Bard GVDM-26 User Manual

Page 1
INSTALLATION INSTRUCTIONS
GVDM-26
DOMESTIC HOT WATER DESUPERHEATER
PUMP MODULE KIT
© Copyright 2009
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual No.: 2100-517 Supersedes: NEW File: Volume I, Tab 9 Date: 02-06-09
Manual 2100-517 Page 1 of 11
Page 2
CONTENTS
General ................................................................. 3
Description ............................................................ 3
Location ................................................................. 3
Electrical Connection............................................. 3
Soldering Tubing ................................................... 3
Installation Procedure – General ........................... 3
Operation of the Heat Recovery Unit .................... 4
Start Up and Check Out ........................................ 4
Maintenance .......................................................... 4
Control Board Sequence of Operation ................ 10
WIRING DIAGRAM
............................................................ 5
FIGURES
Figure 1 Mounting Directly onto Unit ................. 6
Figure 2 Air Purge Port ...................................... 7
Figure 3 Remote Mounting & Piping .................. 8
Figure 4 Single Tank System .............................9
Figure 5 Thermistor .........................................10
Figure 6 Replacement Parts ............................ 11
Manual 2100-517 Page 2 of 11
COPYRIGHT FEBRUARY 2009
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO USA 43506
Page 3
GENERAL
The pump module kit should only be installed by trained technicians. These instructions serve as a guide to the technician installing the pump module kit. They are not intended as a step-by-step procedure with which the mechanically inclined owner can install the unit.
DESCRIPTION
The system is designed to heat domestic water using heat recovered from a water source unit’s hot discharge gas.
LOCATION
There are two options for the mounting location of the GVDM-26 Domestic Hot Water Desuperheater Module. First, there are pre-punched mounting holes for it on the side of the geothermal heat pump beneath the filter rack. Factory supplied in the kit are interconnect tubes that connect the pump module to the water source unit (See Figure 1).
The second is to locate the GVDM-26 on a wall adjacent to the geothermal unit or storage tank/water heater. (See Figures 3 and 4.)
Because of potential damage from freezing or condensation, the unit must be located in a conditioned space, therefore the GVDM-26 must be installed indoors.
Locate the storage tank as close to the geothermal heat pump and pump module as the installation permits. Keep in mind that water lines should be a maximum of 25 feet long measured one way. Also, the vertical lift should not exceed 20 feet. This is to keep pressure and heat losses to a minimum.
ELECTRICAL CONNECTION
The GVDM-26 is equipped with a standard 115V 3-prong plug. The unit is rated at .9 amps and can normally be plugged into any convenient electrical outlet.
NOTE: Make sure outlet is grounded, and that the
circuit will handle the added load. If any concerns in this regard you should run a separate grounded circuit to the main panel.
INSTALLATION PROCEDURE – GENERAL
Before beginning the installation, turn off all power supplies to the water heater and unit, and shut off the main water supply line.
TWO TANK – In order to realize the maximum energy savings from the heat recovery system, it is recommended that a second water storage tank be installed in addition to the main hot water heater. Fossil fuel fired water heaters must be a two-tank installation.
Tanks specifically intended for hot water storage are available from water heater manufacturers (solar hot water storage tanks). A well insulated electric water heater without the electric heating elements will also make a suitable storage tank.
The size of storage tank should be as large as space and economy permit but in no event should it be less than one-half of the daily water requirements for the occupants. As a guide in estimating the daily family water requirements, The Department of Energy recommends a figure of 16.07 gallons of hot water per day per individual. For example, a family of four would require 64.3 gallons per day (4 x 16.07).
ONE TANK – The single hot water tank may be a new hot water heater (sized to 100% of daily water requirements) or the existing water heater in the case of a retrofit installation. The existing water heater should be drained and flushed to remove all loose sediment. This sediment could damage the circulating pump. The bottom heating element should be disconnected.
NOTE: Make sure water heater thermostats are set
below 125° on One Tank Unit.
WATER PIPING – All water piping must adhere to all state and local codes. Refer to piping diagrams for recommended one and two tank installations. Piping connections are 1/2 inch nominal copper plumbing.
A cleanable “Y” type strainer should also be included to collect any sediment.
SOLDERING TUBING
NOTE: The “inlet” and “outlet” thermistors should be
removed from the tubes prior to soldering/ brazing operation so they are not damaged. They are clipped onto the “DSH COIL INLET” and from “DSH OUTLET” tubes of the GVDM­26 Module. Once soldering operations are complete, and the tubes have cooled, reattach the sensors and wrap with provided insulation.
WARNING
Never alter or plug factory installed pressure relief valve on water heater or auxiliary tank.
Manual 2100-517 Page 3 of 11
Page 4
OPERATION OF THE HEAT RECOVERY UNIT
START UP AND CHECK OUT
The pump module is a very simple device containing basic controls and a circulating pump. Heat is transferred from the hot refrigerant (discharge gas) to the cool water.
The operation of the Desuperheater Pump Module is controlled first by the operation of the Geothermal Heat Pump and secondly by internal controls within the Pump Module. A low voltage signal from Thermostat “Y” is connected to the internal control board of the GVDM-26 and acts as the primary on/off switch for the circulating pump.
Also connected to this board is a temperature overlimit device which shuts down the GVDM-26 once inlet water has exceeded 125° so the water cannot create a scald condition.
There are also two (2) thermistor sensors connected to the control board. These thermistors are measuring and controlling to ensure there is a positive heat differential across the water being circulated. When operating in Part Load Condition, there are certain conditions (Ground Loop Temperatures versus Hot Water Temperatures) that potential exists where heat could transfer from the hot water into the refrigeration system instead of the refrigeration system into the hot water. Through the control board logic, these thermistors ensure there is at least 2° positive differential between entering/leaving water temperatures and will shut down the pump accordingly.
Be sure all shut off valves are open and all power supplies are on. Open a hot water faucet to permit any air to bleed from the plumbing.
NOTE: The inherent design of this pump for maximum
efficiency means this pump is not self-priming. It is imperative to check that the air has been adequately bled from the system. There is a bleed-port built into the pump module that can be utilized after the system water has been fully restored. See Figure 2 for this bleed port location.
Turn ON the air conditioning system and verify the circulating pump will operate. Feel the “Water to Unit” and “Water from Water Heater” tubes for noticeable difference in temperature. Turn OFF the system and verify that the circulating pump stops.
NOTE: When checking the refrigerant operating
pressures of the ground source heat pump. The GVDM-26 must be turned off. With the GVDM-26 operating a wide variance in pressures can result, giving the service technician the indication there is a charge problem when the unit is operating correctly.
MAINTENANCE
CLEANING THE HEAT EXCHANGER – If scaling of the coil is strongly suspected, the coil can be cleaned with a solution of phosphoric acid (food grade acid). Follow the manufacturer’s directions for the proper mixing and use of cleaning agent.
Manual 2100-517 Page 4 of 11
Page 5
NC
LINE VOLTAGE
WATER SENSORS
TSTAT
3 AMP
FUSE
POWER
PUMP OUTLET
NL
OVER T EMP. LIMIT
OUTLET INLET
Y
RC
24VAC L N
CONTROL
LOGIC
NO
C
BLUE BLUE
THERMISTOR
BLUE BLUE
THERMISTOR
GREEN
PUMP
4053-113
LOW VOLTAGE
WIRING
PUMP CONTROL
HIGH VOLTAGE
WALL PLUG
RED
FACTORY
DESUPERHEATER
TEMPERATURE
MOTOR
24 VAC
LIMIT
BI-METAL
FIELD WIRING
WHITE
WHITE
YELLOW
BLACK
BLACK
BLACK
BLACK
BLACK
WIRING DIAGRAM
Manual 2100-517 Page 5 of 11
Page 6
Figure 1
MOUNTING DIRECTLY ONTO UNIT
FILTER ASSEMBLY
Manual 2100-517 Page 6 of 11
DESUPERHEATER PUMP MODULE
ATTACH TO UNIT USING PROVIDED SCREWS
INLET AND OUTLET TUBES SUPPLIED WITH PUMP MODULE
MIS-2647
Page 7
INLET FROM WATER HEATER
Figure 2
AIR PURGE PORT
AIR PURGE PORT
NOTE: PUMP IS NOT SELF-PRIMING, IT I S RECOMMENDED TO MANUALLY BLEED-OFF AIR.
FROM DSH COIL OUTLET
INLET THERMISTOR
NOTE: REMOVE DURING TUBE SOLDERING, THEN RE-INSTALL AND WRAP WITH PROVIDED INSULATION.
OUTLET THERMISTOR
NOTE: REMOVE DURING TUBE SOLDERING, THEN RE-INSTALL AND WRAP WITH PROVIDED INSULATION.
NOTE: INSTALLER MUST INSURE THAT THE INLET THERMISTOR IS RE-LOCATED BACK TO THE INLET TUBE AND THE OUTLET THERMISTOR IS LOCATED BACK ON THE OUTLET TUBE.
OUT TO WATER HEATER
OUT TO DSH COIL INLET
VERIFY BY CONNECTIONS ON CONTROL BOARD
MIS-2651
Manual 2100-517 Page 7 of 11
Page 8
Figure 3
REMOTE MOUNTING & PIPING
Manual 2100-517 Page 8 of 11
Page 9
Figure 4
SINGLE TANK SYSTEM
Manual 2100-517 Page 9 of 11
Page 10
CONTROL BOARD SEQUENCE of OPERATION
The desuperheating control board will make a determination whether or not to energize the pump relay inclusive on the control board.
A. It will constantly monitor inputs from two temperature
sensors, Inlet & Outlet water sensors.
B. It will constantly monitor the Y signal.
C. Upon acknowledgment of Y signal, and following two
minutes, the control board will energize the pump relay.
D. After 1½ minutes, based on temperature difference
between Outlet & Inlet sensors, and the presence of Y signal, the following will take place:
THERMISTOR
TEMPERATURE F vs RESISTANCE R OF TEMPERATURE SENSOR
FR F R
0.35
0.25
0.35
0.45
0.55
0.65
0.75
0.85
0.95
0.06
0.16
0.26
0.36
0.46
0.56
0.66
0.76
0.86
0.96
0.07
0.17
0.27
0.37
0.47
0.57
0.67
0.77
0.87
0.97
0.08
0.18
0.28
0.38
0.48
0.58
0.68
0.78
0.88
47391 76881 57381 98971 43471 48961 74561 22161 01751 01351
12941 44541 77141 02831 47431 73131 01821 29421 38121 38811
19511 70311
13011 26701
10501 74201 00001 0679 6259 9929 7709 2688 3568 9448 0528 7508 9687 6867
E. The Over Temperature Limit Switch is placed in series
F. The 3-amp fuse is put in series with the R connection to
Figure 5
1.) If temperature difference is greater than 3°F, then the control will continue to energize pump relay.
2.) If temperature difference is less than 3°F, then the control will de-energize the pump relay.
3.) The control will next wait for 10 minutes before repeating Step #1 (above).
with the line voltage. Therefore, continuity between L of line voltage and L of pump output is forced broken when the Over Temperature Limit Switch opens (see Wiring Diagram).
the board. Whenever the fuse is blown, the control will lose power and consequently, the relay will disengage.
0.98
0.09
0.19
0.29
0.39
0.49
0.59
0.69
0.79
0.89
0.99
0.001
0.101
0.201
0.301
0.401
0.501
0.601
0.701
0.801
0.901
0.011
0.111
0.211
0.311
0.411
0.511
0.611
0.711
0.811
0.911
0.021
0.121
0.221
0.321
0.421
7057 4337 5617 0007 0486 3866
1356 3836 9326 8906
1695 7285 7965 0755 6445 6235 8025 4905 2894 3784 7674 3664 2654 4644 7634 4724 2814 3904 6004
1293 8383 7573 8763
1063 6253 2543
Manual 2100-517 Page 10 of 11
Page 11
Figure 6
REPLACEMENT PARTS
2
1
3
4
5
6
.oNgniwarD.oNtraPnoitpircseD
14-473-721SesaB 2171-2048timiLerutarepmeTretaW 3173-311tekcarBdraoBlortnoC
4411-1028draoBlortnoCretaehrepuseD 5540-4168teloiVpmA-3esuF 6040-8048rotsimrehTteltuO/telnI 7010-0038pmuPgnitalucriC
SN4-002-331SrevoC
7
MIS-2669
Manual 2100-517 Page 11 of 11
Loading...