Bard FUSION-TEC WR36BPA, FUSION-TEC WR58BPA, FUSION-TEC WR36BPB, FUSION-TEC WR58BPB Service Instructions Manual

FUSION-TEC® WALL-MOUNT
AIR CONDITIONER
Models:
WR36BPA WR58BPA
WR36BPB WR58BPB
NOTE: LC6000 controller is required for operation when
WR**BP* units are used.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com
Manual: 2100-695 Supersedes: NEW Date: 5-10-19
Page 1 of 54
CONTENTS
Using the TEC-EYETM ....................................................6
TEC-EYE Hand-Held Diagnostic Tool ...................................6
TEC-EYE Screen Structure and Password Level ..............
TEC-EYE
Main Status Screen ....................................................7
Quick Menu ..............................................................8
Setpoints ...........................................................8
Information ........................................................8
Staging Information .....................................8
Orphan Mode Staging ...................................8
Master Staging ............................................8
A/C Circuit Measurements .............................9
Last 24 Hour Operation ................................9
Component Lifetime Hours ...........................9
Software Version ..........................................9
Alarm Log ..........................................................9
Addressing Wall-Mount Units ....................................10
Executing a Run Test ...............................................10
Run Test Parameter Descriptions ........................11
Reset to Factory Defaults ..........................................11
Acronyms ....................................................7
Operation ..................................................................... 12
Unit On/Off ....................................................................12
Alarm Adjustment ...........................................................12
Acknowledging Alarms .............................................12
Clearing Alarms .......................................................12
Clearing Alarm Logs and Counters .............................12
Exporting Alarm Logs ...............................................12
Exporting 7 Day Logs ...............................................13
Orphan Model ................................................................13
Zone ..............................................................................13
Temperature/Humidity Control ..........................................13
Temperature/Humidity Control Components ................13
Return Air Temperature Sensor ...........................13
Return Air Temperature Alarm .....................14
Temperature/Humidity Control Operation ....................14
Heating Sequence.............................................15
Staging ............................................................15
Adjusting Cooling Staging ...........................15
Adjusting Heating Staging ..........................16
Dehumidification ..............................................16
Electronic Expansion Valve (EEV) .....................................16
EEV Components .....................................................16
Electronic Expansion Valve ................................16
EEV Instructions for Vacuum, Reclaim,
Charge Unit ...............................................16
System Pressures .......................................17
Suction Pressure Transducer ..............................17
Troubleshooting the Suction Pressure
Transducer ................................................18
Suction Pressure Alarm ..............................18
Suction Temperature Sensor ..............................18
Suction Temperature Alarm .........................18
EEV Operation .........................................................19
EEV Superheat Control ......................................19
Additional EEV Alarms .............................................19
Low Superheat Alarm ........................................19
Indoor Airflow .................................................................19
Cooling Sequence: Economizer Available ...............
Economizer Operation in Orphan Mode .........
Cooling Sequence: Economizer Not Available .........
Evaporator Freeze Condition Alarm .................
14 14 15
18
Indoor Airflow Components .......................................19
Blower .............................................................19
Blower Status Switch .................................20
7
Blower Status Alarm ...................................21
Filters ..............................................................22
Dirty Filter Switch .............................................22
Dirty Filter Alarm .......................................22
Filter Indicator Light .........................................22
Indoor Airflow Operation ...........................................23
High Sensible Mode ..........................................23
Blower Speed Control ........................................23
Additional Indoor Airflow Alarms ...............................23
Supply Air Temperature Alarm ............................23
Condenser Fan ...............................................................23
Condenser Fan Components ......................................23
Condenser Fan .................................................23
Liquid Line Pressure Transducer .........................24
Troubleshooting the Liquid Pressure
Transducer ................................................24
Liquid Pressure Transducer Alarm ...............24
Liquid Temperature Sensor ................................24
Condenser Fan Operation..........................................25
Condenser Fan Speed Control
High Pressure Control........................................25
Condenser Fan Speed .................................25
Second Stage Drop Out ..............................26
Low Ambient Control .........................................26
Additional Condenser Fan Alarms ..............................26
Dirty Condenser Coil Alarm ................................26
Compressor ....................................................................26
Compressor Components ..........................................26
Compressor ......................................................26
Compressor Control Module (CCM) .....................26
Delay-on-Make Timer ..................................26
Short Cycle Protection/Delay-on-Break .........26
High Pressure Detection .............................26
Test Mode .................................................26
High Pressure Safety Switch ..............................28
Refrigerant High Pressure Alarm ..................28
Phase Monitor ..................................................28
Compressor Operation ..............................................28
Compressor Low Temperature Limit ....................28
Additional Compressor Alarms ...................................29
Refrigerant Low Pressure Alarm ..........................29
Economizer ....................................................................29
Economizer Components ..........................................29
Actuator ...........................................................29
Dust Sensor .....................................................30
Dust Sensor Failure Alarm ..........................30
High Dust Limit Alarm ................................30
Damper Blade ..................................................31
Minimum Damper Position .........................31
Damper Switch .................................................31
Damper Failed to Open Alarm .....................31
Damper Failed to Close Alarm .....................32
Outdoor Temperature and Humidity Combination
Sensor .............................................................32
Outdoor Temperature Sensor Failure Alarm ...33
Supply Temperature Sensor ...............................33
Brownout Protection w/Adjustment ........................
Outdoor Humidity Sensor Failure Alarm ..........
............................25
27
33
Manual 2100-695 Page 2 of 54
Supply Temperature Sensor Failure Alarm ....33
High Supply Air Temperature Alarm .............33
Low Supply Air Temperature Alarm ..............33
Economizer Operation ..............................................34
Emergency Cooling Mode ................................................35
Emergency Ventilation Mode ............................................35
Model/Serial Number Configuration ..................................35
Electric Heat Option .......................................................36
Electric Heat Components ........................................36
Electric Heating Element ...................................36
Thermal Overload ..............................................36
Electric Heat Operation ............................................36
Bard Guard Anti-Theft System Option ...............................36
Smoke Detector Unit Disable Option .................................36
Inverter Option ...............................................................36
Refrigerant Information ...........................................40
General ..........................................................................40
Topping Off System Charge ..............................................40
Safety Practices..............................................................40
Important Installer Note ..................................................40
R410-A Refrigerant Charge ..............................................40
Pressure Service Ports .....................................................41
Maintenance ................................................................ 42
Standard Maintenance Procedures ...................................42
Bard Guard Anti-Theft System Option ...............................42
Troubleshooting ......................................................... 43
8301-067 Outdoor Temperature/Humidity Sensor ..............43
8301-067 Sensor Connections .................................43
8301-067 Humidity Sensor Test Value Outputs ..........46
8301-067 Humidity Sensor Calibration .....................46
8
301-057 Blower Status Switch/Dirty Filter Switch ...............
8612-061 Dust (Particulate) Sensor Control Board ............48
8612-061 Control Board Output Signal Not
Responsive to Dust ..................................................48
8301-073 Dust (Particulate) Sensor .................................50
8408-044 Return Air Sensor/Suction Sensor .....................51
8301-066 Supply Air Sensor ...........................................52
8406-157 Liquid Line Pressure Transducer ......................53
8406-158 Suction Pressure Transducer ............................54
47
FIGURES AND TABLES
Figure 1 TEC-EYE Display and Interface .........................6
Figure 2 TEC-EYE Connection to Unit Control .................6
Figure 3 Quick Menu Icons ...........................................8
Figure 4 Cool and Heat Setpoints ..................................8
Figure 5 Orphan Mode Staging ......................................8
Figure 6 Master Staging ................................................8
Figure 7 A/C Circuit Measurements ................................9
Figure 8 Last 24 Operation ...........................................9
Figure 9 Software Version..............................................9
Figure 10 Changing Unit Address ..................................10
Figure 11 Executing Run Test ........................................10
Figure 12 Run Test Summary ........................................10
Figure 13 Run Test: Motors & Sensors ............................11
Figure 14 Run Test: A/C Circuit .....................................11
Figure 15 Restoring Factory Default Settings ..................11
Figure 16 Clearing All Alarms ........................................12
Figure 17 Clearing Alarm Logs and Counters ...................12
Figure 18 Changing Zone ..............................................13
Figure 19 Adjusting Return Air Sensor ...........................13
Figure 20 Staging ........................................................14
Figure 21 Enabling Free Cooling Delay ...........................15
Figure 22 Viewing Unit Stages .......................................15
Figure 23 Adjusting Cooling Stage Differentials ...............16
Figure 24 Adjusting Heating Stage Differentials ..............16
Figure 25 Overriding EEV Output ...................................17
Figure 26 Electronic Expansion Valve and Service Tool ....17
Figure 27 Adjusting Suction Pressure Transducer Values ..18 Figure 28 Figure 29 Adjusting Suction Temperature Sensor Values ..18 Figure 30
Figure 31 Putting Blower Output into Override Mode .......19
Figure 32 Dirty Filter Switch/Blower Status Switch ..........21
Figure 33 Verifying Differential Airflow Status .................21
Figure 34 Adjusting Air Flow Alarm Delay .......................21
Figure 35
Figure 36 Enabling High Sensible Mode .........................23
Figure 37 Verifying Condenser Fan Output ......................23
Figure 38 Fan Blade Setting .........................................24
Figure 39 Adjusting Liquid Pressure Transducer Values ....24
Figure 40 Voltage/Pressure: Liquid Pressure Transducer ...24
Figure 41 Adjusting Liquid Temperature Values ...............25
Figure 42 Liquid Pressure Control Setpoint .....................25
Figure 43
Figure 44 Adjusting Compressor Delays ..........................28
Figure 45 Adjusting Compressor Low Temp Limit ............29
Figure 46
Figure 47 Damper Output and Override ..........................29
Figure 48 Dust Sensor ..................................................30
Figure 49
Figure 50 Adjusting Minimum Damper Position ..............31
Figure 51 Damper Switch .............................................31
Figure 52 Adjusting Damper Alarm Delay .......................32
Figure 53 Outdoor Air Sensor ........................................32
Figure 54 Outdoor Humidity Sensor ...............................32
Figure 55 Supply Air Sensor ..........................................33
Figure 56 Adjusting Supply Air Temperature Differential ..33
Figure 57 Economizer Setup A2 ....................................34
Figure 58
Figure 59 FUSION-TEC WR Series Nomenclature ............37
Figure 60
Figure 61 8301-067 Sensor Electrical Connections ........43
Figure 62 8301-067 Sensor Terminal Connections ..........43
Figure 63 8301-067 DIP Switch/Output Configuration ....46
Figure 64 8301-057 Air Differential Switch Terminals .....47
Figure 65 8612-061 Dust Sensor Alarm Board ...............48
Figure 66
Table 1
Table 2 Unit Status Messages ......................................7
Table 3 Unit Specific Superheat Settings ....................19
Table 4A WR36BP* Blower Speeds ..............................20
Table 4B WR58BP* Blower Speeds ..............................20
Table 5 Rated Airflow ................................................20
Table 6 Indoor Blower Performance ............................20
Table 7 Maximum ESP of Operation:
Electric Heat Only .........................................20
Table 8 Filter Switch Pressure Settings .......................21
Table 9 Economizer Default Settings ...........................35
Table 10 FUSION-TEC WR Series Board Terminals .........39
Table 11 Cooling Pressures ..........................................41
Table 12 8301-067 Sensor: Temperature to
Thermocouple Resistance ..............................44
Table 13 8301-067 Sensor: Relative Humidity to
Humidity Sensor Current Output .....................45
Table 14 8301-073 Sensor: Dust/Volts .........................50
Table 15 8408-044 Sensor: Temperature/Resistance ....51
Table 16 8301-066 Sensor: Temperature/Resistance .....52
Table 17 8406-157 0-65psi Pressure Transducer ..........53
Table 18 8406-1580-250psi Pressure Transducer .........54
Voltage/Pressure: Suction Pressure Transducer ..
Adjusting Freeze Setpoint and Alarm Delay .......
Dirty Filter Switch and Filter Indicator Light .......
8201-164 Compressor Control Module
Adjusting Low Pressure Alarm Settings ...............
Adjusting Dust Sensor Alarm Setpoint
Economizer Setup A3 .....................................
FUSION-TEC WR Series Unit Control Board .......
Dust Sensor Alarm Board Power Supply Check ..
LC6000/TEC-EYE Passwords (Defaults) ................
..............27
................30
18
18
22
29
35
38
49
6
Manual 2100-695 Page 3 of 54
GENERAL INFORMATION
Air Conditioning System
This Bard air conditioning system is composed of FUSION-TEC WR Series wall-mounted air conditioners matched with an LC6000 lead/lag controller. The wall mounts are specifically engineered for telecom/motor control center rooms.
NOTE: The LC6000 lead/lag controller and FUSION-
TEC WR Series wall-mount units are designed specifically to work together. The controller cannot run other brands of systems, nor can other controllers run the FUSION-TEC WR Series wall-mount units. They are a complete system, and must be used together.
Wall-Mount Air Conditioner Units
The wall-mount units operate on VAC power. will supply 100% of rated cooling airflow in free cooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.
Each of these units are fully charged with refrigerant and have optional auxiliary heat.
The units
General
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use without duct work. Flanges are provided for transition from unit to wall grilles.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Additional Publications for information on codes and standards.
Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to methods of Air Conditioning Contractors of America (ACCA). The supply flange should be installed in accordance with the Standards of the National
Fire Protection Association for the Installation of Air
Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with
instructions, installer should adhere to local codes.
Shipping Damage
Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
These units must remain in upright position at all times.
Additional Publications
These publications can help when installing the air conditioner. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI) 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE)
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA) Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-695 Page 4 of 54
ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
NOTICE: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to “NOTICE” the word “CAUTION” without the safety alert symbol may be used to indicate a message not related to personal injury.
!
WARNING
Electrical shock hazard. Have a properly trained individual perform
these tasks. Failure to do so could result in electric shock
or death.
!
WARNING
Fire hazard. Maintain minimum 1/4" clearance between the
supply ange and combustible materials.
Failure to do so could result in re causing damage, injury or death.
!
WARNING
Heavy item hazard. Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.
Manual 2100-695 Page 5 of 54
USING THE TEC-EYE
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
TM
FIGURE 1
ALARM KEY
MENU KEY
ESCAPE KEY
ALARM KEY
Allows viewing of active alarms Silences audible alarms Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level Cancels a changed entry
TEC-EYE Hand-Held Diagnostic Tool
The TEC-EYE service tool is used to communicate with the FUSION-TEC unit logic board. By connecting directly to the logic board inside the unit control panel, it is possible to perform diagnostics on the unit, adjust certain settings and verify unit and economizer operation through a run test procedure. The TEC-EYE service tool is required for unit setup and operation. The TEC-EYE is supplied with the LC6000 controller but can also be ordered separately (Bard P/N 8301-059).
The menu driven interface provides users the ability to scroll through two menu levels: Quick Menu and Main Menu. The menus permit the user to easily view, control and configure the unit.
The controller is completely programmed at the factory; the default setpoints and their ranges are easily viewed and adjusted from the TEC-EYE display. The program and operating parameters are permanently stored on FLASH-MEMORY in case of power failure.
The TEC-EYE connects to the wall-mount unit control board via an RJ11 modular phone connector as shown in Figure 2.
When not being used, the TEC-EYE hand-held diagnostic tool should be stored inside or near the LC6000 controller. Do not let the TEC-EYE leave the shelter site.
UP KEY
ENTER KEY
DOWN KEY
UP KEY
Steps to next screen in the display menu Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field Advances cursor
DOWN KEY
Steps back to previous screen in the display menu Changes (decreases) the value of a modifiable field
FIGURE 2
TEC-EYE Connection to Unit Control
Modular Phone Connector for TEC-EYE Hand-Held Diagnostic Tool
TABLE 1
LC6000/TEC-EYE Passwords (Defaults)
User 2000
Technician 1313
Engineer 9254
Use UP or DOWN keys and ENTER key to enter password
Manual 2100-695 Page 6 of 54
TEC-EYE Screen Structure and Password Level
Quick Menu Setpoints (Orphan Mode Temperature Control) Information Alarm Log Main Menu System Config: A1-A10 User (2000) Adv Sys Config: B1-B8 Technician (1313) I-O Config: C1-C15 Technician (1313) On/Off: User (2000) Alarm Logs: User (2000) Settings Date/Time: Technician (1313) Language: User (2000) Import/Export Unit Parameters: Engineer (9254) Alarm Log Export: User (2000) 7 Day Log Export: User (2000) Initialization Alarm Management: User (2000) System Default: Engineer (9254) Change Passwords Logout
In addition to the menu structure above, there are also Status and Alarm screens.
TEC-EYE Acronyms
MAT – Mixed air temperature (calculated value) RAT – Return air temperature SAT – Supply air temperature OAT – Outdoor air temperature OAH – Outdoor air humidity ODP – Outdoor dew point (calculated value) Blower – Indoor blower speed Fan – Outdoor fan speed Damper – Free cooling damper position FC – Free cooling status CL1 – Compressor stage 1 status CL2 – Compressor stage 2 status H1 – Heater stage 1 status H2 – Heater stage 2 status ST – Number of start requests in last hour
NOTE: Digital refers to On/Off whereas analog is a
variable input.
Main Status Screen
The Main Status Screen is the default start-up screen and also the return screen after 5 minutes of no activity. The screen can be accessed at any time by pressing the ESCAPE key repeatedly.
The wall-mount unit address is displayed in the upper right corner on the main Main Status Screen (see Figure 1). The Main Status Screen also shows the current date, time, return air temperature (RAT), mixed air temperature (MAT), supply air temperature (SAT), outdoor air temperature (OAT), outdoor air humidity (OAH) and outdoor dew point (ODP) conditions. Blower
speed, condenser fan speed, damper position and unit status are also displayed. See Table 2 for wall-mount unit status messages.
TABLE 2
Unit Status Messages
Message Description
Waiting...
Orphan Mode
LC Online
Cont. Blower
Power Loss
Free Cooling Unit is actively economizing.
Optimized Cool
Cooling Unit is actively mechanical cooling.
Heating Unit is actively heating.
Passive Dehum
Active Dehum
Self Test Unit is performing a self test.
Off by Alarm
Off by DI
Off by LC
Off by Keyboard
Override Active
Emergency Vent
Emergency Cool
Emergency Off
PLC is on and has not started running the application yet.
Unit is on and in orphan mode with no calls for heating or cooling.
Unit is on and communicating with the LC6000 with no heating or cooling calls.
Unit is operating with continuous blower when no heating or cooling calls are present.
Unit has experienced a loss of main utility power. Alarm only available with inverter units.
Unit is mechanical cooling while actively economizing.
Unit is taking measures to decrease humidity without using extra energy.
Unit is taking active measures to decrease humidity.
Unit has major fault preventing operation.
Unit is disabled by the local unit disable/smoke input.
Unit has been turned off by the supervisory controller.
Unit has been turned off by the local user.
There is an active override on the system.
Unit is in Emergency Ventilation. LC6000 has an active hydrogen alarm.
Unit is in Emergency Cooling. Indoor temperatures have exceeded high temp alarms.
Unit is in Emergency Off. LC6000 has an active smoke alarm.
Manual 2100-695 Page 7 of 54
The Quick Menu is accessible from the Screen
. Setpoints, Information and Alarm Log are available through the Quick Menu. Pressing the UP or DOWN keys while on the change the Quick Menu icon displayed (see Figure
3). Press the ENTER key when the desired icon is displayed.
Main Status Screen
Main Status
will
FIGURE 3
Quick Menu Icons
Alarm Log Information
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
Quick Menu
Setpoints
From this screen, the local unit heating and cooling setpoints, used for orphan mode operation only, can be changed.
Once the supervisory controller (LC6000) is connected, cooling and heating setpoints will be communicated and local cooling and heating setpoints will be replaced with the communicated cooling and heating setpoints.
If at any time the wall-mount unit(s) loses communication with the LC6000 controller, the wall­mount unit(s) will go into orphan mode and operate using the last communicated setpoints.
To verify or change the wall-mount unit cooling and heating setpoints in orphan mode:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints icon. Press ENTER key.
3. Press ENTER key to scroll to the selected choice
(see Figure 4).
Setpoints
FIGURE 4
Cool and Heat Setpoints
4. Press UP or DOWN key on desired value until value displays correctly.
5. Press ENTER key to save and scroll to next parameter.
6. Press ESCAPE key until Main Menu screen is displayed.
Information
The information screens are used as a quick reference to show unit operational information such as staging, A/C circuit measurements, last 24 hour run times and software version.
Staging Information
Staging information is used to show if free cooling is available or if any unit operation should be taking place. The look of the staging display depends on if the unit is communicating with a supervisory controller or operating in orphan mode.
Orphan Mode Staging
If the unit is operating in orphan mode, the title will display as Unit Staging (see Figure 5). This signifies that the local unit has control of the unit heating and cooling stages.
FIGURE 5
Orphan Mode Staging
Master Staging
If the unit is communicating with a supervisory controller, the title will display as Master Staging (see Figure 6). This signifies that the supervisory controller has control of the unit heating and cooling stages.
FIGURE 6
Master Staging
Manual 2100-695 Page 8 of 54
A/C Circuit Measurements
A/C Circuit Information can be found in two screens within the information menu (see Figure 7). The information and measurements provided are liquid line temperature, liquid line pressure, condensing saturated temperature, suction line temperature, suction line pressures, suction saturated temperature, super heat, sub-cooling and electronic expansion valve position.
FIGURE 7
A/C Circuit Measurements
Software Version
The Software Version screen displays the model number of the unit as well as all software version information for the PLC (see Figure 9).
FIGURE 9
Software Version
NOTICE
It is important to check the software version
during installation to ensure that the latest
version has been installed. Current software
versions, change log and installation
instructions are available on the Bard website at
http://www.bardhvac.com/software-download/
Last 24 Hour Operation
Last 24 Hour Operation information tracks the runtimes (Time) of different components or operations in the last 24 hour period (see Figure 8).
FIGURE 8
Last 24 Hour Operation
Alarm Log
The alarm log screens show a log of each alarm. There will be a log for when alarm occurred and if the alarm auto clears, it will show when the alarm cleared.
Manual 2100-695 Page 9 of 54
Addressing Wall-Mount Units
Each unit must have a unique address for the system to operate correctly with th LC controller (Ex: 1, 2, 3, ...14 depending on the number of units). The wall­mount unit address is displayed in the upper right corner on the Status screen on the TEC-EYE display (see Figure 1 on page 6).
To change the unit address:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press ENTER key to scroll to Unit Address (see Figure 10).
5. Press UP or DOWN keys to change the address to a value between 1 and 14.
7. Press ENTER key to save.
See page 13 for information on changing unit zone.
FIGURE 10
Changing Unit Address
FIGURE 11
Executing Run Test
7. Press UP or DOWN key to scroll between Run Test Summary, Motors & Sensors and A/C Circuit
screens.
NOTE:
The Run Test Summary screen (Figure 12) contains a readout of the test that is currently taking place, and the Task the technician should be completing to verify operation.
If the Run Test screens have been exited out of, they can be returned to by navigating to Run Test A10 as provided in the instructions above, pressing ENTER key to scroll to Return to Screens, pressing UP or DOWN key to change value to YES and pressing ENTER key.
Executing a Run Test
This unit has the ability to perform a run test that will operate all available unit functions in order to quickly determine unit operation. Some unit parameters are adjustable.
To execute a run test:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Run Test A10 screen.
5. Press ENTER key to scroll to Run Test Enable parameter (see Figure 11).
6. Press UP or DOWN key to change value to ON. The run test will begin and the screen will change to
Run Test Summary.
FIGURE 12
Run Test Summary
The Motors & Sensors screen (Figure 13) displays output and estimated positional values for unit motors and actuators, and also temperature and humidity sensor values.
Manual 2100-695 Page 10 of 54
FIGURE 13
Run Test: Motors & Sensors
The A/C Circuit screen (Figure 14) displays all unit inputs, outputs and calculations associated with the A/C circuit operation.
FIGURE 14
Run Test: A/C Circuit
7. Press UP or DOWN key to change value to YES; press ENTER key.
8. System will restart with default values.
FIGURE 15
Restoring Factory Default Settings
Run Test Parameter Descriptions
Econ Stage Time: Amount of time (in seconds) allowed for damper blade movement in each direction.
Cool Stage Time: Amount of time (in seconds) allowed for each stage of cooling.
Heat Stage Time: Amount of time (in seconds) allowed for heating stage.
Reset to Factory Defaults
To reset to factory default settings:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter ENGINEER password 9254.
3. Press UP or DOWN keys to scroll to Settings; press ENTER key.
4. Press UP or DOWN keys to scroll to Initialization; press ENTER key.
5. Press UP or DOWN keys to scroll to the Default Installation screen.
6. Press ENTER key to scroll to Reset to Factory Defaults (see Figure 15).
Manual 2100-695 Page 11 of 54
OPERATION
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
Unit On/Off
The wall-mount unit can be turned on and off from the TEC-EYE. Turning the unit off with the following instructions will disable all unit operation.
To turn the unit on or off:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to On/Off; press ENTER key.
4. Press UP or DOWN keys to change value from On to Off or from Off to On.
5. Press ESCAPE key several times to return to Main Menu screen.
The wall-mount unit may also be turned off by certain alarms. Below is a list of conditions that will disable unit operation to prevent damage to unit or property:
• System Off (set from LC6000)
• Emergency Off (set from LC6000)
• Unit Disable Input
• Invalid Model Number Size
• Return Air Sensor Failure Alarm in Orphan Mode
• Damper Failed to Close Alarm
• No Airflow Alarm (will cycle unit to attempt blower restart)
the screen at the end of the alarm list (shown in Figure
16) and press and hold the ALARM key for 3 seconds.
FIGURE 16
Clearing All Alarms
Clearing Alarm Logs and Counters
To clear the alarm log and alarm counters:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Settings; press ENTER key.
4. Press UP or DOWN keys to scroll to Initialization. (Alarm Management 1/2 screen will be displayed.)
5. Press ENTER key to scroll to Clear Alarm Log (see Figure 17).
6. Press UP or DOWN key to change value to YES; press ENTER key.
7. Press ENTER key to scroll to Clear Counters.
8. Press UP or DOWN key to value to YES; press ENTER key.
• Power Loss Input Active on Non-Inverter Model Number
Alarm Adjustment
Acknowledging Alarms
Alarm conditions activate a red LED indicator that backlights the ALARM function key. As an option, an alarm condition may also be enunciated by an audible alarm signal. An alarm is acknowledged by pressing the ALARM key. This calls up alarm display screen(s) that provide a text message detailing the alarm condition(s).
Clearing Alarms
Alarms can only be cleared after the alarm condition has been corrected. To clear a single alarm, press and hold the ALARM key for 3 seconds while viewing a specific alarm screen. To clear all alarms, navigate to
Manual 2100-695 Page 12 of 54
FIGURE 17
Clearing Alarm Logs and Counters
Exporting Alarm Logs
See latest version of Supplemental Instructions manual 7960-815 for information on exporting alarm logs.
Exporting 7 Day Logs
See latest version of Supplemental Instructions manual 7960-816 for information on exporting 7 day I/O logs.
Orphan Mode
FUSION-TEC WR Series wall-mount units have the capability to run without the LC6000 controller attached—this feature is called orphan mode. This keeps the shelter between 60°F and 77°F (factory default settings) by the use of the factory-installed return air sensor in each wall-mount unit. In orphan mode, no auxiliary temperature measurement devices are required for operation. The wall-mount unit automatically uses a continuous blower setting to circulate room air into the return air inlet and uses the return air temperature sensor to control room temperature.
To change default setpoints, refer to Setpoints on page 8.
During installation, the ability to run in orphan mode allows deactivation of one of the existing, older wall­mount units, while keeping the shelter cool with the other unit still operating. Once the first of the Bard wall-mount units is installed and powered on, it will operate in orphan mode—keeping the climate inside the shelter stable and the installers comfortable while the remainder of the older equipment is removed and the remaining Bard wall-mount units and LC6000 controller are installed.
Additionally, should any or all of the FUSION-TEC WR Series wall-mount units lose communication with the LC6000 controller (such as during maintenance), they will continue to serve the shelter’s needs until a repair can be made.
Zone
When paired with a supervisory controller that uses zones to control groups of wall units, this unit uses the zone setting to relay to the supervisory controller what zone it is set to operate in.
To change the zone:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Unit Setup A1
screen.
5. Press ENTER key to scroll to Zone (see Figure 18).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save value.
FIGURE 18
Changing Zone
Temperature/Humidity Control
Temperature/Humidity Control Components
Return Air Temperature Sensor
The unit is equipped with a return air temperature sensor to monitor the space temperature when the unit is in orphan mode. The return air sensor is located in the upper part of the return opening in such a way that it is exposed to the entering airstream. An alarm signal will be sent to the LC controller if the return air temperature sensor is disconnected. The temperature is measured with a 10k ohm NTC thermistor.
This sensor can be verified and adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Return Air Sensor C4.
5. Verify the measurement displayed on screen is accurate (see Figure 19).
FIGURE 19
Adjusting Return Air Sensor
6. If the measurement needs to be adjusted, apply an offset value by pressing ENTER to scroll to Offset.
7. Press UP or DOWN keys to adjust the offset.
Manual 2100-695 Page 13 of 54
8. The update will not take effect until the cursor is moved out of the Offset parameter.
9. Once adjusted, press the ESCAPE key several times to return to Main Menu screen.
Return Air Temperature Alarm
When the return air temperature sensor value is out of range (-41.0 to 303.0°F), the controller will generate a sensor failure alarm to indicate the sensor is not working properly.
This alarm is fixed and cannot be adjusted.
Temperature/Humidity Control Operation
When the unit is connected to the LC controller, it will receive all of its heating, cooling and ventilation commands from the controller. When the unit is in orphan mode, it will heat, cool and ventilate based on the return air temperature measurement. The return air temperature will be compared to the cooling setpoint. Based on differentials above and below the setpoint, the available cooling and heating stages will be utilized.
To change or view the unit setpoint:
1. From the Status screen, press UP or DOWN key until Quick Menu displays Setpoints icon ( ). Press ENTER key.
2. Press ENTER key to scroll to Cool Setpoint or Heat Setpoint (see Figure 4 on page 8).
3. Press UP or DOWN keys to change the value to desired heating and/or cooling setpoint.
Cooling Sequence – Economizer Available
NOTE: This description is based on the example shown
in Figure 20 and Figure 23 (page 16).
If the return air temperature is higher than 79°F (Setpoint of 77°F + Stage 1 On Differential of 2°F) and outdoor conditions are acceptable for economizing, the unit will enable economizer operation (free cooling). If the return air temperature is higher than 80°F (Setpoint of 77°F + Stage 2 On Differential of 3°F), the unit will enable mechanical cooling stage 1. If the return air temperature is higher than 81°F (Setpoint of 77°F + Stage 3 On Differential of 4°F), the unit will enable mechanical cooling stage 2. Each stage will then be disabled when the return air temperature reaches the setpoint plus the stage off differential.
Economizer Operation in Orphan Mode
In orphan mode,there is a chance that the economizer will not be given ample time to operate before the heat load requires more cooling. In this case, there is a delay that can be enabled in order to allow for the most amount of free cooling to be utilized before the compressor is staged on.
Free Cooling
Available
Free Cooling
Mechanical
Cooling Stage 1
Mechanical
Cooling Stage 2
Free Cooling
Not Available
Mechanical
Cooling Stage 1
Mechanical
Cooling Stage 2
Not Used
Heat Stage 1
FIGURE 20
Staging
Setpoint
72°F 73°F 74°F 75°F 76°F 77°F 78°F 79°F 80°F 81°F 82°F 83°F
Off
55°F 56°F 57°F 58°F 59°F 60°F 61°F 62°F 63°F 64°F 65°F 66°F
Off
Deadband
Setpoint
Deadband
On
On
NOTE: Deadband refers to a region where one end limit will turn the heating or cooling function on and the opposite end
limit will turn the heating or cooling function off.
Manual 2100-695 Page 14 of 54
To enable this delay:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Adv Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to FC Comp. Delay B7.
5. Press ENTER key to scroll to Enable (see Figure
21).
6. Press UP or DOWN key to change the value.
7. Press ENTER key to save value and move cursor to Delay.
8. Press UP or DOWN keys to change the time value.
9. Press ENTER key to save value and move cursor to top of the screen.
10. Press ESCAPE key several times to return to Main Menu screen.
FIGURE 21
Enabling Free Cooling Delay
when the return air temperature reaches the setpoint plus the stage off differential.
Staging
The unit will stage the cooling components based on the cooling demand referenced in the temperature control. The unit will stage the economizer on first if the indoor and outdoor conditions are favorable. The compressor stage 1 will be enabled next as the demand increases. Finally, the compressor stage 2 will be enabled as the demand continues to increase.
The unit is only equipped with one stage of heat and will turn on based on the heating demand.
To view unit stages:
1. From the Status screen, press UP or DOWN key until Quick Menu displays Unit Information icon
( ). Press ENTER key.
2. The cooling and heating demand are visible on this screen. The unit stages will display here when active as FC, CL1, CL2 or H1 (see Figure 22).
FIGURE 22
Viewing Unit Stages
Cooling Sequence – Economizer Not Available
NOTE: This description is based on the example shown in Figure 20 and Figure 23.
If the return air temperature is higher than 79°F (Setpoint of 77°F + Stage 1 On Differential of 2°F), the unit will enable mechanical cooling stage 1. If the return air temperature is higher than 80°F (Setpoint of 77°F + Stage 2 On Differential of 3°F), the unit will enable mechanical cooling stage 2. Each stage will then be disabled when the return air temperature reaches the setpoint plus the stage off differential.
Heating Sequence
NOTE: This description is based on the example shown in Figure 20 and Figure 23.
If the return air temperature is below 58°F (Setpoint of 60°F + Stage 1 On Differential of -2°F), the unit will enable electric heat stage 1. If the return air temperature is below 57°F (Setpoint of 60°F + Stage 2 On Differential), the unit will enable electric heat stage 2 (if available). Each stage will then be disabled
Adjusting Cooling Staging
This unit uses staging differentials to control cooling operation. The on differential for a stage references the number of degrees above the setpoint at which the stage turns on. The off differential for a stage references the number of degrees below the setpoint at which the stage turns off.
To adjust cooling stage differentials:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Adv Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Cooling Setup B4.
5. Press ENTER key to scroll to Stage 1 On Differential (see Figure 23 on page 16).
Press UP or DOWN keys to adjust number of
6. degrees above setpoint to turn cooling operation on.
Manual 2100-695 Page 15 of 54
7. Press ENTER key to save value and move cursor to Stage 1 Off Differential.
8. Press UP or DOWN keys to adjust number of degrees below setpoint to turn cooling operation off.
9. Press ENTER key to save value and move cursor to next stage differential.
10. Repeat steps 6 through 9 for Stage 2 and Stage 3 differentials.
11. Press ESCAPE key several times to return to Main Menu screen.
FIGURE 23
Adjusting Cooling Stage Differentials
Adjusting Heating Staging
This unit uses staging differentials to control heating operation. The on differential for a stage references the number of degrees below the setpoint at which the stage turns on. The off differential for a stage references the number of degrees above the setpoint at which the stage turns off.
To adjust heating stage differentials:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Adv Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Heating Setup B5.
5. Press ENTER key to scroll to Stage 1 On Differential (see Figure 24).
6. Press UP or DOWN keys to adjust number of degrees below setpoint to turn heating operation on.
7. Press ENTER key to save value and move cursor to Stage 1 Off Differential.
8. Press UP or DOWN keys to adjust number of degrees above setpoint to turn heating operation off.
9. Press ENTER key to save value and move cursor to next stage differential.
10. Repeat steps 6 through 9 for Stage 2 and Stage 3 differentials.
11. Press ESCAPE key several times to return to Main Menu screen.
FIGURE 24
Adjusting Heating Stage Differentials
Dehumidification
The unit uses a dehumidification sequence that does not require the electric heat to run at the same time as the compressor. Instead, the unit will turn on the compressor to cool down to the heating setpoint. Once the lower setpoint has been reached, the unit will heat the space back up to the upper setpoint. This cycle continues until the humidity level in the shelter reaches an acceptable level. At this point, the unit will revert back to normal operation. The economizer will also be disabled while the unit is in the dehumidification mode.
NOTE: This feature is dependent upon the LC6000
indoor humidity sensors and a command from the LC to enter dehumidification mode. See the latest revision of LC6000 Service Instructions 2100-669 for adjustment of the dehumidification setpoint and differentials.
Electronic Expansion Valve (EEV)
EEV Components
Electronic Expansion Valve
The electronic expansion valve is a stepper motor that is controlled with a step output from the controller. The valve is capable of 480 steps represented by a 0-100% signal on the controller. The motor drives a needle valve that regulates the flow of refrigerant.
EEV Instructions for Vacuum, Reclaim, Charge Unit
The electronic expansion valve moves to the 20% open position when the unit is not actively cooling. The valve may need to be manually positioned for service or troubleshooting. The valve can be positioned by using a menu override.
Manual 2100-695 Page 16 of 54
To manually override the valve:
NOTE: The unit must be off to perform this override.
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config; press ENTER key.
4. Press UP or DOWN keys to scroll to EEV Service C15.
Press ENTER key to scroll to Enable (see Figure 25).
5.
6. Press UP or DOWN key to change Disable to Enable.
7. Press ENTER key to scroll to Position.
8. Press UP or DOWN keys to adjust to the desired value.
9. Press ENTER key to save.
FIGURE 25
Overriding EEV Output
The valve can also be opened or closed using the EEV service tool (Bard Part # 2151-021). This magnetic EEV service tool (shown in Figure 26) is used to manually open the EEV. To do this, remove the EEV stator coil (red color with retaining nut on top), slide the magnetic tool over the shaft where the stator was removed and turn in a clockwise direction to open the valve to the full open position (directional arrows are provided on the tool). Opening the valve to the full open position will aid in the refrigerant reclamation and evacuation processes.
With the stator removed, the resistance should be 40 ohms +/- 10%. There are two sets of three wires that will have this resistance.
Reapply the EEV stator coil and retaining nut. Upon powering the unit back up, the control board will automatically drive the EEV back to the fully shut position, and then back to the 20% open position prior to starting the compressor back up. Once the compressor starts, the control board will again modulate the EEV position to control the system superheat.
FIGURE 26
Electronic Expansion Valve (EEV) and Service Tool
EEV Stator
Coil
EEV
EEV Service
Tool
System Pressures
To view system pressure and temperatures during this process:
1. From the Status screen, press UP or DOWN key until Quick Menu displays Information icon ( ). Press ENTER key.
2. Press UP or DOWN keys to scroll to EEV 1 Circuit and EVD 1 Compressor screens (see Figure 7 on page 9).
3. Reference the Pressures and Temperatures on EVD 1 Compressor and the Superheat and Subcooling on EEV 1 Circuit.
Suction Pressure Transducer
The unit has a pressure transducer installed on the suction line between the evaporator coil and compressor. The transducer is used for system monitoring of suction system pressures. The sensor is used with the suction temperature sensor to provide a real time superheat calculation that determines the EEV position.
This sensor can be verified and adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Liquid Pr Sensor C9.
5. Verify the measurement displayed on screen is accurate (see Figure 27 on page 18).
6. If the measurement needs to be adjusted, apply an offset value by pressing ENTER to scroll to Offset.
7. Press UP or DOWN keys to adjust the offset.
Manual 2100-695 Page 17 of 54
Loading...
+ 37 hidden pages