Bard H24AA-A, H42AA-A, H48AA-A, H60AA-A, H36AA-A Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
WALL-MOUNTED PACKAGED
AIR CONDITIONER
Models:
H24AA-A H36AA-A H42AA-A H48AA-A H60AA-A
H24LA-A H36LA-A H42LA-A H48LA-A H60LA-A
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-647 Supersedes: NEW Date: 9-3-15
Page 1 of 28
Page 2
CONTENTS
Getting Other Information and Publications .... 3
Wall Mount General Information .........................4
Air Conditioner Wall Mount Model Nomenclature ....... 4
Shipping Damage ................................................... 4
General .................................................................. 4
Duct Work .............................................................. 5
Filters .................................................................... 5
Condensate Drain .................................................. 5
Installation ............................................................... 6
Wall Mounting Information ...................................... 6
Mounting the Unit .................................................. 6
Minimum Clearances .............................................. 6
Clearances Required ............................................... 6
Wiring – Main Power ............................................. 13
Wiring – Low Voltage Wiring ................................... 14
Dirty Filter Switch and Relay .................................. 14
Economizer Fail Time Delay Relay .......................... 14
Start Up ................................................................... 15
General ................................................................ 15
Topping Off System Charge .................................... 15
Safety Practices.................................................... 15
Important Installer Note ........................................ 15
High Pressure and Low Pressure Switches ............... 16
Condenser Fan Operation ...................................... 16
Service Hints........................................................ 16
Sequence of Operation .......................................... 16
Compressor Control Module ................................... 16
Pressure Service Ports ........................................... 17
Service ..................................................................... 18
Fan Blade Setting Dimensions ............................... 18
Removal of Fan Shroud ......................................... 18
R410A Refrigerant Charge ..................................... 18
Figures
Figure 1 Unit Dimensions .................................. 7
Figure 2A H24 Mounting Instructions ................... 8
Figure 2B H36 Mounting Instructions ................... 9
Figure 2C H42, 48, 60 Mounting Instructions ..... 10
Figure 3 Electric Heat Clearance ...................... 11
Figure 4 Wall Mounting Instructions ................. 12
Figure 5 Wall Mounting Instructions ................. 12
Figure 6 Common Wall Mounting Installations ... 13
Figure 7 Fan Blade Setting .............................. 18
Figure 8A H***A Wiring Diagram – Top ............... 26
Figure 8B H***A Wiring Diagram – Bottom .......... 27
Figure 9 H***A Low Voltage Diagram for Unit
and MV Connections ........................... 28
Tables
Table 1 Sequence of Operation ....................... 17
Table 2 Fan Blade Dimension ......................... 18
Table 3 Cooling Pressure ................................ 19
Table 4A Electrical Specifications H**A Series ... 20 Table 4B Electrical Specifications H**L Series ... 20
Table 5 Recommended Airflow ........................ 21
Table 6 Indoor Blower Performance ................. 21
Table 7 Max ESP of Operation Elec Heat Only .. 21
Table 8 Electric Heat ..................................... 21
Table 9 Optional Accessories .......................... 22
Table 10 Vent and Control Options .................... 22
Table 11 Unit Low Voltage Terminal Connection
Chart – MV Series Controller ............... 23
Table 12 Unit Low Voltage Terminal Connection
Chart – MC Series Controller ............... 24
Table 13 Unit Low Voltage Terminal Connection
Chart – Cooling/Heating Thermostat ..... 25
Manual 2100-647 Page 2 of 28
Page 3
GETTING OTHER INFORMATION AND PUBLICATIONS
These publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation ..............ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air .......................ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J
Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-647 Page 3 of 28
Page 4
WALL MOUNT GENERAL INFORMATION
AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE
H 42 A 4 – A 05 Y P X X X J
MODEL SERIES
CAPACITY
24 – 2 Ton 36 – 3 Ton 42 – 3½ Ton 48 – 4 Ton 60 – 5 Ton
A – Right Hand Air Conditioner L – Left Hand Air Conditioner
!
WARNING
REVISIONS
VOLTS & PHASE
A – 230/208/60/1
VENTILATION OPTIONS
B – Blank-Off Plate (No Ventilation) Y – 100% Economizer Temperature Z – 100% Economizer Enthalpy
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
KW
CONTROL MODULES
(See Spec. Sheet)
COIL OPTIONS
COLOR OPTIONS
X – Beige (Standard) 1 – White 4 – Buckeye Gray 5 – Desert Brown 6 – Dark Bronze A – Aluminum S – Stainless Steel
FILTER OPTIONS
P – 2 inch Pleated MERV 8
!
CAUTION
X – Standard 1 – Phenolic Coated Evaporator 2 – Phenolic Coated Condenser 3 – Phenolic Coated Evaporator and Condenser
OUTLET OPTIONS
X – Front (Standard)
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
Manual 2100-647 Page 4 of 28
Page 5
DUCT WORK
FILTERS
All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage.
Refer to Table 5 for maximum static pressure available for duct design.
Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum.
For the H Model Series 36-60, a 1/4" clearance to combustible material for the first 3' of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 2A-C and Figure 3 for further details.
Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
A 2" pleated MERV 8 is standard with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the filter access panel.
CONDENSATE DRAIN
A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8".
Any grille that meets with 5/8" louver criteria may be used. It is recommended that Bard Return Air Grille Kit RG2W thru RG5W or RFG2W thru RFG5W be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm.
NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure.
Manual 2100-647 Page 5 of 28
Page 6
INSTALLATION
WALL MOUNTING INFORMATION
1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 2.
2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
MOUNTING THE UNIT
1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0 clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material for Model Series H36, H42, H48 and H60. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures 2A-C for details on opening sizes.
Clearances Required for Service Access and Adequate Condenser Airflow
LEFT
MODELS
H24A, H36A 15" 20" 10'
H24L, H36L 20" 15" 10'
H42A, H48A, H60A 20" 20" 10'
H42L, H48L, H60L 20" 20" 10'
NOTE: For side-by-side installation of two H**A models there
must be 20" between units. This can be reduced to 15" by using a H**L model (left side compressor and controls) for the left unit and H**A (right side compressor and controls) for right unit.
SIDE
RIGHT
SIDE
3. Locate and mark lag bolt locations and bottom mounting bracket location (see Figure 2).
4. Mount bottom mounting bracket.
5. Hook top rain flashing, attached to front-right corner of supply flange for shipping, under back bend of top.
Position unit in opening and secure with fasteners
6. sufficient for the application such as 5/16 lag bolts; use 7/8" diameter flat washers on the lag bolts.
7. Secure rain flashing to wall and caulk across entire length of top (see Figure 2).
DISCHARGE
SIDE
Minimum Clearances Required to Combustible Materials
MODELS
H24A, H24L 0" 0"
H36A, H36L 1/4" 0"
H42A, H42L H48A, H48L H60A, H60L
!
WARNING
Failure to provide the 1/4" clearance between the supply duct and a combustible
surface for the rst 3' of duct can result in re causing damage, injury or death.
SUPPLY AIR DUCT
FIRST 3'
1/4" 0"
CABINET
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. On side-by-side installations, maintain a minimum of 20" clearance on right side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.
10. Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or other large object can cause obstructions to the condenser discharge air. Recirculation or reduced airflow caused by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
For units with blow through condensers, it is
recommended there be a minimum distance of 10' between the front of the unit and any barrier or 20' between the fronts of two opposing (facing) units.
Manual 2100-647 Page 6 of 28
Page 7
H60A, L
FIGURE 1
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
WIDTH
DEPTH
MODEL
H24A, L 33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00 9.00
H36A, L 38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 4.19 12.00 9.00
H42A, L H48A, L
H60A, L 42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
(W)
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
HEIGHT
(D)
All dimensions are in inches. Dimensional drawings are not to scale.
SUPPLY RETURN
(H)
A B C B E F G I J K L M N O P Q R S T
H**A RIGHT UNIT
5.88
Built In
Rain Hood
W
Filter Access Panel
F
G
Ventilation Air
Condenser
Economizer
1
Standard flush vent door for non-Econ. models
Air Outlet
4° Pitch
C. Breaker/ Disconnect
Access Panel
(Lockable)
Economizer Air Intake Hood
Controls
7"
Low Voltage
High Voltage
Heater
Access
Panel
Electric
Heat
Electrical Entrance
Electrical Entrance
Front View
D
Cond.
Air
Inlet
Side View
J
Drain
2.13 Side Wall
A
Mounting
Brackets
(Built In)
I
Top Rain
Flashing Shipping Location
Optional
C
H
Electrical
Entrances
K
L
M
P
N
Q
Not used when EWM economizer is installed. Filter access is through the EWM hood.
Electric Heat
Heater Access Panel
C. Breaker/ Disconnect Access Panel (Lockable)
Standard flush
vent door for
non-Econ.
models
Economizer Air Intake Hood
Economizer controls (opposite side)
Low Voltage Electrical Entrance
High Voltage Electrical Entrance
7"
H**L LEFT UNIT
R
S
S
S
S
S
T
Drain
.44
Supply Air Opening
Return Air Opening
Bottom
Installation
Bracket
E O
B
Back View
Built In Rain Hood 4° Pitch
Side Wall Mounting Brackets (Built In)
Top Rain
Flashing
Shipping
Location
Optional Electrical Entrances
P
Q
2.13
A
I
C
H
K
L
M
N
J
D
Cond.
Air
Inlet
Not used when EWM economizer is installed. Filter access is through the EWM hood.
E O
Supply Air Opening
B
Return Air Opening
Back View
W
Filter Access Panel
Ventilation Air
Condenser
Air Outlet
Front ViewSide View
.44
Bottom Installation Bracket
MIS-3624
1
5.88
MIS-3625
R
S
S
S
S
S
T
F
G
Manual 2100-647 Page 7 of 28
Page 8
12"
12"
12"
12"
12"
20"
20"
1"
3"
4"
Typ.
8"
20
1
2
"
12"
1"
3
1
8
"
4"
Typ.
5"
7
8
"
3
13
16
"
2" 2"
7
1
16
" 7
1
16
"
NOTES:
RAIN FLASHING
RETURN AIR
HEATER ACCESS
ENTIRE LENGTH OF TOP.
TOP
WALL
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
WALL STRUCTURE
OPENING
TOP FLASHING AT TIME OF INSTALLATION.
THE SIDE MOUNTING FLANGES AND UNDER
DUCT
Wall Opening and Hole Location View Right Side View
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
SUPPLY AIR
SUPPLIED
Return Opening
Supply Opening
H**A UNIT SHOWN, H**L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
MIS-3658
FIGURE 2A
H24AA, H24LA Mounting Instructions
Manual 2100-647 Page 8 of 28
Page 9
28"
A
C
D
C
12"
12"
12"
12"
12"
5
1
16
"
B
E
14"
4
11
16
" 4
11
16
"
4"
Typ.
2
7
8
"
7
8
"
7
8
"
4"
Typ.
7
8
"
3
1
8
"
SUPPLIED
H*A UNIT SHOWN, H*L UNIT
MIS-3659
SUPPLY AIR
ENTIRE LENGTH OF TOP.
TOP
OF CAULKING ALONG
PANEL
FOAM AIR SEAL
WALL STRUCTURE
RAIN FLASHING
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
MATERIALS
NOTES:
1/4" CLEARANCE ON ALL
HEATER ACCESS
TOP FLASHING AT TIME OF INSTALLATION.
THE SIDE MOUNTING FLANGES AND UNDER
SILICONE CAULKING BE PLACED BEHIND
IS ON OPPOSITE (LEFT) SIDE.
OPENING
CONTROLS AND HEATER ACCESS
DUCT
RETURN AIR
Right Side View
SEAL WITH BEAD
IT IS RECOMMENDED THAT A BEAD OF
WALL
Wall Opening and Hole Location View
Return Opening
16 7/84 7/164 5/89 7/829 7/8
17 5/83 11/165 3/88 3/8
28 3/8
EDCBA
COMBUSTIBLE MATERIALS
RECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
COMBUSTIBLE MATERIALS
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
Supply Opening
FIGURE 2B
H36AA, H36LA Mounting Instructions
Manual 2100-647 Page 9 of 28
Page 10
D
16"
16"
16"
16"
16"
1
7
8
"
6
1
2
" 6
1
2
"
2
1
8
"
7
8
"
1"
3"
4"
Typ.
4"
Typ.
6
1
2
"
30"
E
16"
A CC
3
1
8
"
B
Wall Opening and Hole Location View
RETURN AIR
1
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
29
DUCT
COMBUSTIBLE MATERIALS
A B C DE
30 1/2
10 1/2
6 1/4 1 1/4 29 3/4
32 12 5 1/2
2
NOTES:
WALL STRUCTURE
1
SUPPLY AIR
IT IS RECOMMENDED THAT A BEAD OF
OPENING
Right Side View
RAIN FLASHING
SILICONE CAULKING BE PLACED BEHIND
RECOMMENDED 1" CLEARANCE FROM
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
TOP.
PANEL
HEATER ACCESS
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL
1/4" CLEARANCE ON ALL
MATERIALS
Supply Opening
FOAM AIR SEAL
SUPPLIED
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
1
Return Opening
MIS-416 E
Dimension is 21" on 95" tall units.
2
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
3
FIGURE 2C
Manual 2100-647 Page 10 of 28
H42AA, H42LA, H48AA, H48LA, H60AA, H60LA Mounting Instructions
"
"
Page 11
FIGURE 3
Electric Heat Clearance
NOTE: SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES.
!
WARNING
A minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the
rst 3' of ducting.
It is important to insure that the 1/4" minimum spacing is
maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a re causing damage, injury or death.
Manual 2100-647 Page 11 of 28
Page 12
FIGURE 4
DUCT
OPENING
RETURN AIR
SUPPLY AIR
WOOD FRAME WALL INSTALLATION
OPENING
WALL BEFORE
MOUNT ON UNIT
OPENING
BEFORE INSTALLATION
BOTTOM MOUNTING
CONCRETE BLOCK WALL INSTALLATION
BRACKET. MOUNT ON
OPENING
WOOD OR STEEL SIDING
OPENING
INSTALLING UNIT.
RETURN AIR
WALL STRUCTURE
RETURN AIR
SUPPLY AIR
FACTORY SUPPLIED
RAIN FLASHING.
SUPPLY AIR
MIS-548 A
SIDE VIEW
I
A
C
K
E + 1.000
B
1.000
SUPPLY DUCT
OVER FRAME
INTERIOR FINISHED WALL
ALL AROUND DUCT
FRAMING MATERIAL
EXTERIOR FINISH WALL
OPENING
FOR ACTUAL DIMENSIONS.
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
ATTACH TO TOP
1.000" CLEARANCE
1.000" CLEARANCE
PLATE OF WALL
C
SEE UNIT DIMENSIONS, FIGURE 2,
OPENING
RETURN DUCT
2 x 6
ATTACH TO BOTTOM
OVER FRAME
PLATE OF WALL
L
THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.
MIS-549 B
ALL AROUND DUCT
Wall Mounting Instructions
FIGURE 5
Wall Mounting Instructions
Manual 2100-647 Page 12 of 28
Page 13
FIGURE 6
Common Wall Mounting Installations
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
OR BELOW CEILING RAFTERS AS SHOWN
RAIN
FLASHING
OUTSI DE
WALL
RAFTERS
FINISHED CEI LI NG SURFACE
SUPPLY AIR DUCT W/ GRILLE
RETURN AI R OPENI NG W/ GRILLE
FREE AIR FLOW
NO DUCT
WIRING – MAIN POWER
Refer to the unit rating plate for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
RAIN
FLASHING
SUPPLY AIR DUCT
OUTSI DE
WALL
RAFTERS
FINISHED CEI LI NG SURFACE
RETURN AI R OPENI NG W/ GRILLE
DUCTED SUPPLY RETURN AT UNIT
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.
See “Start Up” section beginning on page 15 for important information on three phase scroll compressor start ups.
See Tables 4A and 4B (page 20) for electrical specifications.
Manual 2100-647 Page 13 of 28
Page 14
WIRING – LOW VOLTAGE WIRING
Low Voltage Connection
These units use a 24-volt AC low voltage circuit. Tables 11 – 13 on pages 23 – 25 show the low voltage connections for units operated with the MV Series controller, MC Series controller or connected directly to a cooling/heating thermostat.
All models are equipped with dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:
TAP RANGE 240 253 – 216 208 220 – 187
NOTE: The voltage should be measured at the field
power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).
DIRTY FILTER SWITCH AND RELAY
These units include an adjustable dirty filter indicator switch. This switch if connected to normally closed contacts on the filter relay wired to terminals 10 and 11 on the low voltage terminal block.
Filter Replacement Procedure
Filter Switch Adjustment
1. Turn off unit power.
2. Remove upper front door. Front screws on unit top can be removed for ease of removing upper front door.
3. Locate filter switch on control panel side next to blower assembly.
4. Remove single phillips head screw on front of cover. Remove cover.
5. Set pressure by adjusting knob. Do not adjust knob drastically to avoid nuisance alarm signalw or non-functionality.
6. Replace cover.
7. Replace upper front door.
8. Turn on unit power.
ECONOMIZER FAIL TIME DELAY RELAY
NOTE: Applies only to units with economizers.
These units employ a time delay relay to open the nomally closed contacts at terminals 12 and 13 on the low voltage terminal block. This will activate an alarm signal on the MV Series controller. The time delay is set to 500 seconds as a factory default. Avoid adjustment to settings lower than 180 seconds.
For units not equipped with economizer:
1. Turn off unit power.
2. Remove filter door.
3. Replace filter.
4. Press Reset button.
5. Verify filter light is off.
6. Replace filter door.
7. Turn on unit power.
For units equipped with economizer:
1. Turn off unit power.
2. Remove hood cover.
3. Remove mist eliminator. Inspect and clean if necessary.
4. Remove filter door.
5. Remove and replace filter.
6. Replace filter door.
7. Replace mist eliminator.
8. Replace hood cover.
Timer to be set here
(500 seconds)
MIS-3054
9. Turn on unit power.
Manual 2100-647 Page 14 of 28
Page 15
START UP
THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL.
GENERAL
1. Use separate service equipment to avoid cross
contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800
psi/250 psi low).
4.
R-410A is a binary blend of HFC-32 and HFC-125.
5. R-410A is nearly azeotropic—similar to R-22 and
R-12. Although nearly azeotropic, charge with liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming potential.
8. R-410A compressors use Polyol Ester oil.
9. Polyol Ester oil is hygroscopic; it will rapidly absorb
moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used; even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with small amount of nitrogen when inserting plugs.
TOPPING OFF SYSTEM CHARGE
If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating (see criteria above) and charging to the nameplate charge. If done correctly, topping off the system charge can be done without problems.
With R-410A, there are no significant changes in the refrigerant composition during multiple leaks and recharges. R-410A refrigerant is close to being an azeotropic blend (it behaves like a pure compound or single component refrigerant). The remaining refrigerant charge in the system may be used after leaks have occurred and then “top-off” the charge by utilizing the pressure charts on the inner control panel cover as a guideline.
REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction.
!
WARNING
Failure to conform to these practices could
lead to damage, injury or death.
SAFETY PRACTICES
1. Never mix R-410A with other refrigerants.
2. Alwasys use gloves and safety glasses. Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin.
3. Never use air and R-410A to leak check; the mixture may become flammable.
4. Do not inhale R-410A; the vapor attacks the nervous system, creating dizziness, loss of coordination and slurred speech. Cardiac irregularities, unconsciousness and ultimate death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly at warmer temperatures. Once a cylinder or line is full of liquid, any further rise in temperature will cause it to burst.
IMPORTANT INSTALLER NOTE
For improved start up performance wash the indoor coil with dishwashing detergent.
Manual 2100-647 Page 15 of 28
Page 16
HIGH PRESSURE AND LOW PRESSURE SWITCHES
All H**A/H**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switches. The first time the high or low pressure switches are tripped, they will reset automatically. If tripped a second time, reset the switches by turning the thermostat off, then back on again, resetting the compressor control module.
CONDENSER FAN OPERATION
NOTE: Certain models may be equipped with a low ambient control (LAC), and if so equipped the condenser fan motor may have a delayed start until system refrigerant operating pressure builds up. After starting, the fan motor may or may not cycle depending upon ambient conditions. This is normal operation. The condenser fan motor on 230/208
volt, one and three phase, 60 HZ units is a two-speed motor that comes factory wired on high speed for peak performance. If ambient conditions permit, it can be reconnected to low speed (red wire) for lower sound level. See unit wiring diagram.
SERVICE HINTS
1. Caution owner/operator to maintain clean air filters at all times and to not needlessly close off supply and return air registers. This reduces airflow through the system, which shortens equipment service life as well as increasing operating costs.
2. Check all power fuses or circuit breakers to be sure they are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential.
SEQUENCE OF OPERATION
COOLING – 24VAC from MV controller at terminal 4 (Y) pulls in compressor contactor, starting the compressor and outdoor motor. (See Note under Condenser Fan Operation if equipped with low ambient control.) Terminal 9 (G) indoor motor circuit is energized by the MV controller on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a call for heating from the MV controller makes at the relay board pulling in heat contact for the strip heat and blower operation. On a call for second stage heat, R-W2 makes bringing on second heat contactor, if so equipped. See Table 1 on following page.
COMPRESSOR CONTROL MODULE
The compressor control module (CCM) is standard on all models covered by this manual. The compressor
control module is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.
Adjustable Delay-on-Make and Delay-on-Break Timer
On initial power up and any time power is interrupted to the unit, the delay-on-make period begins, which is the time set on the potentiometer (delay-on-break time) plus 10% of the delay-on-break setting. When the delay-on-make period is complete and the high pressure switch and low pressure switch are closed, the compressor contactor is energized. Upon shutdown (end of the call for cooling), the delay-on-break timer starts and prevents restart (next call for cooling) until the delay-on-break period has expired.
During routine operation of the unit with no power interruptions, the compressor will operate on demand with no delay.
High Pressure Switch and Lockout Sequence
If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay-on­break time has expired. If the high pressure switch opens again in this same operating cycle, the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat or main power resets the manual lockout.
Low Pressure Switch, Bypass and Lockout Sequence
If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will re-energize after the delay-on-make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds, the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat or main power resets the manual lockout.
Alarm Relay Output
Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever the compressor is locked out due to HPC or LPC sequences as described.
NOTE: Both high and low pressure switch controls are
inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner unit model. The lockout features, both soft and manual, are a function of the compressor control module.
Manual 2100-647 Page 16 of 28
Page 17
Adjustments
Typical Settings for Dual Unit Installation:
Adjustable Delay-on-Make and Delay-on-Break Timer
The potentiometer is used to select delay-on-break time from 30 seconds to 5 minutes. Delay-on-make (DOM) timing on power up and after power interruptions is equal to 2 minutes plus 10% of delay-on-break (DOB) setting:
0.5 minute (30 seconds) DOB = 123 second DOM
1.0 minute (60 seconds) DOB = 126 second DOM
2.0 minute (120 seconds) DOB = 132 second DOM
Unit 1: DOB set at 2 minutes and DOM is 132 seconds Unit 2: DOB set at 4 minutes and DOM is 144 seconds
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found on page 19 covering all models. It is imperative to match the correct pressure table to the unit by model number.
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM
During routine operation of the unit with no power interruptions, the compressor will operate on demand with no delay.
TABLE 1
Sequence of Operation
Terminal Description Use
1 Compressor on Output Signal from Jade to MV Economizer Only "A"
2 24VAC HOT from Terminal 2 Connected to Unit Transformer 24V HOT "R"
3 24VAC COMMON from Unit Transformer to MV 24V COMMON "C"
4 Unit Compressor Operation Cooling Operation "Y"
5 Close Damper Input (Close Blade 100%) Economizer Only "F"
6 Electric Heat On Operation, Stage 1 and 2 Heating Operation "W1"
7 1st Stage Cooling Input, 1st Stage Cooling Signal to Jade Economizer Only "Y1"
8 2nd Stage Cooling Input, 2nd Stage Cooling Signal to Jade Economizer Only "Y2"
9 Blower Operation (Indoor Blower On) Blower Operation "G"
10 Filter Switch Normally Closed Dry Contacts Alarm Signal "4"
11 Filter Switch Normally Closed Dry Contacts Alarm Signal "5"
12 Blade Switch Delay Relay Normally Closed Dry Contacts Economizer Only "8"
13 Blade Switch Delay Relay Normally Closed Dry Contacts Economizer Only "9"
14 Occupied Signal Input, Econ Emergency Open (Open Blade 100%) Economizer Only "E"
15 Econ Open Output (6V HOT, 24V HOT after Blade Open 100% and delay) Economizer Only "10"
16 Alarm Relay Common Dry Contact Comp Alarm Signal "3"
17 Alarm Relay Normally Open Dry Contact Comp Alarm Signal "2"
18 Alarm Relay Normally Closed Dry Contact Comp Alarm Signal "1"
24VAC HOT to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
19
Wire*
20 2nd Stage Heating On Operated Through Jumper to Terminal 6
Blade Switch Terminal 24V HOT When Blade is Open, Sends Signal from Switch
21
to Delay Relay
* Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also
be removed to break 24VAC power to unit.
24V HOT "RT"
Heating Operation,
2nd Stage
Economizer Only "7"
Series "2" Reference
"W2'
Manual 2100-647 Page 17 of 28
Page 18
SERVICE
FAN BLADE SETTING DIMENSIONS
The correct fan blade setting for proper air delivery across the outdoor coil is shown in Figure 7. Refer to Table 2 for unit specific dimension.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 7
Fan Blade Setting
AIRFLOW
"A"
MIS-1724
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3. Remove nine (9) screws holding fan shroud to condenser and bottom.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade and shroud assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall
.
R-410A REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.
The pressure table on the following page shows nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
TABLE 2
Fan Blade Dimension
Model
H24 1.00"
H36 1.25"
H42 H48 H60
Dimension
1.75"
A
Manual 2100-647 Page 18 of 28
Page 19
TABLE 3
Cooling Pressure
Air Temperature Entering Outdoor Coil °F
Model
H24A/L
H36A/L
H42A/L
H48A/L
H60A/L
Return Air Temp
(DB/WB)
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
75/62
80/67
85/72
Pressure 75 80 85 90 95 100 105 110 115 120 125
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
123 314
132 322
137 333
117 323
125 331
129 343
123 323
132 331
137 343
120 330
128 338
132 350
127 344
136 353
141 365
124 334
133 343
138 355
120 346
128 355
132 367
125 346
134 355
139 367
122 353
131 362
136 375
129 362
138 371
143 384
126 355
135 364
140 377
122 370
130 379
135 392
128 371
137 380
142 393
125 377
134 387
139 401
131 380
140 390
145 404
128 377
137 387
142 401
124 394
133 404
138 418
130 395
139 405
144 419
127 402
136 412
141 426
134 401
143 411
148 425
129 401
138 411
143 425
127 419
136 430
141 445
132 421
141 432
146 447
130 428
139 439
144 454
136 421
145 432
150 447
131 425
140 436
145 451
129 446
138 457
143 473
135 447
144 458
149 474
132 454
141 466
146 482
137 444
147 455
152 471
133 451
142 463
147 479
131 473
140 485
145 502
137 474
146 486
151 503
134 482
143 494
148 511
140 467
150 479
155 496
135 479
144 491
149 508
134 500
143 513
148 531
138 501
148 514
153 532
136 510
145 523
150 541
142 492
152 505
157 523
137 507
146 520
151 538
136 528
145 542
150 561
140 528
150 542
155 561
137 540
147 554
152 573
145 518
155 531
160 550
139 536
149 550
154 569
137 558
147 572
152 592
142 558
152 572
157 592
139 570
149 585
154 605
148 545
158 559
164 579
141 567
151 582
156 602
138 587
148 602
153 623
144 587
154 602
159 623
141 601
151 616
156 638
151 573
161 588
167 609
Low side pressure ± 4 PSIG High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated,
check condenser fan wiring. See “Condenser Fan Operation”.
Manual 2100-647 Page 19 of 28
Page 20
TABLE 4A
Electrical Specifications H***A Series
Single Circuit Multiple Circuit
Rated
MODEL
H24AA-A00, A0Z
H36AA-A00*, A0Z*
H42AA-A00, A0Z
H48AA-A00, A0Z
H60AA-A00, A0Z
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
* Top outlet supply option is available only factory installed and only on the selected models.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical
A04 A05
230/208-1 A08 A10
A05*
A08
230/208-1
A10*
A15
A05 A10
230/208-1 A15 A20
A05 A10
230/208-1 A15 A20
A05 A10
230/208-1 A15 A20
Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
Code and all local codes.
Volts &
Phase
No. Field
Power
Circuits
1 1 1 1 1 1 1 1 1
1 or 2
1 1
1 1 or 2 1 or 2
1
1
1 1 or 2 1 or 2
1
1
1 1 or 2 1 or 2
Minimum
Circuit
Ampacity
21 25 30 46 56 29 32 47 58 84 32 32 58 84
110
34 34 58 84
110
38 38 60 86
112
Maximum
External
Fuse or
Ckt. Brkr.
30 30 30 50 60 35 35 50 60 90 50 50 60 90
125
50 50 60 90
125
60 60 60 90
125
Field
Power
Wire Size
10 10 10
8 6 8 8 8 6 4 8 8 6 4 2 8 8 6 4 2 8 8 6 3 2
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
10 10 10 10 10 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10
86585826
10 10 10
86585826
10 10 10
86606026
52
52
52
606030
606030
606030
60
60
60
6610
6610
6610
6
6
6
101010
101010
101010
10
10
10
TABLE 4B
Electrical Specifications H***L Series
Single Circuit Dual Circuit
Rated
MODEL
H24LA-A00, A0Z
H36LA-A00, A0Z
H42LA-A00, A0Z
H48LA-A00, A0Z
H60LA-A00, A0Z
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
* Top outlet supply option is available only factory installed and only on the selected models.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to Note 8 of Table 310 regarding Ampacity
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical
A05
230/208-1
A08 A10
A05
230/208-1
A10 A15
A05
230/208-1
A10 A15
A05
230/208-1
A10 A15
A05
230/208-1
A10 A15
Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
Code and all local codes.
Volts &
Phase
No. Field
Power
Circuits
1 1 1 1 1 1 1
1 or 2
1 1 1
1 or 2
1 1 1
1 or 2
1 1 1
1 or 2
Minimum
Circuit
Ampacity
21 30 46 56 29 32 58 84 32 32 58 84 34 34 58 84 38 38 60 86
Maximum
External
Fuse or Ckt.
Brkr.
30 30 50 60 35 35 60 90 50 50 60 90 50 50 60 90 60 60 60 90
Field
Power
Wire Size
10 10
8 6 8 8 6 4 8 8 6 4 8 8 6 4 8 8 6 3
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breake
Field Power
Wire S
Ground
Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
10 10 10 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10
8 58 26 60 30 6 10 10 10 10 10 10
8 60 26 60 30 6 10 10 10
Manual 2100-647 Page 20 of 28
Page 21
TABLE 5
Recommended Airflow
Model
H24A, H24L 800 .30 700 - 950 Single
H36A, H36L 1100 .30 1000 - 1300 High
H42A, H42L 1350 .40 1250 - 1600 Low
H48A, H48L 1550 .35 1450 - 1750 High
H60A, H60L 1800 .30 1700 - 2000 High
* Rated CFM and ESP on factory speed connection.
Speed
ESP
(Inch H20)
0.0
0.1 960 925
0.2 905 870
0.3 835 800
0.4 750 720
0.5 640 610 970 895 705 680
H24 H36 H42 H48 H60
Single High Low High Low High Low High Low
Dry
Wet
Dry
Wet
Coil
1010
Coil
975
Coil
1400 1310
1340 1260
1265 1185
1180 1100
1080 1010
Coil
Dry
Coil
965 955
940 930
905 890
860 850
800 785
Nominal
Rated
CFM *
Nominal
Rated
ESP *
Recommended
TABLE 6
Indoor Blower Performance
Wet
Dry
Wet
Coil
Coil
1980 1940 1800 1705 2000 1940 1750 1700 2105 2010 1540 1460
1905 1880 1700 1640 1910 1865 1675 1615 2045 1960 1480 1395
1820 1760 1615 1565 1820 1770 1600 1540 1970 1885 1400 1315
1735 1665 1530 1450 1720 1605 1500 1425 1895 1800 1300 1220
1615 1565 1425 1350 1575 1500 1375 1320 1800 1700 1220 1150
1510 1380 1100 1000 1420 1190 1075 1030 1705 1605 1110 1070
Coil
Dry
Coil
Airflow Range
Wet Coil
Dry
Coil
Factory Speed
Connection
Wet
Dry
Coil
Coil
Wet Coil
Dry
Coil
Wet Coil
Dry
Coil
Wet Coil
TABLE 7
Maximum ESP of Operation
Electric Heat Only
Model H24A/L H36A/L H42A/L, H48A/L H60A/L
Outlet FRONT FRONT TOP FRONT FRONT
Speed Single High Low High Low High Low High Low
-A0Z
-A04
-A05
-A08
-A10
-A15
-A20
.50
.50 .50
.50
.50 .50 .50 .40
.50
.50 .50 .45 .35
.50 .50
.50
.50 .45
.35
.50
.50
.50 .50 .50
.50
.50
.50 .50 .45
.50
.50
.50 .50 .50
.50
.50
.50 .50 .40
TABLE 8
Electric Heat
Models
(KW)
4 16.7 13650 14.4 10240
5 20.8 17065 18.1 12800
8 33.3 27300 28.8 20475
10 41.6 34130 36.2 25600
15 62.5 51250 54.0 38400
20 83.2 68260 72.1 51200
240V-1 208V-1
Amps BTUH Amps BTUH
Manual 2100-647 Page 21 of 28
Page 22
Right Hand Units
Heater Kits
Circuit Breakers
(WMCB)
&
Pull Disconnects
(WMPD)
TABLE 9
Optional Accessories
A-A
A-A
A-A
A
A
H36
H24
EHWA02-A05B X
EHW02A-A08B X
EHWA02A-A10B X
EHWA24-A04B X
EHWA03-A05B X
EHWA03-A08B X
EHWA03-A10B X
EHWA03-A15B X
EHW4TA-A05 X X
EHWA05-A10B X X X
EHWA05-A15B X X X
EHWA05-A20B X X X
EHW5TA-A05 X
WMCB-03A X
WMCB-05A X
WMCB-08A X X
WMCB-09A X
A
H42
A-A A
H48
A-A A
H60
Left Hand Units
Heater Kits
Circuit Breakers
(WMCB)
&
Pull Disconnects
(WMPD)
A-A
A-A
A-A
L
L
H36
H24
EHWA02A-A05LB X
EHW02A-A08LB X
EHWA02-A10LB X
EHWA03-A05LB X
EHWA03-A10LB X
EHWA03-A15LB X
EHW4TA-A05L X X X
EHWA05-A10LB X X X
EHWA05-A15LB X X X
WMCB-03A X
WMCB-05A X
WMCB-08A X X
WMCB-09A X
L
H42
A-A L
H48
A-A L
H60
TABLE 10
Vent and Control Options
Part Number Description
CMC-14 ODT X X X
CMC-15 Start Kit (230V 1-Phase) X X X
CMC-23 DDC X X
CMC-24 DDC X
CMC-28 LAC X X X
BOP-2 Blank Off Plate X
EWM2-E EWM2-T
Economizer - Bldg. Equipment, Enthalpy Economizer - Bldg. Equipment, DB Temp.
BOP-3 Blank Off Plate X
EWM3-E EWM3-T
Economizer - Bldg. Equipment, Enthalpy Economizer - Bldg. Equipment, DB Temp.
BOP-5 Blank Off Plate X
EWM5-E EWM5-T
Economizer - Bldg. Equipment, Enthalpy Economizer - Bldg. Equipment, DB Temp.
H24
X X
X X
H36
H42
X X
H48
H60
Manual 2100-647 Page 22 of 28
Page 23
TABLE 11
Unit Low Voltage Terminal Connection Chart – MV Series Controller
Terminal Description MV Terminal Connection
1 Compressor on Output Signal from Jade to MV "A" on Relay Board "A"
2 24VAC HOT from Terminal 2 Connected to Unit Transformer to MV "R" on Relay Board "R"
3 24VAC COMMON from Unit Transformer to MV "C" on Relay Board "C"
Unit Compressor Operation, Unit Receives Signal from MV for Compressor/
4
Condenser Fan On
5 Close Damper Input (Close Blade 100%), Unit Receives Signal from MV "F" on Relay Board "F"
6 Electric Heat On Operation, Stage 1 and 2, Unit Receives Signal from MV "W" on Relay Board "W1"
7 1st Stage Cooling Input, 1st Stage Cooling Signal to Jade from MV "Y1" on Relay Board "Y1"
8 2nd Stage Cooling Input, 2nd Stage Cooling Signal to Jade from MV "Y2" on Relay Board "Y2"
9 Blower Operation (Indoor Blower On), Unit Receives Signal from MV "G" on Relay Board "G"
10 Filter Switch Normally Closed Dry Contacts, MV Signals Dirty Filter Alarm "4" on Relay Board "4"
11 Filter Switch Normally Closed Dry Contacts, MV Signals Dirty Filter Alarm "5" on Relay Board "5"
Blade Switch Delay Relay Normally Closed Dry Contacts, MV Signals Blade
12
Switch Fail Alarm*
Blade Switch Delay Relay Normally Closed Dry Contacts, MV Signals Blade
13
Switch Fail Alarm*
Occupied Signal Input, Econ Emergency Open (Open Blade 100%), Unit
14
Receives Signal from MV
Econ Open Output (6V HOT, 24V HOT after Blade Open 100% and Delay), Sends
15
Signal to MV
Alarm Relay Common Dry Contact, MV Signals Compressor Fail Alarm "LOCKOUT 3" on Alarm
16
Alarm Relay Normally Open Dry Contact, MV Signals Compressor Fail Alarm "LOCKOUT 2" on Alarm
17
18 Alarm Relay Normally Closed Dry Contact Not Used on MV "1"
24VAC HOT to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
19
Wire**
20 2nd Stage Heating On Operated Through Jumper to Terminal 6 Not Used on MV "W2'
Blade Switch Terminal 24V HOT When Blade is Open, Sends Signal from Switch
21
to Delay Relay
"Y" on Relay Board
"8" on Relay Board
"9" on Relay Board
"ECONE" on Alarm Board
"DAMPER" on Comm Board
Board
Board
Building Smoke Alarm
(optional)
Not Used on MV "7"
Series "2" Reference
"Y"
"8"
"9"
"E"
"10"
"3"
"2"
"RT"
* Blade switch delay relay fail alarm set to 500 second delay from factory. ** Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also
be removed to break 24VAC power to unit.
Manual 2100-647 Page 23 of 28
Page 24
TABLE 12
Unit Low Voltage Terminal Connection Chart – MC Series Controller
Terminal Description MC Terminal Connection
1 Compressor on Output Signal from Jade to MC "A" on Relay Board "A"
2 24VAC HOT from Terminal 2 Connected to Unit Transformer to MC "R" on Relay Board "R"
3 24VAC COMMON from Unit Transformer to MC "C" on Relay Board "C"
Unit Compressor Operation, Unit Receives Signal from MC for Compressor/
4
Condenser Fan On
5 Close Damper Input (Close Blade 100%), Unit Receives Signal from MC* "F" on Relay Board "F"
6 Electric Heat On Operation, Stage 1 and 2, Unit Receives Signal from MC "W" on Relay Board "W1"
7 1st Stage Cooling Input, 1st Stage Cooling Signal to Jade from MC "Y1" on Relay Board "Y1"
8 2nd Stage Cooling Input, 2nd Stage Cooling Signal to Jade from MC "Y2" on Relay Board "Y2"
9 Blower Operation (Indoor Blower On), Unit Receives Signal from MC "G" on Relay Board "G"
10 Filter Switch Normally Closed Dry Contacts Not Used on MC "4"
11 Filter Switch Normally Closed Dry Contacts Not Used on MC "5"
12 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used on MC "8"
13 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used on MC "9"
Occupied Signal Input, Econ Emergency Open (Open Blade 100%), Unit
14
Receives Signal from MC
15 Econ Open Output (6V HOT, 24V HOT after Blade Open 100% and Delay) Not Used on MC "10"
Alarm Relay Common Dry Contact, MC Signals Compressor Fail Alarm "LOCKOUT 3" on Alarm
16
Alarm Relay Normally Open Dry Contact, MC Signals Compressor Fail Alarm "LOCKOUT 2" on Alarm
17
18 Alarm Relay Normally Closed Dry Contact Not Used on MC "1"
24VAC HOT to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
19
Wire**
20 2nd Stage Heating On Operated Through Jumper to Terminal 6 Not Used on MC "W2'
Blade Switch Terminal 24V HOT When Blade is Open, Sends Signal from Switch
21
to Delay Relay
* Requires signal from "R" on MC controller to "F" on MC controller. ** Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also
be removed to break 24VAC power to unit.
"Y" on Relay Board "Y"
"E" on Alarm Board "E"
Board
Board
Building Smoke Alarm
(optional)
Not Used on MC "7"
Series "2"
Reference
"3"
"2"
"RT"
Manual 2100-647 Page 24 of 28
Page 25
TABLE 13
Unit Low Voltage Terminal Connection Chart – Cooling/Heating Thermostat
Terminal Description MC Terminal Connection
1 Compressor on Output Signal from Jade Not Used "A"
2 24VAC HOT from Terminal 2 Connected to Unit Transformer to Thermostat "R" on Tstat "R"
3 24VAC COMMON from Unit Transformer to Thermostat "C" on Tstat "C"
Unit Compressor Operation, Unit Receives Signal from MC for Compressor/
4
Condenser Fan On
5 Close Damper Input (Close Blade 100%) Not Used "F"
6 Electric Heat On Operation, Stage 1 and 2, Unit Receives Signal from Thermostat "W" on Tstat "W1"
7 1st Stage Cooling Input, 1st Stage Cooling Signal – Economizer Use Only Economizer 24V Signal "Y1"
8 2nd Stage Cooling Input, 2nd Stage Cooling Signal – Economizer Use Only Economizer 24V Signal "Y2"
9 Blower Operation (Indoor Blower On), Unit Receives Signal from Thermostat "G" on Tstat "G"
10 Filter Switch Normally Closed Dry Contacts Not Used "4"
11 Filter Switch Normally Closed Dry Contacts Not Used "5"
12 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used "8"
13 Blade Switch Delay Relay Normally Closed Dry Contacts Not Used "9"
14 Occupied Signal Input, Econ Emergency Open (Open Blade 100%) Not Used "E"
15 Econ Open Output (6V HOT, 24V HOT after Blade Open 100% and Delay) Not Used "10"
16 Alarm Relay Common Dry Contact Not Used "3"
17 Alarm Relay Normally Open Dry Contact Not Used "2"
18 Alarm Relay Normally Closed Dry Contact Not Used "1"
24VAC HOT to Terminal 2 from Unit Transformer Through Smoke Alarm Jumper
19
Wire*
20 2nd Stage Heating On Operated Through Jumper to Terminal 6 Not Used "W2'
Blade Switch Terminal 24V HOT When Blade is Open, Sends Signal from Switch
21
to Delay Relay
"Y" on Tstat "Y"
Building Smoke Alarm
(optional)
Not Used "7"
Series "2" Reference
"RT"
* Replace jumper wire with smoke alarm connections to interrupt 24VAC unit power if smoke alarm is used in shelter. Jumper can also
be removed to break 24VAC power to unit.
Manual 2100-647 Page 25 of 28
Page 26
FIGURE 8A
H***A Wiring Diagram – Top
Black
Black/White
31
Compressor
Black/White
C
R
S
Compressor
Crankcase Heater
Outdoor
Fan Motor
MIS-3770
Condenser Section
Black
Brown
27
Yellow
Red
Start Kit (Opt.)
Yellow
C
Yellow
Yellow
Yellow
Dual Can Capacitor
HERM
FAN
"MV CONNECTIONS"
Red/White
Black/White
103
Yellow
104
Blue
106
Brown
Orange
109
110
111
112
113
Blue/Black
Blue/Black
Red/Black
Red/Black
123
Black
116
117
118
119 102
120
121
103
Blue
Red
Red/Blue
Brown
Yellow/Black
2
2
"R" "A"
3
3
"C"
4
4
"Y"
5
5
"F"
6
6
"W1"
7
7
"Y1"
818
"Y2"
9
"G"
10
"4"
11
11 10 9 8
"5"
12
"8"
13
13
"9"
14
14
E
ECON
15
DAMPER
16
LOUT
17 15
LOUT
2 3
18
19
19
20
2021 17 16
21
11
112
1
Low Voltage
Red
Module
Red
Hi Press. Control
Blue
Condenser Section
Field Connections
To MV Controller
Wire Identification numbers
Red/White
"SMOKE JUMPER"
Optional
Field
for Bard use only.
99
Factory
A
Used
122
if Option Not
Wires Connect
Smoke
P6
Low Voltage
High Voltage
Yellow
Red/White
9 8
Black/White
6
Blue/White
Purple
Pink
5 2 1
Jumper
Yellow/Red
7
Brown/White
1012
Green
4
Yellow/White
11
12 Pin Vent
Option Plug
Blue
Low Press. Control
Indoor
Fan Motor
Evaporator Section
Brown
Brown
Capacitor
Indoor Fan
Yellow
Red (Lo)
Black (Hi)
Red
Ground Lug
13
130
Hi Voltage Connections
L2
L1
Orange
Black
31
103
9
COM
Indoor
NC
NO
Red/Black
Filter Reset Button
230/208-60-1
Per Nameplate
Red
Blue
Brown
11
106
Heat Plug
6 Pin Electric
6
5
129
4
3
120
2
1
103
109
Black/White
33
Parking
Terminal
75° C.
WARNING
!
Black
Red
Red
Black
Operation
tap for 208V
130
Red Wire to 208V
8
Transformer
Alarm
COM
NO
116
208V
COM
240V
C
R
119
31
9
Relay
Black/White
NC
117
118
DANGER
!
USE COPPER CONDUCTORS
ONLY SUITABLE FOR AT LEAST
136
131
103
111
SERVICING.
*DISCONNECT POWER BEFORE
*ELECTRICAL SHOCK HAZARD
Black
Black
136
L2
L1
Ground
T2
T1
Contactor
Compressor
103
7
Black/White
Eyelet
Yellow/Red
Black
Black
Low Ambient Control (opt.)
12
(Opt.)
Block #2
Terminal
29
30
Pink
103
Black/White
A
B
Blower Relay
Orange/Black
128
Blk/Wht
113
32
110
Filter
Relay
7
1 3
9
6 4
132
124
Red/White
112
T1
T2
COM
103
500
23
Time
Delay
Relay
Red/White
132
Light
Orange/Black
132
Filter Switch
128
104
CCALRC
NCNO
HPCRY
2
LPC
MINUTES
10
Black/White
133
Blue
Blue
Red/White
135
135
Manual 2100-647 Page 26 of 28
Page 27
FIGURE 8B
H***A Wiring Diagram – Bottom
COMPRESSOR OUTPUT
24V COMMON INPUT
24V HOT INPUT
1ST STAGE COOLING INPUT
CLOSE DAMPER INPUT
OCCUPIED SIGNAL INPUT
2ND STAGE COOLING INPUT
ECON OPEN OUTPUT
GROUND
ECON FAILURE OUTPUT
NC
BLUE/WHITE
CONTACT POSITION
Yellow
Blue/White
Yellow/Red
Yellow/White
3
DAMPER BLADE IN
THE CLOSED POSITION
IS SHOWN WITH THE
13
2
1
YELLOW/WHITE
DAMPER MOTOR
BL. SWITCH
1
FEMALE
RED
12 PIN PLUG
1
MALE
12 PIN PLUG
BLACK
3
8
NO
COM
ORANGE/BLACK
4
7
3
BROWN
4
BROWN
Red/White
Purple
Brown/White
OUTSIDE AIR
TEMPERATURE
BLACK11RED
982
SENSOR
12
Black/White
Pink
Green
46
SENSOR
MIXED AIR
TEMPERATURE
24V HOT INPUT
9
12 PIN PLUG
12 PIN PLUG
11
FEMALE
7
MALE
1ST STAGE COOLING INPUT
2ND STAGE COOLING INPUT
COMPRESSOR OUTPUT
24V COMMON INPUT
ECON FAILURE OUTPUT
CLOSE DAMPER INPUT
OCCUPIED SIGNAL INPUT
GROUND
ORANGE
ORANGE
6
5
1
12
ECON OPEN OUTPUT
7
4
10
2ND STAGE COOLING OUTPUT (not used)
6
823
5
MIS-3710
YELLOW/WHITE
THIS WIRE IS PART OF
BLACK
YELLOW/RED
GREEN
OCC
OAT +
BROWN/WHITE
4
3
2
1
EXH1
E-GND
AUX1-O
S-BUS
S-BUS
OAT -
BLUE
YELLOW/WHITE
6
5
AUX2-I
12 PIN PLUG MALE 7
ORANGE
ORANGE
MAT +
MAT -
1
23465
PLUG PLUG
PLUG
PLUG
PINK
Y2-I
IAQ +
1
ORANGE
Y2-O
IAQ -
2
PURPLE
456
Y1-I
IAQ24V
3
RED
YELLOW
ECONOMIZER CONTROL PANEL
123
3
C
R
Y1-O
BLACK
RED
RED/BLACK
NO
48
RELAY
MODULE
COM
ACT 24V
ACT -
ACT +
654
ECONOMIZER CONTROL
NC
RED
BLACK
BROWN
BROWN
BLUE/WHITE
ORANGE/BLACK
connect to "S-BUS" terminals.
For Enthalpy version, these wires
Temperature econ. version shown.
Manual 2100-647 Page 27 of 28
Page 28
Low Voltage
Terminal Strip
3
2
10
11
6
20
9
16
17
18
12
13
21
4
19
1
5
7
Hot
Common
8
14
15
Filter Light
Filter
Switch
Filter Reset Button
R on
Compressor
Control Module
Filter
Relay
Pin 6 on Heater Plug
Pin 3 on Heater Plug
Pin 1 on Heater Plug
Blower Relay
Alarm Relay
Transformer 24VAC
Hi Press. Sw.
Pin 8 on Vent Plug
Pin 1 on Vent Plug
Pin 2 on Vent Plug
Pin 5 on Vent Plug
Pin 7 on Vent Plug
Pin 10 on Vent Plug
Time Delay Relay
T1T2
Y HPC
Lo Press. Sw.
LPC
LPC
Alarm Relay
ALR
CC
Comp. Control Module
R
MV
Controller
C
4
5
W
G
L3
L2
8
9
Y
A
F
Y1
Y2
EE
DR
Pin 6 on Vent Plug
Pin 9 on Vent Plug
Pin 12 on V. Plug
Compressor
Contactor
COMNC
5
42
1 3
5
4
1 3
Low Voltage
Ladder Diagram
for Unit and MV
Connections
Blk/Wht
Red/Wht
Blue/Blk
Blue/Blk
Blue
Brown
Orange
Black
Red
Blue
Red/Blk
Red/Blk
Yel/Blk
Red/Blue
Yellow
Yellow
Blue/Wht
Purple
Pink
Yel/Red
Brown/Wht
Blk/Wht
Blk/Wht
Org/Blk
Red/Wht
Org/Blk
Pink
Bk/Wh
BlueBlue
RedRed
Rd/W Bk/W
MIS-3712
FIGURE 9
H***A Low Voltage Ladder Diagram for Unit and MV Connections
Manual 2100-647 Page 28 of 28
Loading...