Bard HAC601-BD040, HAC601-AD040, HAC421-AD040, HAC481-AD040, HAC181-AD040 User Manual

...
INSTALLATION INSTRUCTIONS
SPLIT AIR CONDITIONER OUTDOOR SECTION
Models:
HAC181-AD040 HAC241-AD040 HAC301-AD040 HAC361-AD040 HAC421-AD040 HAC481-AD040 HAC481-BD040 HAC601-AD040 HAC601-BD040
FOR USE WITH: MA TCHING INDOOR BLOWER COIL UNITS AND MA TCHING ADD
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914 . . . Moving ahead just as planned.
Manual No.: 2100-346C Supersedes: 2100-346B File: Volume 1, Tab 4 Date: 09-04-02
© Copyright 2002
CONTENTS
Split Air Conditioner General Information......... 1
Split Air Conditioner Model Nomenclature ............... 1
Application and Location ....................................4
General .................................................................... 4
Shipping Damage .................................................... 4
Application ............................................................... 4
Location ................................................................... 4
Mounting Unit Outside on Slab................................. 4
Important Installer Note............................................ 4
Installing Refrigerant Tubing..................................... 4
Sweat Style Tubin Connections: Sweat
Indoor Unit and Sweat Outdoor Unit ........................ 5
Field Fabricated Tubing Connections: Quick Connect Indoor Unit and Sweat
Outdoor Unit Using CTO Kit..................................... 6
Wiring Instructions ..............................................9
General .................................................................... 9
Control Circuit Wiring ............................................... 9
Wall Thermostats..................................................... 9
Optional Controls ................................................... 12
Installation Instructions – CMA-5 ............................ 12
Installation Instructions – CMA-6 ............................ 12
Installation Instructions – CMA-10A........................ 13
Installation Instructions – CMA-13A........................ 14
Charging Instructions ........................................ 15
Pressure Service Ports .......................................... 15
System Start-Up (Indoor Units
without Expansion V alves....................................... 15
Service ................................................................17
Service Hints.......................................................... 17
Fan Blade Setting Dimensions ............................... 17
Pressure T ables ................................................ 20-23
FIGURES
Figure 1.................................................................... 1
Figure 2.................................................................... 4
Figure 3.................................................................... 5
Figure 4.................................................................... 5
Figure 5.................................................................. 12
Figure 6.................................................................. 12
Figure 7.................................................................. 12
Figure 8.................................................................. 13
Figure 9.................................................................. 14
TABLES
Table 1 ..................................................................... 1
Table 2 ..................................................................... 2
Table 3 ..................................................................... 3
Table 4 ..................................................................... 6
Table 6 ..................................................................... 9
Table 7 ..................................................................... 9
Table 8 ..................................................................... 9
Table 9 ................................................................... 15
Table 10 ................................................................. 15
Table 11 ................................................................. 16
Table 12 ................................................................. 17
Table 13 ................................................................. 20
Table 14 ................................................................. 20
Table 15 ................................................................. 21
Table 16 ................................................................. 21
Table 17 ................................................................. 22
Table 18 ................................................................. 22
Table 19 ................................................................. 23
SPLIT AIR CONDITIONER MODEL NOMENCLATURE
HAC 36 1 – A DXXX
FIGURE 1
UNIT DIMENSIONAL DRAWING
Customized Unit Code Electrical Characteristics
A – 230/208-60-1 B – 230/208-60-3
Modification Code Capacity – 3 Ton or
approx. 36,000 BTU Basic Model Number
ALTERNATE ELECTRICAL ENTRANCES
ON BACK
HIGH VOLTAGE
ENTRANCE
LOW VOLTAGE
ENTRANCE
REFRIGERANT
SHUTOFF
VALVES
D
W
H
C
B
F
A
E
MIS-1789
TABLE 1
UNIT DIMENSIONS
"W"
.oNledoM
181CAH 142CAH
103CAH 163CAH
htdiW
00.0400.5100.62521.5881.0200.4521.7881.42
00.5400.5100.62521.5881.5200.4521.7881.92
"D"
htpeD
"H"
thgieHABCEF
124CAH 184CAH
00.0500.5100.23526.6886.8200.4526.8886.23
106CAH
Manual 2100-346 Page 1
TABLE 2
RATED CFM AND AIR FLOW DATA
(WET COIL – COOLING)
wolfriAdetaR
gnisnednoC
tinU
.oNledoM
A-181CAH
A142CAH
A-103CAH
A-163CAH
A-124CAH
B-,A-184CAH
B-,A-106CAH
rotaropavE
lioC
.oNledoM
A-SA03A A-SA42S
B42CB
A-SA03A A-SA42S
B42CB
A-SA63A
B63CB
A-SA73A
B63CB
A-SA24A
A-SA84A B63CB B06CB
B-SA16A B06CB
B-SA16A B06CB
MFC
056 056 056
008 087 057
000,1 000,1
001,1 001,1
004,1 005,1 002,1 005,1
007,1 007,1
067,1 008,1
erusserP
O
HporD
2
51.
42.
81.
03.
02.
81.
03.
62.
82.
03.
detaR
.P.S.E
53.deM
02.hgiH
03.woL
72.hgiH
51.
83.
52.woL
82.hgiH
rotoM
deepS
paT
hgiH
woL
dednemmoceR
egnaRwolFriA
517-055 517-055 517-055
019-007 098-086 019-007
571,1-058 571,1-058
022,1-029 022,1-029
055,1-072,1 526,1-052,1 023,1-020,1 526,1-052,1
578,1-054,1 578,1-054,1
059,1-005,1 579,1-525,1
metsyS
ecifirO
deriuqeR
250.
250.
250.
550.
550.
550.
360.
360.
960.
960.
870.
870.
870.
870.
180.
180.
290.
290.
* * *
* *
* *
* *
* * *
* *
Q Measured across the evaporator coil assembly, including drain pan. R External static pressure available for the duct system -- supply and return. All blower coils have multispeed
motors, and value shown is at the recommended rated speed. Consult specification air flow charts with the blower coil units for complete information at other speeds.
* IMPORT ANT INFORMA TION
Proper sized orifice is not factory installed in indoor section. Proper orifice size is shipped with outdoor unit packaged with its installation instructions for indoor sections listed on this page. The orifice must be replaced with the proper system orifice shown above in T able 2.
For other evaporator coil models not listed, see indoor coil installation instructions for proper orifice information.
Manual 2100-346 Page 2
!
TABLE 3
SPECIFICATIONS
SLEDOMA-181CAHA-142CAHA-103CAHA-163CAHA-124CAHA-184CAHB-184CAHA-106CAHB-106CAH
)HP/V/ZH06(gnitaRlacirtcelE1-802/0321-802/0321-802/0321-802/0321-802/0321-802/0323-802/0321-802/0323-802/032
egnaRegatloVgnitarepO352-791352-791352-791352-791352-791352-791352-781352-791352-781
yticapmAtiucriCmuminiM515191025262715312
¬
eziSeriWdleiF41412121010121801
rekaerBtiucriCromumixaMesuFyaleD020203030454520653
802/032spmAtinUlatoT6.8/9.74.11/2.010.41/4.318.51/5.416.91/1.910.12/4.914.31/8.217.62/7.222.71/3.51
ROSSERPMOC
802/032stloV802/032802/032802/032802/032802/032802/032802/032802/032802/032
spmAdaoLdetaR5.7/8.63.01/1.99.21/3.217.41/4.311.81/6.715.91/9.719.11/3.112.52/2.127.51/8.31
tnerruCnoitceleStiucriChcnarB6.83.017.317.411.815.916.213.627.51
802/032spmArotoRkcoL94/9465/6557/5728/28501/501201/20119/19531/531051/051
taeHesacknarCenoNenoNenoNenoN
RESNEDNOCdnaROTOMNAF
MPR/PHrotoMnaF5286/15286/15286/15286/15284/15284/15284/15284/15284/1
spmArotoMnaF1.11.11.11.15.15.15.15.15.1
noisremmI
epyT
noisremmI
epyT
noisremmI
epyT
enoNenoN
Manual 2100-346
Page 3
retemaiDnaF000,2–"02000,2–"02000,2–"02000,2–"02006,2–"42006,2–"42006,2–"42006,2–"42006,2–"42
METSYSTCENNOCTAEWS
DIeziSeniLnoitcuS"8/5"4/3"4/3"4/3"8/7"8/7"8/7"8/7"8/7
DIeziSeniLdiuqiL"4/1"8/3"8/3"8/3"8/3"8/3"8/3"8/3"8/3
.zO22-RegnahCyrotcaF.zo37.zo97.zo48.zo69.zo201.zo551.zo551.zo351.zo351
.SBLTHGIEWGNIPPIHS
551551081081052052052552552
APPLICATION and LOCATION
GENERAL
These instructions explain the recommended method to install the air cooled remote type condensing unit, the interconnecting refrigerant tubing and the electrical wiring connections to the unit.
The condensing units are to be used in conjunction with the matching evaporator coils or evaporator blower units for comfort cooling applications as shown in the specification sheet.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving part must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
APPLICATION
LOCATION
The condensing unit is designed to be located outside with free and unobstructed condenser air inlet and discharge. It must also permit access for service and installation. Condenser air enters the coil from the rear of the unit as shown in Figure 2 with electrical service access.
MOUNTING UNIT OUTSIDE ON SLAB
A solid level base or platform, capable to support the unit’s weight, must be set at the outdoor unit predetermined location. The base should be at least two inches larger than the base dimensions of the unit and at least two inches higher than surrounding grade level. The required unit minimum installed clearances must be maintained as called out in Figure 2 when locating and setting the base.
Remove the unit from its shipping carton and position the unit on the prepared base or platform.
NOTE: These units employ internally sprung
compressors; therefore, it is not necessary to remove or loosen the base mounting bolts on the compressor prior to operation.
Consideration should be given to the electrical and tubing connections when placing the unit to avoid unnecessary bends or length of material.
Size of unit for a proposed installation should be based on heat loss calculation and air duct sizing made according to methods of Air Conditioning Contractors of America. The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
FIGURE 2
INSTALLATION CLEARANCE
IMPORTANT INSTALLER NOTE
For improved start up performance, wash the indoor coil with a dishwashing detergent.
INSTALLATION REFRIGERANT TUBING
The information that follows on installing refrigerant tubing and for changing the system orifice (if required) covers applications listed in the front of this installation instruction only. Although other indoor units may be of similar construction, the installation instructions for these units should be consulted for proper installation of those units prior to installation.
This information is provided for the field service personnel to install refrigerant tubing in compliance with Section 608 of Title VI National Recycling and Emission Reduction Program for the U.S. Clean Air Act effective July 1, 1992.
Consult manual 2100-002 on procedure for leak test – evacuation – charging before installation refrigerant tubing that requires any refrigerant recovery or system evacuation. Manual 2100-002 is included with the unit installation instruction package when shipped from the factory.
Manual 2100-346 Page 4
MIS-589
FIGURE 3
INSTALLING REFRIGERANT TUBING
NOTE:
If the orifice does not have to be changed, skip the instructions outlined further in Step 3 and proceed to Step 8.
3. Disassemble Flow Control Assembly by turning body
4. If existing orifice has not dropped out of the body when
5. Insert proper sized orifice fully into the flow control
Do not braze line to units! If orifice needs to be
changed, change out orifice first.
hex.
disassembled, remove by using a pin or paper clip. Discard this original orifice.
body with rounded “bullet” nose towards the unit as shown in Figure 4. Insure the orifice stays inserted in body before connecting mating half. See chart in the outdoor unit installation instructions for proper size.
pp5
SWEAT STYLE TUBING CONNECTIONS: SWEAT INDOOR UNIT and SWEAT OUTDOOR UNIT
Use only refrigeration grade (dehydrated and sealed) copper tubing. Care must be taken to insure that the tubing is kept clean and dry before and during installation. Do not remove the plugs from the tubing ends, coil connections or base valves until the connection is ready to be brazed.
The suction line must be insulated with a minimum of 3/8” Armaflex or equivalent before cutting and making connections.
1. Being careful not to kink, route both the suction line and liquid line between the indoor unit and outdoor unit. Use a tubing bender to make any necessary bends in tubing. When necessary to bend the insulated tube suction line, cut the insulation around its circumference at a distance far enough beyond the point of the bend so as to clear the tubing bender. Slip the insulation back together and vapor seal the joint with tape. Coil any excess tubing in a horizontal place with the slope of the tubing toward the condensing unit. See Figure 3.
CAUTION
1. Be careful not to tear the insulation when pushing it through hole in masonry or frame walls. 2. When sealing the tube opening in house wall, use a soft material to prevent tube damage and vibration transmission. 3. Avoid excessive bending in any one place to avoid kinking.
2. The tubing ends should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contaminants from entering the system.
CAUTION
Be sure there is no dirt introduced into the flow control - orifice assembly . Be sure to install the orifice with the bullet nose pointing in the proper direction as shown in Figure 4. Failure to do so will result in improper operation.
FIGURE 4
FLOW CONTROL ASSEMBLY
FIELD ORIFICE REPLACEMENT INSTRUCTIONS
pp5
6. Thread assembly halves together by hand to insure proper mating of threads and tighten until bodies “bottom” or a definite resistance is felt.
7. Using a marker pen or ink pen, mark a line lengthwise from the union nut to the bulkhead. Then tighten an additional 1/6 turn (or 1 hex flat). The misalignment of the line will show the amount the assembly has been tightened. This final 1/6 turn is necessary to insure the formation of the leakproof joint.
8. Wrap a wet rag around the copper stub before brazing.
9. Flux the copper tube and insert into the stub. Braze the joint using an alloy of silver or copper and phosphorus with a melting temperature above 1,100° F for copper to copper joints. The phosphorus will act as a flux, therefore, no flux will be required.
Manual 2100-346 Page 5
A copper-silver alloy with a high silver content should be used when iron or steel material is involved in the joint. These alloys require the use of silver solder flux. Alloys containing phosphorus should not be used with iron or steel. Phosphorus reacts with the iron forming iron phosphate which is extremely brittle.
FIELD FABRICATED TUBING CONNECTIONS: QUICK CONNECT INDOOR UNIT and SWEAT OUTDOOR UNIT USING CTO KIT
Use only refrigeration grade (dehydrated and sealed) copper tubing. Care must be taken to insure that the tubing is kept clean and dry before and during installation. Do not remove the plugs from the tubing ends, coil connections or base valves until the connection is ready to be brazed.
CAUTION
1. Brazing alloys with a melting temperature below 700° F should not be used. 2. Lead­tin or tin-antimony solders should not be used due to their low melting point and necessity for corrosive fluxes.
To further prevent the formation of copper oxide inside the tubing, dry nitrogen may be purged through the refrigerant system during brazing.
WARNING
Never purge or pressurize a system with oxygen. An explosion and fire will result.
10. After brazing, quench with wet rag to cool the joint and remove any flux residue.
11. Leak test all connections using an electronic leak detector or a halide torch.
The suction line must be insulated with a minimum of 3/8” Armaflex or equivalent before cutting and making connections.
1. Being careful not to kink, route both the suction line and liquid line between the indoor unit and outdoor unit. Use a tubing bender to make any necessary bends in tubing. When necessary to bend the insulated tube suction line, cut the insulation around its circumference at a distance far enough beyond the point of the bend so as to clear the tubing bender. Slip the insulation back together and vapor seal the joint with tape. Coil any excess tubing in a horizontal place with the slope of the tubing toward the condensing unit. See Figure 3.
CAUTION
1. Be careful not to tear the insulation when pushing it through hole in masonry or frame walls. 2. When sealing the tube opening in house wall, use a soft material to prevent tube damage and vibration transmission. 3. Avoid excessive bending in any one place to avoid kinking.
12. Evacuate suction line, liquid line and indoor unit through outdoor unit base valves.
13. Open both the suction and liquid base valves to the fully open position. Refer to section later in installation instructions for details on setting proper system charge.
cisaB
gnisnednoC ledoMtinU
181CAH"4/1"8/5"4/1"8/5"8/3"4/3 142CAH"8/3"8/5"8/3"4/3"8/3"4/3 103CAH"8/3"8/5"8/3"4/3"8/3"4/3 163CAH"8/3"8/5"8/3"4/32/1"8/7 124CAH"8/3"4/3"8/3"8/72/1"8/7 184CAH"8/3"8/7"8/3"8/72/1"8/1-1 106CAH"8/3"8/7"8/3"8/72/1"8/1-1
Manual 2100-346 Page 6
diuqiLnoitcuSdiuqiLnoitcuSdiuqiLnoitcuS
TABLE 4
TUBING CHART
).tF(htgneLeniLtnaregirfeR
02-006-12001-16
2. The tubing ends should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contaminants from entering the system.
NOTE: Do not make any tubing connection at indoor unit
at this time. Make all brazing of joints and evacuate both suction and liquid line first.
3. Wrap a wet rag around the copper stub before brazing.
4. Flux the copper tube and insert into the stub. Braze the joint using an alloy of silver or copper and phosphorus with a melting temperature above 1,100° F for copper to copper joints. The phosphorus will act as a flux, therefore, no flux will be required.
A copper-silver alloy with a high silver content should be used when iron or steel material is involved in the joint. These alloys require the use of silver solder flux. Alloys containing phosphorus should not be used with iron or steel. Phosphorus reacts with the iron forming iron phosphate which is extremely brittle.
8. Recover charge from the indoor unit. A. Connect the suction line only to the indoor unit as
outlined in Steps 15, 16, and 17.
B. Recover indoor unit and suction line unit charge
through service port located on outdoor unit base valve.
9. Disassemble Flow Control Assembly by turning body hex.
10. If existing orifice has not dropped out of the body when disassembled, remove by using a pin or paper clip. Discard this original orifice.
11. Insert proper sized orifice fully into the flow control body with rounded “bullet” nose towards the unit as shown in Figure 4. Insure the orifice stays inserted in body before connecting mating half. See chart in the outdoor unit installation instructions for proper size.
To further prevent the formation of copper oxide inside the tubing, dry nitrogen may be purged through the refrigerant system during brazing.
CAUTION
1. Brazing alloys with a melting temperature below 700° F should not be used. 2. Lead-tin or tin-antimony solders should not be used due to their low melting point and necessity for corrosive fluxes.
WARNING
Never purge or pressurize a system with oxygen. An explosion and fire will result.
5. After brazing, quench with wet rag to cool the joint and remove any flux residue.
6. Leak test all connections using an electronic leak detector or a halide torch.
7. Evacuate suction line and liquid line through outdoor unit base valves.
CAUTION
Be sure there is no dirt introduced into the flow control – orifice assembly. Be sure to install the orifice with the bullet nose pointing in the proper direction as shown in Figure 4. Failure to do so will result in improper operation.
12. Thread assembly halves together by hand to insure proper mating of threads and tighten until bodies “bottom” or a definite resistance is felt.
13. Using a marker pen or ink pen, mark a line lengthwise from the union nut to the bulkhead. Then tighten an additional 1/6 turn (or 1 hex flat). The misalignment of the line will show the amount the assembly has been tightened. This final 1/6 turn is necessary to insure the formation of the leakproof joint.
14. Evacuate the suction line and indoor unit through the outdoor unit base valve before connecting all other tubing. Refer to section later in installation instructions for details on setting the proper refrigerant charge.
15. Remove (remaining) protector caps and plugs (if orifice was changed). Inspect fittings and if necessary carefully wipe coupling seats and threaded surfaces with a clean cloth to prevent the inclusion of dirt or any foreign material in the system.
If orifice does not have to be changed, skip the instructions outlined further in Step 8 and proceed to Step 15.
Manual 2100-346 Page 7
16. Lubricate male half diaphragm and synthetic rubber seal with refrigerant oil. Thread coupling halves together by hand to insure proper mating of threads. Be sure to hold the coupling firmly to prevent movement of the coupling and tubing. Failure to do so could tear out the diaphragm causing a blockage of the system. Use proper size wrenches (on coupling body hex and on union nut) and tighten until coupling bodies ”bottom” or a definite resistance is felt.
TABLE 5
COUPLINGS
eziSgnilpuoCsdnuoPteeF
6-21-01
01-54-53 11-54-53 21-56-05
CAUTION
After starting to tighten up the fitting, never try to back it off or take it apart.
17. Using a marker or ink pen, mark a line lengthwise from the coupling union nut to the bulkhead. Then tighten an additional 1/4 turn. The misalignment of the line will show the amount the coupling has been tightened. This final 1/4 turn is necessary to insure the formation of leakproof joint. If a torque wrench is used, the torque values shown in Table 5 are recommended.
18. Leak test all connections using an electronic leak detector or a halide torch.
19. When tubing is installed in attics or drop ceilings, insulate the couplings on the larger tube thoroughly with 3/8” wall thickness, closed cell sponge tube insulation or equivalent. Failure to insulate will result in water damage to ceiling since the fitting will “sweat” and drop water on the ceiling.
Manual 2100-346 Page 8
WIRING INSTRUCTIONS
GENERAL
All wiring must be installed in accordance with the National Electrical Code and local codes. In Canada, all wiring must be installed in accordance with the Canadian Electrical Code and in accordance with the regulations of the authorities having jurisdiction. Power supply voltage must conform to the voltage shown on the unit serial plate. A wiring diagram of the unit is attached to the inside of the electrical cover. The power supply shall be sized and fused according to the specification supplied. A ground lug is supplied in the control compartment for equipment ground.
The unit rating plate lists a “Maximum Time Delay Fuse” or HACR type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
CONTROL CIRCUIT WIRING
For split systems, the minimum control circuit wiring gauge needed to insure proper operation of all controls in both indoor and outdoor units will depend on two factors:
1. The rated VA of the control circuit transformer.
Example: 1 . Control circuit transformer rated at 40 VA
2. Maximum total distance of control circuit wiring 85 feet.
From Table 6, minimum of 18 gauge wire should be used in the control circuit wiring.
For control circuit transformers rated other than those listed, use the next lower rated transformer listed.
Example: 1 . Control circuit transformer rated at 55 VA
From table use 50VA transformer.
There are two (2) separate control diagrams for fossil fuel furnaces with air conditioners.
Control diagrams for the various circuit which could be encountered with blower coils can be found in the installation instructions of the blower coil.
TABLE 7
CONTROL DIAGRAMS
metsyS
sledoMllA001-1904101-1904
ecanruFsaG
margaiDlortnoC
ecanruFliO
margaiDlortnoC
2. The maximum total distance of the control circuit wiring. (This is the distance between the wall thermostat to the indoor unit plus the distance between the indoor unit to the outdoor unit.)
The following table should be used to determine proper gauge of control circuit wiring required.
TABLE 6
CONTROL CIRCUIT WIRING
foAVdetaR
tiucriClortnoC
remrofsnarT
046.1
051.2
567.2
remrofsnarT
yradnoceS
V42@ALF
WALL THERMOSTATS
The following wall thermostats and subbases should be used as indicated, depending on the application.
TABLE 8
WALL THERMOSTAT and SUBBASE
COMBINATIONS
latoTmumixM
foecnatsiD
tiucriClortnoC
teeFnigniriW
56eguag02 09eguag81
541eguag61 032eguag41
54eguag02 06eguag81
001eguag61 061eguag41 052eguag21
04eguag02 55eguag81 58eguag61
531eguag41 012eguag21
tatsomrehTesabbuSserutaeFetanimoderP
200-3048
113F78T
140-3048
C-4308T
530-3048
08-59F1
240-3048
G1158T
340-3048
002MC
720-3048
17-29F1
300-4048
0221A925Q
---
---
---
---
---
yrucreM;loocegats1,taehegats1
otua-no:naFlooc-ffo-taeh:metsyS
yrucreM;loocegats1,taehegats1
otua-no:naFlooc-ffo-taeh:metsyS
loocegats2,taehegats2
elbammargorP
cinortcelE
loocegats1,taehegats2
looc-otua-ffo-taeh:metsyS
cinortcelEotua-no:naF
loocegats1,taehegats1
otua-no:naFlooc-ffo-taeh:metsyS
noitcApanS
loocegats2,taehegats3
elbammargorP
cinortcelE
Manual 2100-346 Page 9
Manual 2100-346 Page 10
Manual 2100-346 Page 11
OPTIONAL CONTROLS
INSTALLATION INSTRUCTIONS — CMA-6
FIGURE 5
COMPONENT MOUNTING LOCATION
CMA-5 & CMA-13A LOW
CMA-5 COMPRESSOR TIME DELA Y RELAY
SK109 LOW VOLTAGE START KIT
MIS-1302
AMBIENT FAN CYCLING CONTROL TERMINAL BLOCK
CMA-10A & CMA-13A COMPRESSOR CONTROL
INSTALLATION INSTRUCTIONS — CMA-5
Disconnect all power to the unit. Remove control panel cover.
1. Mount compressor TDR in position shown in Figure 5 with screw provided.
2. Disconnect yellow low voltage (Y) wire at the compressor contactor coil and reconnect to the Y1 or #3 terminal of the TDR.
3. Connect yellow wire from terminal (Y) of the TDR to the (Y) terminal of the compressor contactor coil. This is the terminal that the wire was removed from in Step 2.
4. Recheck wiring. Refer to Figure 9. Energize unit. Compressor should start. Remove power and reapply. Compressor should not start until the 5 minute time delay has expired.
Disconnect all power to unit. Remove control panel inner and outer cover.
1. Mount terminal block in position shown in Figure 5.
2. Disconnect black high voltage outdoor motor lead from compressor contactor and reconnect to terminal block.
3. Route low ambient control wires up through the bushing in the bottom of the control panel. Connect the low ambient control wires between the terminal block and T2 of the compressor contactor.
4. Remove service port cap on discharge line. Install the low ambient control on the discharge line with the flare tee adapter that is brazed to the low ambient control. Check for pressure at the flare tee dill valve after installation to insure that the dill valve in the unit service port was depressed by the flare tee connector. Check for leaks at the flare tee connectors. Replace service port cap on the flare tee service port and tighten.
5. Recheck wiring. See Figure 10. Check for proper operation of the unit by energizing in cooling mode. The condenser fan motor should not run until the discharge pressure has exceeded 300 PSI. Should the discharge pressure fall below 200 PSI while running, the condenser fan motor will de-energize until the head pressure builds to 300 PSI.
6. Apply “This unit equipped with CMA-6 control module” label to the inside of the control panel cover above the wiring diagrams.
7. Replace all panels and covers. This completes installation.
FIGURE 7
INSTALLATION INSTRUCTIONS FOR
CMA-6 LOW AMBIENT FAN CYCLING CONTROL
5. Apply “This unit equipped with CMA-5 control module” label to inside of the inner control panel cover above wiring diagram.
6. Replace all panels and covers. This completes installation.
FIGURE 6
INSTALLATION INSTRUCTIONS
FOR CMA-5 COMPRESSOR TIME DELAY RELAY
MIS-598
Manual 2100-346 Page 12
MIS-594
INSTALLATION INSTRUCTIONS – CMA-10A
Disconnect all power to unit. Remove control panel cover.
1. Screw compressor control module and terminal block into control panel as shown in Figure 5.
2. Disconnect yellow low voltage wire form compressor contactor and reconnect to terminal “Y” of the compressor control module.
3. Connect the yellow wire from the compressor control module to “Y” side of the compressors contactor coil. This is the same terminal from which the wire was removed in Step 2.
4. Connect the black wire form the compressor control module to common “C” side of the compressor contactor coil.
5. Connect a field supplied wire from “R” of the indoor unit to “R” on the compressor control module.
6. Route the high (red) and low (blue) pressure switch wires through the bushing in the bottom of the control panel. Connect the low pressure switch wire to terminals LPC of the compressor control module.
7.Remove service port caps on both the suction and discharge lines. Install the high pressure switch on the discharge line to the flare tee adapter that is brazed to the controls. Install the low pressure switch on the suction line. Check for pressure at the flare tee dill valves after installation to insure that the dill valve in the unit service port was depressed by the flare tee connector. Check for leaks at the flare tee connectors. Replace service port caps on the flare tee service ports and tighten.
8. Adjust the compressor time delay relay to the desired delay on break. Two minutes are recommended. This TDR is variable form 30 seconds to 5 minutes.
9. Recheck wiring. Energize unit is first stage cooling. Compressor should not start until the time delay has expired. This will be 10% of the delay on break period. Run the unit for at least 5 minutes. The unit should not go into lockout.
10. Apply “This unit equipped with CMA-10A control module.” label to the inside of the inner control panel cover above the wiring diagram.
11. Replace all panels and covers. This completes installation.
FIGURE 8
INSTALLATION INSTRUCTIONS FOR
CMA-10A DUAL PRESSURE CONTROL and
COMPRESSOR TIME DELAY RELAY
MIS-1303
Manual 2100-346 Page 13
INSTALLATION INSTRUCTIONS – CMA-13A
Disconnect all power to unit. Remove control panel cover.
1. Screw compressor control module and terminal block into control panel as shown in Figure 5.
2. Disconnect yellow low voltage wire from compressor contactor and reconnect to terminal “Y” of the compressor control module.
3. Connect the yellow wire from the compressor control module to “Y” side of the compressor’s contactor coil. This is the same terminal from which the wire was removed in Step 2.
4. Connect the black wire from the compressor control module to common “C” side of the compressor contactor coil.
5. Connect a field supplied wire from “R” of the indoor unit to “R” on the compressor control module.
6. Route the high (red) and low (blue) pressure switch wires through the bushing in the bottom of the control panel. Connect the low pressure switch wire to terminals LPC of the compressor control module. Connect the high pressure switch wires to terminals HPC of the compressor control module.
7. Disconnect the high voltage outdoor motor lead and reconnect to the terminal block installed in Step 1.
8. Route the LAC (black) wires up through the busing in the bottom of the control panel. Connect one wire to the terminal block and the other to “T2” of the contactor. This will be the same terminal from which
the high voltage outdoor motor lead was removed in Step 7.
9. Remove service port caps on both the suction and discharge lines. Install the high pressure switch and the low ambient control on the discharge line with the flare tee adapter that is brazed to the controls. Install the low pressure switch on the suction line. Check for pressure at the flare tee dill valves after installation to insure that the dill valve in the unit service port was depressed by the flare tee connector. Check for leaks at the flare tee connectors. Replace service port caps on the flare tee service ports and tighten.
10. Adjust the compressor time delay relay to the desired delay on break. Two minutes are recommended. This TDR is variable from 30 seconds to 5 minutes.
11. Recheck wiring. Energize unit in first stage cooling. Compressor should not start until the time delay has expired. This will be 10% of the delay on break period. Run the unit for at least 5 minutes. The unit should not go into lockout. The condenser fan motor should not run until the discharge pressure has exceeded 300 PSI. Should the discharge pressure fall below 200 PSI while running the condenser fan motor will de-energize until the head pressure builds to 300 PSI.
12. Apply “This unit equipped with CMA-13A control module.” label to the inside of the inner control panel cover above the wiring diagram.
13. Replace all panels and covers. This completes installation.
FIGURE 9
INSTALLATION INSTRUCTIONS FOR
CMA-13A DUAL PRESSURE CONTROL, LOW AMBIENT FAN CYCLING CONTROL
and COMPRESSOR TIME DELAY RELAY
MIS-1304
Manual 2100-346 Page 14
CHARGING INSTRUCTIONS
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.
SYSTEM START-UP (INDOOR UNITS WITHOUT EXPANSION VALVES)
1. Close disconnect switch(es) and set the thermostat to cool and the temperature to the highest setting.
2. Check for proper airflow across the indoor coil by referring to indoor unit installation.
3. Connect the service gauges and allow the unit to run for at least 10 minutes or until pressures are stable. Check pressures to the system pressure table attached to the outdoor unit service panel. For optimum system performance, go to Step 4.
4. Install a thermometer on the suction line approximately 6" to 10" from the compressor. Optimum system performance will occur with a refrigerant charge resulting in a suction line superheat as determined from the following calculations.
A. Measure outdoor air dry bulb temperature
________ ºF
B. Measure indoor air wet bulb temperature
________ ºF C. Measure suction pressure ______PSIG D. Measure suction line temperature ________ ºF E. Determine optimum system superheat
from Table 9 using outdoor air dry bulb (Step B) and indoor air wet bulb (Step A)
________ ºF
TABLE 9
SYSTEM SUPERHEAT
tneibmAroodtuO
F(erutarepmeT
)bluByrD
501 59 09 58 08 57
95367617
1
1
1
3
1
7
3
9
8
41
01
02
bluBteWF
5
)8( 41 91 52 03
TABLE 10
SATURATED SUCTION TEMPERATURE R-22
noitcuSdetarutaS
GISPerusserPnoitcuS
05 35 55
85 16 36
56 76 07
37 67 97
28 68
62 82 03
23 43 63
83 93 14
34 54 74
94
15
)F(erutarepmeT
erutarepmeTriAnruteR
02 62 33 93 24
F. Determine saturated suction temperature
from suction pressure using Table 10 ________ ºF
G. Determine system superheat:
Suction line temperature (Step D) ________ ºF
- Saturated suction temperature (Step F)
- ________ ºF
= System superheat
= ________ ºF
H. Adjust the system superheat (Step G) to the
optimum system superheat (Step E) by adding charge to lower the superheat or removing charge to raise the superheat.
I. Check final system operating pressures to the
system pressure tables as was done in Step 3.
Manual 2100-346 Page 15
TABLE 11
TOTAL SYSTEM OPERATING CHARGE
(Includes charge for the basic outdoor unit,
indoor coil and 25’ of interconnecting tubing.)
noitceSroodtuOnoitceSroodnI
A-SA03A
A-181CAH
A-142CAH
A-103CAH
A-163CAH
A-124CAH
B-,A-184CAH
B-,A-106CAH
A-SA42S
B42CB
A-SA03A A-SA42S
B42CB
A-SA63A
B63CB
A-SA73A
B63CB
A-SA24A
A-SA84A B63CB B06CB
A-SA16A B06CB
A-SA16A B06CB
.zo37 .zo37 .zo87
.zo08 .zo08 .zo97
.zo48 .zo59
.zo89 .zo69
.zo201 .zo711 .zo501 .zo241
.zo551 .zo571
.zo351 .zo561
SCHEDULE FOR TABLE 11
retemaiDeniLdiuqiL.tFreP22-R.zO
"4/1 "8/3
22-RlatoT
).zO(egrahC
Installer Note: Stamp or mark the final system charge
determined above on the outdoor unit serial plate.
"2/1
52.0
06.0
02.1
Q
R
R
R
R
R
R
Includes 25 of 1/4 diameter liquid line. For other than 25 and
Q
other tube sizes, adjust the total charge according to the following schedule.
Includes 25 of 3/8 diameter liquid line. For other than 25 and
R
other tube sizes, adjust the total charge according to the following schedule.
Manual 2100-346 Page 16
SERVICE
ledoMAnoisnemiDsnoitacoLbuHnaF
181CAH 142CAH 103CAH 163CAH
"5B
124CAH 184CAH 106CAH
"4/3-4C
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and return air registers. This reduces air flow through the system, which shortens equipment service life, as well as, increasing operating costs.
2. Check all power fuses or circuit breakers to be sure that they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and unrestricted air flow circulation is essential.
FAN BLADE SETTING DIMENSIONS
Shown in Figure 10 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 10
FAN BLADE
C
B
A
7960-337
TABLE 12
FAN BLADE SETTING
Manual 2100-346 Page 17
Manual 2100-346 Page 18
Manual 2100-346 Page 19
TABLE 13
PRESSURE TABLE
HAC181-A
roodnI noitceS
A-SA03SA
A-SA42S
B42CB
Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
T ests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
riAnruteR
.pmeTerusserP
BD57
BW26
BD08
BW76
BD58
BW27
BD57
BW26
BD08
BW76
BD58
BW27
56075708580959001501011511
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
86
07
27
47
67
87
08
051
071
781
302
622
442
452
07
37
67
97
18
48
68
961
381
891
312
822
442
062
67
97
28
58
78
09
29
771
191
602
55
26
86
261
871
391
77
87
87
461
081
891
67
97
28
771
191
602
122
632
252
962
37
87
902
422
08 312
032
58
78
122
632
18
48
042
652
18
28
48
642
362
09
29
252
962
lioCroodtuOgniretnEerutarepmeTriA
28
48
58
852
552
642
88
09
29
672
392
013
49
69
89
682
403
223
68
78
78
272
882
403
68
88
09
082
692
313
49
69
89
682
403
223
78 023
39 823
99 043
78 023
39 923
99 043
TABLE 14
PRESSURE TABLE
HAC241-A
roodnI noitceS
A-SA03SA
A-SA42S
B42CB
Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
T ests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
riAnruteR
.pmeTerusserP
BD57
BW26
BD08
BW76
BD58
BW27
BD57
BW26
BD08
BW76
BD58
BW27
56075708580959001501011511
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
06
46
86
17
47
67
87
271
091
702
422
142
852
572
66
07
37
67
97
771
591
312
032
742
37
67
97
28
58
581
302
022
832
752
56
96
37
77
08
971
491
902
522
07
37
57
77
97
401
251
291
522
37
67
97
28
58
581
302
022
832
652
18
38
562
282
78
98
372 28
142
752
152
962 78
372
192
38 372
18
38 082
98
192
lioCroodtuOgniretnEerutarepmeTriA
08 292
58 992
903 48
092 58
482
903
18
28
803
523
68
78
613
333
19
29
49
623
443
58
68
603
423
68
88
182
072
19
29
49
623
443
28
143
88 053
59 263
78
143
98 252
59 263
Manual 2100-346 Page 20
TABLE 15
PRESSURE TABLE
HAC301-A
roodnI noitceS
A-SA63A
B63CB
Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
T ests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
riAnruteR
.pmeTerusserP
BD57
BW26
BD08
BW76
BD58
BW27
BD57
BW26
BD08
BW76
BD58
BW27
56075708580959001501011511
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
26
56
76
96
261
381
402
422
86
07
27
47
761
881
012
032
57
77
87
08
171
491
612
832
16
56
96
27
581 76
091 47
891
102
712
432
17
47
77
702
322
932
77
08
38
512
232
842
17
37
57
442
262
082
67
87
08
052
962
782
28
48
68
852
872
792
57
77
97
052
662
282
08
28
48
652
272
982
68
88
09
562
282
992
lioCroodtuOgniretnEerutarepmeTriA
77
87
08
792
313
923
28
48
58
503 88
513
892 68
603 29
613
123
833
09
29
333
943
18
28
38
413 78
223 39
333
133
88 933
59
153
TABLE 16
PRESSURE TABLE
HAC361-A
18
443 78
353 49
563 48
743 98
653 69
863
roodnI
noitceS
A-SA73A
B63CB
Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
T ests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
riAnruteR
.pmeTerusserP
BD57
BW26
BD08
BW76
BD58
BW27
BD57
BW26
BD08
BW76
BD58
BW27
56075708580959001501011511
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
66
86
07
27
47
67
87
181
791
312
032
642
262
872
17
37
57
77
97
18
38
681
202
912
532
252
862
582
77
97
191
802
36
66
871
591
66
96
481
002
27
57
881
602
18
38
58
78
98
622
342
062
872
592
86
07
27
47
67
212
822
542
262
972
27
57
87
08
28
712
432
152
962
682
87 422
18
38
68
88
242
062
872
692
lioCroodtuOgniretnEerutarepmeTriA
08
28
48
492
013
623
58
78
98
203
813
533
19
39
59
213
033
743
87
97
18
692
313
133
48
58
78
403 09
413
123
933
29
49
233
153
68 343
19 153
79 463
28 843
88 753
59 963
Manual 2100-346 Page 21
TABLE 17
PRESSURE TABLE
HAC 421-A
roodnI
noitceS
A-SA24A
B63CB
A-SA84A
B06CB
Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
T ests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
riAnruteR
.pmeTerusserP
BD57
BW26
BD08
BW76
BD58
BW27
BD57
BW26
BD08
BW76
BD58
BW27
5708580959001501011511
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
46 302
96 802
37 612
37 212
77 812
38 422
76 812
27 422
77 232
47 822
97 432
58
142
07 332
57 042
08 842
67 442
18
052 78
852
27 052
77 652
38 562
77 062
38 762
98 672
47 662
97 372
58 282
97 772
58 482
19
492
67 382
28 092
78 003
18
492 78
203 39
492
lioCroodtuOgniretnEerutarepmeTriA
77 003
28 803
98 813
28 213
98 023
59
133
87 813
48 623
09 733
48 033
09 933
79 053
TABLE 18
PRESSURE TABLE
HAC481-A, HAC481-B
97 633
58 543
19
953 68
943 29
853 99
073
roodnI noitceS
-SA16A
B
B06CB
Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
T ests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
riAnruteR
.pmeTerusserP
BD57
BW26
BD08
BW76
BD58
BW27
BD57
BW26
BD08
BW76
BD58
BW27
5708580959001501011511
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
47 802
87 412
48 022
86 242
67 842
28 752
57 322
08 922
68 632
07 052
77 652
38 562
77 832
28 542
88 352
27 062
87 662
48 672
87 452
48
162
09 072
47 272
08 872
68 882
08
172
68 872
29 882
67 582
18
292 78
203
28 882
88 692
49 603
87 003
28 803
88 813
lioCroodtuOgniretnEerutarepmeTriA
38 603
09 413
69 523
97 713
48 523
09 633
58 423
19
333 79
443 08
633 58
443
19
653
78 343
39 253
99 463
18
653 78
563 39
873
Manual 2100-346 Page 22
TABLE 19
PRESSURE TABLE
HAC601-A, HAC601-B
roodnI
noitceS
-SA16A
B
B06CB
Low side pressure ± 2 PSIG (suction line 8 inches from compressor) High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
T ests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
riAnruteR
.pmeTerusserP
BD57
BW26
BD08
BW76
BD58
BW27
BD57
BW26
BD08
BW76
BD58
BW27
5708580959001501011511
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
ediSwoL ediShgiH
76 722
27 232
87 042
46 322
96 032
67 732
96 342
47 942
08 852
76 932
27 642
87 552
17
062 67
662 28
672 07
752 57
462 08
372
37 672
87 482
48 392
27 572
77 382
28 392
57 392
08
103
68
113
47 592
97 303
58 413
67 013
28 813
88 923
67 613
18
523 58
633
lioCroodtuOgniretnEerutarepmeTriA
87 623
48 633
09 643
77 933
28 843
78 063
97 343
68 353
29 463
87 363
38 273
98 583
97 953
88 073
49 283
87 883
48 893
09
114
Manual 2100-346 Page 23
Loading...