These publications can help you install the air
conditioner or heat pump. You can usually find these at
your local library or purchase them directly from the
publisher. Be sure to consult current edition of each
standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation .............. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ...................... ANSI/NFPA 90B
Heating and Air Conditioning Systems
Load Calculation for Residential ....... ACCA Manual J
Winter and Summer Air Conditioning
Duct Design for Residential ............. ACCA Manual D
Winter and Summer Air Conditioning and Equipment
Selection
1 Motor will deliver consistent CFM through voltage supply range with no deterioration
(197-253V for all 230/208V models).
2 Continuous CFM is the total air being circulated during continuous (manual fan) mode.
3 Will occur automatically with a call for “Y” for cooling mode operation.
4 Will occur automatically with a call for “W1” for heating mode operation.
EXCEPTION:The rated CFM maybe adjusted +/- 15%, see Table 8. The CFM light on the Blower Control
Board can also be used to “count” the CFM of delivered air, see section on CFM light.
Units are shipped completely assembled and internally
wired, requiring only duct connections, thermostat
wiring, 230/208 volt AC power wiring, and water
piping. The equipment covered in this manual is to be
installed by trained, experienced service and installation
technicians. Any heat pump is more critical of proper
refrigerant charge and an adequate duct system than a
cooling only air conditioning unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heat pump system should be carefully read before
beginning the installation. Note particularly any tags
and/or labels attached to the equipment.
While these instructions are intended as a general
recommended guide, they do not in any way supersede
any national and/or local codes. Authorities having
jurisdiction should be consulted before the installation
is made.
SHIPPING DAMAGE
Upon receipt of the equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
APPLICATION
Capacity of the unit for a proposed installation should
be based on heat loss calculations made in accordance
with methods of the Air Conditioning Contractors of
America, formerly National Warm Air Heating and Air
Conditioning Association. The air duct system should
be sized and installed in accordance with Standards of
the National Fire Protection Association for the
Installation of Air Conditioning and Venting systems of
Other than Residence Type NFPA No. 90A, and
residence Type Warm Air Heating and Air Conditioning
Systems, NFPA No. 90B.
compressor compartment and re-securing the control
panel on the opposite side of the water coil. (See Figure
2.) The two (2) access doors from the right hand return
can be transferred to the left-hand return side and the
one (1) left hand panel can be transferred to the right
hand side.
Unit casing suitable for 0 inch clearance with 1-inch
duct clearance for at least the first 4 feet of duct. These
units are not approved for outdoor installation and
therefore must be installed inside the structure being
conditioned. Do not locate in areas subject to freezing
in the winter or subject to sweating in the summer.
Before setting the unit, consider ease of piping, drain
and electrical connections for the unit. Also, for units
which will be used with a field installed heat recovery
unit, consider the proximity of the unit to the water
heater or storage tank. Place the unit on a solid base,
preferably concrete, to minimize undesirable noise and
vibration. DO NOT elevate the base pan on rubber or
cork vibration eliminator pads as this will permit the
unit base to act like a drum, transmitting objectionable
noise.
DUCTWORK
If the unit is to be installed in a closet or utility room
which does not have a floor drain, a secondary drain pan
under the entire unit is highly recommended.
DO NOT install the unit in such a way that a direct path
exists between any return grille and the unit. Rather,
insure that the air entering the return grille will make at
least one turn before entering the unit or coil. This will
reduce possible objectionable compressor and air noise
from entering the occupied space.
Design the ductwork according to methods given by the
Air Conditioning Contractors of America. When duct
runs through unconditioned spaces, it should be
insulated with vapor barrier. It is recommended that
flexible connections be used to connect the ductwork to
the unit in order to keep the noise transmission to a
minimum.
LOCATION
The unit may be installed in a basement, closet, or
utility room provided adequate service access is insured.
The unit is shipped from the factory as a right hand
return and requires access clearance of two feet
minimum to the access panels on this side of the
unit. If unit is to be field converted to left hand return
the opposite side will require access clearance of two
feet minimum.
Unit may be field converted to left hand return by
removing four (4) screws that secure the control panel
cover, removing two (2) screws that hold the control
panel in place, sliding the control panel through the
WARNING
Failure to provide the 1-inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
a fire.
Manual 2100-317J
Page9 of 39
FIELD-CONVERSION TO LEFT HAND RETURN
REMOVE SINGLE AND
DOUBLE DOORS
1 REMOVE 4 SCREWS SECURING
COVER
2 REMOVE 2 SCREWS HOLDING
CONTROL BOX TO CORNER PANEL
REMOVE 2 SCREWS SECURING
PANEL TO BASE.
3 PASS CONTROL PANEL THROUGH
COMPRESSOR SECTION
4 RE-SECURE CONTROL PANEL ON
OPPOSITE SIDE IN SAME MANNER
AS ORIGINALLY ATTACHED
FIGURE 2
REPOSITION DOORS SO DOUBLE DOORS
ARE ON CONTROL PANEL SIDE, AND
SINGLE DOOR ON OPPOSITE SIDE
Manual 2100-317J
Page10 of 39
TOP VIEW
FILTER
This unit must not be operated without a filter. It comes
equipped with disposable filters, which should be
checked often and replaced if dirty. Insufficient airflow
due to undersized duct systems or dirty filters can result
in nuisance tripping of the high or low pressure control.
Refer to Table 2 for correct airflow and static pressure
requirements. (See Figures 3A & 3B.)
filled with water prior to start up. The use of plugged
tees in place of elbows to facilitate cleaning is highly
recommended.
Drain lines must be installed according to local
plumbing codes. It is not recommended that any
condensate drain line be connected to a sewer main.
The drain line enters the unit through the 3/4" FPT
coupling on the coil side of the unit.
CONDENSATE DRAIN
Determine where the drain line will run. This drain line
contains cold water and must be insulated to avoid
droplets of water from condensing on the pipe and
dripping on finished floors or the ceiling under the unit.
A trap MUST BE installed in the drain line and the trap
FIGURE 3A
GSVS24 - 42 MODELS
PIPING ACCESS TO UNIT
Water piping to and from the unit enters the unit casing
from the coil side of the unit under the return air filter
rack. Piping connections are made directly to the unit
and are 3/4" FPT for models 24 - 42, and 1" FPT for
models 48-60. (See Figure 4.)