Bard I36Z1-A, I36Z1-B, I36Z1-C, I48Z1-A, I48Z1-B Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
MIS-3116
I-TEC SERIES
PACKAGED HEAT PUMP
Models:
I36Z1-A I36Z1-B I36Z1-C
I48Z1-A I48Z1-B I48Z1-C
I60Z1-A I60Z1-B I60Z1-C
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-578E Supersedes: 2100-578D Date: 11-10-14
Page 1 of 41
CONTENTS
Getting Other Information and Publications
For more information, contact these publishers: ........... 3
General ......................................................................... 4
 ANSIZ535.5Denitions................................................ 4
I-TEC General Information
I-TEC Model Nomenclature .......................................... 5
Shipping Damage ......................................................... 8
Unit Removal From Skid ............................................... 8
Handling Unit After Removal From Skid ....................... 8
Required Steps after Final Placement ........................ 10
Minimum Installation Clearances ................................ 10
Securing Unit to Structure ........................................... 10
Seismic Considerations .............................................. 10
Rubber Mat ................................................................. 10
Duct Work ................................................................... 16
Filters .......................................................................... 16
Condensate Drain ....................................................... 17
With No Vent Option ................................................... 17
With Commercial Room Ventilator .............................. 17
Installation Instructions
Mounting the Unit ........................................................ 20
Wiring — Main Wiring .................................................. 20
Wiring — Low Voltage Wiring ...................................... 21
Low Voltage Connections ........................................... 21
Start Up
R-410A Refrigerant Required ......................................... 26
Topping Off System Charge ........................................... 26
Safety Practices.............................................................. 26
Description of Standard Equipment ................................ 26
Important Installer Note .................................................. 26
Phase Monitor ................................................................ 26
Three Phase Scroll Compressor .................................... 26
Service Hints .................................................................. 26
Sequence of Operation................................................... 27
Pressure Service Ports ................................................... 27
Defrost Cycle .................................................................. 28
I-TEC Commercial Room Ventilator System
General Description .................................................... 29
Control Wiring ............................................................. 29
Recommended Control Sequences ............................ 29
Setting the Ventilation CFM Levels ............................. 29
Annual Maintenance ..................................................... 33
Troubleshooting
Solid State HP Control Troubleshooting Procedure ....... 34
Checking Temperature Sensor ....................................... 35
Troubleshooting ECM™ 142R Motor .....................36 & 37
Replacing the Motor .......................................................37
Troubleshooting Indoor ECM™ Motor ....................38 & 39
Fan Blade Setting Dimensions ....................................... 40
Refrigerant Charge ......................................................... 40
Figures
Figure 1 Unit Dimensions ........................................... 7
Center of Gravity .......................................... 8
Figure 2A Unit on Lift .................................................... 8
Figure 2B Unit Side....................................................... 8
Wall Mounting Bracket Location ................................... 10
Bracket Wall Sect. View & Wood Framed Install ...........11
Figure 3 Compressor Shipping Bolts........................ 12
Figure 4 Removal of Air Duct ................................... 12
Figure 5A Ducted Application ..................................... 13
Figure 5B 3" Riser Application .................................... 13
Figure 5C 6" Riser Application .................................... 14
Figure 5D Req'd. Clearances & Rec. Access ............. 15
Figure 6 Supply Duct Connections ........................... 16
Figure 7 Filter Location............................................. 16
Figure 8 Drain Locations .......................................... 17
Figures 9A & 9B Unit Mounting ............................18 & 19
Figure 10 Component Location .................................. 20
Figure 11 Basic Heat Pump w/No Vent Pkg. .............. 22
Figure 12 Heat Pump w/CRV, without CO Figure 13 Heat Pump with CRV & CO
Figure 14 Defrost Cycle .............................................. 28
 Figure15 CRVMotorSpeed/CFMConguration ....... 30
Figure 16 CRV Speed Change Terminal Access ........ 31
 Figure17 VentilationAirowDiagram ........................ 32
Figure 18 Control Disassembly .................................. 39
Figure 19 Winding Test ............................................... 39
Figure 20 Drip Loop.................................................... 39
Figure 21 Control Connector Motor Half .................... 40
Control .... 23
2
Control .......... 24
2
Tables
Table 1 Factory Built-In Electric Heat Table ............... 5
Table 1A Indoor Blower Performance........................... 5
Table2 Elec.Specications ....................................... 6
Center of Gravity Table .................................. 8
Table 3 Operating Voltage Range ............................ 21
Table 4 Wall Thermostats ......................................... 21
Table 5 Troubleshooting ........................................... 34
Table 6 Temperature vs Resistance of
Temperature Sensor .................................... 35
Table 7 Troubleshooting ECM™ 142R .................... 37
Table 8 Cooling Mode .............................................. 37
Table 9 Heat Pump Mode ........................................ 37
Troubleshooting ECM™ Blower Motors ....................... 40
Power Connector ......................................................... 40
Table 10A Pressures: Full Load Cooling Table 10B Pressures: Full Load Heating Table 11A Pressures: Part Load Cooling Table 11B Pressures: Part Load Heating
I36Z-I60Z ..... 41
I36Z-I60Z ..... 41
I36Z-I60Z .... 41
I36Z-I60Z .... 41
Manual 2100-578E Page 2 of 41
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation ...............ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ..................... ACCA Manual J or
Winter and Summer Manual N Air Conditioning
Low Pressure, Low Velocity ......... ACCA Manual D or
Duct System Design Manual Q Winter and Summer Air Conditioning
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration, and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-578E Page 3 of 41
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The I-TEC must be installed with the Bard manufactured IWS wall sleeve and ILG louver grille accessories. These are sold as separate accessories. Any substitutions will void the manufacturer’s warranty.
The unit is designed for use with or without ductwork. For use without ductwork, Plenum Box IPBDFZ18­color (18" height) or IPBDFZ12-color (12" height) is recommended.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical connections to it.
These instructions and any instructions packaged with any separate equipment required to make up the entire heating and air conditioning system should be carefully read before beginning the installation. Note particularly “Start Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss or heat gain calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
ANSI Z535.5 Denitions:
Danger: Indicate[s] a hazardous situation which, if not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
Warning: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
Caution: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
Notice: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to “NOTICE” the word “CAUTION” without the safety alert symbol may be used to indicate a message not related to personal injury.
Manual 2100-578E Page 4 of 41
I-TEC Series General Information
I-TEC MODEL NOMENCLATURE Z-Version (CA) 2-Stage Air Source Heat Pumps
I 36 Z 1 A 0Z M P 1 X X 2
MODEL SERIES
NOMINAL CAPACITY
36 = 36,000 BTUH 48 = 48,000 60 = 60,000
SYSTEM TYPE:
H/P CA Design
REVISION
SPECIAL UNITS
(–) = Standard C = 460V Circuit
Breaker
VOLTS & PHASE |
A = 230/208, 60-1 B = 230/208, 60-3 C = 460-60-3
ELECTRIC HEAT
0Z = No heat w/breaker 04 = 4KW 1-Phase 05 = 5KW 1-Phase 06 = 6KW 3-Phase 09 = 9KW 3-Phase 10 = 10KW 1-Phase 15 = 15KW 1 & 3-Phase 18 = 18KW 3-Phase 20 = 20KW 1-Phase
VENTILATION OPTIONS
B = Blank-Off Plate M = Multi-Speed CRV
COLOR OPTIONS
X - Beige paint 1 - White paint 4 - Gray paint
FILTER OPTIONS
P = 2" Pleated MERV 8 M = 2" Pleated MERV 11 N = 2" Pleated MERV 13
VINYL GRAPHICS OPTIONS
X - None A - Letter Assigned as Req'd.
CONTROLS
X = 24V Terminal Block Only w/o CompleteStat 1 = CompleteStat THO (Temp, Humidity & Occupancy) 2 = CompleteStat THO w/CO2 3 = CompleteStat THO w/Ethernet 4 = CompleteStat THO w/CO2 & Ethernet
Note:CompleteStatmustbeeld
installed & wired. All units have
COIL TREATMENT
X - Std. Hydrophilic Fin Evap. & Uncoated Alum. Cond. Coil 1 - Phenolic Coated ID Coil 2 - Phenolic Coated OD Coil 3 - Phenolic Coated ID & OD Coil
TABLE 1
FACTORY BUILT-IN ELECTRIC HEAT TABLE
Models I36Z1-A I36Z1-B I36Z1-C I48Z1-A
KW
10.0 34,130 25,598 34,130 25,598 34,130 25,598
15.0 51,195 38,396 51,195 38,396 51,195 51,195 38,396 51,195 38,396 51,195 51,195 38,396
18.0 61,434 46,076 61,434
20.0 68,260 51,195 68,260 51,195
240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1 240V-3 208V-3 460V-3 240V-1 208V-1
BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH BTUH
4.0 13,652 10,239
5.0 17,065 12,799 17,065 12,799 17,065 12,799
6.0 20,478 15,359 20,478 20,478 15,359 20,478
9.0 30,717 23,038 30,717 30,717 23,038 30,717
I48Z1-B I60Z1-B
I48Z1-C I60Z1-C
24V terminal block.
I60Z1-A
Model Rated ESP Max. ESP
I36Z1
I48Z1
I60Z1
.15 0.50 600 1150 850 700 1400
.20 0.50 725 1500 1050 700 1400
.20 0.50 850 1700 1200 700 1400
Motor will deliver consistent CFM through voltage supply range with no deterioration. kContinuous fan CFM is the total air being circulated during continuous fan mode. lWilloperateatratedFullLoadAirowwhenoperatingwithHeatPump. mWill occur automatically with a call for "W3" or "Emergency Heat" signal from the thermostat (Heat Pump Operation is terminated at this condition).
TABLE 1A
INDOOR BLOWER PERFORMANCE
k
Continuous
CFM
Rated 2nd
Stage CFM
Rated 1st
Stage CFM
l
5 - 9 KW
CFM
13.5 - 18
KW CFM
Manual 2100-578E Page 5 of 41
m
TABLE 2
ELECTRICAL SPECIFICATIONS
Single Circuit Multiple Circuit
Rated
MODEL
Volts,
Hertz &
Phase
I36Z1-A0Z
A05
230/208-1
A10
A15
I36Z1-B0Z
B06
230/208-3
B09
B15
I36Z1-C0Z
C06
460-3
C09
C15
I48Z1-A0Z
A04 A05
230/208-1
A10
A15 A20
I48Z1-B0Z
B06
230/208-3
B09
B15 B18
I48Z1-C0Z
C06
230/208-1
C09
C15 C18
I60Z1-A0Z
A05
230/208-1
A10
A15 A20
I60Z1-B0Z
B06
230/208-3
B09
B15 B18
I60Z1-C0Z
C06
460-3
C09
C15 C18
These“MinimumCircuitAmpacity”valuesaretobeusedforsizingtheeldpowerconductors.RefertotheNationalElectricCode(latestrevision),Article310forpowerconductorsizing. Caution: Whenmorethanoneeldpowerconductorcircuitisrunthroughoneconduit,theconductorsmustbederated.Payspecialattentiontonote8oftable310regarding
Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
MaximumsizeofthetimedelayfuseorHVACtypecircuitbreakerforprotectionofeldwiringconductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes. Maximum KW that can operate with the heat pump is 10KW for 1-Phase and 9KW for 3-Phase.
Represents Electric Heat only. Electric Control Circuit will lock-out Heat Pump Operation.
No.
Field
Power
Circuits
1
1 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1
1
1
1
1
1
1
1
1 1 or 2 1 or 2 1 or 2 1 or 2
1
1
1
1 1 or 2
1
1
1
1
1
Minimum
Circuit
Ampacity
26 52 78 84
22 40 49 51
11 20 24 28
34 54 59 85 85
110
26 44 53 53 53
15 25 29 29 29
44 70 96 96
112
31 49 58 58 63
15 25 29 29 29
Maximum
External
Fuse or
Ckt. Brkr.
40 60 80 90
30 45 50 60
15 20 25 30
50 60 70 90 90
110
35 50 60 60 60
20 30 30 30 30
60
80 100 100 120
45
60
60
60
70
20
30
30
30
30
Field
Power
Wire
Size
8 6 4 4
10
8 8 6
14 12 10 10
8 6 6 3 3 2
8 8 6 6 6
12 10 10 10 10
8 4 3 3 2
8 8 6 6 6
12 10 10 10 10
Ground
Wire
10 10
10 10 10 10
14 12 10 10
10 10
10 10 10 10 10
12 10 10 10 10
10
10 10 10 10
12 10 10 10 10
Minimum
Circuit
Ampacity
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
8
26265252404060
8
8
35
8
35
8
35
6
59
8
44
8
44
8
44
6
60
8 31 54 45 60 8 6 10 10
26 52 52 52
26 52 52 52
Maximum
External
Fuse or Ckt.
Breaker
60
45
30
45
60
45
60
60
60
60
30
60
60
60
60
60
60
Field Power
Wire Size
8
6
8
6
8
10
8
6
8
6
6
6
8
10
8
6
8
6
6
6
Ground Wire
Size
101010
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Manual 2100-578E Page 6 of 41
Back View
Air
Supply
Sleeve
Outer
Inner
Sleeve
Air
Return
RUBBER MATT
PART #5451-027
MIS-3114 A
WIRE TIES
PART #7950-031
"
3
4
1
(2) Opt.
Unit Drain
Entrances
"
4
3
1
Unit Specification Sheet
"
3
8
31
FIGURE 1 — UNIT DIMENSIONS
20" x 24" Supply Frame
"
7
26
Total Depth
8
Right Side View
High Voltage
Entrance
"
4
3
18
2"
Sides Removed
30" With Doors and
Wire Channel
Electric Heat
Outer
Sleeve
Openings
(2) Return
Hinges
(4) Lift-Off
Inner
Sleeve
94"
Locking
Door Latch
Return
Electrical
Disconnect
Air
" 50
1
4
"
3
4
71
Upper
Section
(2) Side
Handles
Drains
(2) Unit
58"
Door Latch
Locking
8"
"
8
1
22
"
1
2
24
"
1
4
22
Lower
Section
" 15
5
8
RUBBER MATT &
FRONT TRIM LOCATION
"
3
4
3
(Remove Sides)
Side Forklift Holes
Front Forklift Holes
(Remove Front Trim)
2
20" 18"
61 " Total Width
" With Sides Removed
1
8
46
"
1
4
3
Top View
24"
"
4
1
28
Entrance
Low Voltage
"
1
4
9
Front View
Filters
Return Air
(2) 2"x24"x30"
Control Panel
Air Filters
(2) 16" x 25"
Vent Exhaust
Manual 2100-578E Page 7 of 41
CENTER OF GRAVITY
CENTER OF GRAVITY
"X"
"Y"
FRONT OF UNIT
Unit Tested
I36Z1-A, B 13½" 31" 43½" 47"
I36Z1-C 13½" 31½" 43½" 47"
I48Z1-A, B 13½" 31" 43½" 47"
I48Z1-C 13½" 31½" 43½" 47"
I60Z1-A, B 13½" 31" 43½" 47"
I60Z1-C 13½" 31½" 43½" 47"
DOOR TO CENTER
"X" Dimension "Y" Dimension "Z" Dimension "Z" Dimension
LEFT SIDE
TO CENTER
FLOOR TO CENTER
CRV & ERV
FLOOR TO CENTER
NO VENT
"Z"
MIS-3268
Manual 2100-578E Page 8 of 41
SHIPPING DAMAGE
Upon receipt of equipment, the unit should be checked for external signs of shipping damage. The skid must remain attached until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
UNIT REMOVAL FROM SKID
WARNING
This unit is heavy and requires more than one person to handle during installation and removal from the skid. Extreme caution must be taken to prevent injury to personnel and damage to the unit. Use appropriate safety equipment, including gloves when handling. Failure to do so may result in serious injury.
A forklift or a lift rated for the load (Figure 2A) is required to lift the unit off from the skid. This unit is top heavy and should never be tipped while moving it.
The I-TEC is designed to be lifted off the skid from the front or rear of the unit without having to remove any doors or side panels. See Figure 1 for fork openings. The shipping brackets on front and rear of the unit must be removed and discarded. The unit can now be lifted straight up and the skid can be slid out from underneath.
Tip unit from left side only. Failure to do so may result in injury due to unit top-heaviness or compressor damage!
HANDLING UNIT AFTER REMOVAL FROM SKID
If a wide and tall opening exists, the I-TEC can be moved as a complete assembled unit. If not, use the following directions for dis-assembly to allow it to pass through a 36" wide door.
1. Depress and release both top & bottom door latches and open doors.
2. Remove doors by lifting straight up & off from the hinge pins.
3. Remove cabinet sides by rst removing the four (4) sheet metal
screws from the front (leading edge) of the side panel. The panel will not fall off. Swing the panel away from the chassis 20-30 degrees & then pull forward from the two (2) tabs supporting the rear edge. At this point, the unit can be tipped on its left side enough to get dolly carts under it. Use dolly carts to move unit into installation area. Use care not to damage vent wire harness. This method is not suggested due to unit weight and if a forklift or unit lift is available, continue with
the following steps for separation of top section & bottom base.
4. On each side of the unit is a tie plate that secures the top & bottom sections with four (4) cap bolts. Using a ½" wrench or socket, remove these screws from both plates & set aside.
5. If the unit is equipped with a CRV, you must unplug the wire harness on the left-hand side of the control box.
6. A forklift or a lift rated for the load is required to lift the top section off from the bottom base. Do not attempt to do this manually! Failure to do so could result in the unit tipping over & causing bodily injury &/or damage to the unit.
7. The top section can be forked from either the RH or LH side. See Figure 1 for fork openings.
8. Carefully lift the top section straight up avoiding tipping.
9. Move the top section through the doorway & place on at
surface free of debris.
10. The bottom base can now be moved through the doorway the same way.
11. Reassemble the unit by reversing this procedure.
FIGURE 2A UNIT ON LIFT
LEFT SIDE of UNIT
FIGURE 2B UNIT SIDE
CRV
(4) CAP BOLTS
FORK OPENING
(Visible after removing tie plate)
HARNESS CONNECTION
(Covers entire width; shortened for illustration purposes to show Fork Openings)
TIE PLATE
Manual 2100-578E Page 9 of 41
REQUIRED STEPS AFTER FINAL PLACEMENT
MIS-3029
2"
1 11/16"
43 3/8"
Ø1/4"
94" FROM BOTTOM
OF BRACKET TO
FLOOR WITHOUT
RISER KIT
7/8"
3/4"
1 1/2"
BRACKET
The compressor is secured to the base with two (2) bolts for shipping. Although the unit will perform as designed with the shipping bolts in place, there may be noticeable additional noise and vibration noted. To obtain the lowest noise and vibration levels, remove the shipping bolts after
the unit is in its nal operating location. To gain access
to the compressor, the compressor access panel must be removed (Figure 7). Once this panel is removed, the CRV air duct must be removed. See Figure 4.
The air duct is removed by pulling it straight toward you; there are no screws securing it in place. Both the top and bottom slide toward you at the same time (pull hard). Once removed, the compressor is visible as well as the tags on the shipping bolts (Figure 3).
After the compressor shipping bolts have been removed, the CRV air duct can be slid back in place and the compressor access panel attached.
MINIMUM INSTALLATION CLEARANCES
The minimum installation height to the bottom of the
roof or xed ceiling for ducted applications is 9 ft. 7 in.
This provides enough clearance to install the duct work. See Figure 5A.
The IWS Series wall sleeve has a built-in vertical
adjustment to t window sill heights from 31-34 inches.
If additional height is required, two riser platform accessories are available. The IRZ3 increases the unit height by 3 inches (Figure 5B) and the IRZ6 by 6 inches (Figure 5C).
Several construction options are available for unit
installation of the IZ Series. Serviceability and lter
access must be considered before installing. See Figure 5D for required clearances and recommended service access dimensions.
SECURING UNIT TO STRUCTURE
Shipped with the I-TEC unit is a wall mounting bracket (screwed to shipping skid on backside of unit). This bracket can be utilized to secure the top portion of the unit to the
wall using the appropriate eld supplied hardware based
upon the material you are fastening to. (There are several offset holes, sized to accept up to a 1/4" diameter fastener that will easily allow you to hit studs on a framed wall.) See
BRACKET SECTION VIEW (Page 10) for locating this top wall bracket which will need to be applied after the unit is
located in the nal position.
Additional/optional mounting holes for up to a 3/8" diameter fastener are also available in the backside and base of the unit. These can be accessed by:
• removing the air lters (uppermost set)
• removing the compressor section service door (lower set)
• removing vent door and vent partitions (base set)
Refer to WOOD FRAMED INSTALLATION (Page 10) for additional framing required to secure unit to wall.
The additional/optional mounting holes will require a long extension to drive the fasteners.
SEISMIC CONSIDERATIONS
The I-TEC product features several locations for product securement but all site conditions are different. Consult with a licensed Seismic Engineer to advise of particular needs when attaching the I-TEC unit to the structure.
RUBBER MAT
Unit rests on rubber mat placed under base rails during
installation. Place mat on oor ush with wall and
centered over wall opening.
WALL MOUNTING
BRACKET LOCATION
Manual 2100-578E Page 10 of 41
35"
17
1 2
"
"
3 4
18 7
3 8
"
(4) optional Unit
Mounting holes
C
L
C
L
Mounting holes
(4) optional Unit
Bracket
*
** Separate telescoping sleeves available for different wall thicknesses.
Centered on
Optional Top
*
* Higher Sill Heights Acheivable With Base Kit.
Opening
Wall
Room Floor Level
Outside
Sleeve Mounting
Hole Locations
FLOOR MOUNTING HOLE & CENTERLINES
8
20
7
6"
8
20 "
2
32
1
7
"
"29
"
17
8"
56
8"
20
7 8
"
8
""94
1
31" Min.
20"
34" Max.
3"
1
48-1/2" Max.
48" Min.
3
Centered
8
Centered
43-1/4" Max.
"
49
16
8
"
20"
20"
20"
43
7
42-3/4" Min.
"
16
11
15
4
43
3 8
"
Duct
Grille
Floor
Optional
Outside
Ceiling
Wall Sleeve**
Telescoping
Wall
Unit
Optional
Trim or
Supply Duct
Box
31" Min.
34" Max.
C
L
Wall Section View
Right Side View
Front (Wall Only) View
C
L
MIS-3196 A
6.00
41.75
56.50
29.568.00
8.0036.88
20.88
MIS-3197
(4) lower fastener
holes
Floor
riser kit. If unit uses riser kit add appropriate dimension to height.
Inner wall
Unit
*
(4) Upper fastener holes
* Height dimension shown without
BRACKET WALL SECTION VIEW
WOOD FRAMED INSTALLATION (for Wall Attachment)
Manual 2100-578E Page 11 of 41
COMPRESSOR SHIPPING BOLTS
COMPRESSOR
SHIPPING BOLT
FIGURE 3
COMPRESSOR
SHIPPING BOLT
CRV
AIR DUCT
FIGURE 4
REMOVAL OF AIR DUCT
Manual 2100-578E Page 12 of 41
INSTALLATION
9'-5"
MINIMUM
REQUIRED
HEIGHT
9'-10" MINIMUM CLEARANCE RECOMMENDED TO BOTTOM OF ROOF OR FIXED CEILING
3" RISER
FIELD SUPPLIED DUCT
MIS-3199
TURNING VANES RECOMMENDED
MINIMUM
12"
4" MINIMUM FROM
TOP OF UNIT TO
DUCT BOTTOM
BOTTOM OF ROOF
FLOOR
OR FIXED CEILING
SUSPENDED CEILING
20"
MINIMUM
7'-9 3/4"
UNIT HEIGHT
9'-7" MINIMUM CLEARANCE RECOMMENDED TO BOTTOM OF ROOF OR FIXED CEILING
9'-2"
MINIMUM
REQUIRED
INSTALLATION
HEIGHT
BOTTOM OF ROOF
FLOOR
OR FIXED CEILING
SUSPENDED CEILING
20"
MINIMUM
7'-9 3/4"
UNIT HEIGHT
FIELD SUPPLIED DUCT
MIS-3198
TURNING VANES RECOMMENDED
MINIMUM
12"
4" MINIMUM FROM
TOP OF UNIT TO
DUCT BOTTOM
FIGURE 5A
DUCTED APPLICATION – BASIC UNIT
FIGURE 5B
3" RISER APPLICATION
Manual 2100-578E Page 13 of 41
INSTALLATION
9'-8"
MINIMUM
REQUIRED
HEIGHT
10'-1" MINIMUM CLEARANCE RECOMMENDED TO BOTTOM OF ROOF OR FIXED CEILING
6" RISER
FIELD SUPPLIED DUCT
MIS-3200
TURNING VANES RECOMMENDED
MINIMUM
12"
4" MINIMUM FROM
TOP OF UNIT TO
DUCT BOTTOM
FLOOR
OR FIXED CEILING
BOTTOM OF ROOF
SUSPENDED CEILING
20"
MINIMUM
7'-9 3/4"
UNIT HEIGHT
FIGURE 5C
6" RISER APPLICATION
Manual 2100-578E Page 14 of 41
12" MIN.
REQUIRED CLEARANCES & RECOMMENDED ACCESS
WING WALL CONSTRUCTION TOP VIEW
FIGURE 5D
12"
MIN.
61 1/2"
CLOSET CONSTRUCTION TOP VIEW
61 1/2"
12" MIN.
48" MIN.
LEFT CORNER CONSTRUCTION TOP VIEW
12" MIN.
12" MIN.
31 3/8"
12"
MIN.
12" MIN.
FOR LEFT
SIDE
ACCESS
RECOMMENDED SERVICE
ACCESS DIMENSIONS
FILTERS
24" MIN.
24" MIN.
12" MIN.
FOR RIGHT
SIDE
ACCESS
0" REQUIRED
12" RECOMMENDED
RIGHT CORNER CONSTRUCTION TOP VIEW
0" REQUIRED
12" RECOMMENDED
48"
MIN. FOR
FILTER ACCESS
Unit can be located in corner with 0" clearance as long as other side is unobstructed
MIS-3230
Manual 2100-578E Page 15 of 41
DUCT WORK
MIS-2959
SUPPLY DUCT AND FASTENERS TO BE FIELD SUPPLIED
24"
20"
BEND THE PROVIDED SUPPLY FRAME FLANGES UP FOR DUCT INSTALLATION
Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work must be properly sized
for the design airow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
The I-TEC series heat pump has provision to attach a supply air duct to the top of the unit. Duct connection
size is 20 inches x 24 inches. The anges are shipped at and must be bent upward using sheet metal anging pliers. The duct work is eld supplied. See Figure 6 for
suggested attachment method.
Make sure to seal the slots in the bend-up ange at the time of securing your ductwork to the ange. This can
be accomplished with either foil tape or caulk. Failing to do so may cause air leakage/whistling of air.
FIGURE 6
SUPPLY DUCT CONNECTIONS
The unit is equipped with a variable speed indoor blower motor which increases in speed with an increase in duct static pressure. The unit will therefore deliver
proper rated airow up to the maximum ESP shown
in Table 1A. However, for quiet operation of the air system, the duct static should be kept as low as practical, within the guidelines of good duct design.
FILTERS
Two 2-inch throw away lters (24 x 30) and two 1-inch throw away lters (16 x 25) are supplied with each unit. The 2-inch lters slide into brackets on both sides
for the return air openings. If a CRV vent option is
used, there are two (2) additional 1" throw away lters included with that option. See Figure 7 for specic locations. The lters are serviced from the inside of
the building by opening the cabinet doors, and do not require any tools to access.
FIGURE 7
FILTER LOCATION
24" X 30" 2"
FILTERS
INDOOR
BLOWER
ACCESS
NOTE: Unit cabinet, supply air duct and duct free
plenum are approved for “0” clearance to combustible material.
The I-TEC series heat pumps are designed for use with free return (non-ducted) and either duct free with the use of IPBDFZ Series Plenum Box (18" or 12") or a duct supply air system.
The IPBDZ Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille.
When used with a ducted supply, a Cabinet Extension may be used to conceal the ductwork above the unit to the ceiling. The ICX28 extends 28" above the unit for a total height of 10'-2" or can be trimmed to any height.
Manual 2100-578E Page 16 of 41
COMPRESSOR
ACCESS
ACCESS TO
WASHABLE
FILTERS
VENT & FLOOR
MOUNTING HOLE
ACCESS DOOR
MIS-3202
(2) Unit
Drain Entrances
Drain Area
Drains
Insulate
(2) Optional Unit
(2) Drain
Access
Locations
MIS-3115 A
(2) OPTIONAL DRAIN HOLES IN BASE
WALL
BASE VIEW
16 1/2"
18 3/4"
7 3/16"
40 3/4"
35"
OPTIONAL FLOOR MOUNTING HOLES
CONDENSATE DRAIN
There are two condensate drain connections from the condenser drain pan (compressor area). These are visible from the rear of the unit. Factory installed tubing connects the two drains at a tee connection and then a single drain hose with a barbed hose connector carries the condensate to the draining option of your choice. Enough tubing is provided to reach all drain options and can be cut down in length.
The unit is shipped from the factory with the drain line on the left-hand side as you look at the rear of the unit. The tubing can be removed from the drain connections
and ipped for a right-hand drain. See Figure 8.
The drain can be routed directly through the oor or
through the wall. There are also two optional drain locations in the lower rear back panel. See Figure 8.
The I-TEC design does not require a trap in the condensate disposal tubing. Check your local codes to see if a “P” trap is required.
For a stand pipe oor drain or through the wall, there is
adequate hose length to reach needed location behind the unit. The lower rear portion of the cabinet is recessed approximately 4 inches allowing room for a “P” trap (if
required) to be installed with the cabinet ush with the wall.
Keep in mind, the drain line must be able to be removed from the unit if necessary to remove the unit from the wall.
Access plates are located on the rear of the unit for servicing the drain trap. See Figure 8. If the drain line
is to be routed through an unconditioned space, it must be protected from freezing.
The condensate drain line can also be routed back into the unit through either the right-hand or left-hand optional drain locations on the rear of the unit. The hole is covered by insulation on the inside of the unit and will have to be cut away. Located inside the unit, about 12 inches in from the front on both the left and right side are drain holes in the bottom of the base. These holes are covered with insulation and are not visible from inside vent option area. They are located very close to the side panels and can be found by pressing down on the insulation or looking at back of vent option area (See Figure 8). Cut insulation away to expose the hole. A drain trap can now be installed inside of the cabinet, and the drain hose routed directly
through the oor.
Once the I-TEC is installed, the rear drains exiting the condenser section can be easily serviced with removal of the pre-painted metal sides (lift-off doors, remove four [4] screws to remove side).
If side access is not available, the drain lines and trap can be serviced by removing either one of the drain access panels on the rear of the unit (in the ventialtion package area.) See Figure 8.
After drain installation is complete, drain area must be insulated for sound purposes with 45" x 24 piece of insulation. See Figure 8.
¾"
x 6"
WITH NO VENT OPTION
To remove the drain access panels in the rear of this section, simply remove the front door/cover from the box. Rear drain access panels are now visible on both right-hand and left-hand sides in rear of box.
WITH COMMERCIAL ROOM VENTILATOR
1. Open hinged front doors.
2. Disconnect unit power to eliminate shock hazard.
3. Remove front cover/door of CRV vent package.
(Can leave lter access panels in place.)
4. Unplug wires coming in on left side from upper unit section.
Unplug two wire harness from front (intake) blower.
5.
6. Remove two (2) screws securing front (intake) blower and slide blower out of unit.
7. Remove four (4) screws that retian the partition behind/beneath intake blower removed in Step #6.
8. Rear drain access panels are now visible on both right-hand and left-hand sides in rear of box.
FIGURE 8 — DRAIN LOCATIONS
Manual 2100-578E Page 17 of 41
D
REF.
A AND B
REF.
(4) 5/16" - 1/2" NON-TAPPING
REF.
E
REF.
(6) 5/16" - 3/4" NON-TAPPING
C
(4) 1-1/2" LONG SCREWS
REF.
E
(18) 5/16" - 3/4" SELF TAPPING
B
C
REF.
REF.
REF.
A
REF.
D
MIS-3014 A
Use (4) 1-1/2" Long
Louver Grille to
Outer Sleeve.
Screws to Attach
to Outer Sleeve
to Attach Inner Sleeve
Self Tapping Screws
Use (6) 3/4" Long
Unit Fan Shroud
Exhaust Sleeve to
Screws to Attach
Use (6) 3/4" Long
Use (12) 3/4" Long
to Attach Inner Sleeve to Unit Back
Self Tapping Screws
Use (4) 1/2" Long Screws to Attach frame to Exhaust Sleeve
Use (12) Field Supplied Concrete or Wood Screws to Secure Outer Sleeve to Structure.
outer sleeve.
IMPORTANT!
IMPORTANT!
between inner and
entire perimeter seam
seal between unit and sleeve.
IMPORTANT!
Doing so may compromise water
to not damage gasketing material.
Use care when inserting screws
Apply Caulk bead to
Apply liberal amount of caulk to back of flange before installing.
Pull Inner Frame Out Until Flush With Grille Mounting Angle
FIGURE 9A
UNIT MOUNTING
Manual 2100-578E Page 18 of 41
(SIZE VARIES)
OUTDOOR GRILLE
INSIDE WALL
AND SLEEVE
INTERIOR FLOOR
AREA BETWEEN WALL
OUTSIDE WALL (INSULATED)
(INSULATED)
FILL INSULATION
UNIT
SLEEVE
MIS-3201 A
DRAIN AREA (INSULATED WITH 6" BATT MATERIAL)
FIGURE 9B
UNIT MOUNTING
NOTICE: In order to achieve optimum sound reduction, the following areas need insulated:
1. Outside wall.
2. Area between sleeve and wall.
3. Drain area behind unit.
Manual 2100-578E Page 19 of 41
INSTALLATION INSTRUCTIONS
MOUNTING THE UNIT
The wall sleeve is attached to the I-TEC unit from the outside of the building. See Figures 9A & 9B. Refer to wall sleeve Manual 2100-562 supplied with sleeve.
Following are the steps for attaching the I-TEC to the wall sleeve.
1. Lift the unit into place making sure that it is aligned side to side. Align unit with rubber mat.
2. Push the unit back until the rear panel touches the sleeve gasket.
3. This unit must be level from side to side and from front to back. If adjustments are necessary, shim up under the base rails with sheets of metal or any substance not affected by moisture.
4.
Attach the sleeve to the unit using the ten (10) ¾"
long self-tapping screws supplied with the sleeve.
5.
The exhaust sleeve has three (3) ¾" long screw slots
in each side ange. Line these up with the screw
engagement holes in the fan panel. Attach using six (6) ¾" long pointed sheet metal screws supplied with the sleeve. Extend the sleeve out until it is
ush with the louver grill attachment angles.
6.
Lock the sleeve in place using two (2) ½" long
pointed sheet metal screws on each side by shooting through the slot into a pre-punched hole.
7. A bottom trim piece is shipped loose for installation beneath the doors. Attach the trim piece to the unit with screws provided.
8. The compressor is secured to the base with two
(2) bolts for shipping. Both bolts are identied
with a tag. Remove shipping bolts (Figure 3).
WIRING – MAIN POWER
Refer to the unit rating plate and/or Table 2 for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each unit is marked with a “Minimum Circuit
Ampacity”. This means that the eld wiring used must be
sized to carry that amount of current. Depending on the
installed KW of electric heat, there may be two eld power
circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only suitable for at least 75°C”. THESE INSTRUCTIONS MUST BE ADHERED TO. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater
sizes. Also shown are the number of eld power circuits
required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection, and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
See “START UP” section for information on three phase scroll compressor start-ups.
The eld wiring conduit connections are located on the top
right-hand corner of the unit with a wire raceway to feed the wires down to the circuit breaker(s). See Figure 10.
REFRIGERANT PORT
Manual 2100-578E Page 20 of 41
ELECTRIC HEAT
INDOOR BLOWER
LOW VOLTAGE
OUTDOOR FAN
VENT OPTION
FIGURE 10
COMPONENT LOCATION
WIRE RACEWAY
EVAPORATOR COIL
CONTROL PANEL
CONDENSER COIL
COMPRESSOR
WIRING – LOW VOLTAGE WIRING
230/208V, 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS.
All Equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are as noted in Table 3.
TABLE 3 — OPERATING VOLTAGE RANGE
TAP RANGE
240V 253 – 216
208V 220 – 187
NOTE: The voltage should be measured at the eld power
connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
The standard unit includes a remote thermostat connection terminal strip. See Figures 11 through 16 for connection diagrams. Compatible thermostats are listed in Table 4.
TABLE 4 — WALL THERMOSTATS
“W2” terminal is rst stage electric heat (if equipped). First stage electric heat can be operated simultaneously with the heat pump operating.
“A” terminal is the ventilation input. This terminal energizes any factory installed ventilation option.
“W3” terminal is second stage electric heat. When “W3” terminal is energized, it locks out compressor operation to limit discharge air temperature and required branch circuit ampacity.
NOTE: For total and proper control using DDC, a minimum of 9 controlled outputs are needed when above 10KW Electric Heat is employed with ventilation, a total of 8 controlled outputs with below 10KW Electric Heat with Ventilation, 7 controlled outputs below 10KW Electric Heat with no ventilation, 7 controlled outputs with no Electric Heat, but with ventilation, and 6 controlled outputs with no electric
heat and no ventilation. If Dehumidication Model
& Vent, 10 controlled outputs are needed when above 10KW Electric Heat is employed with ventilation.
Thermostat Predominant Features
8403-060
(1120-445)
8403-067
(CDT-2W40-LCD-RLY)
CS9B-THO
CS9B-THOC
CS9BE-THO
CS9BE-THOC
3 Stage Cool; 3 Stage Heat Programmable/Non-Programmable Electronic HP or Conventional Auto or Manual changeover
Carbon Dioxide Sensor with LCD for Sensor Readings
3 Stage Heat, 3 Stage Cool, Prog/NonProg, HP or Conv, Auto or Manual Changeover, Humidity Sensor w/
dehumidication,MotionSensorw/IntelligentLearning
Control, BACnet-compatible
3 Stage Heat, 3 Stage Cool, Prog/NonProg, HP or Conv, Auto or Manual Changeover, Humidity Sensor w/
dehumidication,CO2Sensor,MotionSensorw/Intelligent
Learning Control, BACnet-compatible
3 Stage Heat, 3 Stage Cool, Prog/NonProg, HP or Conv, Auto or Manual Changeover, Humidity Sensor w/
dehumidication,MotionSensor,IntelligentLearningControl,
BACnet-compatible, Ethernet-compatible
3 Stage Heat, 3 Stage Cool, Prog/NonProg, HP or Conv, Auto or Manual Changeover, Humidity Sensor w/
dehumidication,CO2Sensor,MotionSensorw/Intelligent
Learning Control, BACnet-compatible, Ethernet-compatible
LOW VOLTAGE CONNECTIONS
These units use a grounded 24 volt AC low voltage circuit.
“G” terminal is the fan input.
“Y1” terminal is the compressor part load input.
“Y2” terminal is the compressor full load input.
“B/W1” terminal is the reversing valve input.
The reversing valve must be energized for heating mode.
“R” terminal is 24 VAC hot.
“C” terminal is 24 VAC grounded.
“L” terminal is compressor lockout output. This
terminal is activated on a high or low pressure trip and
condensate overow trip by the electronic heat pump
control. This is a 24 VAC output.
LOW VOLTAGE CONNECTIONS FOR DDC CONTROL
Fan Only Energize G
Cooling Part Load Energize G, Y1
Cooling Full Load Energize G, Y1, Y2
HP Heating Part Load Energize G, Y1, B/W1
HP Heating Full Load Energize G, Y1, Y2, B/W1
HP Heating Full Load + Electric Heat (up to 10KW)
Heating with Bank #1 Electric Heat Only Energize G, W2
Emergency Heat (Heat pump operation is negated for this condition)
Ventilation Energize A
Energize G, Y1, Y2, B/W1, W2
Energize G, W2, W3
GENERAL
This unit is equipped with a variable speed ECM motor.
The motor is designed to maintain rated airow up to
the maximum static allowed. It is important that the blower motor plugs are not plugged in or unplugged while the power is on. Failure to remove power prior to unplugging or plugging in the motor could result in motor failure.
CAUTION
Do not plug in or unplug blower motor connectors while the power is on. Failure to do so may result in motor failure.
Manual 2100-578E Page 21 of 41
FIGURE 11
6 4W3 A DL
B/W1
Y2Y1RT GC W2
Low Voltage Term. Strip
R 3
SC
W1/E
A DLO/BY2Y1
24V
G
COM
W2
Completestat Model #CS9B-THO or Model #CS9BE-THO
SC
SC
GND
Thermostat
W1/E
A
YO/D
LO/BY2Y1R GC W2
Bard #8403-060
Blue
Yellow
Orange
Red
1
Not needed below 15KW
Factory installed jumper. Remove jumper and connect to N.C fire alarm
2
2
2
1
3
3 Relay Provided with Completestat
White
MIS-3203 A
BASIC HEAT PUMP WITH NO VENTILATION PACKAGE
Manual 2100-578E
Page 22 of 41
FIGURE 12
6 4W3 A DL
B/W1
Y2Y1RT GC W2
Low Voltage Term. Strip
R 3
COM
G
24V
Y1 Y2 O/B L DA GND
SCSCSC
Completestat Model #CS9B-THO or Model #CS9BE-THO
W2
W1/E
Thermostat
W1/E
A
YO/D
LO/BY2Y1R GC W2
Bard #8403-060
Blue
Yellow
Orange
MIS-3204 A
1
Not needed below 15KW.
2
to N.C fire alarm circuit if emergency shutdown required.
Factory installed jumper. Remove jumper and connect
3
Connect to "G" terminal when thermostat has "Occupancy Signal".
without "Occupancy Signal" is used.
Install a jumper between "G" and "A" only when thermostat
4
3
4
CRV Wiring Harness
1
2
BROWN/WHITE
ORANGE
BLACK/WHITE
RED/WHITE
2
Red
5
5 Relay Provided with Completestat
White
HEAT PUMP WITH CRV, WITHOUT CO2 CONTROL
Manual 2100-578E Page 23 of 41
SC
W1/E
A DLO/BY2Y1
24V
G
COM
W2
Completestat Model #CS9B-THO or Model #CS9BE-THO
SC
SC
GND
5
2
1
6
W1/E
A
YO/D
LO/BY2Y1R GC W2
Thermostat Bard #8403-060
W1/E
A DLO/BY2Y1
24V
G
COM
W2
Completestat Model #CS9B-THO or Model #CS9BE-THO
SC
SC
SC
GND
Thermostat
W1/E
A
YO/D
LO/BY2Y1R GC W2
Bard #8403-060
Blue
Yellow
Orange
MIS-3205 A
Not needed below 15KW.
1
B/W1
2
to N.C fire alarm circuit if emergency shutdown required.
Factory installed jumper. Remove jumper and connect
3
3
4
CRV Wiring Harness
RT
Connect to "G" terminal when thermostat has "Occupancy Signal".
4
BROWN/WHITE
ORANGE
BLACK/WHITE
RED/WHITE
1
W3 A DL 4Y2Y1
GC W2
Term. Strip
R 6
2
3
Voltage
Low
directly to "A" and do not use seperate CO2 controller.
If CS9B-THOC or CS9BE-THOC is used, connect "Brown/White"
5
5
Bard #8403-067
CO2 Control
6
6
Red
2
6
Relay Provided with Completestat
White
Install a jumper between "G" and "A" only when thermostat without "Occupancy Signal" is used.
FIGURE 13
HEAT PUMP WITH CRV AND CO2 CONTROL
NOTE: Bard 8403-060
thermostat must be in programmed operation mode and in programmed fan mode for ventilation to function.
Manual 2100-578E
Page 24 of 41
START UP
THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.
GENERAL:
1. Use separate service equipment to avoid cross contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A refrigerant.
3. Use manifold gauges rated for R-410A (800 psi/250 psi low).
4. R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic - similar to R-22 and R-12. Although nearly azeotropic, charge with liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than R-22, and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero, but must be reclaimed due to its global warming potential.
8. R-410A compressors use Polyol Ester oil.
9.
Polyol Ester oil is hygroscopic; it will rapidly absorb
moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used - even a deep vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above), and charging to the nameplate charge. However, if done correctly, topping off the system charge can be done without problems.
With R-410A, there are no signicant changes in the
refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge, in the system, may be used after leaks have occurred and then “top-off” the charge by utilizing the charging charts on the inner control panel cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.
WARNING
Failure to conform to these practices could lead to injury or death.
SAFETY PRACTICES:
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses. Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become ammable.
4. Do not inhale R-410A – the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never ll cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands signicantly
at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.
Manual 2100-578E Page 25 of 41
START UP
DESCRIPTION OF STANDARD EQUIPMENT
Solid State Electronic Heat Pump Control
Provides efcient 30, 60 or 90-minute defrost cycle. A thermistor sensor and speed up terminal for service along with a 8-minute defrost override are standard on the electronic heat pump control. By default, the I-TEC are factory shipped on the 90-minute defrost cycle.
High / Low Pressure Switch
Provides refrigerant circuit high pressure and loss of charge protection. Includes lockout circuit built into heat pump control that is resettable from room thermostat.
Five Minute Compressor Time Delay
Provides short cycle protection for the compressor which extends compressor life. Built into the electronic heat pump control as standard.
Condensate Overow
Senses and provides system shut down if draining issue causes water level to rise in the lower drain pan.
Low Ambient Control
The low ambient control permits cooling operation down to 0°F outdoor ambient.
IMPORTANT INSTALLER NOTE
For improved start-up performance, wash the indoor coil with a dishwasher detergent.
PHASE MONITOR
All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contactor is allowed to energize.
If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.
THREE PHASE SCROLL COMPRESSOR START UP INFORMATION
Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction,
verication of proper rotation must be made.
Verication of proper rotation direction is made by
observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation also results in an elevated sound level over that with correct rotation, as well as substantially reduced current draw compared to tabulated values.
Verication of proper rotation must be made at the time
the equipment is put into service. If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor. However, reverse operation for even one hour may have a negative impact on the bearing due to oil pump out.
All three phase scroll compressors used in the I-TEC series are wired identically internally. As a result, once
the correct phasing is determined for a specic system or
installation, connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction. The direction of rotation of the motor may be changed by reversing any two line connections to the unit.
SERVICE HINTS
1.
Caution user to maintain clean air lters at all
times. Also, not to needlessly close off supply air
registers. This may reduce airow through the
system, which shortens equipment service life as well as increasing operating costs and noise levels.
2.
Switching to heating cycle at 75°F or higher outside temperature may cause a nuisance trip of the remote reset high pressure switch. Turn thermostat off, then on to reset the high pressure switch.
3.
The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired operating mode before trying to diagnose any reported service problems.
4. Check all power fuses or circuit breakers to be sure they are the correct rating.
5.
Periodic cleaning of the outdoor coils to permit
full and unrestricted airow circulation is essential.
6. Annual maintenance is required to make sure that all of the systems are functioning properly.
a. Check to make sure that the drains are not
obstructed in any way.
b. Remove any debris in the condenser section
of the unit.
c. Inspect and wash outdoor coils as necessary.
7. All motors are sealed and require no oiling.
Manual 2100-578E Page 26 of 41
SEQUENCE OF OPERATION
PRESSURE SERVICE PORTS
COOLING PART LOAD – Circuit R-Y1 makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.
COOLING FULL LOAD – Circuit R-Y1 & Y2 makes at the thermostat energizing the 2nd stage solenoid in the compressor. The default position of the compressor staging solenoid is non-energized. The compressor will run at low capacity until this solenoid is energized.
HEATING STAGE 1 – A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing “Auto” changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season and thus eliminating pressure equalization noise except during defrost, are to be used. On “Auto” option a circuit is completed from R-B and R-Y1 on each heating “on” cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second option has no “Auto” changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in “Heat” position, the “B” terminal being constantly energized from R. A thermostat demand for Stage 1 heat completes R-Y1 circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor.
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number. Upper and lower service doors must be attached to obtain proper reading.
HEATING STAGE 2 – Circuit R-Y1 & Y2 makes at the thermostat energizing the 2nd stage solenoid in the compressor.
Manual 2100-578E Page 27 of 41
DEFROST CYCLE
120*
SW1SW
2 TIME (SEC)
OFF OFF
ON ON
OFF ON OFF
ON
30 60
180
MIS-2668 A
OFF
LOW PRESSURE BYPASS TIMER SWITCH *(FACTORY SETTING 120 SECONDS)
ACCUMULATED DEFROST TIME TIMER (FACTORY SETTING 60 MIN.)
ON
The defrost cycle is controlled by temperature and time on the solid state heat pump control. See Figure 14.
When the outdoor temperature is in the lower 40°F temperature range or colder, the outdoor coil temperature is 32°F or below. This coil temperature is sensed by the coil temperature sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30°F or below, the coil temperature sensor sends a signal to the control logic of the heat pump control and the defrost timer will start accumulating run time.
After 30, 60 or 90 minutes of heat pump operation at 30°F or below, the heat pump control will place the system in the defrost mode. Factory default setting is 90 minutes.
During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57°F, the coil temperature sensor will send a signal to the heat pump control which will return the system to heating operations automatically.
If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operation automatically after 8 minutes.
The heat pump defrost control board has an option of 30, 60 or 90-minute setting. All models are shipped from the factory on the 90-minute pin. If special circumstances require a change to another time, remove the wire from the 90-minute terminal and reconnect to the desired terminal.
The manufacturer’s recommendation is for 90-minute defrost cycles. Refer to Figure 14.
There is a cycle speed up jumper on the control. This can be used for testing purposes to reduce the time between defrost cycle operation without waiting for time to elapse.
Use a small screwdriver or other metallic object, or another ¼ inch QC, to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost.
Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals. It may take up to 15 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start.
As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run through the 1-minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence.
There is an initiate defrost jumper (sen jump) on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region.
By placing a jumper across the SEN JMP terminals (a ¼ inch QC terminal works best) the defrost sensor mounted on the outdoor coil is shunted out & will activate the timing circuit. This permits the defrost cycle to be checked out in warmer weather conditions without the outdoor temperature having to fall into the defrost region.
In order to terminate the defrost test the SEN JMP jumper must be removed. If left in place too long, the
compressor could stop due to the high pressure condition created by operating in the cooling mode with outdoor fan off. Pressure will rise rapidly as there is likely
no actual frost on the outdoor coil in this articial test
condition. There is also a 5-minute compressor time delay function
built into the Heat Pump Control to protect the compressor from short cycling conditions. The board’s LED will have a fast blink rate when in the compressor time delay function. In some instances, it is helpful to the service technician to override or speed up this timing period, and shorting out the SPEEDUP terminals for a few seconds can do this.
FIGURE 14
HEAT PUMP CONTROL
DEFROST CYCLE
(FACTORY SETTING 90 MIN.)
Manual 2100-578E Page 28 of 41
I-TEC COMMERCIAL ROOM
5.500
2.585 2.585 2.585 .745
NO. NO. DATE
PART
NAME
DWG.
Bryan, Ohio
DISTRIBUTION 1 2 3 4 5
MAT'L
Bard Mfg. Co.
CHECKED
DRAWN BYSCALE
PART
APPROVED
DISCONNECT ALL ELECTRICAL
IN SEVERE INJURY OR AMPUTATION.
IN SEVERE INJURY OR AMPUTATION.
7961-754-2
C
LABEL SHEET #1
REQUIRE PROPER PHASING. REFER
DISCONNECT THE REMOTE
7961-754
3 PHASE SCROLL COMPRESSORS
EXPOSED MOVING PARTS.
FAILURE TO DO SO CAN RESULT
ELECTRICAL SHOCK CAN RESULT
IN SEVERE INJURY OR AMPUTATION.
POWER BEFORE SERVICING.
EXPOSED MOVING PARTS.
WARNING
IN SERIOUS INJURY OR DEATH.
DISCONNECT THE REMOTE
7961-754-1
DISCONNECT ALL ELECTRICAL
ELECTRICAL SHOCK CAN RESULT
ELECTRIC POWER SUPPLY OR
7961-754-1
WARNING
!
HAZARD OF ELECTRICAL SHOCK.
PROPER START UP INFORMATION.
IMPORTANT
SUPPLIES BEFORE SERVICING.
IN SERIOUS INJURY OR DEATH.
1:1
11/17/2011
7961-754-8
TO INSTALLATION INSTRUCTIONS FOR
Piece
Front Trim
EXPOSED MOVING PARTS.
SUPPLIES BEFORE SERVICING.
CGB
7961-754-2
WARNING
!
HAZARD OF ELECTRICAL SHOCK.
!
WARNING
DAY RSP
WARNING
!
!
WARNING
7961-754-2
7961-754-1
DISCONNECT ALL ELECTRICAL
7961-754-9
POWER BEFORE SERVICING. FAILURE TO DO SO CAN RESULT
POWER BEFORE SERVICING. FAILURE TO DO SO CAN RESULT
ELECTRIC POWER SUPPLY OR
VENTILATOR SYSTEM
GENERAL DESCRIPTION
The I-TEC Commercial Room Ventilator (CRV) is designed to be used with all Bard I-TEC models. The only intent of this device is to provide the required ventilation by delivering fresh air to meet I.A.Q. (Indoor Air Quality) requirements. In the installed application, this system also includes exhaust provisions which are balanced with the intake air to maintain building pressurization requirements of ASHRAE 62.1 Standard.
Ventilation is accomplished with (2) blower/ motor assemblies for maximum ventilation at low sound levels. The intake and exhaust blowers are programmed independently and are balanced to maintain a slight positive pressurization in accordance to ASHRAE 62.1 Standard.
The I-TEC CRV is also provided with lters to reduce
the required service needed and to further improve the I.A.Q. The exhaust air blowers and intake air blowers
are protected by two (2) throw away lters. Both are
accessible without the need for tools.
CONTROL WIRING
The I-TEC CRV comes wired from the factory set to 450 CFM of ventilation. Care must be taken when deciding how to control the operation of the ventilator. When designing the control circuit for the ventilator, the following requirements must be met.
1.
The indoor blower must be run whenever the I-TEC
CRV is run.
2.
Select and congure the correct CFM ventilation
level that the I-TEC CRV needs to operate and
congure the system to this level following later
instructions within this section. Over ventilating
serves no useful purpose and signicantly affects the overall efciency of the heat pump system.
System operating costs would also increase.
3. Run the I-TEC CRV only during periods when the conditioned space is occupied. Running the ventilation during unoccupied periods wastes energy, decreases the expected life of the CRV, and can result in large moisture buildup in the structure. Running the CRV when the structure is unoccupied allows moisture to build up in the structure because there is little or no cooling load.
Thus, the air conditioner is not running enough to remove the excess moisture being brought in. Use a control system that in some way can control the system based upon occupancy.
Operating the I-TEC CRV during unoccupied periods can result in a build up of excess moisture in the structure.
RECOMMENDED CONTROL SEQUENCES
Several possible scenarios are listed below:
1. Use a programmable electronic thermostat with auxiliary terminal to control the CRV based on daily programmed occupance periods. Bard markets and recommends Bard Part #8403-060 programmable electronic thermostat.
2. temperature, humidity and occupancy control with learning capability into a single device. No programming required.
3. upon a room occupancy schedule to control the CRV.
4. lights in a room are usually on only when occupied.
5. Use a manual timer that the occupants turn to
energize the CRV for a specic number of hours.
6. Use a programmable mechanical timer to energize the CRV and indoor blower during occupied periods of the day.
NOTE: The ventilation package comes with a blower interlock function, but is disabled when it is shipped from the factory in case you do not utilize a thermostat with an occupancy output, or a occupancy sensor and must tie “A” terminal to “G” terminal to drive the ventilation package. If you do have a thermostat or control that does drive occupancy output, you will need to remove the tape from the orange wire located in the low voltage terminal box, and connect it to the “G” terminal to activate this function. (See Figures 11-13.)
SETTING THE VENTILATION CFM LEVELS
The I-TEC CRV has four pre-set levels of ventilation CFM available. These are 300, 375, 450 and 525 CFM of ventilation air. The I-TEC CRV is shipped from the factory set on the 450 CFM ventilation level. To change between these four different levels of provided ventilation
CFM, rst refer to Figure 15 to look up the corresponding
CFM needed for the intake and exhaust blowers to meet the design criteria and determine which “speed/wire color” is needed. Then, perform the following steps.
1. front door latches).
2. Throw main power disconnect to the “OFF” position to eliminate risk of injury or death due to electrical shock.
3. Remove six (6) screws holding front CRV door in place (See Figure 16).
4. Locate “Brown Wire with White Trace” that has a black terminal on the end where it connects to the terminal strip (See Figure 15).
5. Move “Brown Wire with White Trace” to the corresponding CFM level needed in accordance with Figure 15.
Use Bard CompleteStat™ that incorporates
Use a DDC control system to control the CRV based
Tie the operation of the CRV into the light switch. T he
!
HAZARD OF ELECTRICAL SHOCK. ELECTRICAL SHOCK CAN RESULT IN SERIOUS INJURY OR DEATH. DISCONNECT THE REMOTE ELECTRIC POWER SUPPLY OR SUPPLIES BEFORE SERVICING.
Open front swinging doors of main unit (by popping
Manual 2100-578E Page 29 of 41
FIGURE 15
MED. HI
7961-7554
MOTOR SPEEDS
LO
MED. LO
HI
BLACK
SPEED
BLUE
MED-LO
VENT OPTION INTAKE/EXHAUST SPEEDS
7961-755-2
RED
HI
MED-HIBLUE
ORANGE
NOM. CFM
BLACK
WIRE COLOR
LO
ORANGE
RED
WIRE WITH WHITE TRACE.
300
375
450
525
TO CHANGE SPEEDS, MOVE BROWN
BROWN/WHITE
Move brown/white wire to corresponding motor speed for required ventilation CFM. Factory setting is Medium Hi (450 CFM).
MIS-3206
CRV MOTOR SPEED/CFM CONFIGURATION
Manual 2100-578E Page 30 of 41
FIGURE 16
BLOWER SPEED
CONTROL LOCATION
BLOWER SPEED CONTROL
BLOWER REMOVED FOR CLARITY
CRV DOOR TO ACCESS CRV COMPONENTS
REMOVE (9) SCREWS FROM
MIS-3207 A
CRV INTAKE BLOWER NOTE: CRV EXHAUST BLOWER IS BEHIND INTAKE BLOWER
CRV SPEED CHANGE TERMINAL ACCESS
Manual 2100-578E Page 31 of 41
Indoor Air
VENT EXHAUST
Supply Air
Outdoor Air
BLOWER
BLOWER
INTAKE
VENT
SUPPLY BLOWER
Return Air
MIS-3208
FIGURE 17
VENTILATION AIRFLOW DIAGRAM
Manual 2100-578E Page 32 of 41
ANNUAL MAINTENANCE
1. Inspect and conduct the same procedures as outlined under Quarterly Maintenance.
2. To maintain peak latent (moisture) removal capacity, it is recommended that the energy recovery wheels be sprayed with a diluted nonacid based evaporator coil cleaner or alkaline detergent solution such as 409.
NOTE: Do not use acid based cleaners, aromatic
solvents, temperatures in excess of 170° F or steam. Damage to the wheel may result.
Do not disassemble and immerse the entire
heat wheel in a soaking solution, as bearing and other damage may result.
3. Rinse wheel thoroughly after application of the cleaning solution, and allow to drain before reinstalling.
4. No re-lubrication is required to heat wheel bearings of the drive motor, or to the intake and exhaust blower motors.
5. If any belt chirping or squealing noise is present, apply a small amount of LPS-1 or equivalent dry
lm lubricant to the belt.
Manual 2100-578E Page 33 of 41
TROUBLESHOOTING
SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE
1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit.
2. Turn thermostat blower switch to “fan on” – the indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.)
3. Turn thermostat blower to “auto” position. Indoor blower should stop.
4. Set system switch to “heat” or “cool”. Adjust thermostat to call for heat or cool. The indoor blower, compressor and outdoor fan should start.
NOTE: If there was no power to 24 volt transformer, the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection.
CODES FUNCTION
Slow Blink Normal Operation
Fast Blink Compressor Time Delay
1 Blink Low Pressure Switch Failure
2 Blink High Pressure Switch Failure
  orCondensateOverow 
Switch Activated
3 Blink Defrost Mode Active
 4Blink HighPressureorOverow
Switch Lockout
TABLE 5 — TROUBLESHOOTING
Symptom Description, Check & Possible Causes What & How to Check / Repair
Compressor will not start (heating or cooling)
Fan outdoor motor does not run (cooling or heating except during defrost)
Reversing valve does not energize (heating only)
Unit will not go into defrost (heating only)
Unit will not come out of defrost (heating only)
1. Check for LED illumination.
IsthereanLEDilluminatedontheboard(ashing)?
2. Check for error codes.
IstheLEDashingaCode?
3. Check for power at board.
Isthere24voltsACbetweenRandC?
4. Check codes.
Whatcodeisblinking?
5. Compressor delay active.
Wait for 5 minute delay or jump board's "speed up pins".
6. Low pressure fault. Check wiring circuit and unit pressures.
7A. High pressure fault. Check wiring circuit and unit pressures.
7B. Condensate overow fault.
8. Check for Compressor input signal.
Isthere24voltsACbetweenYandC?
9. No power to board.
10. Check for Compressor output signal.
Isthere24voltsACbetweenCC&C?
11. No "Y" compressor input signal.
12. No "CC" compressor output signal.
13. Faulty board. Replace defrost board.
Heat pump control defective
Motor defective Check for open or shorted motor winding. Replace motor.
Motor capacitor defective
Heat pump control defective
Reversing valve solenoid coil defective Check for open or shorted coil. Replace solenoid coil.
Temperature sensor or heat pump control defective
Temperature sensor or heat pump control defective.
Yes = go to Step #2; No = go to Step #3
Yes = go to Step #4; No = go to Step #8
Yes = go to Step #13; No = go to Step #9
Code "1", go to Step #6; Code "2", go to Steps #7A & #7B; Fast Blink, go to Step #5
Check for proper operation; if still needed, go back to Step #1.
Check upper indoor coil drains; check lower outdoor coil drains; check main drain line.
Yes = go to Step #10; No = go to Step #11
The unit either does not have unit voltage, the transformer is bad or the unit wiring is incorrect.
Yes = go to Step #12; No = go to Step #13
Check thermostat wiring, incorrect phase of unit (see section on Phase
Monitor),andnallyunitwiring.
Checkcompressorcontactorforproperoperationandnallycheck
compressor.
Check across fan relay on heat pump control. (Com-NC) Replace heat pump control.
Check capacitor rating. Check for open or shorted capacitor. Replace capacitor.
Check for 24V between RV-C and B-C.
1. Check control circuit wiring.
2. Replace heat pump control
Disconnect temperature sensor from board and jumper across "SPEEDUP" terminals and "SEN JMP" terminals. This should cause the unit to go through a defrost cycle within one minute.
1. If unit goes through defrost cycle, replace temperature sensor.
2. If unit does not go through defrost cycle, replace heat pump control.
Jumper across "SPEEDUP" terminal. This should cause the unit to come out of defrost within one minute.
1. If unit comes out of defrost cycle, replace temperature sensor.
2. If unit does not come out of defrost cycle, replace heat pump control.
Manual 2100-578E Page 34 of 41
CHECKING TEMPERATURE SENSOR
1. Disconnect temperature sensor from board and from right-hand outdoor coil.
2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
3. Check resistance reading to chart of resistance use sensor ambient temperature. (Tolerance of part is ± 10%.)
TABLE 6
TEMPERATURE (F) VS RESISTANCE (R) OF TEMPERATURE SENSOR
F R F R F R F R
-25 196871 13 56985 51 19374 89 7507
-24 190099 14 55284 52 18867 90 7334
-23 183585 15 53640 53 18375 91 7165
-22 177318 16 52051 54 17989 92 7000
-21 171289 17 50514 55 17434 93 6840
-20 165487 18 49028 56 16984 94 6683
-19 159904 19 47590 57 16547 95 6531
-18 154529 20 46200 58 16122 96 6383
-17 149355 21 44855 59 15710 97 6239
-16 144374 22 43554 60 15310 98 6098
-15 139576 23 42295 61 14921 99 5961
-14 134956 24 41077 62 14544 100 5827
-13 130506 25 39898 63 14177 101 5697
-12 126219 26 38757 64 13820 102 5570
-11 122089 27 37652 65 13474 103 5446
-10 118108 28 36583 66 13137 104 5326
-9 114272 29 35548 67 12810 105 5208
-8 110575 30 34545 68 12492 106 5094
-7 107010 31 33574 69 12183 107 4982
-6 103574 32 32634 70 11883 108 4873
-5 100260 33 31723 71 11591 109 4767
-4 97064 34 30840 72 11307 11 0 4663
-3 93981 35 29986 73 11031 111 4562
-2 91008 36 29157 74 10762 112 4464
-1 88139 37 28355 75 10501 113 4367
0 85371 38 27577 76 10247 114 4274
1 82699 39 26823 77 10000 115 4182
2 80121 40 26092 78 9760 11 6 4093
3 77632 41 25383 79 9526 11 7 4006
4 75230 42 24696 80 9299 11 8 3921
5 72910 43 24030 81 9077 11 9 3838
6 70670 44 23384 82 8862 120 3757
7 68507 45 22758 83 8653 121 3678
8 66418 46 22150 84 8449 122 3601
9 64399 47 21561 85 8250 123 3526
10 62449 48 20989 86 8057 124 3452
11 60565 49 20435 87 7869
12 58745 50 19896 88 7686
4. If sensor resistance reads very low, then sensor is
shorted and will not allow proper operation of the heat pump control.
5. If sensor is out of tolerance, shorted, open, or reads
very low ohms then it should be replaced.
Manual 2100-578E Page 35 of 41
TROUBLESHOOTING ECM™ 142R OUTDOOR FAN MOTOR
2.585
.833 .833
3.706
4.250
5.500
7961-755-3
7961-755-3
DISCONNECT ALL ELECTRICAL
IN SEVERE INJURY OR AMPUTATION.
EXPOSED MOVING PARTS.
WARNING
POWER BEFORE SERVICING.
THIS DOOR
INTAKE VENT FILTER BEHIND
THIS DOOR
!
SUPPLIES BEFORE SERVICING.
!
WARNING
7961-755-1
FAILURE TO DO SO CAN RESULT
IN SERIOUS INJURY OR DEATH. DISCONNECT THE REMOTE ELECTRIC POWER SUPPLY OR
HAZARD OF ELECTRICAL SHOCK. ELECTRICAL SHOCK CAN RESULT
INTAKE VENT FILTER BEHIND
Do not operate motor without fan blade attached. Such operations will cause the motor to oscillate up and down.
You must obtain the correct replacement motor from the manufacturer that is a direct replacement for the failed motor.
USING THE WRONG MOTOR VOIDS ALL WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.
1. In normal operation, this motor may rock back and forth on start up. Do not replace if this is the only
symptom identied.
2. If the system is operating properly, but the motor appears to run slower than it should, the motor is
good. High efciency systems with optimized fan
blades are engineered to run slow to decrease noise. The Bard I-TEC Series models also adjust fan speed based upon varied outdoor ambient
conditions to optimize sound and unit efciency.
3. If the system is noisy, freezing up, running a high head pressure, tripping the high pressure switch or compressor overload, check the following:
a. Ensure cleanliness of condenser coil(s) and
fan blade/shroud.
b. Conrm the fan blade is not bent or deformed,
isn’t rubbing on the shroud, and that it is tight on the motor shaft. Also ensure the motor is secure in its mounting system, and the mounting system is secure to the unit.
c. The Bard I-TEC is equipped with a low ambient control pressure switch. This pressure switch completes the 24VAC Common feed to the outdoor fan motor control in cooling mode. If this switch is defective, or if the outdoor air temperature is too cold to raise the head pressure to the 325# switch closing set-point, or the system charge is too low, this could be the cause
Manual 2100-578E Page 36 of 41
of the issue. (In heat pump {heating} mode, the low ambient fan cycling control is bypassed.)
d. If motor is not running, go to next section.
4. If the motor does not appear to be running at the proper speed or does not shut off, refer to the next section for voltage checks to determine if the motor is getting the proper input signals.
If the motor IS NOT receiving any communication, troubleshoot the communication issue using the diagnostic table for the Fan Logic Control.
a. This motor uses a 7 wire harness to control
the motor.
• Line power is connected as follows:
“Red Wire” connects to “L1” “Black Wire” connects to “L2” “Green/Yellow Wire” connects to “Ground”
• Control power is connected as follows:
“Blue Wire” connects to Fan Relay of the Defrost Logic Control, and subsequently connects to 24VAC Common through the Fan Logic Control Board. “Yellow Wire” connects to “Y” on the Fan Logic Control Board. “White Wire” connects to “W” on the Fan Logic Control Board. “Orange
NOTE: A combination of the “Yellow”, “White” and “Orange” wires being energized (with
24V “R” signal) determines ve (5) different
Wire” connects to “O” on the Fan Logic Control Board.
speeds the fan motor will operate at. The Fan Logic Control Board uses an outdoor thermistor sensor to determine the speed the
TABLE 7
TROUBLESHOOTING ECM™ 142R OUTDOOR FAN MOTOR
fan should operate. It also utilizes the “B” reversing valve input for heat pump mode to determine speed should operate.
Check Line Power to Motor
Check for 24VAC common signal to motor (against Transformer "R" Signal)
Check 24VAC "hot" outputs (to "Blue" on Fan Logic Control) to motor. See the following tables based upon outdoor temperature and model of operation.
TROUBLESHOOTING FAN LOGIC CONTROL
Please reference the Thermistor Temperature/Resistance Chart in this manual (Table 6).
GREEN STATUS LED – Blinks indicating there
is a call for fan operation (simultaneous to call for compressor operation) and is normal.
RED STATUS LIGHT (LA) – Is illuminated when
low ambient control switch is in the closed position. (NOTE: This is not required in heat pump operation as the low ambient switch is bypassed in this mode of operation.)
YELLOW STATUS LIGHT (B) – Is illuminated
when there is a reversing valve call (for heat pump
Check between Red and Black Wires for Line Power
Verify Ground by checking Green Wire to L1 and L2 Line Power
Check "BR" terminal of Fan Logic Control Board
Check "Blue" Fan Lead on "Fan Relay Terminal" of "Defrost Logic Control"
** Is not energized in cooling mode until Low Ambient Fan Cycling Control is closed by 325 PSIG refrigerant pressure.
** Circuit is completed automatically when "B" is energized on the Fan Logic Control Board
operation). (NOTE: As mentioned above, this mode of operation negates the low ambient fan cycling control.)
If the board is reading a fan temperature thermistor value of 3375Ω or less (equivalent to 125°F or an "open" sensor), the fan will operate at the highest speed setting (energizes "W" and "Y" outputs on the board).
If the board is reading a fan temperature value of 118,110Ω or greater (equivalent to -10°F or a "shorted" sensor), the fan will operate at the highest speed setting (energizes "W" and "Y" outputs on the board).
If the low ambient switch is open, the red light will not be illuminated and the "BR" terminal will show open. The "BR" terminal is the "24 volt common" switching output to the outdoor fan motor.
TABLE 8
COOLING MODE
O.D. Temp Sensor 24VAC Signals Between
Below 55°F Orange to Blue
Between 56° - 69°F White to Blue
Between 70° - 85°F Yellow to Blue
Between 86° - 112°F Orange and White to Blue
Above 112°F White and Yellow to Blue
O.D. Temp Sensor 24VAC Signals Between
Above 56°F Orange to Blue
Between 55° - 30°F White to Blue
Between 29° - 14°F Yellow to Blue
Below 13°F Orange and White to Blue
TABLE 9
HEAT PUMP MODE
If the output signals are not matching the specied temperature range, then go to Table #6 and verify the thermistor output
curve. If the motor is receiving proper communications and proper high voltage power, and is still not running, proceed with Motor Replacement. (When checking the resistance/temperature curve, don’t forget about the optional 2.2k ohm fan control resistor assembly.)
REPLACING THE MOTOR
This motor is replaced in one piece. The control cannot be replaced separately from the motor. Even if the control is remotely located, the replacement part will be a new control with harness and new motor.
You must have the correct replacement motor from the manufacturer that is a direct replacement for the failed motor.
USING THE WRONG MOTOR VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.
Always mount the replacement motor and control
according to the manufacturers specications using
all required hardware to reduce vibration. Make sure all wires are free of the fan blade and not pinched in mountings or cabinet through points.
Manual 2100-578E Page 37 of 41
TROUBLESHOOTING INDOOR ECM™ BLOWER MOTORS
CAUTION:
Disconnect power from unit before removing or replacing connectors, or servicing motor. To avoid electric shock from the motor’s capacitors, disconnect power and wait at least 5 minutes before opening motor.
Symptom Cause/Procedure
Motor rocks slightly This is normal start-up for ECM
when starting
Motor won’t start Check blower turns by hand
• No movement
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
(G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
Perform Moisture Check
• Motor rocks, • Check for loose or compliant motor mount
but won’t start
• Perform motor/control replacement check
Motor oscillates up • It is normal for motor to oscillate with no
load & down while being on shaft tested off of blower
Motor starts, but runs erratically
• Varies up and down • Check line voltage for variation or “sag” or intermittent • Check low voltage connections
(G, Y, W, R, C) at motor, unseated pins in motor harness connectors
• Check “Bk” for erratic CFM command (in
variable-speed applications)
• Check out system controls, Thermostat
Perform Moisture Check
• “Hunts” or “puffs” at • Does removing panel or lter reduce high CFM (speed) “pufng”?
- Reduce restriction
- Reduce max airow
• Stays at low CFM • Check low voltage (Thermostat) wires and
despite system call connections
for cool or heat CFM • Verify fan is not in delay mode; wait until
delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check
• Stays at high CFM • “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
complete
• Perform motor/control replacement check
• Blower won’t shut off
Check for Triac switched thermostat or solid­ state relay
Excessive noise • Determine if it’s air noise, cabinet, duct or
motor noise; interview customer, if necessary
• Air noise • High static creating high blower speed?
- Is airow set properly?
- Does removing lter cause blower to slow down? Check lter
- Use low-pressure drop lter
- Check/correct duct restrictions
• Check power at motor
• Make sure blower wheel is tight on shaft
Current leakage from controls into G, Y or W?
Symptom Cause/Procedure
• Noisy blower or cabinet Check for loose blower housing, panels, etc.
• High static creating high blower speed?
- Check for air whistling through seams in ducts, cabinets or panels
- Check for cabinet/duct deformation
• “Hunts” or “puffs” at • Does removing panel or lter reduce
high CFM (speed)
- Reduce restriction
- Reduce max. airow
Evidence of Moisture
• Motor failure or • Replace motor and
malfunction has occurred and moisture is present
• Evidence of moisture
present inside air mover
“pufng”?
Perform Moisture Check
Perform Moisture Check
Do Don’t
• Check out motor, controls, • Automatically assume the motor is bad. wiring and connections thoroughly before replacing motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
water can’t get in positions
- Install “drip loops”
• Use authorized motor and • Replace one motor or control model # with
model #’s for replacement another (unless an authorized replacement)
• Keep static pressure to a • Use high pressure drop lters some have
minimum: H20 drop!
- Recommend high • Use restricted returns efciency, low static lters
- Recommend keeping lters
clean.
- Design ductwork for min. static, max. comfort
- Look for and recommend ductwork improvement, where necessary
• Size the equipment wisely • Oversize system, then compensate with low airow
• Check orientation before • Plug in power connector backwards inserting motor connectors • Force plugs
½”
Moisture Check
• Connectors are oriented “down” (or as recommended by equipment
manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet
Comfort Check
• Check proper airow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?
Manual 2100-578E Page 38 of 41
TROUBLESHOOTING INDOOR ECM™ BLOWER MOTORS (Cont’d.)
Replacing ECM Control Module
To replace the control module for the GE variable-speed indoor blower motor you need to take the following steps:
1. You MUST have the correct replacement module. The controls are
factory programmed for specic operating modes. Even though they look
alike, different modules may have completely different functionality.
USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.
2. Begin by removing AC power from the unit being serviced. DO NOT WORK ON THE MOTOR WITH AC POWER APPLIED. To avoid
electric shock from the motor’s capacitors, disconnect power and wait at least 5 minutes before opening motor.
3. It is not necessary to remove the motor from the blower assembly, nor the blower assembly from the unit. Unplug the two cable connectors to the motor control assembly. There are latches on each connector. DO NOT PULL ON THE WIRES. The plugs remove easily when properly released.
4. Locate the screws that retain to t metal of the unit and remove them. Remove two (2) nuts that retain the control to the bracket and then remove two (2) nuts that retain sheet metal motor control end plate. Refer to Figure 18.
5. Disconnect the three (3) wires interior of the motor control by using
your thumb and forenger squeezing the latch tab and the opposite side
of the connector plug, gently pulling the connector. DO NOT PULL ON THE WIRES, GRIP THE PLUG ONLY. Refer to Figure 18.
6. The control module is now completely detached from the motor. Verify with a standard ohmmeter that the resistance from each motor lead (in the motor plug just removed) to the motor shell is >100K ohms. Refer to Figure 19. (Measure to unpainted motor end plate.) If any motor lead fails this test, do not proceed to install the control module. THE MOTOR IS DEFECTIVE AND MUST BE REPLACED. Installing the new control module will cause it to fail also.
he motor control bracket to the sheet
7. Verify that the replacement control is correct for your application.
Refer to the manufacturer’s authorized replacement list. USING THE
WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION. Orient the control module so that the 3-wire
motor plug can be inserted into the socket in the control. Carefully insert the plug and press it into the socket until it latches. A SLIGHT CLICK
WILL BE HEARD WHEN PROPERLY INSERTED.
8. Reverse the steps #5, 4, 3 to reconnect the motor control to the
motor wires, securing the motor control cover plate, mounting the control to the bracket, and mounting the motor control bracket back into the unit. MAKE SURE THE ORIENTATION YOU SELECT
FOR REPLACING THE CONTROL ASSURES THE CONTROL’S CABLE CONNECTORS WILL BE LOCATED DOWNWARD IN THE APPLICATION SO THAT WATER CANNOT RUN DOWN THE CABLES AND INTO THE CONTROL. DO NOT
OVERTIGHTEN THE BOLTS.
9. Plug the 16-pin control plug into the motor. The plug is keyed.
Make sure the connector is properly seated and latched.
10. Plug the 5-pin power connector into the motor. Even though the
plug is keyed, OBSERVE THE PROPER ORIENTATION. DO NOT FORCE THE CONNECTOR. It plugs in very easily when properly oriented. REVERSING THIS PLUG WILL CAUSE IMMEDIATE
FAILURE OF THE CONTROL MODULE.
Final installation check. Make sure the motor is installed as follows:
11.
a. Motor connectors should be oriented between the 4 o’clock and 8 o’clock positions when the control is positioned in its
nal location and orientation.
b. Add a drip loop to the cables so that water cannot enter the motor by draining down the cables. Refer to Figure 20.
The installation is now complete. Reapply the AC power to the HVAC equipment and verify that the new motor control module is working properly. Follow the manufacturer’s procedures for disposition of the old control module.
Only remove Hex Head Bolts
ECM 2.0
Note: Use the shorter bolts and
alignment pin
supplied when replacing an ECM 2.0
control.
Figure 18 Figure 19
Figure 3
Control Disassembly
Push until Latch Seats Over Ramp
ECM
2.3/2.5
Hex-head Screws
From Motor
Circuit
Board
Motor
Motor Connector (3-pin)
Control Connector (16-pin)
Power Connector (5-pin)
Motor Connector (3-pin)
Back of Control
Figure 4
Winding Test
Motor OK when R > 100k ohm
Figure 20
Figure 5
Drip Loop
Connector Orientation
Between 4 and 8 o'clock
Drip Loop
Manual 2100-578E Page 39 of 41
10
1 2 3 4 5 6 7 8
1615141312119
3 51 2 4
MIS-2839
TROUBLESHOOTING ECM™ BLOWER MOTORS (Cont’d.)
MODE of
OPERATION
Thermostat
24 VAC
Inuput Signals
Pin #1 24 VAC "C" (Common) Signal, Always Energized
Pin #2 X
Pin #3 24 VAC "C" (Common) Signal, Always Energized
Pin #4 Not Used
Pin #5 Not Used
Pin #6 X X X X X X X
Pin #7 Not Used
Pin #8 Not Used
Pin #9 X X X
Pin #10 Not Used
Pin #11 Not Used
Pin #12 24 VAC Hot "R" Signal, Always Energized
Pin #13 X X
Pin #14 X X X X X
Pin #15 X X X X X X X X X
Pin #16 Not Used
Continuous
OFF
"G"
Blower
(Ventilation
Mode)
Part Load
Cooling
"G",
"Y1","Y2"
Full Load
Cooling
"G",
"Y1","Y2"
Dehum.
Mode
(when
equipped)
"D"
Part Load Heat
Pump
"G", "B",
"Y1"
Full
Load
Heat
Pump
"G", "B",
"Y1", "Y2"
Heat Pump
Full Load w/
1st Bank of
Elec. Heat
"G", "Y1", "Y2", "B",
"W1"
Heat Pump
Full Load w/
1st & 2nd Bank
of Elec. Heat
"G", "Y1", "Y2", "B",
"W2", "W3"
Emergency
Heat Mode
"G",
"W2", "W3"
FIGURE 21 — CONTROL CONNECTOR MOTOR HALF
POWER CONNECTOR
MOTOR HALF
FAN BLADE SETTING DIMENSIONS
The position of the fan blade should be ush with the leaving face of the orice plate. Check to make sure
the blades do not extend beyond the rear casing of the unit. Spin the blade by hand to make sure it does not hit the ring.
POWER CONNECTOR
PWB HEADER AMP 1-350945-0
PIN Description
1
2
3 Chassis Ground
4 AC Line
5 AC Line
*
Suggested mating connector
Jumper Pin 1 to Pin 2 for 120VAC Line Input Only **
Housing — AMP 350809-1 Contact — AMP 350537-1
** WARNING — Applying 240VAC line input with PIN 1 to PIN 2 jumper in place will permanently damage unit!
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity
and efciency ratings were determined by testing with
this refrigerant charge quantity. The following pres­sure tables (Tables 10A & 10B and 11A & 11B) show nominal pressures and temperatures for the units. Since many installation specic situations can affect the pres­sure readings, this information should only be used by
certied technicians as a guide for evaluating proper
system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
Manual 2100-578E Page 40 of 41
Model
I36Z1
I48Z1
I60Z1
Model
I36Z1
I48Z1
I60Z1
TABLE 10A — FULL LOAD COOLING PRESSURE/TEMPERATURE
Return Air
Temp. Pressure 55° 60° 65° 70° 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° 125°
75° DB
62° WB
80° DB
67° WB
85° DB
72° WB
75° DB
62° WB
80° DB
67° WB
85° DB
72° WB
75° DB
62° WB
80° DB
67° WB
85° DB
72° WB
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
126 209
137 219
154 217
118 221
132 223
140 234
123 218
137 219
146 231
127 231
139 239
155 240
121 239
134 242
144 253
124 241
137 244
147 255
129 252
141 260
157 262
124 257
137 261
147 271
124 265
138 269
148 279
130 274
142 280
158 285
126 275
139 280
151 289
125 289
138 294
150 303
131 295
144 300
159 307
129 293
141 299
154 307
126 312
139 319
151 327
132 317
148 314
160 330
131 311
141 348
158 326
127 336
140 341
153 352
134 338
149 341
162 352
134 329
144 373
161 344
128 360
140 375
154 376
135 360
150 359
163 375
136 347
148 366
165 362
129 383
141 392
156 400
136 381
151 381
164 397
139 365
151 375
168 380
129 407
141 418
157 424
137 407
152 407
165 424
140 397
152 408
170 414
131 431
143 443
159 450
138 433
153 433
166 451
141 430
154 442
171 448
132 456
144 469
161 475
139 458
154 458
167 477
142 462
155 475
173 482
134 481
146 494
162 501
140 484
155 484
168 504
143 494
156 508
174 515
135 505
147 519
164 527
141 510
156 510
169 531
144 527
157 541
175 549
136 530
149 544
166 552
TABLE 10B — FULL LOAD HEATING PRESSURE/TEMPERATURE
Return Air
Temp. Pressure 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60° 65° 70°
70° DB
70° DB
70° DB
Low Side
High Side383174531951320573226332470326763278232992356
Low Side
High Side33268402764728554293603016730974318813268933497342
Low Side
High Side38285422894629350297543015830563309673138033594357
101 382
107 388
106 349
100 365
114 395
114 356
107 372
120 401
122 363
114 380
127 408
130 370
120 387
141 536
157 535
171 540
145 559
159 575
177 583
138 554
150 570
167 578
133 414
138 377
127 395
Model
I36Z1
I48Z1
I60Z1
Model
I36Z1
I48Z1
I60Z1
TABLE 11A
PART LOAD COOLING PRESSURE/TEMPERATURE
Return Air
Temp. Pressure 55° 60° 65° 70° 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° 125°
75° DB
62° WB
80° DB
67° WB
85° DB
72° WB
75° DB
62° WB
80° DB
67° WB
85° DB
72° WB
75° DB
62° WB
80° DB
67° WB
85° DB
72° WB
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
131 188
145 192
158 198
126 172
137 171
150 177
127 196
138 196
152 203
133 209
146 213
159 219
127 196
139 197
152 203
127 218
139 219
153 226
134 230
148 234
161 240
129 221
141 222
154 229
128 240
140 242
153 249
136 250
149 254
162 260
130 245
142 248
156 254
128 261
141 265
154 271
137 271
150 275
163 281
131 269
144 274
158 280
129 283
142 288
155 294
139 292
154 292
164 302
133 294
147 312
160 305
130 305
143 316
156 317
140 313
154 320
166 323
134 318
148 346
162 331
130 326
144 347
157 340
142 333
155 336
167 343
135 343
150 355
164 357
131 348
144 359
158 363
143 354
155 358
168 364
137 367
151 377
166 382
131 370
145 380
159 385
144 379
156 383
169 389
138 390
152 401
167 407
133 394
147 405
161 411
145 403
158 408
171 415
139 414
154 426
168 431
134 418
149 430
163 436
146 428
159 433
172 440
140 438
155 450
170 456
136 443
150 455
165 461
148 453
160 458
173 466
141 461
156 474
171 481
138 467
152 480
167 487
149 478
161 483
175 491
142 485
157 498
173 505
139 491
154 505
169 512
TABLE 11B
PART LOAD HEATING PRESSURE/TEMPERATURE
Return Air
Temp. Pressure 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60° 65° 70°
70° DB
70° DB
70° DB
Low Side
High Side452705127257274632766927875280812828728494300
Low Side
High Side332614226750272582786628475290832959130197311
Low Side
High Side372614427052280592896729974308823188932797339
100 315
103 320
104 350
110 321
113 330
111 359
119 326
122 340
119 368
129 332
132 350
126 378
138 337
141 360
134 387
150 502
163 508
176 517
144 508
159 523
174 530
141 515
156 530
171 537
148 343
151 370
141 396
Air Temperature Entering Outdoor Coil °F
Manual 2100-578E Page 41 of 41
Loading...