Figure 6Replacement Parts ............................ 11
Manual 2100-517
Page2 of 11
COPYRIGHT FEBRUARY 2009
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO USA 43506
Page 3
GENERAL
The pump module kit should only be installed by trained
technicians. These instructions serve as a guide to the
technician installing the pump module kit. They are not
intended as a step-by-step procedure with which the
mechanically inclined owner can install the unit.
DESCRIPTION
The system is designed to heat domestic water using heat
recovered from a water source unit’s hot discharge gas.
LOCATION
There are two options for the mounting location of the
GVDM-26 Domestic Hot Water Desuperheater Module.
First, there are pre-punched mounting holes for it on the
side of the geothermal heat pump beneath the filter rack.
Factory supplied in the kit are interconnect tubes that
connect the pump module to the water source unit (See
Figure 1).
The second is to locate the GVDM-26 on a wall adjacent
to the geothermal unit or storage tank/water heater. (See
Figures 3 and 4.)
Because of potential damage from freezing or
condensation, the unit must be located in a conditioned
space, therefore the GVDM-26 must be installed indoors.
Locate the storage tank as close to the geothermal heat
pump and pump module as the installation permits.
Keep in mind that water lines should be a maximum of
25 feet long measured one way. Also, the vertical lift
should not exceed 20 feet. This is to keep pressure and
heat losses to a minimum.
ELECTRICAL CONNECTION
The GVDM-26 is equipped with a standard 115V 3-prong
plug. The unit is rated at .9 amps and can normally be
plugged into any convenient electrical outlet.
NOTE: Make sure outlet is grounded, and that the
circuit will handle the added load. If any
concerns in this regard you should run a
separate grounded circuit to the main panel.
INSTALLATION PROCEDURE – GENERAL
Before beginning the installation, turn off all power
supplies to the water heater and unit, and shut off the
main water supply line.
TWO TANK – In order to realize the maximum energy
savings from the heat recovery system, it is
recommended that a second water storage tank be
installed in addition to the main hot water heater. Fossil
fuel fired water heaters must be a two-tank installation.
Tanks specifically intended for hot water storage are
available from water heater manufacturers (solar hot
water storage tanks). A well insulated electric water
heater without the electric heating elements will also
make a suitable storage tank.
The size of storage tank should be as large as space and
economy permit but in no event should it be less than
one-half of the daily water requirements for the
occupants. As a guide in estimating the daily family
water requirements, The Department of Energy
recommends a figure of 16.07 gallons of hot water per
day per individual. For example, a family of four would
require 64.3 gallons per day (4 x 16.07).
ONE TANK – The single hot water tank may be a new
hot water heater (sized to 100% of daily water
requirements) or the existing water heater in the case of a
retrofit installation. The existing water heater should be
drained and flushed to remove all loose sediment. This
sediment could damage the circulating pump. The
bottom heating element should be disconnected.
NOTE: Make sure water heater thermostats are set
below 125° on One Tank Unit.
WATER PIPING – All water piping must adhere to all
state and local codes. Refer to piping diagrams for
recommended one and two tank installations. Piping
connections are 1/2 inch nominal copper plumbing.
A cleanable “Y” type strainer should also be included to
collect any sediment.
SOLDERING TUBING
NOTE: The “inlet” and “outlet” thermistors should be
removed from the tubes prior to soldering/
brazing operation so they are not damaged.
They are clipped onto the “DSH COIL INLET”
and from “DSH OUTLET” tubes of the GVDM26 Module. Once soldering operations are
complete, and the tubes have cooled, reattach
the sensors and wrap with provided insulation.
WARNING
Never alter or plug factory installed pressure
relief valve on water heater or auxiliary tank.
Manual2100-517
Page3 of 11
Page 4
OPERATION OF THE HEAT RECOVERY UNIT
START UP AND CHECK OUT
The pump module is a very simple device containing
basic controls and a circulating pump. Heat is
transferred from the hot refrigerant (discharge gas) to the
cool water.
The operation of the Desuperheater Pump Module is
controlled first by the operation of the Geothermal Heat
Pump and secondly by internal controls within the Pump
Module. A low voltage signal from Thermostat “Y” is
connected to the internal control board of the GVDM-26
and acts as the primary on/off switch for the circulating
pump.
Also connected to this board is a temperature overlimit
device which shuts down the GVDM-26 once inlet water
has exceeded 125° so the water cannot create a scald
condition.
There are also two (2) thermistor sensors connected to
the control board. These thermistors are measuring and
controlling to ensure there is a positive heat differential
across the water being circulated. When operating in
Part Load Condition, there are certain conditions
(Ground Loop Temperatures versus Hot Water
Temperatures) that potential exists where heat could
transfer from the hot water into the refrigeration system
instead of the refrigeration system into the hot water.
Through the control board logic, these thermistors
ensure there is at least 2° positive differential between
entering/leaving water temperatures and will shut down
the pump accordingly.
Be sure all shut off valves are open and all power
supplies are on. Open a hot water faucet to permit any
air to bleed from the plumbing.
NOTE: The inherent design of this pump for maximum
efficiency means this pump is not self-priming.
It is imperative to check that the air has been
adequately bled from the system. There is a
bleed-port built into the pump module that can
be utilized after the system water has been fully
restored. See Figure 2 for this bleed port
location.
Turn ON the air conditioning system and verify the
circulating pump will operate. Feel the “Water to Unit”
and “Water from Water Heater” tubes for noticeable
difference in temperature. Turn OFF the system and
verify that the circulating pump stops.
NOTE: When checking the refrigerant operating
pressures of the ground source heat pump. The
GVDM-26 must be turned off. With the
GVDM-26 operating a wide variance in
pressures can result, giving the service
technician the indication there is a charge
problem when the unit is operating correctly.
MAINTENANCE
CLEANING THE HEAT EXCHANGER – If scaling of
the coil is strongly suspected, the coil can be cleaned
with a solution of phosphoric acid (food grade acid).
Follow the manufacturer’s directions for the proper
mixing and use of cleaning agent.
Manual 2100-517
Page4 of 11
Page 5
NC
LINE VOLTAGE
WATER SENSORS
TSTAT
3 AMP
FUSE
POWER
PUMP OUTLET
NL
OVER T EMP. LIMIT
OUTLET INLET
Y
RC
24VACLN
CONTROL
LOGIC
NO
C
BLUE
BLUE
THERMISTOR
BLUE
BLUE
THERMISTOR
GREEN
PUMP
4053-113
LOW VOLTAGE
WIRING
PUMP CONTROL
HIGH VOLTAGE
WALL PLUG
RED
FACTORY
DESUPERHEATER
TEMPERATURE
MOTOR
24 VAC
LIMIT
BI-METAL
FIELD
WIRING
WHITE
WHITE
YELLOW
BLACK
BLACK
BLACK
BLACK
BLACK
WIRING DIAGRAM
Manual2100-517
Page5 of 11
Page 6
Figure 1
MOUNTING DIRECTLY ONTO UNIT
FILTER ASSEMBLY
Manual 2100-517
Page6 of 11
DESUPERHEATER
PUMP MODULE
ATTACH TO UNIT
USING PROVIDED
SCREWS
INLET AND OUTLET TUBES
SUPPLIED WITH PUMP MODULE
MIS-2647
Page 7
INLET FROM WATER
HEATER
Figure 2
AIR PURGE PORT
AIR PURGE PORT
NOTE: PUMP IS NOT SELF-PRIMING, IT I S
RECOMMENDED TO MANUALLY BLEED-OFF
AIR.
FROM DSH COIL
OUTLET
INLET THERMISTOR
NOTE: REMOVE DURING TUBE
SOLDERING, THEN RE-INSTALL
AND WRAP WITH PROVIDED
INSULATION.
OUTLET THERMISTOR
NOTE: REMOVE DURING TUBE
SOLDERING, THEN RE-INSTALL
AND WRAP WITH PROVIDED
INSULATION.
NOTE: INSTALLER MUST INSURE THAT THE INLET THERMISTOR
IS RE-LOCATED BACK TO THE INLET TUBE AND THE OUTLET
THERMISTOR IS LOCATED BACK ON THE OUTLET TUBE.
OUT TO WATER HEATER
OUT TO DSH COIL INLET
VERIFY BY CONNECTIONS ON CONTROL BOARD
MIS-2651
Manual2100-517
Page7 of 11
Page 8
Figure 3
REMOTE MOUNTING & PIPING
Manual 2100-517
Page8 of 11
Page 9
Figure 4
SINGLE TANK SYSTEM
Manual2100-517
Page9 of 11
Page 10
CONTROL BOARD SEQUENCE of
OPERATION
The desuperheating control board will make a determination
whether or not to energize the pump relay inclusive on the
control board.
A. It will constantly monitor inputs from two temperature
sensors, Inlet & Outlet water sensors.
B. It will constantly monitor the Y signal.
C. Upon acknowledgment of Y signal, and following two
minutes, the control board will energize the pump relay.
D. After 1½ minutes, based on temperature difference
between Outlet & Inlet sensors, and the presence of Y
signal, the following will take place:
THERMISTOR
TEMPERATURE F vs RESISTANCE R OF TEMPERATURE SENSOR
E. The Over Temperature Limit Switch is placed in series
F. The 3-amp fuse is put in series with the R connection to
Figure 5
1.) If temperature difference is greater than 3°F, then
the control will continue to energize pump relay.
2.) If temperature difference is less than 3°F, then the
control will de-energize the pump relay.
3.) The control will next wait for 10 minutes before
repeating Step #1 (above).
with the line voltage. Therefore, continuity between L
of line voltage and L of pump output is forced broken
when the Over Temperature Limit Switch opens (see
Wiring Diagram).
the board. Whenever the fuse is blown, the control will
lose power and consequently, the relay will disengage.