These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for Residential ....... ACCA Manual J
Winter and Summer Air Conditioning
Duct Design for Residential ............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
1Motor will automatically step through the various airflows with thermostatic control
2ESP = External Static Pressure (inches of water)
3Maximum allowable duct static
4Continuous airflow is the CFM being circulated with manual fan operation without any additional function occurring.
5Will occur automatically for first 5 minutes of Part Load Cooling Operation.
6Will occur automatically after five minutes of Part Load Cooling Operation.
7This is a field option for noisy installations to de-rate Full Load airflow (requires change in control panel).
8Will occur automatically with control signal input (will not be defeated for electric heat operation).
+75°C copper wire ++ HACR type circuit breaker
* C - for copper / N for Cupro-Nickel water coil
1 Heat pump only. Optional field-installed heaters are separate circuit.
Units are shipped completely assembled and internally
wired, requiring only duct connections, thermostat wiring,
230/208 volt AC power wiring, and water piping. The
equipment covered in this manual is to be installed by
trained, experienced service and installation technicians.
These instructions and any instructions packaged with any
separate equipment required to make up the entire heat
pump system should be carefully read before beginning the
installation. Note particularly any tags and/or labels
attached to the equipment.
While these instructions are intended as a general
recommended guide, they do not in any way supersede any
national and/or local codes. Authorities having jurisdiction
should be consulted before the installation is made.
SHIPPING DAMAGE
Upon receipt of the equipment, the carton should be
checked for external signs of shipping damage. If damage
is found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.
APPLICATION
Capacity of the unit for a proposed installation should be
based on heat loss calculations made in accordance with
methods of the Air Conditioning Contractors of America.
The air duct system should be sized and installed in
accordance with Standards of the National Fire Protection
Association for the Installation of Air Conditioning and
Venting systems of Other than Residence Type NFPA No.
90A, and residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.
Unit casing suitable for 0 inch clearance with 1-inch duct
clearance for at least the first 3 feet of duct. These units
are not approved for outdoor installation and therefore
must be installed inside the structure being conditioned.
Do not locate in areas subject to freezing in the winter or
subject to sweating in the summer.
Before setting the unit, consider ease of piping, drain and
electrical connections for the unit. Also, for units which
will be used with a field installed heat recovery unit,
consider the proximity of the unit to the water heater or
storage tank. Place the unit on a solid base, preferably
concrete, to minimize undesirable noise and vibration. DONOT elevate the base pan on rubber or cork vibration
eliminator pads as this will permit the unit base to act like a
drum, transmitting objectionable noise.
DUCTWORK
If the unit is to be installed in a closet or utility room which
does not have a floor drain, a secondary drain pan under
the entire unit is highly recommended.
DO NOT install the unit in such a way that a direct path
exists between any return grille and the unit. Rather, insure
that the air entering the return grille will make at least one
turn before entering the unit or coil. This will reduce
possible objectionable compressor and air noise from
entering the occupied space.
Design the ductwork according to methods given by the Air
Conditioning Contractors of America. When duct runs
through unconditioned spaces, it should be insulated with
vapor barrier. It is recommended that flexible connections
be used to connect the ductwork to the unit in order to keep
the noise transmission to a minimum.
LOCATION
The unit may be installed in a basement, closet, or utility
room provided adequate service access is insured. The unit
is shipped from the factory as a right hand return and
requires access clearance of two feet minimum to theaccess panels on this side of the unit. If unit is to be field
converted to left hand return the opposite side will require
access clearance of two feet minimum.
Unit may be field converted to left hand return by
removing two (2) screws that secure the control panel
cover, removing four (4) screws that hold the control panel
in place, laying the control panel down, sliding it under the
blower and re-securing the control panel on the opposite
side of the unit. (See Figure 2.) The two (2) access doors
from the right hand return can be transferred to the lefthand return side and the one (1) left-hand panel can be
transferred to the right hand side.
WARNING
Failure to provide the 1-inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
a fire.
Manual 2100-510E
Page9 of 38
FIGURE 2
FIELD-CONVERSION TO LEFT HAND RETURN
3
Panel removed for clarity.
Does not need removed
to change control panel location.
1. Remove control panel fill plate.
2. Remove two screws securing control panel to unit.
3. Pass control panel through blower section rotating 180°.
4. Re-secure control panel on opposite si de in same manner
as original ly attached.
5. Move double doors t o control panel side of unit.
2
MIS-2617
1
Manual 2100-510E
Page10 of 38
FILTER
This unit must not be operated without a filter. It comes
equipped with 2" disposable filters, which should be
checked often and replaced if dirty. Insufficient airflow
due to undersized duct systems or dirty filters can result in
nuisance tripping of the high or low pressure controls.
Refer to Table 2 for correct airflow and static pressure
requirements.
NOTE: The filter rack is installed on the unit as shipped
for right-hand return. If you require left-hand return, you
will need to remove the filter access door and remove the
screws holding the filter rack to the unit (slide downward
from underneath unit top). Invert the filter rack 180° to
move filter access door to the other side of the unit, and
reverse the previous steps (see Figure 3).
CONDENSATE DRAIN
Drain lines must be installed according to local plumbing
codes. It is not recommended that any condensate drain
line be connected to a sewer main.
Determine where the drain line will run and then select one
of four (4) locations for the condensate to exit the unit
casing (see Figure 4). There are knockouts in the unit
casing that can be selected for the condensate exit. Internal
of the unit, there is a clear flexible hose with a termination
fitting installed. When installed properly, this hose will
create a trap internal of the unit and will remain serviceable
if the drain system requires cleaning or service. Supplied in
the parts bag of the unit is a 3/4" PVC male adaptor that
will secure the internal drain components to the sheet metal
casing at the location you selected.
NOTE: You will need to bend the duct attachment flanges
up using duct bills or similar device, as the unit is shipped
with them collapsed.
AIR FILTERS
ledoMeziSretliFytitnauQ
S72VG
S83VG
S15VG
S16VG
S17VG
"2x"52x"021
"2x"52x"612
NOTE: This drain line will contain cold water and must be
insulated to avoid droplets of water from condensing on the
pipe and dripping on finished floors or the ceiling below
the unit.
PIPING ACCESS TO UNIT
Water piping to and from the unit enters the unit cabinet on
either side of the unit. The connection directly at the unit is
a special double o-ring fitting with a retainer nut that secures
it in place. (It is the same style fitting used for the flow
center connection on ground loop applications.) You may
come in and out either side of the unit in any combination as
the installation dictates. One side has both connections
closed off with a double o-ring plug seal with retaining caps.
One or both of these are transferred to opposite side depending upon installation requirements.
Note: All double o-ring fittings require “hand tightening
only”. Do not use wrench or pliers as retainer nut can be
damaged with excessive force.
Various fittings are available so you may then connect to
the unit with various materials and methods. These
methods include 1" barbed fittings (straight and 90°), 1"
MPT (straight and 90°), and 1-1/4" hot fusion fitting
(straight only) (see Figures 3 & 4).
Manual 2100-510E
Page11 of 38
frame 180°
to unit. Rotate filter rack
holding fi lter rack frame
Remove all screws
rack install ed.
Left-hand access filter
FIGURE 3
FILTER RACK – GV MODELS
install ed location.
does not need to be rotat ed. Leave in factory
Filter rack channel on GV51S1,61S1,71S1
MIS-2618
first r em ove filter rack door and filters.
To convert filter rack to left -hand access
Front of Unit
Manual 2100-510E
Page12 of 38
Filter rack shipped for
right-hand access f rom factory.
Drawing show s dual air filter
models GV51S1,61S1,71S1.
GV27S1,38S 1 have only one air filt er.
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.