b. Ensure that the motors control inputs are wired to the factory
supplied wiring diagram to insure motor is getting proper
control signals and sequencing.
c. Remove the lter and check that all dampers, registers, and
grilles are open and free owing. If removing the lters
corrects the problem, clean or replace with a less restrictive
lter. Also check and clean the blower wheel or coil as
necessary.
d. Check the external static pressure (total of both supply and
return) to insure that you are within the ranges as listed on the
unit serial plate. If higher than allowed, additional duct work
is needed.
FIGure 10
e. If the motor does not shut off at the end of the cycle, wait for
any programmed delays to time out (no more than 90
seconds). Also make sure that there is no call for
“Continuous Fan” on the “G” terminal.
f. If the above diagnostics do not solve the problem, conrm the
voltage checks in the next section below, then continue with
the “Model X13 Communication Diagnostics”.
If the Motor is Not Running
1. Check for proper high voltage and ground at the (L/L1) (G) (N/
L2) connections at the motor (see Figure 10). Correct any voltage
issues before proceeding to the next step. The X13 Motor is voltage
specic. Only the correct voltage should be applied to the proper
motor. Input voltage within plus or minus 10% of the nominal 230
VAC is acceptable.
2. If the motor has proper high voltage and ground at the (L/
L1) (G) (N/L2) connections, then continue with the “Model X13
Communication Diagnostics”.
↓
L2 LINE
POWER
EARTH
GROUND
↓
L1 LINE
POWER
NOTE: MOTOR IS CONS TANTLY
POWERED BY LINE VOLTAGE
Manual 2100-467K
Page 23 of 24
trOubleshOOtInG Ge x13-serIes ecm2.3™ mOtOrs cOnt’D.
FIGURE11
™
MOTORS
CONT’D.
2.Initiateademandfromthethermostatandcheckthevoltagebetweenthecommonandtheappropriatemotorterminal(1-5).("G"inputistypicallyonterminal#1,butrefer to wiring diagram!)
a.If the low voltage communication is not present, check
the demand fromthe thermostat. Also check theoutput terminaland wire(s) from the terminal strip orcontrol relay(s) to the motor.
b.If the motor has proper high voltage as identified
above (Motor not Running #1), and proper low voltagetoaprogrammedterminal,andisnotoperating,themotorisfailed,andwillrequirereplacement.
Model X13 Communication Diagnostics
The X13 motor is communicated through 24 VAC low voltage
(Thermostat Control Circuit Wiring).
1. Start with unit wiring diagram to conrm proper
connections and voltage (see Figure 11).
24VAC Common
FIGure 11
2. Initiate a demand from the thermostat and check the
voltage between the common and the appropriate motor
terminal (1-5). (“G” input is typically on terminal #1, but refer
to wiring diagram!)
a. If the low voltage communication is not present, check
the demand from the thermostat. Also check the
output terminal and wire(s) from the terminal strip or
control relay(s) to the motor.
b. If the motor has proper high voltage as identied
above (Motor not Running #1), and proper low voltage
to a programmed terminal, and is not operating, the
motor is failed, and will require replacement.
24VAC "R" Signal thro ugh
thermostat output.
24VAC Common
24VAC "R" Signal thro ugh
thermostat output.
Manual 2100-467K
Page 24 of 24
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.