Bard H42A2-A, H48A2-A, H60A2-A, H42L2-A, H48L2-A Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
WALL MOUNTED PACKAGED
AIR CONDITIONERS
Models:
H42A2-A H48A2-A H60A2-A
H42L2-A H48L2-A H60L2-A
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Page 1 of 19
CONTENTS
Getting Other Information and Publications 3
Wall Mount General Information
Wall Mount Model Nomenclature Shipping Damage
General ................................................................4
Duct Work ................................................................ 5
Filters ................................................................ 5
Condensate Drain
Installation Instructions
Wall Mounting Information Mounting the Unit Clearances Required Minimum Clearances Wiring – Main Power Wiring – Low Voltage Wiring Dirty Filter Switch & Relay Economizer Fail Time Delay Relay
..................................................... 4
.................................................... 5
...................................................... 6
................................................ 6
................................................ 6
............................................... 12
.............................. 4
........................................ 6
................................... 12
...................................... 12
......................... 12
Start Up
General ..............................................................13
Topping Off System Charge Safety Practices Important Installer Note High Pressure Switch Condenser Fan Operation Service Hints Sequence of Operation Compressor Control Module Adjustments Pressure Service Ports
Troubleshooting
Fan Blade Setting Dimensions Refrigerant Charge Removal of Fan Shroud
...................................................... 13
........................................................... 14
............................................................ 14
................................................. 15
.................................... 13
........................................... 13
.............................................. 13
...................................... 14
........................................... 14
................................... 14
........................................... 14
................................ 15
.......................................... 15
Figures
Figure 1 Unit Dimensions ...................................... 7
Figure 2 Mounting Instructions - H42, 48, 60 ........ 8
Figure 3 Electric Heat Clearance .......................... 9
Figure 4 Wall Mounting Instructions .................... 10
Figure 5 Wall Mounting Instructions .................... 10
Figure 6 Common Wall Mounting Installations .... 11
Figure 7 Fan Blade Setting ................................. 15
Tables
Table 1 Fan Blade Dimensions .......................... 15
Table 2 Cooling Pressure .................................. 16
Table 3 Electrical Specications H**A, H**L ......17
Table 4 Recommended Airow .......................... 18
Table 5 Indoor Blower Performance .................. 18
Table 6 Electric Heat .......................................... 18
Table 7 Optional Accessories ............................ 19
Table 8 Vent & Control Options .........................19
Manual 2100-585B Page 2 of 19
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help you install the air
conditioner or heat pump. You can usually nd these
at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ....................... ANSI/NFPA 70
Standard for the Installation ............... ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ....................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-585B Page 3 of 19
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
H 42 A 2 – A 05 Y P X X X J
MODEL NUMBER
CAPACITY
42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton
A - Right Hand Air Conditioner L - Left Hand Air Conditioner
VENTILATION OPTIONS
B - Blank-off Plate (No Ventilation) Y - 100% Economizer Temperature Z - 100% Economizer Enthalpy
REVISIONS
KW
VOLTS & PHASE
A - 230/208/60/1
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
CONTROL MODULES
(See Spec. Sheet)
COIL OPTIONS
COLOR OPTIONS
X - Beige (Standard) 1 - White 4 - Buckeye Gray 5 - Desert Brown 6 - Dark Bronze A - Aluminum S - Stainless Steel
FILTER OPTIONS
P - 2 inch Pleated MERV 8
X - Standard 1 - Phenolic Coated Evaporator 2 - Phenolic Coated Condenser 3 - Phenolic Coated Evaporator and Condenser
OUTLET OPTIONS
X - Front (Standard)
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-585B Page 4 of 19
DUCT WORK
FILTERS
All duct work, supply and return, must be properly
sized for the design airow requirement of the
equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 5 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
For model series H42, H48 and H60 a 1/4 inch
clearance to combustible material for the rst three feet
of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 2 and 3 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
A 2-inch pleated MERV 8 is standard with each
unit. The lter slides into position making it easy to service. This lter can be serviced from the outside by removing the lter access panel.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG5 or RFG5 be installed when no return duct is used. Contact distributor or factory for ordering
information. If using a return air lter grille, lters must be of sufcient size to allow a maximum velocity
of 400 fpm.
NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure.
Manual 2100-585B Page 5 of 19
INSTALLATION INSTRUCTIONS
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 2.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
WARNING
Failure to provide the 1/4 inch clearance between the supply duct and a combustible
surface for the rst 3 feet of duct can result in re causing damage, injury or death.
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 inch clearance,
but the supply air duct ange and the rst 3 feet
of supply air duct require a minimum of 1/4 inch clearance to combustible material for model series H42, H48 and H60
. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 2 for details on opening sizes.
3. Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 2.
4. Mount bottom mounting bracket.
5. Hook top rain ashing, attached to front - right of supply ange for shipping, under back bend of top.
6. Position unit in opening and secure with 5/16 lag
bolts; use 7/8 inch diameter at washers on the lag
bolts.
7. Secure rain ashing to wall and caulk across entire
length of top. See Figure 2.
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips, and to allow proper
airow to the outdoor coil. Additional clearance
may be required to meet local or national codes.
10.
Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or other large object can cause obstructions to the condenser
discharge air. Recirculation or reduced airow caused
by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
For units with blow through condensers, it is
recommended there be a minimum distance of 10' between the front of the unit and any barrier or 20' between the fronts of two opposing (facing) units.
Clearances Required for Service Access
and Adequate Condenser Airow
MODELS LEFT SIDE RIGHT SIDE
H42A, H48A, H60A 20" 20"
H42L, H48L, H60L 20" 20"
NOTE: For side by side installation of two (2) H**A models there
must be 20" between units. This can be reduced to 15" by using
a H**L model (left side compressor and controls) for the left unit
and HA (right side compressor and controls) for right unit.
Manual 2100-585B Page 6 of 19
Minimum Clearances Required to Combustible Materials
MODELS
H42A, L / H48A, L H60A, L
SUPPLY AIR DUCT
FIRST THREE FEET
1/4" 0"
CABINET
Loading...
+ 13 hidden pages