Table 9 Vent and Control Options ...................... 22
Manual 2100-585C
Page 2 of 22
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ....................... ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ....................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
FOR MORE INFORMATION, CONTACT
THESE PUBLISHERS:
ACCAAir Conditioning Contractors of America1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370
Fax: (202) 234-4721
ANSIAmerican National Standards Institute11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
NFPANational Fire Protection AssociationBatterymarch Park
P.O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555
Fax: (617) 984-7057
Manual 2100-585C
Page 3 of 22
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
H 42 A 2 – A 05 Y P X X X J
MODEL SERIES
CAPACITY
24 - 2 Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
A - Right Hand Air Conditioner
L - Left Hand Air Conditioner
VENTILATION OPTIONS
B - Blank-off Plate (No Ventilation)
Y - 100% Economizer Temperature
Z - 100% Economizer Enthalpy
REVISIONS
KW
VOLTS & PHASE
A - 230/208/60/1
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
CONTROL MODULES
(See Spec. Sheet)
COIL OPTIONS
COLOR OPTIONS
X - Beige (Standard)
1 - White
4 - Buckeye Gray
5 - Desert Brown
6 - Dark Bronze
A - Aluminum
S - Stainless Steel
FILTER OPTIONS
P - 2 inch Pleated MERV 8
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator
and Condenser
OUTLET OPTIONS
X - Front (Standard)
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any
national and/or local codes in any way. Authorities
having jurisdiction should be consulted before the
installation is made. See Page 3 for information on
codes and standards.
Size of unit for a proposed installation should be based
on heat loss calculation made according to methods
of Air Conditioning Contractors of America (ACCA).
The air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
Manual 2100-585C
Page 4 of 22
DUCT WORK
FILTERS
All duct work, supply and return, must be properly
sized for the design airow requirement of the
equipment. Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing. All duct
work or portions thereof not in the conditioned space
should be properly insulated in order to both conserve
energy and prevent condensation or moisture damage.
Refer to Table 5 for maximum static pressure available
for duct design.
Design the duct work according to methods given by
the Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect
the duct work to the equipment in order to keep the
noise transmission to a minimum.
For the H model series 36-60, a 1/4 inch clearance
to combustible material for the rst three feet of duct
attached to the outlet air frame is required. See Wall
Mounting Instructions and Figures 2A-C and Figure 3
for further details.
Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.
A 2-inch pleated MERV 8 is standard with each
unit. The lter slides into position making it easy to
service. This lter can be serviced from the outside by
removing the lter access panel.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at
the top of the unit down to the unit base. There are
openings in the unit base for the drain hose to pass
through. In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.
Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct. The spacing between
louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria
may be used. It is recommended that Bard Return Air
Grille Kit RG2W thru RG5W or RFG2W thru RFG5W
be installed when no return duct is used. Contact
distributor or factory for ordering information. If using
a return air lter grille, lters must be of sufcient size
to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable
installation codes may limit this cabinet to
installation only in a single story structure.
Manual 2100-585C
Page 5 of 22
INSTALLATION
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings
must be cut through the wall as shown in Figure 2.
2. On wood frame walls, the wall construction must be
strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected
to insure that they are capable of carrying the
weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets
which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket, attached
to skid for shipping, is provided for ease of
installation, but is not required.
2. The unit itself is suitable for 0 inch clearance,
but the supply air duct ange and the rst 3 feet
of supply air duct require a minimum of 1/4 inch
clearance to combustible material for model series
H36,
H42, H48 and H60
. However, it is generally
recommended that a 1-inch clearance is used for
ease of installation and maintaining the required
clearance to combustible material. See Figures
2A-C for details on opening sizes.
Minimum Clearances Required to
Combustible Materials
MODELS
H24A, H24L0"0"
H36A, H36L1/4"0"
H42A, H42L
H48A, H48L
H60A, H60L
SUPPLY AIR DUCT
FIRST THREE FEET
1/4"0"
CABINET
WARNING
Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the rst 3 feet of duct can result in
re causing damage, injury or death.
Clearances Required for Service Access
and Adequate Condenser Airow
LEFT
MODELS
H24A, H36A15"20"10'
H24L, H36L20"15"10'
H42A, H48A, H60A20"20"10'
H42L, H48L, H60L20"20"10'
NOTE: For side by side installation of two (2) H**A models there
must be 20" between units. This can be reduced to 15" by using
a H**L model (left side compressor and controls) for the left unit
and H**A (right side compressor and controls) for right unit.
RIGHT
SIDE
3. Locate and mark lag bolt locations and bottom
mounting bracket location. See Figure 2.
4. Mount bottom mounting bracket.
5. Hook top rain ashing, attached to front - right of
supply ange for shipping, under back bend of top.
6. Position unit in opening and secure with 5/16 lag
bolts; use 7/8 inch diameter at washers on the lag
bolts.
7. Secure rain ashing to wall and caulk across entire
length of top. See Figure 2.
8. For additional mounting rigidity, the return air
and supply air frames or collars can be drilled
and screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum
of 20 inches clearance on right side to allow access
to control panel and heat strips, and to allow proper
airow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
10.
Care should be taken to ensure that the recirculation
and obstruction of condenser discharge air does not
occur. Recirculation of condenser discharge air
can be from either a single unit or multiple units.
Any object such as shrubbery, a building or other
large object can cause obstructions to the condenser
discharge air. Recirculation or reduced airow caused
by obstructions will result in reduced capacity,
possible unit pressure safety lockouts and reduced
unit service life.
SIDE
DISCHARGE
SIDE
Manual 2100-585C
Page 6 of 22
For units with blow through condensers, it is
recommended there be a minimum distance of 10'
between the front of the unit and any barrier or 20'
between the fronts of two opposing (facing) units.
FIGURE 1
Dimensions of Basic Unit for Architectural & Installation Requirements (Nominal)