Bard HA4S4KA, HA5S4KA, HL4S4KA, HL5S4KA Installation Instructions Manual

INSTALLATION INSTRUCTIONS
WALL-MOUNTED
PACKAGED AIR CONDITIONER
Models:
HA4S4KA HA5S4KA
HL4S4KA HL5S4KA
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
MIS-2498
Manual: 2100-646 Supersedes: NEW Date: 9-3-15
Page 1 of 26
CONTENTS
Getting Other Information and Publications
Wall Mount General Information
Air Conditioner Wall Mount Model Nomenclature Shipping Damage General Duct Work Filters
............................................................... 7
........................................................... 7
................................................................. 7
Condensate Drain
Installation
Wall Mounting Information Mounting the Unit Typical Installations Wiring – Main Power Wiring – Low V
................................................. 7
................................................ 7
............................................................... 8
.................................... 8
................................................ 8
.............................................. 8
............................................. 8
oltage Wiring ................................. 12
......................... 4
..... 4
Dirty Filter Switch and Relay ............................... 13
Economizer Fail Time Delay Relay ........................ 13
Figures
Figure 1 Unit Dimensions .................................. 5
Figure 2
Mounting Instructions .......................... 9
Figure 3 Wall Mounting Instructions ................. 10
Figure 4
Wall Mounting Instructions ................. 10
Figure 5 Common Wall Mounting Installations ... 11
Figure 6 Electric Heat Clearance ...................... 12
Figure 7 Start Up Label ................................... 17
Figure 8
Fan Blade Setting .............................. 18
Figure 9 Control Disassembly ........................... 21
Figure 10 Winding Test ...................................... 21
Figure 11 Drip Loop .......................................... 21
Figure 12 H***S4 Wiring Diagram – Top ............. 24
Figure 13
H***S4 Wiring Diagram – Bottom ........ 25
Figure 14 H***S4 Low Voltage Ladder Diagram
for Unit and MV Connections ............... 26
3
Start Up ................................................................... 14
General Topping Off System Charge Safety Practices Important Installer Note Service Hints Sequence of Operation High and Low Pressure Switch Compressor Control Module Motor Start Device Pressure Service Ports Crankcase Heaters
Service
Compressor Solenoid Fan Blade Setting Dimensions
............................................................. 14
................................. 14
................................................. 14
...................................... 14
..................................................... 14
........................................ 15
............................. 15
................................. 15
.............................................. 16
........................................ 16
.............................................. 16
..................................................................... 18
.......................................... 18
............................. 18
Removal of Fan Shroud ....................................... 18
R-410A Refrigerant Charge ................................. 19
Troubleshooting GE ECM
TM
Motors ....................... 20
Optional Accessories ........................................... 21
Tables
Table 1 Electric Heat ....................................... 4
Table 2 Dimensions of Basic Unit ...................... 5
Table 3 Electrical Specifications ....................... 6
Table 4
Sequence of Operation ....................... 15
Table 5 Fan Blade Dimensions ........................ 18
Table 6 Cooling Pressure ................................ 19
Table 7 Indoor Blower Performance ................. 22
Table 8
Optional Accessories Table 9 Optional Accessories
RH Units .......... 22
LH Units .............22
Manual 2100-646 Page 2 of 26
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code
Standard for the Installation of Air Conditioning and Ventilating
Systems .......................................... ANSI/NFPA 90A
Standard for Warm Air Heating and Air Conditioning Systems
Load Calculation for Residential
inter and Summer
W Air Conditioning
Low Pressure, Low Velocity Duct System Design for
inter and Summer
W Air Conditioning
..............ACCA Manual J or Manual N
............. ACCA Manual D or Manual Q
...................... ANSI/NFPA 70
............ANSI/NFPA 90B
For more information, contact these publishers:
ACCA
Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
11 West Street, 13th Floor
Manual 2100-646 Page 3 of 26
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
HA 4S 4 K A 05 B P X X X J
MODEL NUMBER
HA – Right Hand HL – Left Hand
CAPACITY
4S – 4 Ton 5S – 5 Ton
REVISION
K – Accumulator
VOLTS & PHASE
A – 230/208-1
– No KW
0Z w/Circuit Breaker
or Pull Disconnect 05 – 5 KW 08 – 8 KW 10
– 10 KW
15 – 15 KW
KW
VENTILATION OPTIONS
B – Blank-Off Plate
(No Ventilation)
Y – 100% Economizer
(Temperature)
Z – 100% Economizer
(Enthalpy)
FILTER OPTIONS
P – 2" Pleated MERV 8
CONTROL MODULES
J – Only
COIL OPTIONS
X – Standard 1
Phenolic Coated Evaporator 2
Phenolic Coated
OUTLET OPTIONS
X – Front (Standard)
COLOR OPTIONS
X – Beige (Standard) 4 – Buckeye Gray 5 – Desert Brown 8 – Dark Bronze A – Aluminum S – Stainless Steel
Condenser 3
Phenolic Coated Evaporator and Condenser
TABLE 1
Electric Heat Table
Nominal
KW
5.0 5.0 20.8 17,065 3.75 18.0 12,799
8.0 8.0 33.3 27,304 6.00 28.8 20,478
10.0 10.0 41.7 34,130 7.50 36.1 25,598
15.0 15.0 62.5 51,195 11.25 54.1 38,396
These electric heaters are available in 230/208V units only.
Kw 1-Ph Amps Btuh Kw 1-Ph Amps Btuh
At 240V At 208V
See Table 3 for heater availability by model
Manual 2100-646 Page 4 of 26
TABLE 2
1
Not used when EWM Economizer is installed. Filter access through the EWM hood
MIS-3761
Electrical
Entrances
Optional
Side Wall Mounting
Brackets
(Built In)
Location
Shipping
Return Air Opening
Supply Air Opening
Top Rain
Flashing
Bottom Installation Bracket
Back View
M
L
O
E
R
S1
S1
S1
S2
S2
T
.44
N
Q
P
B
Low Voltage
Electrical Entrance
High Voltage
Electrical Entrance
Economizer Intake Hood
4° Pitch
(Lockable)
Rain Hood
Built In
Air
Inlet
Access
Panel
Cond.
Heater
Electric
Heat
C. Breaker/ Disconnect
Access Panel
Drain
Side View
C H
K
J
I
D
2.13
A
Vent Option Door
1
1
Condenser
Filter Access Panel
Air Outlet
Ventilation Air
Front View
F
G
W
5.75
Condenser
Air Outlet
I
A
C
K
2.13
H
J
N
Q
P
M
L
O
E
.44
W
5.88
F
G
R
S
S
S
S
S
T
D
B
1
High Voltage
Drain
Economizer
Inlet
Front View
Side View
1
Electrical
Cond.
Air
Back View
Door
Bottom
Installation
Bracket
Side Wall Mounting Brackets
Flashing Shipping Location
Optional Electrical Entrances
Panel
Air
Ventilation
Electrical Entrance
MIS-3762
Intake Hood
Entrance
(Built In)
Top Rain
Low Voltage
Filter Access Panel
Access Panel (Lockable)
Vent Option
Disconnect
Electric Heat
Heater Access
Return Air Opening
1
Rain Hood 4° Pitch
1
Supply Air Opening
C. Breaker/
Built In
Economizer Controls Opposite Side
1
Not used when EWM economizer is installed. Filter access through the EWM hood.
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
WidthWDepthDHeight
Unit
HA4S4 HL4S4
42.075 22.432 94.875 9.88 29.88 15.88 29.88 43.88 19.10 41.66 30.00 42.68 36.94 44.69 42.43 3.37 43.00 33.88 10.00 1.44 16.00 21.00 1.88
HA5S4 HL5S4
All dimensions in inches. Dimensional drawings are not to scale.
Supply Return
H
E F G I J K L M N O P Q R S1 S2 TA B C B
FIGURE 1
Unit Dimensions
HA*S4 RIGHT UNIT
HL*S4 LEFT UNIT
Manual 2100-646 Page 5 of 26
Wire
Ground
10
10
10
10
10
10
10
10
Field
Power
Wire Size
Maximum
or Ckt. Brkr.
External Fuse
Circuit
Ampacity
Minimum
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
TABLE 3
Wire
Ground
Electrical Specifications
Field
Power
Wire Size
10
8
30
45
26
37
8
101010
88643
6
8
60
45
52
37
8
101010
88663
10
8
30
50
26
44
8
6
8
60
50
52
44
8
Single Circuit Multiple Circuit
Maximum
or Ckt. Brkr.
External Fuse
Circuit
Ampacity
Minimum
Power
Circuits
No. Field
Volts
Rated
and Phase
Model
4545607090
3838536389
111
1 or 2
1 or 2
230/208-1
- A05
- A08
- A10
HA/L4S4 - A0Z
- A15
5050607090
4444536389
111
HA/L5S4 - A0Z
Manual 2100-646 Page 6 of 26
1 or 2
1 or 2
230/208-1
- A05
- A08
- A10
- A15
CAUTION: When more than one filed power conductor circuit is run through one conduit, the conductors must be derated.
conductor sizing.
Pay special attention to Note * of Table 310 regarding Ampacity Adjustment Factors when more than three conductors are in a raceway.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest version), Article 310 for power
Based on 75°C copper wire. All wiring must conform to the National Electric Code (NEC) and all local codes.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
DUCT WORK
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 7 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of 1" of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
A 1/4" clearance to combustible material for the first 3' of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 4 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
!
CAUTION
Some installations may not require any return air duct. A return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8".
Any grille that meets the 5/8" louver criteria, may be used. It is recommended that Bard Return Air Grille Kit RG-5 or RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE:
If no return air duct is used, applicable
installation codes may limit this cabinet to installation only in a single story structure.
FILTERS
A 2" pleated MERV 8 filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-646 Page 7 of 26
INSTALLATION
WALL MOUNTING INFORMATION
1. Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3.
On wood-frame walls, the wall construction must
2. be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. See Figures 4 and 5.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation.
2.
The unit itself is suitable for 0 clearance, but the
supply air duct flange and the first 3’ of supply air duct require a minimum of 1/4” clearance to combustible material. If a combustible wall, use a minimum of 30-1/2” x 10-1/2” dimensions for sizing. However, it is generally recommended that a 1” clearance is used for ease of installation and maintaining the required clearance to combustible material. The supply air opening would then be 32” x 12”. See
Figures 2, 3 and 6 for details.
3. Locate and mark lag bolt locations and bottom mounting bracket location (see Figure 4).
Mount bottom mounting bracket.
4.
5. Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.
6.
Position unit in opening and secure with 5/16"
lag bolts; use 7/8" diameter flat washers on the lag bolts.
Secure rain flashing to wall and caulk across
7. entire length of top (see Figure 2).
8.
For additional mounting rigidity, the return air
and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20" clearance on right side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
TYPICAL INSTALLATIONS
See Figure 5 for common ways to install the wall mount unit.
!
WARNING
Failure to provide the 1/4" clearance between the supply duct and a combustible
surface for the rst 3' of duct can result in re causing damage, injury or death.
Clearances Required for Service Access and Adequate Condenser Airflow
MODELS
HA4S4, HL4S4 HA5S4, HL5S4
NOTE: For side-by-side installation of two H**S4 models, there
must be 20" between units. This can be reduced to 15" by using a HL*S4 model (left side compressor and con­trols) for the left unit and HA*S4 (right side compressor and controls) for right unit.
See H**S4 Specification S3458.
LEFT SIDE
20" 20" 10”
RIGHT
SIDE
DISCHARGE
SIDE
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75ºC copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
Manual 2100-646 Page 8 of 26
Loading...
+ 18 hidden pages