Bard PA13302-A, PA13602-C, PA13602-B, PA13482-C, PA13362-A User Manual

...
SINGLE PACKAGE
AIR CONDITIONERS
MODELS
PA13242-A PA13302-A PA13362-A PA13362-B PA13422-A PA13422-B PA13422-C PA13482-A PA13482-B PA13482-C PA13602-A PA13602-B
PA13602-C
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914 . . . Moving ahead just as planned.
Manual : 2100-467K Supersedes: 2100-467J File: Volume II Tab 10 Date: 07-25-12
Manual 2100-467K Page 1 of 24
CONTENTS
Getting Other Informations and Publications .........3
General Instructions
Important .................................................................4
Shipping Damage .....................................................4
General .................................................................4
Field Installed Heater Packages (Optional) ..............4
Installation
Location ...............................................................10
Slab Mounting .........................................................10
Typical Installations .........................................10 & 13
Condensate Drain Trap ...........................................13
Air Filters ...............................................................13
Wiring – Main Power ...............................................14
Wiring – 24V Low Voltage Control Circuit ...............14
Transformer Taps ....................................................14
Thermostats ............................................................14
Figures
Figure 1A Unit Dimensions .......................................8
Figure 1B Unit Dimensions .......................................9
Figure 2 Slab Mounting at Ground Level .............. 11
Figure 3 Airow and Service Access
Clearances .............................................11
Figure 4 Elevated Mounting Platform ...................12
Figure 5 Condensate Drain Trap ..........................13
Figure 6 Low Voltage Wiring ................................15
Figure 7 Low Ambient Control Wiring ...................18
Figure 8 Fan Blade Setting ...................................19
Figure 9 Brazing Diagram ....................................22
Figure 10 Motor Connections .................................23
Figure 11 Wiring (Connections/Voltage) .................24
Start Up and Operation
General ...............................................................16
Topping Off System Charge ....................................16
Safety Practices ......................................................16
Start Up Notes ........................................................16
Three Phase Scroll Compressor Start Up
Information ..............................................................17
Sequence of Operation ...........................................17
Indoor Blower Motor ................................................17
Compressor Control Module ...........................17 & 18
Adjustments ............................................................18
Low Ambient Control ...............................................18
Service and Troubleshooting
Service Hints ...........................................................19
Pressure Service Ports ...........................................19
R-410A Refrigerant Charge ....................................19
Fan Blade Settings .................................................19
Pressure Tables ..............................................20 & 21
Suction and Discharge Tube Brazing ......................22
Troubleshooting GE Blower Motors .................23-24
Tables
Table 1 Rated CFM & ESP ...................................4
Table 2 Electrical Specications ...........................5
Table 3 Opt. Field Installed Heater Packages .......6
Table 4 Opt. Field Installed Elec. Heater ..............7
Table 5 Filter Requirements & Sizes ...................13
Table 6 Thermostat Wire Size .............................14
Table 7 Wall Thermostats ...................................14
Table 8 Indoor Blower Performance ...................19
Table 9 Pressure T able .......................................20
Table 10 Pressure Table .......................................21
Manual 2100-467K Page 2 of 24
Getting Other Information and Publications
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code .......................ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for W arm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ...............ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOr mOre InFOrmatIOn, cOntact these PublIshers:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-467K Page 3 of 24
General InstructIOns
ImPOrtant
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return
ducts, must be properly sized for the design airow
requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
shIPPInG DamaGe
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
General
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made.
FIelD InstalleD heater PacKaGes (OPtIOnal)
These packaged air conditioners are manufactured without supplementary electric heaters. Supplementary
heaters are available for simple, fast eld installation.
A separate power circuit is required for the supplementary heaters.
IMPORTANT: Refer to Table 1 when designing duct work for maximum available static pressure with heater installed.
Refer to data shown in Table 3 and 4 for proper application information on all available heater combinations and what units they can be used with. It also shows the applicable circuit ampacities, fuse size, and wire size for each heater combination.
table 1
rateD cFm anD external statIc Pressure
(esP)
model
no.
PA1324 800 Note 0.18 0.50 PA1330 1000 Note 0.23 0.50 PA1336 1100 Note 0.23 0.50 PA1342 1450 Note 0.23 0.50 PA1348 1550 Note 0.28 0.50 PA1360 1750 Note 0.28 0.50
NOTE: ECM motors provide rated CFM up to 0.50 ESP
rated
cFm
recommended
Airow Range
rated
esP
max.
esP
Manual 2100-467K Page 4 of 24
460-60-3
230/208-60-1 230/208-60-3
460-60-3
230/208-60-1 230/208-60-3
460-60-3
table 2
electrIcal sPecIFIcatIOns
230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-3 230/208-60-1 230/208-60-3
model Pa13242-a Pa13302-a Pa13362-a Pa13362-b Pa13422-a Pa13422-b Pa13422-c Pa13482-a Pa13482-b Pa13482-c Pa13602-a Pa13602-b Pa13602-c
electric rating –
60 hz – circuit a
Operating Voltage Range 197 - 253 197 - 253 197 - 253 187 - 253 197 - 253 187 - 253 414-506 197 - 253 187 - 253 414-506 197 - 253 187 - 253 414-506
Minimum Circuit Ampacity 15 18 24 16 33 23 12 33 29 14 39 26 17
Fan motor and condenser
Fan Motor – HP/RPM 1/6 - 825 1/6 - 825 1/6 - 825 1/6 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825 1/4 - 825
BCSC 9 11 15 10 21 15 8 22 14 8 26 16 9
Field Wire Size * 12 10 8 12 10 10 14 8 10 12 8 10 10
Ground Wire Size 12 10 8 12 10 10 14 8 10 14 8 10 12
Delay Fuse – Max. ** 20 25 35 20 50 35 15 50 40 20 60 40 25
Total unit Amps – 230/208 10.8/11.8 13.3/14.8 16.4/18.4 17.0/13.3 16.2/18.1 14.1/15.4 10.4 23.0/24.7 16.9/18.0 10.7 25.3/28.9 17.7/19.9 11.9
compressor – circuit a
Compressor Type Recip. Recip. Recip. Recip. Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Volts 230/208 230/208 230/208 230/208 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460
Rated Load Amps 7.5/8.5 9.5/11 12/14 7.6/8.9 11.8/13.7 8.3/9.6 7.7 17/18.7 10.9/12 7.7 19.3/22.9 11.7/13.9 8.6
Lock Rotor Amps 48/48 57/57 74/74 75/75 115/115 115/115 50 117/117 83.1/83.1 50 134/134 110/110 52
Fan Motor Amps 1.1 1.1 1.1 1.1 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Fan – Dia./CFM 24”/2700 24”/2600 24”/2600 24”/2600 24”/3400 24”/3400 24”/3400 24”/3400 24”/3400 24”/3400 24”/3400 24”/3400 24”/3400
motor and evaporator
Blower Motor – HP/RPM 1/3 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 1/2 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM 3/4 - ECM
Blower Motor – Amps 2.2 2.7 3.3 3.3 3.9 3.9 3.9 4.5 4.5 4.5 5.0 5.0 5.0
CFM Cooling 800 1000 1150 1150 1450 1450 1450 1550 1550 1550 1750 1750 1750
Charge (R-410 oz.) 75 85 120 120 160 160 160 160 160 160 160 160 160
Shipping Weight (pounds) 360 410 410 410 440 440 490 440 440 500 450 450 500
Manual 2100-467K Page 5 of 24
table 3
OPtIOnal FIelD InstalleD heater PacKaGes
OnlY tO be useD WIth the mODels InDIcateD
Pa13242-a Pa13302-a Pa13362-a Pa13362-b Pa13422-a Pa13422-b Pa13422-c Pa13482-a Pa13482-b Pa13482-c Pa13602-a Pa13602-b Pa13602-c
Phase
Volts &
Manual 2100-467K Page 6 of 24
model
EHP323-A10 240/208-1 X X X
EHP323-A05 240/208-1 X X X
heater Package
EHP323-A15 240/208-1 X X
EHP323-B09 240/208-3 X
EHP323-B15 240/208-3 X
EHP513-A05 240/208-1 X X X
EHP513-A10 240/208-1 X X X
EHP513-A15 240/208-1 X X X
EHP513-B09 240/208-3 X X X
EHP513-B15 240/208-3 X X X
EHP513-C09 460-3 X X X
EHP513-C15 460-3 X X X
Circuit B
Wire
Ground
Field
Power
Current
Max.Over
Min.
Circuit
Size
Wiring
Protection
Ampacity
table 4
OPtIOnal FIelD InstalleD electrIc heater table
Circuits
No. Field
Circuit
Heater
Internal
Breaker
240/208V
Htr. Amps
@ 208 Volts
Htr. KW & Capacity
@ 240 Volts
Htr. KW & Capacity
KW BTUH KW BTUH
1 26/23 30/25 10/10 10
30/60
1 26/23 30/25 10/10 10
30/60
1 28/24 30/25 10/10 10
None
1 28/24 30/25 10/10 10
None
1 14 15 14 14
None
Phases
Unit Volts
Heater
Package
Model No.
EHP323-A05 240/208-1 5 17,100 3.75 12,800 20.8/18.1
EHP323-A10 240/208-1 10 34,100 7.50 26,000 41.6/36.2 1 53/46 60/50 6/8 10
EHP323-A15 240/208-1 15 51,200 11.25 38,400 62.5/54.1 1 79/68 80/70 4/4 8
EHP513-A05 240/208-1 5 17,100 3.75 12,800 20.8/18.1
EHP513-A10 240/208-1 10 34,100 7.50 26,000 41.6/36.2 1 53/46 60/50 6/8 10
EHP513-A15 240/208-1 15 51,200 11.25 38,400 62.5/54.1 1 79/68 80/70 4/4 8
EHP323-B09 240/208-3 9 30,700 6.75 23,000 21.7/18.7
EHP323-B15 240/208-3 15 51,200 11.25 38,400 36.2/31.2 1 46/39 50/40 8/8 10
EHP513-B09 240/208-3 9 30,700 6.75 23,000 21.7/18.7
EHP513-B15 240/208-3 15 51,200 11.25 38,400 36.2/31.2 1 46/39 50/40 8/8 10
EHP513-C09 480-3 9 30,700 10.8
EHP513-C15 480-3 15 51,200 18 1 28 30 10 12
conductor wires in accordance with the National Electrical Code and all existing local codes.
MaximumsizeofthetimedelayfuseorHACRcircuitbreakerforprotectionofeldwiringdevices.
These“MinimumCircuitAmpacity”valuesaretobeusedforsizingtheeldpowerconductors.RefertotheNationalElectricCode(latestrevision),Article310forpower
conform to the National Electric Code and all local codes.
Based on wire suitable for 75°C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based on 75°C copper wire. All wiring must
conductor sizing.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and
Manual 2100-467K Page 7 of 24
FIGure 1a
Return opening
Drain access
Supply opening
High voltage knockout
Low voltage knockout
access door
Control panel door
Heater package access panel
Compressor
Heater package knockout
A
E
C
D
L
W
B
F
Condenser air
Condenser air
intake grille
intake grille
access door
Blower motor
Condenser fan
G
47 11/16"
H
Unit Dimension Chart
MIS-2142 A
A C B C H (height) L (length) W (width) D E F G PA/PH1324,1330,1336 5.875 32.875 13.875 32.875 26.25 53.25 38.125 23.25 1.125 1.375 35.625 PA/PH1342,1348,1360 9.875 37.875 15.875 37.875 33.25 55.25 42.375 30.25 1.5 2.375 38.125
Unit
Unit General Dimensions
Supply Size
Return Size
Unit Overall Dimensions
DImensIOns OF unIts
Page 8 of 24
Manual 2100-467K
FIGure 1b
DImensIOns OF unIts
A B
C
G
H
A
D
FE
D
UNIT A B C D E F GH PA/PH1324, 1330, 1336 7 3/16" 38 13/16" 36 3/4" 1 3/8" 33 5/8" 35 1/2" 18 3/16" 17 1/4" PA/PH1342, 1348, 1360 8 3/16" 39 13/16" 36 3/4" 1 3/8" 37 3/4" 39 3/4" 181/2" 171/2"
Manual 2100-467K Page 9 of 24
MIS-3033
InstallatIOn
lOcatIOn
General
The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the living area or adjacent buildings.
slab mOuntInG
A minimum of 24 inches should be provided between the coil inlet and any building surfaces. Provide a minimum of three feet clearance on the service access side of the unit. See Figure 2.
tYPIcal InstallatIOns
1. rOOF mOunteD – The unit is mounted on a
sturdy base on the roof of the building. Return air to the unit is brought through a single return
grille (grilles with built-in lters are best since they enable easy access for lter changing). Return air
ducts are attached to the lower section of the front panel. Supply air is brought from the unit to attic duct work or to a furred down hall. Supply air duct is attached to the top of the front panel.
In roof top installation, as in all installations, the
air conditioner must be level from side to side. However, the unit should have a pitch along the length to assure complete external drainage of precipitation and of defrost condensate.
2.
craWl sPace – Duct work installed in crawl
space must be well insulated and provided with a vapor barrier. In addition, the crawl space must be thoroughly ventilated and provided with a good vapor barrier as a ground cover. It is most desirable to install the unit will be outdoors rather than inside the crawl space, so that it will be readily accessible for service.
3. slab mOunteD at GrOunD leVel – This
type installation is ideal for homes with a slab
oor construction where a roof mounted unit is not
desired. The supply and return duct work can be run through a furred closet space.
4. thrOuGh the Wall – This type installation
requires a suitable framework to be fabricated capable of withstanding the unit weight. Normally the unit will be insulated so as to minimize supply and return duct work.
CAUTION: All outdoor duct work must be
thoroughly insulated and weatherproofed. All attic duct work must be thoroughly insulated. Two inch thick insulation with suitable vapor barrier is recommended for both outdoor and attic runs.
Manual 2100-467K Page 10 of 24
36" min.
24" min.
24" min.
The distance between
1 inch clearance
Access
Air Inlet
Comp-
Nearest Structure
Air Inlet
Supply and Return Ducts
Nearest Structure
Nearest Structure
Building
Control Panel
Access
Control Panel
Access
Heater Package
Access
Blower Service
and
ressor
Blower Motor
Heater Package
Blower
Compressor
from top.
units only).
Condenser fan
and motor access
above fan.
Leave 60" min.
Side
View
View
Top
between duct and
any combustible
material if distance
between outside
wall and unit is less
than 3 feet (needed
on electric heat
MIS-2143 A
Mounting Slab
Ground Level
Package Unit
Supply Duct
from building
Return Duct
requirements.
outside wall and unit
Air Outlet
varies with installation
1/4 inch per foot slope away
Building
FIGure 2
slab mOuntInG at GrOunD leVel
FIGure 3
aIrFlOW anD serVIce access clearances
Manual 2100-467K Page 11 of 24
FIGure 4
Both legs must rest
on surface of platform
32°F or lower climate
12" min. if in
48" min.
48" min.
32°F or lower climate
12" min. if in
on surface of platform
Both legs must rest
Platform can be as
shown or solid
Poured concrete, brick, or block
Metal frame
MIS-2144 A
eleVateD mOuntInG PlatFOrm
*
* AS REqUIRED
Manual 2100-467K Page 12 of 24
*
5. Other InstallatIOns – Many other
installations are possible with the packaged air conditioner. No matter what the installation, always consider the following facts:
A. Insure that the discharge air is not obstructed in
any way so as to cause operation difculties.
B. The indoor coil drain pan is equipped with a
coupling that must be piped through a condensate drain trap to a suitable drain.
C. Always mount the unit is such a position that it
may be easily reached for servicing and maintenance.
D. Insure that the unit is clear so that proper air
ow over the outdoor coil will be maintained.
If this unit is operated in cooling below a 55° outdoor ambient temperature, the installation of low ambient controls (CMA-28) to unit is required.
Prior thought should be given to return air location and
placement of the air lter(s). The air lter(s) must be
of adequate size and readily accessible to the operator of the equipment. Filters must be adequate in size and properly maintained for proper operation. If this is not done, excessive energy use, poor performance, and multiple service problems will result. It is impossible to oversize air lters. Generous sizing will result in cleaner air and coils as well as lower operating costs and extend the time between required changes. Table
5 shows minimum lter areas and recommended lter sizes. Actual lter sizes can vary with the installation due to single or multiple returns utilizing a lter/grille
arrangement or being placed immediately ahead of the indoor coil face in the return air duct.
table 5
FIlter requIrements & sIzes
cOnDensate DraIn traP
It is very important to provide a trap in the condensate drain line to allow a positive liquid seal in the line and assure correct drainage from the coil condensate pan.
Install condensate drain trap shown in Figure 8. Use drain connection size or larger. Do not operate unit without trap. Unit must be level or slightly inclined toward drain. With a trap installed on a unit located in an unconditioned area, water in the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes.
aIr FIlters
Air lters for the return air side of the system are not provided as part of these models, and must be eld supplied and installed as part of the nal installation.
cOnDensate DraIn traP
NOTE: If roof hood accessory is to be used,
FIGure 5
model no.
PA1324 PA1330 PA1336
PA1342 PA1348 PA1360
minimum Filter
Free area
403 Square Inches
(2.8 Square Feet)
473 Square Inches
(3.3 Square Feet)
recommended size
information on air lters may be found under that heading in this manual. Air lters are
supplied as part of that package.
minimum
(2) 14 x 20 x 1
(2) 16 x 20 x 1
Manual 2100-467K Page 13 of 24
WIrInG – maIn POWer
Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that
the eld wiring used must be sized to carry that amount of current. If eld installed heaters are added to the
basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical
Specications” on pages 5 & 7.) All models are suitable for connection with copper wire only. These
instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.
The electrical specications list fuse and wire sizes
(75°F copper) for all models including the most commonly used heater sizes.
The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.
WIrInG – 24V lOW VOltaGe cOntrOl cIrcuIt
Five (5) wires should be run from thermostat subbase
to the 24V terminal board in the unit. A ve conductor,
18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 6.
table 6
thermOstat WIre sIze
transformer
Va
55 2.3
Fla
Wire
Gauge
20 18 16 14 12
maximum
Distance
In Feet
45
60 100 160 250
transFOrmer taPs
230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
taP ranGe 240 253 – 216 208 220 – 187
NOTE: The voltage should be measured at the eld
power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
thermOstats
See specic wiring information for the different models, heater KWs, and voltages on unit and heating wiring
diagrams.
table 7
Wall thermOstats
thermostat Predominant Features
8403-058
(TH5220D1151)
8403-060
(1120-445)
IMPORTANT NOTE: Only the thermostats as shown above will work with this equipment. The thermostats and
correct operation can be assured only by proper selection and application of these parts.
Manual 2100-467K Page 14 of 24
2 stage Cool; 2 stage Heat Electronic Non-Programmable
AutoorManualchangeover
3 stage Cool; 3 stage Heat Programmable/Non-Programmable Electronic
HPorConventional AutoorManualchangeover
E
Y
1120-445
TH5220D1151
Low Voltage Wiring
L
2
C
O
1
Unit Control Panel
Block
Y
C
G R
W1 W2
E
F
Y1C
G R
W1O
Y2 W2
D
A
E
L
AUX
R
G
E
B
RC
3
L
B
Thermostat Subbase
Terminal
HEAT ON UNITS WITH 15 OR MORE KW
YO
Unit 24V
REMOVE JUMPER FOR 2 STAGE ELECTRIC
MIS-2149 C
FIGure 6
lOW VOltaGe WIrInG
Manual 2100-467K Page 15 of 24
start uP
These units require R-410A refrigerant and Polyol Ester oil.
General:
1. Use separate service equipment to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and R-12. Although nearly azeotropic, charge with liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than R-22, and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used - even a deep vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
tOPPInG OFF sYstem charGe
If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above), and charging to the nameplate charge. Topping off the system charge can be done without problems.
With R-410A, there are no signicant changes in the
refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.
saFetY PractIces:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses, Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become ammable.
4. Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never ll cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands signicantly
at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.
start uP nOtes
For improved start up performance, wash the indoor coil with dishwasher detergent.
Manual 2100-467K Page 16 of 24
start uP anD OPeratIOn
three Phase scrOll cOmPressOr start uP InFOrmatIOn
(Models PA13362-B; PA13422-B, -C; PA13482-B, -C; PA13602-B, -C)
All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two LED’s. If the “Y” signal is present at the phase monitor and phases are correct, the green LED will light.
If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.
If a fault condition occurs, reverse tow of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.
sequence OF OPeratIOn
blOWer OnlY – When the “Fan” switch on the
room thermostat is placed in the “On” position (circuit R-G makes), the blower will energize and run until the “Fan” switch is placed back into the “Auto” position. This will allow for constant air circulation at a lower
airow during times when the unit is not in operation
for cooling or heating.
cOOlInG – On a call for cooling from the room
thermostat (circuit R-Y makes), the blower will energize (circuit R-G is automatic when R-Y makes) as well as the compressor, and outdoor fan motor. Note that if the “Fan” switch on the room thermostat is in the “On” position and the blower is already in operation, then the motor will ramp up to the required speed for cooling.
heatInG (1st stage) – On a call for heating
from the room thermostat (circuit R-W1 makes), the blower will energize (circuit R-G is automatic when R-W1 makes). This will place the system into heating operation to maintain the thermostat set temperature. Note that if the “Fan” switch on the room thermostat is in the “On” position and the blower is already in operation, then the motor will ramp up to the required speed for heating.
InDOOr blOWer mOtOr
These models feature a variable speed (ECM) motor
providing high efciency, low sound levels and soft
start capabilities. The motor is self adjusting to provide
the proper airow rate at duct static pressures up to
0.50" WC without user adjustment or wiring changes. On command from the wall thermostat the motor will
start slowly and ramp up to full speed over a period of 10-15 seconds.
When the thermostat is satised the blower will operate
for approximately 1 minute, and then slow down and stop.
cOmPressOr cOntrOl mODule
The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm output.
aDJustable DelaY-On-maKe anD breaK tImer
On a call for compressor operation the delay-on-make period begins which will be 10% of the delay-on- break setting. When the delay-on-make is complete and the high pressure switch (and low pressure switch if employed) is closed, the compressor contactor is energized. Upon shutdown, the delay-on-break timer starts and prevents restart until the delay-on-break and delay-on-make periods have expired.
hIGh Pressure sWItch anD lOcKOut sequence (standard Feature)
If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay­on-make time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm circuit will energize. Recycling the wall thermostat resets the manual lockout.
heatInG (2nd stage) – If the operation of the 1st
Stage electric heaters will not maintain the set room temperature, then the thermostat will call for additional heat to help maintain the set temperature. On a call for second stage heating from the room thermostat (circuit R-W2 makes), additional electric heaters will be energized if installed.
Manual 2100-467K Page 17 of 24
lOW Pressure sWItch, bYPass, anD lOcKOut sequence (standard Feature)
lOW ambIent cOntrOl
If the low pressure switch opens for more that 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay-on-make time delay has expired. If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm circuit will energize. Recycling the wall thermostat resets the manual lockout.
alarm OutPut
Alarm terminal is output connection for applications where alarm signal is desired. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.
NOTE: Both high and low pressure switch controls
are inherently automatic reset devices. The high pressure switch and low pressure switch
cut out and cut in settings are xed by specic
air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.
aDJustments
Optional Low Ambient Control
An optional low ambient control is available for both
factory and eld installed options. The low ambient
control is to be applied to the PA13 Series models when operation below 55° outdoor conditions are anticipated. Without this device, the evaporating pressure would fall off, and the indoor coil would ice over.
The fan cycling control cycles the fan motor on, once the liquid refrigerant pressure reaches 350 psig, and off, once it has dropped to 225 psig. It will continue to cycle between these parameters depending on outdoor temperatures and the load/stage of the system.
This cycling maintains a minimum liquid pressure affecting the minimum suction pressure. This effect insures an evaporating temperature that is slightly above the point of ice formation on the evaporator.
This eld installed option is Bard Part #CMA-28. See
Figure 7.
FIGure 7
lOW ambIent cOntrOl WIrInG
aDJust able Dela Y-On-maKe anD
elaY-On-breaK tImer
D
The potentiometer is used to select Delay-on-Break time from 30 seconds to 5 minutes. Delay-on­Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay­on-Break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (160 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
Manual 2100-467K Page 18 of 24
serVIce anD trOubleshOOtInG
serVIce hInts
1. Caution homeowner to maintain clean air lters at
all times. Also, not to needlessly close off supply
and return air registers. This reduces airow
through the system which shortens equipment service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure that they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full
and unrestricted airow circulation is essential.
Pressure serVIce POrts
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in this manual covering all models on cooling cycle. It is imperative to match the correct pressure table to the unit by model number.
r-410a
reFrIGerant charGe
Fan blaDe settInGs
Shown in Figure 8 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGure 8
Fan blaDe settInG
3¼"
MD-1417BC
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity
and efciency ratings were determined by testing with
this refrigerant charge quantity. The following pressure tables show nominal
pressures for the units. Since many installation
specic situations can affect the pressure readings, this information should only be used by certied
technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
InDOOr blOWer PerFOrmance
model
PA1324 0.10 0.50 600 800 800 PA1330 0.15 0.50 750 1000 1000 PA1336 0.15 0.50 825 1100 1100 PA1342 0.20 0.50 925 1400 1400 PA1348 0.20 0.50 1025 1550 1550 PA1360 0.20 0.50 1150 1750 1750
1 MotorwilldeliverconsistentCFMthroughvoltagesupplyrangewithnodeterioration
(197-253V for all 230/208V models).
2 Continuous CFM is the total air being circulated during continuous (manual fan) mode. 3 Will occur automatically with a call for “Y” for cooling mode operation. 4 Will occur automatically with a call for “W1” for heating mode operation.
rated
esP
max
esP
table 8
continuous
Airow
rated
cooling cFm
m
rated
heating cFm
Manual 2100-467K Page 19 of 24
147
532
157
546
169
565
152
539
162
145
507
155
520
167
538
150
512
160
143
482
153
494
165
512
148
484
158
142
457
151
469
163
485
145
457
156
140
432
150
443
161
459
143
429
141
139
137
402
374
353
153
151
149
147
Air Temperature Entering Outdoor Coil Degree F
138
407
148
418
159
432
137
382
146
392
157
406
135
358
144
367
155
380
553
525
497
469
440
412
400
362
174
172
170
167
165
163
160
158
573
543
514
485
456
427
397
375
142
141
139
138
136
135
133
519
494
468
443
418
393
369
152
150
149
147
146
144
142
532
506
480
455
429
413
378
163
162
160
158
157
155
153
551
524
497
471
444
417
391
table 9
Pressure table
133
131
129
127
125
Pressure 65° 70° 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° 125°
Low Side
75° DB
Return Air
Temperature
334
142
310
140
286
138
262
136
238
134
Low Side
High Side
80° DB
62° WB
343
153
318
151
293
148
269
146
244
144
Low Side
High Side
85° DB
67° WB
355
135
332
329
133
310
304
131
289
278
128
267
253
126
246
Low Side
High Side
High Side
75° DB
72° WB
62° WB
144
340
142
318
140
296
137
274
135
252
Low Side
High Side
80° DB
67° WB
155
352
153
329
150
306
148
284
145
261
Low Side
High Side
85° DB
72° WB
132
344
130
320
128
295
127
271
125
247
Low Side
High Side
75° DB
62° WB
141
353
139
328
137
303
136
278
134
253
Low Side
High Side
80° DB
67° WB
151
365
149
339
148
314
146
288
144
262
Low Side
High Side
85° DB
72° WB
(continued on Page 20 in table 11)
cOOlInG
Manual 2100-467K Page 20 of 24
Model
PA1324
PA1330
PA1336
LOW SIDE PRESSURE +4 PSIG
TablesbaseduponratedCFM(airow)acrosstheevaporatorcoil.
HIGH SIDE PRESSURE +10 PSIG
If incorrect charge suspected (more than +4psigsuction,+10psigliquid),
itisrecommendedrefrigerantchargebereclaimed,systemevacuatedandchargedtoserialplatequantity.
143
551
153
565
165
585
142
547
152
142
523
152
536
163
555
140
520
150
141
494
151
507
162
525
139
492
148
140
466
149
478
160
494
137
465
147
138
437
148
448
159
464
136
438
134
133
132
410
383
359
145
144
142
141
Air Temperature Entering Outdoor Coil Degree F
137
409
146
419
157
434
136
380
144
402
156
404
134
357
143
366
154
379
561
533
505
477
449
421
404
368
163
161
160
158
156
154
153
151
581
552
523
494
465
436
407
381
134
133
132
131
131
130
129
530
505
480
456
431
406
375
143
142
141
141
140
138
138
544
518
493
467
442
426
385
154
153
152
151
150
149
148
563
537
510
484
457
431
398
table 10
Pressure table
132
131
129
128
126
Pressure 65° 70° 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° 125°
Low Side
75° DB
Return Air
Temperature
334
142
343
311
140
319
288
138
295
265
137
272
242
135
248
Low Side
High Side
High Side
80° DB
62° WB
67° WB
152
355
151
330
149
306
147
281
145
257
Low Side
High Side
85° DB
72° WB
130
335
311
129
128
287
127
263
125
239
Low Side
High Side
75° DB
62° WB
139
344
138
319
137
294
135
270
134
245
Low Side
High Side
80° DB
67° WB
150
356
148
330
147
305
145
279
144
254
Low Side
High Side
85° DB
72° WB
128
345
127
315
126
285
125
254
124
224
Low Side
High Side
75° DB
62° WB
137
354
136
323
135
292
134
261
133
230
Low Side
High Side
80° DB
67° WB
147
366
146
334
145
302
144
270
143
238
Low Side
High Side
85° DB
72° WB
Model
cOOlInG
PA1342
PA1348
PA1360
LOW SIDE PRESSURE +4 PSIG
HIGH SIDE PRESSURE +10 PSIG
TablesbaseduponratedCFM(airow)acrosstheevaporatorcoil.
If incorrect charge suspected (more than +4psigsuction,+10psigliquid),
itisrecommendedrefrigerantchargebereclaimed,systemevacuatedandchargedtoserialplatequantity.
Manual 2100-467K Page 21 of 24
suctIOn anD DIscharGe tube brazInG
Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used.
To disconnect: heat joint Areas 2 and 3 slowly and
uniformly until braze material softens and the tube
can be pulled out of suction tting. (See Figure 9.)
To connect:
– Recommended brazing materials: silfos with
minimum 5% silver or silver braze material with
ux.
brazInG DIaGram
– Reinsert tube into tting.
– Heat tube uniformly in Area 1 moving sl owly to
Area 2. When joint reaches brazing temperature, apply brazing material. (See Figure 9)
– Heat joint uniformly around the circumference
to ow braze material completely around the
joint.
– Slowly move torch into Area 3 to draw braze
material into joint. (See Figure 9.)
Do not overheat joint.
FIGure 9
Manual 2100-467K Page 22 of 24
trOubleshOOtInG Ge x13-serIes ecm2.3™ mOtOrs
FIGURE 10
NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C
contain the X13-Series Motors.
TROUBLESHOOTING GE X13-SERIES ECM2.3 MOTORS
If the Motor is Running
1. It is normal for the motor to rock back and forth on start up.
Do not replace the motor if this is the only problem identified.
2. If the system is excessively noisy, does not appear to change speeds in response to a demand (Heat, Cool, Other), or is having symptoms during the cycle such as tripping limit or freezing coil, check the following:
a. Wait for programmed delays to time out. b.Ensure that the motors control inputs are wired to the factory
supplied wiring diagram to insure motor is getting proper control signals and sequencing.
c. Remove the filter and check that all dampers, registers, and
grilles are open and free flowing. If removing the filters corrects the problem, clean or replace with a less restrictive filter. Also check and clean the blower wheel or coil as necessary.
d.Check the external static pressure (total of both supply and
return) to insure that you are within the ranges as listed on the unit serial plate. If higher than allowed, additional duct work is needed.
e. If the motor does not shut off at the end of the cycle, wait for
any programmed delays to time out (no more than 90 seconds). Also make sure that there is no call for “Continuous Fan” on the "G" terminal.
f. If the above diagnostics do not solve the problem, confirm the
voltage checks in the next section below, then continue with the “Model X13 Communication Diagnostics”.
If the Motor is Not Running
1. Check for proper high voltage and ground at the (L/L1) (G) (N/ L2) connections at the motor (see Figure 10). Correct any voltage issues before proceeding to the next step. The X13 Motor is voltage specific. Only the correct voltage should be applied to the proper motor. Input voltage within plus or minus 10% of the nominal 230 VAC is acceptable.
2. If the motor has proper high voltage and ground at the (L/L1) (G) (N/L2) connections, then continue with the “Model X13 Communication Diagnostics”.
NOTE:
Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C contain the X13-Series Motors.
If the Motor is Running
1. It is normal for the motor to rock back and forth on start up. Do
not replace the motor if this is the only problem identied.
2. If the system is excessively noisy, does not appear to change speeds in response to a demand (Heat, Cool, Other), or is having symptoms during the cycle such as tripping limit or freezing coil, check the following: a. Wait for programmed delays to time out. b. Ensure that the motors control inputs are wired to the factory supplied wiring diagram to insure motor is getting proper control signals and sequencing.
c. Remove the lter and check that all dampers, registers, and grilles are open and free owing. If removing the lters
corrects the problem, clean or replace with a less restrictive
lter. Also check and clean the blower wheel or coil as
necessary. d. Check the external static pressure (total of both supply and return) to insure that you are within the ranges as listed on the unit serial plate. If higher than allowed, additional duct work is needed.
FIGure 10
e. If the motor does not shut off at the end of the cycle, wait for any programmed delays to time out (no more than 90 seconds). Also make sure that there is no call for “Continuous Fan” on the “G” terminal.
f. If the above diagnostics do not solve the problem, conrm the
voltage checks in the next section below, then continue with the “Model X13 Communication Diagnostics”.
If the Motor is Not Running
1. Check for proper high voltage and ground at the (L/L1) (G) (N/ L2) connections at the motor (see Figure 10). Correct any voltage issues before proceeding to the next step. The X13 Motor is voltage
specic. Only the correct voltage should be applied to the proper
motor. Input voltage within plus or minus 10% of the nominal 230 VAC is acceptable.
2. If the motor has proper high voltage and ground at the (L/ L1) (G) (N/L2) connections, then continue with the “Model X13 Communication Diagnostics”.
L2 LINE POWER
EARTH
GROUND
L1 LINE POWER
NOTE: MOTOR IS CONS TANTLY
POWERED BY LINE VOLTAGE
Manual 2100-467K Page 23 of 24
trOubleshOOtInG Ge x13-serIes ecm2.3™ mOtOrs cOnt’D.
FIGURE 11
MOTORS
CONT’D.
2. Initiate a demand from the thermostat and check the voltage between the common and the appropriate motor terminal (1-5). ("G" input is typically on terminal #1, but refer to wiring diagram!)
a. If the low voltage communication is not present, check
the demand from the thermostat. Also check the output terminal and wire(s) from the terminal strip or control relay(s) to the motor.
b. If the motor has proper high voltage as identified
above (Motor not Running #1), and proper low voltage to a programmed terminal, and is not operating, the motor is failed, and will require replacement.
Model X13 Communication Diagnostics
The X13 motor is communicated through 24 VAC low voltage (Thermostat Control Circuit Wiring).
1. Start with unit wiring diagram to conrm proper connections and voltage (see Figure 11).
24VAC Common
FIGure 11
2. Initiate a demand from the thermostat and check the voltage between the common and the appropriate motor
terminal (1-5). (“G” input is typically on terminal #1, but refer
to wiring diagram!) a. If the low voltage communication is not present, check the demand from the thermostat. Also check the output terminal and wire(s) from the terminal strip or control relay(s) to the motor.
b. If the motor has proper high voltage as identied above (Motor not Running #1), and proper low voltage
to a programmed terminal, and is not operating, the motor is failed, and will require replacement.
24VAC "R" Signal thro ugh
thermostat output.
24VAC Common
24VAC "R" Signal thro ugh
thermostat output.
Manual 2100-467K Page 24 of 24
Loading...