Unit Status Messages ......................................
Wall-Mount Unit Control Board Terminals ......
8301-066 Sensor: Temperature/Resistance ...
...........26
............29
18
19
28
33
33
47
.............6
37
46
7
Manual 2100-670I
Page 3 of 47
Page 4
GENERAL INFORMATION
Free Cooling Unit System
This Bard Free Cooling Unit System is composed of
FUSION-TEC HR Series wall-mounted air conditioners
matched with an LV1000 lead/lag controller. The wall
mounts are specifically engineered for telecom/motor
control center rooms.
NOTE: The LV1000 lead/lag controller and FUSION-
TEC HR Series wall-mount units are designed
specifically to work together. The controller
cannot run other Bard models or other brands
of systems, nor can other controllers run the
FUSION-TEC HR Series wall-mount units.
They are a complete system, and must be used
together.
Wall-Mount Air Conditioner Units
The FUSION-TEC
power.
The units will supply 100% of rated cooling
airflow in free cooling mode with ability to exhaust
the same amount through the unit itself without any
additional relief openings in the shelter.
Each of these units are fully charged with refrigerant
and have optional auxiliary heat.
HR Series
units operate on VAC
General
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use without duct work. Flanges
are provided for transition from unit to wall grilles.
These instructions explain the recommended method
to install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly any tags
and/or labels attached to the equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Additional Publications for information
on codes and standards.
Sizing of systems for proposed installation should be
based on heat loss and heat gain calculations made
according to methods of Air Conditioning Contractors of
America (ACCA). The supply flange should be installed
in accordance with the Standards of the National
Fire Protection Association for the Installation of Air
Conditioning and Ventilating Systems of Other Than
Residence Type, NFPA No. 90A, and Residence Type
Warm Air Heating and Air Conditioning Systems, NFPA
No. 90B. Where local regulations are at a variance with
instructions, installer should adhere to local codes.
Shipping Damage
Upon receipt of equipment, the cartons should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
These units must remain in upright position at all
times.
Additional Publications
These publications can help when installing the air
conditioner. They can usually be found at the local
library or purchased directly from the publisher. Be
sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA)
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI)
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air
Conditioning Engineers, Inc. (ASHRAE)
National Fire Protection Association (NFPA)
Batterymarch Park
P. O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-670I
Page 4 of 47
Page 5
ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The
signal word “DANGER” is to be limited to the most
extreme situations. DANGER [signs] should not be used
for property damage hazards unless personal injury risk
appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which,
if not avoided, could result in death or serious injury.
WARNING [signs] should not be used for property
damage hazards unless personal injury risk appropriate
to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if
not avoided, could result in minor or moderate injury.
CAUTION [signs] without a safety alert symbol may be
used to alert against unsafe practices that can result in
property damage only.
NOTICE: [this header is] preferred to address practices
not related to personal injury. The safety alert symbol
shall not be used with this signal word. As an
alternative to “NOTICE” the word “CAUTION” without
the safety alert symbol may be used to indicate a
message not related to personal injury.
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform
these tasks.
Failure to do so could result in electric shock
or death.
!
WARNING
Fire hazard.
Maintain minimum 1/4" clearance between the
supply ange and combustible materials.
Failure to do so could result in re causing
damage, injury or death.
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or
serious injury.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp
edges.
Failure to do so could result in personal injury.
Manual 2100-670I
Page 5 of 47
Page 6
USING THE TEC-EYE
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
TM
FIGURE 1
ALARM KEY
MENU KEY
ESCAPE KEY
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
TEC-EYE Hand-Held Service Tool
The TEC-EYE service tool is used to communicate
with the FUSION-TEC unit logic board. By connecting
directly to the logic board inside the unit control
panel, it is possible to perform diagnostics on the unit,
adjust certain settings and verify unit and economizer
operation through a run test procedure. The TEC-EYEservice tool is required for unit setup and operation. The
TEC-EYE is supplied with the LV1000 controller but can
also be ordered separately (Bard P/N 8301-059).
The menu driven interface provides users the ability
to scroll through two menu levels: Quick Menu and
Main Menu. The menus permit the user to easily view,
control and configure the unit.
The controller is completely programmed at the factory;
the default setpoints and their ranges are easily viewed
and adjusted from the TEC-EYE display. The program
and operating parameters are permanently stored on
FLASH-MEMORY in case of power failure.
The TEC-EYE connects to the wall-mount unit control
board via an RJ11 modular phone connector as shown
in Figure 2.
When not being used, the TEC-EYE hand-held
diagnostic tool should be stored inside or near the
LV1000 controller. Do not let the TEC-EYE leave the
shelter site.
UP KEY
ENTER KEY
DOWN KEY
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
FIGURE 2
TEC-EYE Connection to Unit Control
Modular Phone Connector for
TEC-EYE Hand-Held Diagnostic Tool
TABLE 1
LV1000/TEC-EYE Passwords (Defaults)
User2000
Technician 1313
Engineer 9254
Use UP or DOWN keys and ENTER key to enter password
Manual 2100-670I
Page 6 of 47
Page 7
TEC-EYE Screen Structure and Password Level
Quick Menu
Setpoints (Stand Alone Temperature Control)
Information
Alarm Log
Main Menu
System Config: A1-A10 User (2000)
Adv Sys Config: B1-B5 Technician (1313)
I-O Config: C1-C16 Technician (1313)
On/Off: User (2000)
Alarm Logs: User (2000)
Settings
Date/Time: Technician (1313)
Language: User (2000)
Import/Export
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
Trend Log Export: User (2000)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Serial Ports: Technician (1313)
Change Passwords
Logout
In addition to the menu structure above, there are also
Status and Alarm screens.
TEC-EYE Acronyms
MAT – Mixed air temperature (calculated value)
RAT – Return air temperature
SAT – Supply air temperature
OAT – Outdoor air temperature
OAH – Outdoor air humidity
ODP – Outdoor dew point (calculated value)
Blower – Indoor blower speed
Fan – Outdoor fan speed
Damper – Free cooling damper position
FC – Free cooling status
CL1 – Compressor stage 1 status
CL2 – Compressor stage 2 status
H1 – Heater stage 1 status
H2 – Heater stage 2 status
ST – Number of start requests in last hour
NOTE: Digital refers to On/Off whereas analog is a
variable input.
Main Status Screen
The main Status screen is the default start-up screen
and also the return screen after 5 minutes of no
activity. The screen can be accessed at any time by
pressing the ESCAPE key repeatedly.
The wall-mount unit address is displayed in the upper
right corner on the main Status screen (see Figure
1). The main Status screen also shows the current
date, time, return air temperature (RAT), mixed air
temperature (MAT), supply air temperature (SAT)
outdoor air temperature (OAT), outdoor air humidity
(OAH) and outdoor dew point (ODP) conditions. Blower
speed, condenser fan speed, damper position and unit
status are also displayed. See Table 2 for wall-mount
unit status messages.
TABLE 2
Unit Status Messages
MessageDescription
Waiting...
Stand Alone
LV Online
Cont. Blower
Power Loss
FreecoolingUnit is actively economizing.
Optimized Cool
CoolingUnit is actively mechanical cooling.
HeatingUnit is actively heating.
Passive Dehum
Active Dehum
Self TestUnit is performing a self test.
Off by Alarm
Off by DI
Off by LV
Off by Keyboard
Override Active
Emergency Vent
Emergency Cool
Emergency Off
PLC is on and has not started running
the application yet.
Unit is on and in orphan mode with
no calls for heating or cooling.
Unit is on and communicating with
the LV1000 with no heating or
cooling calls.
Unit is operating with continuous
blower when no heating or cooling
calls are present.
Unit has experienced a loss of main
utility power. Alarm only available
with inverter units.
Unit is mechanical cooling while
actively economizing.
Unit is taking measures to decrease
humidity without using extra energy.
Unit is taking active measures to
decrease humidity.
Unit has major fault preventing
operation.
Unit is disabled by the local unit
disable/smoke input.
Unit has been turned off by the
supervisory controller.
Unit has been turned off by the local
user.
There is an active override on the
system.
Unit is in Emergency Ventilation.
LV1000 has an active hydrogen
alarm.
Unit is in Emergency Cooling. Indoor
temperatures have exceded high
temp alarms.
Unit is in Emergency Off. LV1000
has an active smoke alarm.
Manual 2100-670I
Page 7 of 47
Page 8
The Quick Menu is accessible from the main Status
screen. Setpoints, Information and Alarm Log are
available through the Quick Menu. Pressing the UP or
DOWN keys while on the main Status screen will change
the Quick Menu icon displayed (see Figure 3). Press the
ENTER key when the desired icon is displayed.
FIGURE 3
Quick Menu Icons
Alarm LogInformation
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
Quick Menu
Setpoints
From this screen, the local unit heating and cooling
setpoints, used for stand alone operation only, can be
changed.
Once the supervisory controller is connected, cooling
and heating setpoints will be communicated and local
cooling and heating setpoints will be replaced with the
communicated cooling and heating setpoints.
If at any time the wall-mount unit(s) loses
communication with the LV1000 controller, the
wall-mount unit(s) will go into stand alone mode and
operate using the last communicated setpoints.
To verify or change the wall-mount unit cooling and
heating setpoints in stand alone mode:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints icon. Press
ENTER key.
3. Press ENTER key to scroll to the selected choice
(see Figure 4).
Setpoints
FIGURE 4
Cool and Heat Setpoints
4. Press UP or DOWN key on desired value until value
displays correctly.
5. Press ENTER key to save and scroll to next
parameter.
6. Press ESCAPE key until Main Menu screen is
displayed.
Information
The information screens are used as a quick reference
to show unit operational information such as staging,
A/C circuit measurements, last 24 hour run times,
component lifetime hours and software versioning.
Staging Information
Staging information is used to show any unit operation
that should be taking place. The look of the staging
display depends on if the unit is communicating with a
supervisory controller.
Stand Alone Demand and Staging
If the unit is operating in a stand alone mode, the
title will display as Unit Demand (see Figure 5). This
signifies that the local unit has control of the unit
heating and cooling stages.
FIGURE 5
Stand Alone Demand and Staging
Master Staging
If the unit is communicating with a supervisory
controller, the title will display as Master Staging (see
Figure 6). This signifies that the supervisory controller
has control of the unit heating and cooling stages.
FIGURE 6
Master Staging
Manual 2100-670I
Page 8 of 47
Page 9
A/C Circuit Measurements
A/C Circuit Information can be found in two screens
within the information menu (see Figure 7). The
information and measurements provided are liquid line
temperature, liquid line pressure, condensing saturated
temperature, suction line temperature, suction line
pressures, suction saturated temperature, super heat,
sub-cooling and electronic expansion valve position.
Software Version
The Software Version screen displays the model
number of the unit as well as all software version
information for the PLC (see Figure 9). This information
can be used to determine whether a software update
may be required based on information found in the
software change log. This change log can be found at
http://www.bardhvac.com/software-download/.
FIGURE 7
A/C Circuit Measurements
FIGURE 9
Software Version
NOTICE
It is important to check the software version
during installation to ensure that the latest
version has been installed. Current software
versions, change log and installation
instructions are available on the Bard website at
http://www.bardhvac.com/software-download/
Last 24 Hour Operation
Last 24 Hour Operation information tracks the runtimes
(Time) and start calls (Start) of different components or
operations in the last 24 hour period (see Figure 8).
FIGURE 8
Last 24 Hour Operation
Alarm Log
The alarm log screens show a log of each alarm. There
will be a log for when alarm occurred and if the alarm
auto clears, it will show when the alarm cleared.
Manual 2100-670I
Page 9 of 47
Page 10
Addressing Wall-Mount Units
Each unit must have a unique address for the system
to operate correctly with the LV controller (Ex: 1, 2, 3, 4 depending on the number of units). The wall-mount
unit address is displayed in the upper right corner on
the Status screen on the TEC-EYE display (see Figure 1
on page 6).
To change the unit address:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Unit Setup (A1) screen.
5. Press ENTER key to scroll to Controller Address
(see Figure 10).
6. Press UP or DOWN keys to change the address to a
value between 1 and 4.
7. Press ENTER key to save
FIGURE 10
Changing Unit Address
6. Press UP or DOWN key to change value to ON. The
run test will begin and the screen will change to
Run Test Summary.
FIGURE 11
Executing Run Test
7. Press UP or DOWN key to scroll between Run
Test Summary, Motors & Sensors and A/C Circuit
screens.
NOTE:
If the Run Test screens have been exited out
of, they can be returned to by navigating to
Run Test (A10) as provided in the instructions
above, pressing ENTER key to scroll to Return to Screens, pressing UP or DOWN key to
change value to YES and pressing ENTER key.
Executing a Run Test
This unit has the ability to perform a run test that will
operate all available unit functions in order to quickly
determine unit operation. Some unit parameters are
adjustable.
To execute a run test:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Sys Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Run Test (A10)
screen.
5. Press ENTER key to scroll to Run Test Enable
parameter (see Figure 11).
The Run Test Summary screen (Figure 12) contains
a readout of the test that is currently taking place,
and the Task the technician should be completing to
verify operation.
FIGURE 12
Run Test Summary
The Motors & Sensors screen (Figure 13) displays
output and estimated positional values for unit motors
and actuators, and also temperature and humidity
sensor values.
Manual 2100-670I
Page 10 of 47
Page 11
FIGURE 13
Run Test: Motors & Sensors
The A/C Circuit screen (Figure 14) displays all unit
inputs, outputs and calculations associated with the
A/C circuit operation.
FIGURE 14
Run Test: A/C Circuit
7. Press UP or DOWN key to change value to YES;
press ENTER key.
8. System will restart with default values.
FIGURE 15
Restoring Factory Default Settings
Run Test Parameter Descriptions
Econ Stage Time: Amount of time (in seconds)
allowed for damper blade movement in each
direction.
Cool Stage Time: Amount of time (in seconds) allowed
for each stage of cooling.
Heat Stage Time: Amount of time (in seconds)
allowed for heating stage.
Reset to Factory Defaults
To reset to factory default settings:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
ENGINEER password 9254.
3. Press UP or DOWN keys to scroll to Settings; press
ENTER key.
4. Press UP or DOWN keys to scroll to Initialization;
press ENTER key.
5. Press UP or DOWN keys to scroll to the Default Installation screen; press ENTER key.
6. Press ENTER key to scroll to Reset to Factory Defaults (see Figure 15).
Manual 2100-670I
Page 11 of 47
Page 12
OPERATION
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
Unit On/Off
The wall-mount unit can be turned on and off from
the TEC-EYE. Turning the unit off with the following
instructions will disable all unit operation.
To turn the unit on or off:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to On/Off; press
ENTER key.
4. Press UP or DOWN keys to change value from On
to Off or from Off to On.
5. Press ESCAPE key several times to return to Main
Menu screen.
The wall-mount unit may also be turned off by certain
alarms such as the smoke alarm input on the wallmount unit board or the return air temperature sensor
failure when not connected to the LV1000.
Alarm Adjustment
Acknowledging Alarms
Alarm conditions activate a red LED indicator that
backlights the ALARM function key. As an option, an
alarm condition may also be enunciated by an audible
alarm signal. An alarm is acknowledged by pressing the
ALARM key. This calls up alarm display screen(s) that
provide a text message detailing the alarm condition(s).
Clearing Alarms
Alarms can only be cleared after the alarm condition
has been corrected. To clear a single alarm, press and
hold the ALARM key for 3 seconds while viewing a
specific alarm screen. To clear all alarms, navigate to
the screen at the end of the alarm list (shown in Figure
16) and press and hold the ALARM key for 3 seconds.
FIGURE 16
Clearing All Alarms
Clearing Alarm Logs and Counters
To clear the alarm log and alarm counters:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to Settings; press
ENTER key.
4. Press UP or DOWN keys to scroll to Initialization;
press ENTER key. (Alarm Management screen will
be displayed.)
5. Press ENTER key to scroll to Clear Alarm Logs?
(see Figure 17).
6. Press UP or DOWN key to change value to YES;
press ENTER key.
7. Press ENTER key to scroll to Clear Counters.
8. Press UP or DOWN key to value to YES; press
ENTER key.
FIGURE 17
Clearing Alarm Logs and Counters
Exporting Alarm Logs
See latest version of Supplemental Instructions manual
7960-815 for information on exporting alarm logs.
Exporting 7 Day Logs
See latest version of Supplemental Instructions manual
7960-816 for information on exporting 7 day I/O logs.
Stand Alone (Orphan) Mode
FUSION-TEC HR Series wall-mount units have the
capability to run without the LV1000 controller
attached—this feature is called stand alone or
orphan mode. This keeps the shelter between 45°F
and 79°F (factory default settings) by the use of the
factory-installed return air sensor in each wall-mount
unit. In stand alone mode, no auxiliary temperature
measurement devices are required for operation. The
wall-mount unit automatically uses a continuous blower
setting to circulate room air into the return air inlet and
Manual 2100-670I
Page 12 of 47
Page 13
uses the return air temperature sensor to control room
temperature.
To change default setpoints, refer to Setpoints on page 8.
During installation, the ability to run in stand alone
mode allows deactivation of one of the existing, older
wall-mount units, while keeping the shelter cool with
the other unit still operating. Once the first of the Bard
FUSION-TEC HR Series wall-mount units is installed
and powered on, it will operate in orphan mode—
keeping the climate inside the shelter stable and
the installers comfortable while the remainder of the
older equipment is removed and the remaining Bard
FUSION-TEC HR Series wall-mount units and LV1000
controller are installed.
Additionally, should any or all of the FUSION-TEC HR
Series wall-mount units lose communication with the
LV1000 controller (such as during maintenance), they
will continue to serve the shelter’s needs until a repair
can be made.
Temperature/Humidity Control
Temperature/Humidity Control Components
Return Air Temperature Sensor
The unit is equipped with a return air temperature
sensor to monitor the space temperature when the unit
is in stand alone mode. The return air sensor is located
in the upper part of the return opening in such a way
that it is exposed to the entering airstream. An alarm
signal will be sent to the LV controller if the return air
temperature sensor is disconnected. The temperature is
measured with a 10k ohm NTC thermistor.
This sensor can be verified and adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Return Air Sensor (C5); press ENTER key.
5. Verify the measurement displayed on screen is
accurate (see Figure 18).
6. If the measurement needs to be adjusted, apply an
offset value by pressing ENTER to scroll to Offset.
7. Press UP or DOWN keys to adjust the offset.
8. The update will not take effect until the cursor is
moved out of the Offset parameter.
9. Once adjusted, press the ESCAPE key several
times to return to Main Menu screen.
FIGURE 18
Adjusting Return Air Sensor
Return Air Temperature Alarm
When the return air temperature sensor value is out of
range (-41.0 to 303.0°F), the controller will generate
a sensor failure alarm to indicate the sensor is not
working properly.
This alarm is fixed and cannot be adjusted.
Temperature/Humidity Control Operation
The unit utilizes a PID control loop for space control.
This control will compare the space temperature to
the space setpoint. Based on how far away from the
setpoint the temperature is, the loop will output a
cooling or heating capacity number between 0 and
100%. The unit will then take all of the available
cooling methods and distribute them evenly across the
0-100% range. The stages are then brought on as the
heating or cooling capacity reaches the percentage that
brings the stages on or off. There are separate setpoints
for cooling and heating.
To change or view the unit setpoint:
1. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints icon ( ).
Press ENTER key.
2. Press ENTER key to scroll to CoolSetpoint or Heat Setpoint (see Figure 4 on page 8).
3. Press UP or DOWN keys to change the value to
desired heating and/or cooling setpoint.
Cooling
The unit is equipped with 1 stage of freecooling and 2
stages of mechanical cooling (compressor and solenoid)
for a total of 3 cooling stages (see Figure 19 on page
14).
Cooling w/No Economizer
The unit is equipped with 1 stage of freecooling and
2 stages of mechanical cooling (compressor and
solenoid). However, the outdoor conditions are not
favorable for economizer operation so there are a total
of 2 cooling stages (see Figure 20 on page 14).
Manual 2100-670I
Page 13 of 47
Page 14
Freecooling
Compressor Stage 1
Compressor Stage 2
FIGURE 19
Cooling w/Economizer
-10%0%
10%20%30%40%50%60%70%80%90% 100%
Off
DeadbandOn
110% 120%
Deadband(sometimes called a neutral zone or dead zone) is an interval of a signal domain or band where no action occurs
FIGURE 20
Cooling w/No Economizer
Compressor Stage 1
Compressor Stage 2
-10%0%
10%20%30%40%50%60%70%80%90% 100%
Off
DeadbandOn
Deadband(sometimes called a neutral zone or dead zone) is an interval of a signal domain or band where no action occurs
110% 120%
Electric Heat
-10%10%30%50%70%90%110%
Deadband(sometimes called a neutral zone or dead zone) is an interval of a signal domain or band where no action occurs
Manual 2100-670I
Page 14 of 47
Off
FIGURE 21
Heating
DeadbandOn
Page 15
Heating
The unit is equipped with 1 stage of electric heat (see
Figure 21).
Staging
The unit will stage the cooling components based on
the cooling demand referenced in the temperature
control. The unit will stage the economizer on first if
the indoor and outdoor conditions are favorable. The
compressor stage 1 will be enabled next as the demand
increases. Finally, the compressor stage 2 will be
enabled as the demand continues to increase.
The unit is only equipped with one stage of heat and
will turn on based on the heating demand.
To view unit stages:
1. From the Status screen, press UP or DOWN key
until Quick Menu displays Unit Information icon
( ). Press ENTER key.
2. The cooling and heating demand are visible on
this screen. The unit stages will display here when
active as FC, CL1, CL2 or H1 (see Figure 22).
FIGURE 22
Viewing Unit Stages
Electronic Expansion Valve (EEV)
EEV Components
Electronic Expansion Valve
The electronic expansion valve is a stepper motor that
is controlled with a step output from the controller. The
valve is capable of 480 steps represented by a 0-100%
signal on the controller. The motor drives a needle valve
that regulates the flow of refrigerant.
EEV Instructions for Vacuum, Reclaim, Charge Unit
The electronic expansion valve moves to the 20% open
position when the unit is not actively cooling. The
valve may need to be manually positioned for service or
troubleshooting. The valve can be positioned by using a
menu override.
To manually override the valve:
NOTE:The unit must be off to perform this override.
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to TEEV Service (C16); press ENTER key.
Press ENTER key to scroll to Enable (see Figure 23).
5.
6.
Press UP or DOWN key to change Disable to Enable.
7. Press ENTER key to scroll to Position.
8. Press UP or DOWN keys to adjust to the desired
value.
9. Press ENTER key to save.
Dehumidification
The unit uses a dehumidification sequence that does
not require the electric heat to run at the same time
as the compressor. Instead, the unit will turn on the
compressor to cool down to the heating setpoint.
Once the lower setpoint has been reached, the unit
will heat the space back up to the upper setpoint.
This cycle continues until the humidity level in the
shelter reaches an acceptable level. At this point,
the unit will revert back to normal operation. The
economizer will also be disabled while the unit is in
the dehumidification mode.
NOTE: This feature is dependent upon the LV1000
indoor humidity sensors and a command
from the LV to enter dehumidification mode.
See the latest revision of LV1000 Service
Instructions 2100-673 for adjustment of the
dehumidification setpoint and differentials.
FIGURE 23
Overriding EEV Output
The valve can also be opened or closed using the EEV
service tool (Bard Part # 2151-021). This magnetic
EEV service tool (shown in Figure 24 on page 16) is
used to manually open the EEV. To do this, remove the
EEV stator coil (red color with retaining nut on top),
slide the magnetic tool over the shaft where the stator
was removed and turn in a clockwise direction to open
the valve to the full open position (directional arrows
Manual 2100-670I
Page 15 of 47
Page 16
FIGURE 24
Electronic Expansion Valve (EEV) and Service Tool
are provided on the tool). Opening the valve to the full
open position will aid in the refrigerant reclamation and
evacuation processes.
With the stator removed, the resistance should be 40
ohms +/- 10%. There are two sets of three wires that
will have this resistance.
Reapply the EEV stator coil and retaining nut. Upon
powering the unit back up, the control board will
automatically drive the EEV back to the fully shut
position, and then back to the 20% open position
prior to starting the compressor back up. Once
the compressor starts, the control board will again
modulate the EEV position to control the system
superheat.
System Pressures
To view system pressure and temperatures during this
process:
1. From the Status screen, press UP or DOWN key
until Quick Menu displays Information icon
( ). Press ENTER key.
2. Press UP or DOWN keys to scroll to EEV 1 Circuit
and EVD 1 Compressor screens.
3. Reference the Pressures and Temperatures on EVD 1 Compressor and the Superheat and Subcooling
on EEV 1 Circuit.
Suction Pressure Transducer
The unit has a pressure transducer installed on
the suction line between the evaporator coil and
compressor. The transducer is used for system
monitoring of suction system pressures. The sensor is
used with the suction temperature sensor to provide
a real time superheat calculation that determines the
EEV position.
This sensor can be verified and adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Suction Pr Sensor (C11); press ENTER key.
5. Verify the measurement displayed on screen is
accurate (see Figure 25).
6. If the measurement needs to be adjusted, apply an
offset value by pressing ENTER to scroll to Offset.
7. Press UP or DOWN keys to adjust the offset.
8. The update will not take effect until the cursor is
moved out of the Offset parameter.
9. Once adjusted, press the ESCAPE key several
times to return to Main Menu screen.
FIGURE 25
Adjusting Suction Sensor/Transducer
Pressure Values
Manual 2100-670I
Page 16 of 47
Page 17
Troubleshooting the Suction Pressure Transducer
0-250 psig
-5v Nominal .5 – 4.5v Actual
4v/250 psig = .016 volts per 1 psig
Example: 125 psig x .016 + .5 volts = 2.5 volts
Formula for Tech:
Measured Pressure x .016 + Sensor Offset = Expected
Transducer Signal Voltage (see Figure 26).
FIGURE 26
Voltage to Pressure: Suction Pressure Transducer
Suction Pressure Alarm
When the suction pressure transducer value is out
of range (0-250 PSIG), the controller will generate
a sensor failure alarm to indicate the sensor is not
working properly.
This alarm cannot be adjusted.
Suction Temperature Sensor
The suction temperature sensor is used to calculate
superheat. The EEV uses this value to control the EEV.
The temperature is measured with a 10k ohm NTC
thermistor.
The suction temperature sensor measurement can be
verified and adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Suct Temp Sensor (C9); press ENTER key.
5. Verify the measurement displayed on screen is
accurate (see Figure 27).
6. If the measurement needs to be adjusted, apply an
offset value by pressing ENTER to scroll to Offset.
7. Press UP or DOWN keys to adjust the offset.
8. The update will not take effect until the cursor is
moved out of the Offset parameter.
FIGURE 27
Adjusting Suction Temperature Sensor Values
Suction Temperature Alarm
When the suction temperature sensor value is out of
range (-41.0 to 303.0°F), the controller will generate
a sensor failure alarm to indicate the sensor is not
working properly.
This alarm cannot be adjusted.
Evaporator Freeze Condition Alarm
The FUSION-TEC Freeze alarm (Evaporator Coil Freeze
Protection) uses the suction temperature sensor to
alarm and manage operation when conditions are
favorable for an evaporator coil freeze condition.
Whenever the compressor is running, the system will
constantly monitor the suction line temperature. If the
suction line temperature falls below the freeze setpoint
(33°F factory default) for a period of time exceeding
freeze alarm delay time (180 seconds factory default),
the system will alarm a freeze condition. Once a
freeze condition is triggered, the system will stop the
compressor operation and increase the blower speed to
80% in order to rapidly warm and thaw the evaporator
coil. After a period of 5 minutes has elapsed, normal
operation will continue.
To adjust the freeze setpoint and/or alarm delay time:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A7); press ENTER key.
5. Press ENTER key to scroll to Setpoint (see Figure
28 on page 18).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value/scroll to Delay.
8. Press UP or DOWN keys to change to the desired
Delay value.
9. Press ENTER key to save the value.
Manual 2100-670I
Page 17 of 47
Page 18
FIGURE 28
Adjusting Freeze Setpoint and Alarm Delay
EEV Operation
EEV Superheat Control
The electronic expansion valve (EEV) will open or close
to maintain 10° of superheat while the compressor is
running. When the compressor is not running, the valve
will close.
Low superheat protection will be active once the
superheat value is at or below 5°F. At this point,
the control will aggressively close the valve so that
superheat is maintained.
Additional EEV Alarms
Low Superheat Alarm
This alarm will become active when the calculated
superheat goes below 5°F. This alarm will clear itself
when the condition is no longer present.
This alarm cannot be adjusted.
Indoor Airflow
Indoor Airflow Components
Blower
The unit is equipped with a blower that is driven by
an electronically commutated motor (ECM). This
blower is controlled by a 0-10v signal provided from
the controller. This 0-10v signal is converted to a
PWM signal with an adapter. The blowers on both the
HR36AP* and HR58AP* models use a 10" diameter
wheel. The HR36AP* operates between 250-850 rpm
while the HR58AP* operates between 250-1400 rpm.
The blower output can be put into an override mode for
verification or troubleshooting.
To put the blower into override:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Blower Fan (C13); press ENTER key.
5. Press ENTER key to scroll to Blower OV Speed (see
Figure 29).
6. Press UP or DOWN keys to adjust the speed to the
desired output (see Table 3A or 3B).
7. Press ENTER key to scroll to Override.
8. Press UP or DOWN key to change Disabled to
Enabled.
9. Press ENTER key to save.
FIGURE 29
Putting Blower Output into Override Mode
TABLE 3A
HR36AP* Blower Speeds
Mode
Freezestat Active94.09.4 v1500
High Sensible
Full Load Cooling
High Sensible
Part Load Cooling
Standard Full
Load Cooling
Standard Part
Load Cooling
Economizer Standard
Economizer High S/T
Heating63.06.3 v1200
Dehumidification
Mode
Speed
Percentage
94.09.4 v1500
54.05.4 v1100
63.06.3 v1200
43.04.3 v950
90.0
63.0
19.01.9 v470
Controller
Output Volts
9.0 v
6.3 v
CFM
1450
1200
Manual 2100-670I
Page 18 of 47
Page 19
TABLE 3B
HR58AP* Blower Speeds
Mode
Freezestat Active80.08.0 v2260
High Sensible Full
Load Cooling
High Sensible Part
Load Cooling
Standard Full Load
Cooling
Standard Part Load
Cooling
Economizer Standard
Economizer High S/T
Heating35.03.5 v1335
Speed
Percentage
75.07.5 v2180
50.05.0 v1705
55.05.5 v1830
35.03.5 v1335
45.0
75.0
Controller
Output Volts
4.5 v
7.5 v
CFM
1600
1950
Blower Status Switch
The unit is equipped with a differential pressure airflow
switch to monitor the blower (see Figure 30). If the
blower is turned on and the switch doesn't open to
indicate there is differential pressure between the inlet
and outlet of the blower, an alarm will be generated.
For switch settings, see Figure 30.
FIGURE 30
Dirty Filter Switch and Blower Status Switch
Dehumidification
Mode
35.03.5 v1335
TABLE 4
Rated Airflow
Nominal Rated CFM
HighLow
HR36AP*12009500.00
HR58AP*180014000.10
Nominal Rated ESP
TABLE 5
Indoor Blower Performance
SpeedHighLow
ESP
(Inch H
HR36AP*0.00
HR58AP*0.10
Dry
0)
Coil
2
12601200995950
1885180014701400
Wet
Coil
Dry
Coil
TABLE 6
Maximum ESP of Operation
Electric Heat Only
Wet
Coil
Differential airflow status can be viewed by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Digital In
Config (C2); press ENTER key.
5. Reference 7 NoAir row and Val column (see Figure
31).
FIGURE 31
Verifying Differential Airflow Status
ModelStatic Pressure*
-A0Z
-A05
-B0Z
-B06
* Unit is rated for free blow non-ducted
operation with SGR-5W Supply Grille
and RGR-5W Return Grille.
.00"
.00"
.00"
.00"
Manual 2100-670I
Page 19 of 47
Page 20
Blower Status Alarm
If the blower is commanded on and the fan status
switch (differential pressure) has not indicated the fan
is running within 45 seconds, the system will generate
an alarm.
Disabling the blower status switch in I/O Config
disables this alarm.
This alarm is just a notification and will clear itself
when the conditions are no longer present.
To adjust the air flow alarm delay:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A8); press ENTER key.
5. Press ENTER key to scroll to Air Flow Alarm Del
(see Figure 32).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
FIGURE 32
Adjusting Air Flow Alarm Delay
Filters
The unit is equipped with two (2) 20" x 30" x 2" MERV
8 filters. The filters slide into position making them easy
to service. The filters can be serviced from the outside
by removing either the right or left filter access panel.
Dirty Filter Switch
These units are equipped with a differential pressure
switch to indicate when the filter(s) needs to be
replaced (see Figure 30). The dirty filter switch
measures the pressure difference across the filter
through silicone tubing routed to the blower and vent
areas of the unit.
The switch circuit consists of a normally open filter
pressure switch. The switch will open when the
pressure differential goes above the setting indicated
on the dial. When the pressure difference returns below
the setting on the dial, the switch will close.
Adjustment of dirty filter switch may be necessary to
ensure proper operation. See Table 7 and Figure 33 to
aid in setting the filter switch to operate at different
percentages of filter blockage.
Dirty Filter Alarm
The wall-mount unit is equipped with a differential
pressure switch input to the controller (see Figure 30).
When the switch indicates a dirty filter, the controller
will generate an alarm. Once the condition is no longer
present, the alarm will automatically clear. Additionally,
an indicator light will be turned on with the alarm and
turned off when the alarm clears.
Disabling the dirty filter switch in I/O Config disables
this alarm.
The threshold of this alarm is adjusted by changing the
settings on the switch (see Table 7).
Filter Indicator Light
These units are equipped with a 24v indicator light
mounted on side of unit that displays the current status
of the filter (as shown in Figure 33). When the light is
on, the filter needs to be replaced. Once the filter(s) has
been changed, the indicator light will turn off.
Freezestat
Earlier units were equipped with a switch that
monitored the temperature of the refrigerant line
leaving the evaporator coil. To prevent the coil from
freezing and potentially allowing liquid refrigerant from
the evaporator to enter the compressor, the freezestat
switch was designed to open when the temperature at
this sensor is between 26.5°F and 37.5°F and close
again when the temperature is between 49.5°F and
64.5°F. This switch was used in units running software
version 1.0.4 and earlier and has been removed.
The evaporator coil freeze protection alarm is now
calculated using system temperatures (see Evaporator Freeze Condition Alarm on page 17).
Indoor Airflow Operation
Blower Speed Control
The blower is capable of changing speeds to best match
the requirements of the system depending on which
mode the system is in (see Table 3A or 3B on page 19).
The unit will automatically switch to the required
speed for each mode. High sensible mode and
dehumidification mode are both communicated
separately from the LV. For more information on the
high sensible command from LV, please see LV1000
Service Instructions 2100-673.
All units tested equipped with MERV 8 filters. Appropriate supply (SG) and return (RG) grilles installed during testing.
Pressure switch adjustment may be necessary due to variations in filter type, installation and room pressure.
Bard recommends filter switch be set at 50% filter blockage or less. Higher settings may significantly hinder unit
performance.
FIGURE 33
Dirty Filter Switch and Filter Indicator Light
MIS-3901
Manual 2100-670I
Page 21 of 47
Page 22
Additional Indoor Airflow Alarms
Supply Air Temperature Alarm
When the supply air temperature sensor value is out of
range (-41.0 to 303.0°F), the controller will generate
a sensor failure alarm to indicate the sensor is not
working properly.
This alarm is fixed and cannot be adjusted.
Condenser Fan
Condenser Fan Components
Condenser Fan
The unit is equipped with a condenser fan that is driven
by an electronically commutated motor (ECM). This
fan is controlled by a 0-10vdc signal provided from the
controller. The fan operates between 100-1200 rpm.
To view the output of the condenser fan:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Condenser Fan (C15); press ENTER key.
5. Reference Fan Speed parameter for the current
output to the condenser fan (see Figure 34).
FIGURE 34
Verifying Condenser Fan Output
If required, the condenser fan output can be manually
set for 5 minutes for troubleshooting purposes.
While looking at Condenser Fan (C15) screen:
1. Press ENTER key to scroll to Fan OV Speed (see
Figure 36).
2. Press UP or DOWN keys to change the value to the
desired override speed.
3. Press ENTER key to save the value and move
cursor to the Override parameter.
4. Press UP or DOWN keys to change the value from
Disabled to Enabled.
5. The fan should now run at the selected speed. The
output can be verified by again referencing the Fan Speed parameter.
The override will last for 5 minutes or until the Override
parameter is set to Disabled again.
Due to design considerations of the condenser section
of the wall-mount unit, placement/clearance of the
motor/fan blade is critical to heat dispersal. Should a
change of motor or fan blade be necessary, see Figure
35 for proper clearance adjustment.
FIGURE 35
Fan Blade Setting
.75"
(from the closest point on the fan blade)
Liquid Line Pressure Transducer
The unit has a pressure transducer installed on the
liquid line between the condenser and electronic
expansion valve (EEV). The transducer is used for
system monitoring of the liquid side system pressures.
This information is used to indicate when outdoor coil
cleaning is necessary based on outdoor conditions and
system pressures. The sensor is also used to adapt
the condenser fan speed for high and low ambient
conditions.
The liquid pressure sensor input can be verified and
adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Liquid Pr Sensor (C10); press ENTER key.
5. Verify the measurement displayed on screen is
accurate (see Figure 36).
6. If the measurement needs to be adjusted, apply an
offset value by pressing the ENTER key to scroll to
Offset.
7. Press UP or DOWN keys to adjust the offset. The
update will not take effect until the cursor is
moved out of the offset parameter.
Manual 2100-670I
Page 22 of 47
Page 23
8. Once adjusted, the ESCAPE key several times to
return to Main Menu screen.
FIGURE 36
Adjusting Discharge/Liquid Transducer
Pressure Values
Troubleshooting the Discharge/Liquid Pressure
Transducer
Formula for Tech:
Measured Pressure x .00615 + Sensor Offset =
Expected Transducer Signal Voltage (see Figure 37).
The liquid temperature sensor can be verified and
adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Liquid Temp Sensor (C3); press ENTER key.
5. Reference the Value to verify the temperature (see
Figure 38).
6. If an offset needs to be applied, press ENTER key
to scroll to Offset.
7. Press UP or DOWN keys to change the offset to
desired value.
8. Press ENTER key to save.
9. Press ESCAPE key several times to return to Main
Menu screen.
FIGURE 38
Adjusting Discharge/Liquid Temperature Input
FIGURE 37
Voltage to Pressure:
Discharge/Liquid Pressure Transducer
Discharge/Liquid Pressure Transducer Alarm
When the discharge pressure transducer value is out
of range (0-650 PSIG), the controller will generate a
sensor failure alarm to indicate the transducer is not
working properly.
This alarm is fixed and cannot be adjusted.
Liquid Temperature Sensor
The unit is equipped with a liquid line temperature
sensor to monitor the temperature of the liquid
refrigerant leaving the condenser and entering the EEV.
The temperature is measured with a 10k ohm NTC
thermistor.
Condenser Fan Operation
Condenser Fan Speed Control
Mechanical Cooling Only
The condenser fan motor speed is selected based on
outdoor air temperature. Above 80°F, the fan speed
will be set to a nominal output speed. Below 80°F, the
condenser fan speed will operate at reduced speeds
based on outdoor air temperatures until the slowest fan
speed is reached. This operation allows for more stable
head pressures at lower ambient conditions, which also
allows for increased unit efficiency. See Figure 39 on
page 24 for more detail.
NOTE: If the outdoor temperature sensor fails, the
condenser fan speed will be set to the nominal
operating speed.
Optimized Cooling (Concurrent Economizer and
Mechanical Cooling)
During optimized cooling mode, the condenser fan
motor speed will be set to the normal operating speed
and will not change based on outdoor air conditions. If
Manual 2100-670I
Page 23 of 47
Page 24
FIGURE 39
Condenser Fan Speed Control
conditions become unfavorable for optimized cooling,
the system will change to mechanical cooling only.
When this occurs, the fan speed will remain at normal
speed for 2 minutes, allowing for the damper blade to
fully close. After the 2-minute period, the condenser
fan speed may be reduced to optimize head pressures.
During optimized cooling, all fan speed control will be
handled by the low ambient controls and high pressure
controls if system pressures were to get out of range.
High Pressure Control
Condenser Fan Speed
When the liquid pressure reaches 550 PSI, the
condenser fan will speed up, moving as much air as
possible in an attempt to reduce system pressures. The
condenser fan will operate at increased speed until the
liquid pressure reaches 450 PSI. At this point, the fan
will return to normal operating speed.
Second Stage Drop Out
If the liquid pressure reaches 620 PSI, the second
stage of cooling will be disabled for 2 minutes to
reduce the required condenser airflow. After 2 minutes,
if the pressure is less than the pressure cutout, it will
resume stage 2 operation.
Low Ambient Control
At low ambient outdoor air temperatures, the fan motor
will cycle as a means of controlling the system's head
pressure to protect the system from evaporator coil
freeze conditions. The process for this system is as
follows: If the liquid pressure falls below 250 PSI, the
condenser fan will turn off. The fan will remain off
while the compressor remains running, allowing the
head pressure to build up. Once the liquid pressure
reaches 350 PSI, the fan will then turn back on at
the appropriate speed. At lower ambient outdoor
temperatures, this may cycle regularly as normal
operation. In some cases, in higher wind prone areas,
the condenser fan may stay off for prolonged durations
due to low liquid pressures.
Additional Condenser Fan Alarms
Dirty Condenser Coil Alarm
The unit will continuously monitor system conditions
to determine if the condenser coil is dirty or blocked.
If the system monitors three consecutive cooling
cycles that indicate a dirty condenser coil, an alarm
will be generated. This alarm is a notification and will
automatically reset when conditions are no longer
present. The end user has the ability to adjust how
Manual 2100-670I
Page 24 of 47
Page 25
dirty the coil gets before an alarm is generated and how
many consecutive cycles before the alarm is triggered.
To change these settings:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Adv System Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Dirty Cond Alarm (B3); press ENTER key.
5. Press ENTER key to scroll to Alarm Threshold (see
Figure 40).
6. Press UP or DOWN keys to adjust the % restriction
to desired level.
7. Press ENTER key to save value and move the
cursor to Trips before alarm.
8. Press UP or DOWN keys to change the Trips before alarm to the desired value.
9. Press ENTER key to save.
10. Press ESCAPE key several times to return to Main
Menu screen.
FIGURE 40
Adjusting Dirty Condenser Coil Alarm Settings
Compressor
Compressor Components
Compressor
Three Phase Scroll Compressor Start Up Information
Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction. Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.
However, three phase compressors will rotate in either
direction depending upon phasing of the power.
Since there is a 50-50 chance of connecting power
in such a way as to cause rotation in the reverse
direction, verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as substantially
reduced current draw compared to tabulated values.
Verification of proper rotation must be made at the time
the equipment is put into service. If improper rotation
is corrected at this time, there will be no negative
impact on the durability of the compressor. However,
reverse operation for over 1 hour may have a negative
impact on the bearing due to oil pump out.
NOTE: If compressor is allowed to run in reverse
rotation for an extended period of time, the
compressor’s internal protector will trip.
All three phase compressors are wired identically
internally. As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation direction.
The direction of rotation of the compressor may be
changed by reversing any two line connections to the
wall-mount unit.
Compressor Control Module (CCM)
Delay-on-Make Timer
Short Cycle Protection/Delay-on-Break
Test Mode
High Pressure Detection
Brownout Protection with Adjustment
The LPC terminals are jumpered in this application.
Instead, the low pressure transducer is used for low
pressure monitoring.
Delay-on-Make Timer
In the event of power loss, a delay-on-make timer is
included to be able to delay startup of the compressor.
This is desired when more than one unit is on a
structure so that all of the units do not start at the
same time which could happen after a power loss or
building shutdown. The delay-on-make time period is
2 minutes plus 10% of the delay-on-break time period.
To ensure that all of the units do not start at the same
time, adjust the delay-on-break timer on each unit to a
slightly different delay time.
Short Cycle Protection/Delay-on-Break
An anti-short cycle timer is included to prevent short
cycling the compressor. This is adjustable from 30
seconds to 5 minutes via the adjustment knob (see Figure
41 on page 26). Once a compressor call is lost, the time
period must expire before a new call will be initiated.
10% of this time is also considered on the delay-onmake timer (see above).
High Pressure Detection
High pressure switch monitoring allows for a lockout
condition in a situation where the switch is open. If the
high pressure switch opens, the CCM will de-energize
Manual 2100-670I
Page 25 of 47
Page 26
FIGURE 41
8201-164 Compressor Control Module
High Pressure SwitchCompressor Contactor Output
18-30 VAC Input
Y Input from Thermostat
and High Pressure Switch
Troubleshooting Light
Jumper
the compressor. If the switch closes, it will then restart
the compressor after the delay-on-break setting has
expired on the device. If the switch trips again during
the same Y call, the compressor will be de-energized.
The ALR terminal will be energized, signaling the unit
control board that a high pressure event has occurred
(see Refrigerant High Pressure Alarm on page 27).
Test Mode
By rapidly rotating the potentiometer (POT) clockwise
(see Figure 41), all timing functions will be removed
for testing.
The conditions needed for the unit to enter test mode
are as follows: POT must start at a time less than or
equal to the 40 second mark. The POT must then be
rapidly rotated to a position greater than or equal to
the 280 second mark in less than ¼ second. Normal
operation will resume after power is reset or after the
unit has been in test mode for at least 5 minutes.
Brownout Protection with Adjustment
Brownout protection may be necessary if the utility
power or generator power has inadequate power to
prevent the voltage from dropping when the compressor
Alarm Output
Common
Delay-on-Break Time
Adjustment Potentiometer
Brownout Ignore Time DIP Switches*
* Turn on only one switch for that specific ignore time setting
starts. This is rare but can happen if the generator
is undersized at the site or if the site is in a remote
location far from the main power grid. Under normal
circumstances, allowing the brownout to be ignored for
a time period should not be needed. The 8201-164 is
shipped with all the DIP switches in the 'off' or 'do not
ignore' position (see Figure 41).
If ignoring the brownout is needed because of the
above conditions, three preset timers can be set by DIP
switches in order to delay signaling a power brownout
for a specific length of time after compressor contactor
is energized. This allows the compressor a time period
to start even if the voltage has dropped and allows the
voltage to recover. This delay only happens when the
CC terminal energizes. The delay can be set to 500
milliseconds (A DIP switch), 1000 milliseconds (B DIP
switch) or 1500 milliseconds (C DIP switch); time is
not cumulative—only the longest setting will apply. If
the voltage recovers during the brownout time period,
the compressor will start.
If a brownout condition is detected by the 8201-164,
the troubleshooting light will flash blue. The light will
continue to flash until the cooling call is satisfied or
Manual 2100-670I
Page 26 of 47
Page 27
power is removed from the Y terminal. This condition
does not prevent operation, it only indicates that a
brownout condition was present at some point during
the cooling call. If a brownout condition is detected,
CC will be de-energized and will retry after the delayon-make timer is satisfied; this process will continue
until call is satisfied.
If user chooses the 'do not ignore' position when the
site has inadequate utility or generator power, this
could lead to the compressor never starting. The
control will
A common scenario and one that has been seen in the
field is when a unit or units switches from utility power
to generator power. With slower transfer switches, the
time delay between the utility power and generator
power didn’t cause a problem. The units lost power,
shut off and came back on line normally. With the
introduction of almost instantaneous transfer switches,
the millisecond long power glitch can be enough that
the compressor will start to run backwards. In this
scenario, the CCM will catch this and restart the units
normally.
High Pressure Safety Switch
All units have a high pressure switch as a safety device.
This device will open when pressure in the system
reaches 650 PSIG. The sensor is directly connected
to the dedicated compressor control module (see High
Pressure Detection on page 25).
Refrigerant High Pressure Alarm
When the wall-mount unit receives a signal from the
compressor control module (CCM) indicating a high
pressure event, the wall-mount unit will generate an
alarm. Upon receiving the alarm, the wall-mount unit
will remove the “Y” call from the CCM, resetting the
status of the CCM. The alarm will stay present on the
wall-mount unit until manually cleared with TEC-EYE
hand-held diagnostic tool.
In addition to the CCM, the discharge pressure
transducer is used to prevent a high pressure event.
When the discharge pressure is above the discharge
pressure alarm setpoint (set 30 PSI below high
pressure switch, which is 650 PSI), the system will
disable stage 2 of mechanical cooling.
Phase Monitor
Used only on three phase equipment, the phase
monitor is a compressor protection device that will
prohibit operation of the compressor if the device senses
a possible reverse-rotation situation due to incorrect
phasing. On a call for compressor (and only compressor),
the device will check incoming phase, check for severe
voltage imbalance and check for proper frequency.
Under nominal conditions, a green LED light will show
on the face of the monitor. If there is improper phasing,
voltage imbalance or frequency deviation, the device will
show a red LED light and prohibit compressor operation.
see the brownout immediately and not start.
If a fault condition occurs, reverse two of the supply
leads to the unit. Do not reverse any of the unit factory
wires as damage may occur.
Compressor Operation
The compressor will be enabled when the unit (in stand
alone mode) or LV provide a cooling stage 1 call. The
compressor call from the controller has several delays
that may affect the start or stop time of the compressor
in regards to the cooling demand. The compressor has
a minimum on time of 120 seconds to prevent short
cycling the compressor. The compressor also has a
minimum off time of 120 seconds to prevent start
ups before the pressure in the refrigeration system
equalizes. When the second stage is engaged, it also
has a minimum run time of 120 seconds to allow the
system to stabilize before returning to single stage or
shutting down.
These delays can be changed by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Adv System Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Unit Config (B2); press ENTER key.
5. Press ENTER key to scroll to Min On, Min Off,
Min On Same, Unloader Del or Address Delay (see
Figure 42).
6. Press UP or DOWN keys to change the value.
7. Press ENTER key to save value and move the
cursor to next parameter or top of screen.
8. Press ESCAPE key several times to return to Main
Menu screen.
FIGURE 42
Adjusting Compressor Delays
The address-based delay only applies to the wall-mount
unit when in stand alone mode. The controller will
delay the unit compressor based on the value entered
on screen B2 multiplied by the unit address. This is
intended to keep multiple units from starting their
Manual 2100-670I
Page 27 of 47
Page 28
compressors at the same time when there is a quick
change in the load. When connected to the LV, this is
taken care of by LV logic.
Additional Compressor Alarms
Refrigerant Low Pressure Alarm
When the suction pressure transducer indicates
a pressure value less than the low pressure alarm
setpoint of 40 PSIG and there is an active call for
cooling, the controller will disable the compressor (after
a 180-second delay). NOTE: The second call will be
delayed based on the delay off value mentioned in the
compressor section. The controller will try to run the
refrigeration system two (2) times within 900 seconds
before the alarm will lock the compressor out. This
alarm needs to be manually cleared before compressor
operation will resume.
To adjust the low pressure alarm settings:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A6); press ENTER key.
5. Press ENTER key to scroll to Delay to adjust how
long the compressor waits before turning the
compressor off (see Figure 43).
6. Press UP or DOWN keys to adjust the time delay.
7. Press ENTER key to scroll to Two Count Del.
8. Press UP or DOWN keys to adjust the delay value.
9. Press ENTER key to save.
10. Press the ESCAPE key several times to return to
Main Menu screen.
Economizer
Economizer Components
Actuator
The actuator rotates up to 90° based on a 0-10v signal
sent to it by the controller. The actuator is rated at
44 lb-in and is spring return when power is lost. This
component is what opens and closes the damper blade.
To verify the output from the controller to the actuator:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Damper Override (C14); press ENTER key.
5. Reference the Damper Position for the current
output to the damper (see Figure 44).
6. To override the current position, press ENTER key
to scroll to Damper OV Pos.
7. Press UP or DOWN keys to change the value to the
desired output.
8. Press ENTER key to save the value and move
cursor to Override.
9. Press UP or DOWN keys to change the value from
Disabled to Enabled.
10. The Damper Position will update with the new
override value and the damper will travel to that
position.
NOTE: This override will last for 5 minutes or until the
Override is changed back to Disabled.
FIGURE 44
Damper Override
FIGURE 43
Adjusting Low Pressure Alarm Settings
Manual 2100-670I
Page 28 of 47
Dust Sensor
The unit has a dust sensor installed near the outdoor
air inlet. The dust sensor checks for excessive
particulates in the outdoor air, and will close the
economizer if the dust is excessive. The sensor uses a
PWM signal converted to 0-5v output to the controller.
Page 29
To ensure proper performance, cleaning may be
required. Vacuuming or blowing the dust off the sensor
with forced air is recommended. Avoid inserting any objects into the sensor.
The dust sensor can be verified by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Dust Sensor (C8); press ENTER key.
5. Reference the Value for the current sensor reading
(see Figure 45).
6. To apply an offset to the current reading, press
ENTER key to scroll to Offset.
7. Press UP or DOWN keys to adjust the value to the
desired value.
8. Press ENTER key to save the value and move
cursor to next parameter.
NOTE: The sensor can be disabled if required for
troubleshooting.
9. With the cursor on the Enable parameter, press
UP or DOWN keys to change the value from ON to
OFF.
10. Press ENTER key to save.
controller has adjustable software setpoints (default to
80%) to indicate dust levels are too high and to disable
the economizer operation for 5 minutes (unit default).
This alarm is not communicated to the NOC. Once
the conditions are no longer present, the alarm will
automatically clear.
Disabling the dust sensor in I/O Config disables this
alarm.
To adjust the dust sensor alarm setpoint:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A9); press ENTER key.
5. Press ENTER key to scroll to Setpoint (see Figure
46).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
NOTE: When the temperature outside is measured
at or below 0°F, the dust sensor alarm will be
disabled to allow economizer operation. This
is done because the compressor is disabled
below 0°F and the system would not have the
capability to cool.
FIGURE 45
Dust Sensor
Dust Sensor Failure Alarm
When the sensor reads a value that is outside of
the acceptable 0 to 100% range, an alarm will be
generated indicating the sensor has failed. This alarm
is just a notification and will not disable any other
features on the controller.
This alarm is fixed and cannot be adjusted.
High Dust Limit Alarm
When dust content in the air is high and is a risk
to prematurely reducing airflow through the filters,
the unit will restrict the use of the economizer. The
FIGURE 46
Adjusting Dust Sensor Alarm Setpoint
Damper Blade
The system utilizes three damper blades used to bring
in outdoor air and exhaust space air for economizer
operation. The damper blades are made of sheet metal
and are integrated into the equipment.
Damper Switch
The economizer utilizes a magnetic switch to determine
if the damper is operating correctly. This switch will be
closed when the damper is closed and open when the
damper is open.
Manual 2100-670I
Page 29 of 47
Page 30
To verify the status of the switch:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Digital In Config (C2); press ENTER key.
5. Reference the value located at 6Damp row and Val
column (see Figure 47).
6. The input will display ON when the damper is
closed (reflecting closed circuit on damper switch)
and will display OFF when the damper is open
(reflecting open circuit on damper switch).
FIGURE 47
Damper Switch
Damper Failed to Open Alarm
When the controller commands the economizer damper
actuator to a position other than 0% and the damper
switch indicates the damper is not open, after a delay
of 20 seconds the controller will generate a damper
failed to open alarm. This alarm is just a notification
and will not disable any features on the controller.
Disabling the damper switch in I/O Config disables this
alarm.
To adjust the damper failed to open delay:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A4); press ENTER key.
5. Press ENTER key to scroll to Open Delay (see
Figure 48).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
FIGURE 48
Adjusting Damper Alarm Delay
Damper Failed to Close Alarm
When the controller commands the economizer damper
actuator to the 0% position and the damper switch
indicates the damper is not closed, after a delay of 300
seconds the controller will generate a damper failed to
close alarm. This alarm is just a notification and will
not disable any features on the controller.
Disabling the damper switch in I/O Config disables this
alarm.
To adjust the damper failed to close delay:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A4); press ENTER key.
5. Press ENTER key to scroll to Close Delay (see
Figure 48).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
Outdoor Temperature and Humidity Combination
Sensor
The unit is equipped with a combination outdoor
temperature and humidity sensor to monitor
outdoor conditions for the economizer operation.
The temperature is measured with a 10k ohm NTC
thermistor. The humidity is measured with a humidity
sensor that outputs a 4-20mA signal to the controller.
The outdoor temperature can be verified by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Outdoor Air Sensor (C4); press ENTER key.
Manual 2100-670I
Page 30 of 47
Page 31
5. Reference the Value to see the input of the sensor
(see Figure 49).
6. To apply an offset, press ENTER key to scroll to
Offset.
7. Press UP or DOWN keys to change to the desired
value.
8. Press ENTER key to save the value.
FIGURE 49
Outdoor Air Sensor
The outdoor humidity can be verified by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Outdoor Hum Sensor (C7); press ENTER key.
5. Reference the Value to see the input of the sensor
(see Figure 50).
6. To apply an offset, press ENTER key to scroll to
Offset.
7. Press UP or DOWN keys to change to the desired
value.
8. Press ENTER key to save the value.
FIGURE 50
Outdoor Humidity Sensor
Outdoor Temperature Sensor Failure Alarm
When the sensor reads a value that is outside of the
acceptable -41 to 303.0° range, an alarm will be
generated indicating the sensor has failed. This alarm
condition will disable the economizer.
This alarm is fixed and cannot be adjusted.
Outdoor Humidity Sensor Failure Alarm
When the sensor reads a value that is outside of the
acceptable 0 to 100% RH range, an alarm will be
generated indicating the sensor has failed. This alarm
condition will disable the economizer when the mode is
set to temperature and humidity or enthalpy.
This alarm is fixed and cannot be adjusted.
Supply Temperature Sensor
The unit is equipped with a supply air temperature
sensor to monitor the leaving air temperature of the
unit. The temperature is measured with a 10k ohm
NTC thermistor.
The supply air temperature can be verified by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Supply Air Sensor (C6); press ENTER key.
5. Reference the Value to see the input of the sensor
(see Figure 51).
6. To apply an offset, press ENTER key to scroll to
Offset.
7. Press UP or DOWN keys to change to the desired
value.
8. Press ENTER key to save the value.
FIGURE 51
Supply Air Sensor
Manual 2100-670I
Page 31 of 47
Page 32
Supply Temperature Sensor Failure Alarm
When the sensor reads a value that is outside of the
acceptable -41.0 to 303.0° range, an alarm will be
generated indicating the sensor has failed.
This alarm is fixed and cannot be adjusted.
High Supply Air Temperature Alarm
When the supply air temperature measurement for
the economizer to be enabled is above the outdoor air
temperature setpoint (70°F) for 120 seconds, an alarm
will be generated and the economizer will be disabled
until the cooling call has been removed. This alarm will
automatically reset once the economizer is no longer
disabled.
To change the high supply air temperature alarm:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A5); press ENTER key.
5. Press ENTER key to scroll to Hi and Diff value (see
Figure 52).
6. Press UP or DOWN keys to change the differential
to the desired value.
7. Press ENTER key to save and scroll to the next
parameter.
FIGURE 52
Adjusting Supply Air Temperature Differential
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup (A5); press ENTER key.
5. Press ENTER key to scroll to Lo and Diff value (see
Figure 52).
6. Press UP or DOWN keys to change the differential
to the desired value.
7. Press ENTER key to save value and scroll to Delay.
8. Press UP or DOWN keys to adjust the delay value.
NOTE: This delay is also applied to the high supply air
temperature alarm.
9. Press ENTER key to save.
Economizer Operation
The economizer has four types of operation. The
first mode is "None" where the economizer is never
utilized, except for emergency purposes. The second
mode is "Dry Bulb" where the outdoor temperature
is the only consideration for economizer use on a
freecooling call. The third mode is "TempHum" where
the outdoor temperature and humidity are considered
for economizer use on a freecooling call. The fourth
mode is "Enthalpy" where the outdoor temperature,
humidity and calculated dew point are considered for
economizer operation on a freecooling call.
To change the economizer type:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Economizer Setup (A2); press ENTER key.
5. Press ENTER key to scroll to Type (see Figure 53).
Low Supply Air Temperature Alarm
When the supply air temperature is below 45°F for
120 seconds, an alarm will be generated and the
economizer will be disabled until the cooling call has
been removed. This alarm will automatically reset when
the economizer is no longer disabled.
To change the low supply air temperature alarm:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
Manual 2100-670I
Page 32 of 47
FIGURE 53
Economizer Setup
Page 33
6. Press UP or DOWN keys to change the Type
desired value to None, Dry Bulb, TempHum or Enthalpy.
7. Press ENTER key to save the value and scroll to
the next parameter.
NOTE:
The following parameters are for the temperature
consideration for economizer use. Applies to Dry Bulb, TempHum and Enthalpy type.
8. The cursor should now be on the Outdoor Set
parameter.
9. Press UP or DOWN keys to change the parameter
to the desired value.
10. Press ENTER key to save the value and scroll to
the next parameter.
11. The cursor should now be on Off Diff parameter.
12. Press UP or DOWN keys to change the parameter
to the desired value.
13. Press ENTER key to save the value and move to
the next parameter.
14. The cursor is now on the Mixed FC Set parameter.
15. Press UP or DOWN keys to change the parameter
to the desired value.
16. Press ENTER key to save the value.
17. Press the DOWN key to navigate to the A3 screen.
NOTE:
This screen will not display if economizer mode is
set to Dry Bulb or None. Also, the contents of the
screen will change when type is set to Enthalpy
(see Figure 54) as compared to when type is set
to TempHum (see Figure 58 on page 34). The
following menu shows the Enthalpy content which
also contains parameters that would be shown on
TempHum.
18. Press ENTER key to scroll to OA Humid Set (see
Figure 55).
19. Press UP or DOWN keys to change the humidity
setpoint to desired value.
20. If set to TempHum, continue on to Step 22. If set
to Enthalpy, press ENTER key to save the value
and scroll to OA Dew Pt Set.
21. Press UP or DOWN keys to adjust the outdoor dew
point setpoint for economizer operation to the
desired value.
22. Press ENTER key to save the value and scroll to On
Diff.
23. Press UP or DOWN keys to adjust the outdoor
humidity differential for which the economizer is
re-enabled.
24. Press ENTER key to save the value and scroll to
parameter Delay.
FIGURE 54
Economizer Setup – Enthalpy Control
FIGURE 55
Economizer Setup – TempHum Control
25. Press UP or DOWN keys to adjust the time the
actual measurements can be outside of the
disabling parameters before the economizer
operation is disabled.
26. Press ENTER key to save the value.
27. Press ESCAPE key several times to return to Main
Menu screen.
See Table 8 on page 34 for default settings for
economizer operation.
When the economizer is activated during a freecooling
call only, using any of the previously mentioned modes,
a 0-10v analog signal will be sent to the economizer
actuator. Regardless of economizer only, or optimized
cooling mode, the actuator will then open and close the
damper blades to maintain a supply air temperature of
55°F. During optimized cooling mode, the damper blades
will be limited to a max output of 60%. When the supply/
mixed air temperature increases, the damper will open
and when the mixed air temperature decreases, the
damper will close.
The economizer may be disabled by the LV if the system
determines it needs to enter dehumidification mode.
More information about the dehumidification sequence
can be found on page 15 and in the latest revision of
LV1000 Service Instructions 2100-673. In addition
to dehum mode, the economizer may be disabled for
5 minutes (adjustable) if the dust sensor indicates
the outdoor air may cause particulate buildup in the
Manual 2100-670I
Page 33 of 47
Page 34
TABLE 8
Economizer Default Settings
ModeConsiderationEconomizer Available for CoolingEconomizer Not Available for Cooling
Only
Temp
Temp & Humidity
* In Enthalpy mode, outdoor temperature, humidity and calculated dew point are all considered for economizer operation.
Temperature
Humidity
Enthalpy*
Dew Point
air filters. After the time has expired and on a call for
cooling, the economizer will open again to sample the
air. The wall-mount unit will either return to normal
operation or remain locked out for another 5 minutes.
When the outdoor air temperature
is below 70°F
LV Online: When the outdoor humidity
is below 80%
LV Offline: When the outdoor humidity
is below 60%
When the outdoor dew point
is below 55°F
To update model/serial numbers:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
When the outdoor air temperature
is above 75°F
LV Online: When the outdoor humidity
is above 80%
LV Offline: When the outdoor humidity
is above 60%
When the outdoor dew point
is above 60°F
ENGINEER password 9254.
Emergency Cooling Mode
If the shelter temperature is above the high temperature
alarm setpoint on the LV, the unit will be commanded
into emergency cooling mode. In this mode, the
unit will operate the economizer regardless of the
economizer setup, as long as the outdoor temperature is
below the indoor temperature. The cooling demand will
be automatically set to 100% in this mode, meaning
mechanical cooling should be operating at full capacity
while this mode is active. This will stay active until the
LV returns the unit to normal operation. This mode is
only available when connected to the LV.
Emergency Ventilation Mode
If a hydrogen detector is connected to the LV/FUSIONTEC system and there is a hydrogen alarm event, the
system will go into emergency ventilation mode. In
emergency ventilation mode, the economizers on the wall
units will be commanded to 100%. After 2 minutes, the
blowers will turn on in order to exhaust any hydrogen
gas buildup within the shelter. Once the hydrogen alarm
clears, the system will resume normal operation. This
mode is only available when connected to the LV.
3. Press UP or DOWN keys to scroll to Adv Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Factory Settings (B1).
5. Press ENTER key to advance the cursor to the digit
that needs changed in the model/serial number.
6. Press UP or DOWN keys to change value of the
digit.
7. Continue Steps 5 and 6 until the model/serial
number(s) are correct and reflect the number on
the product label.
For more information on the options and settings
available for specific model numbers, please see the
model number breakdown in Figure 57 on page 38.
Electric Heat Option
Electric Heat Components
Electric Heating Element
The unit is optionally equipped with a 1.5kw or 5kw
heat strip. The heat strip is located next to the blower
assembly and uses resistive heat.
Model/Serial Number Configuration
FUSION-TEC wall-mount units configure some settings
based on the model number that is input into the
unit. The model and serial numbers are entered at
the factory and should be retained during a software
update. However, after a software update, it is best
practice to verify that the model and serial numbers are
still present and accurate. If the model and/or serial
number is missing or incorrect, they will need to be
re-entered.
NOTE:
When re-entering the model number, only valid
model number entries will be accepted by the
Thermal Overload
The heater assembly has a thermal overload wired in
series with the heating element. This device has a
cycling limit which opens at 130°F and resets at 80°F.
The limit is also equipped with a redundant thermal
fuse that will open at 150°F.
Electric Heat Operation
The heat strip will be activated on a call for heat. This
call can be generated by the LV or the wall-mount unit
operating in stand alone mode.
PLC.
Manual 2100-670I
Page 34 of 47
Page 35
Bard Guard Anti-Theft System Option
The unit has the option to be shipped from the factory
with a low pressure switch, panel sensors and a speaker.
These devices are used with the Bard Guard BG1000 antitheft controller to provide an anti-theft measure. These
sensors and switch form a loop that when connected to
the BG1000 controller will cause the system to go into
alarm if any of the front panels or coil assemblies are
removed without being disarmed. The speaker provides an
audible alert that the system is being tampered with. The
Bard Guard anti-theft control sensor connection is wired
to terminals 7 and 8 on the wall-mount unit. The speaker
connection is wired to terminals 5 and 6 on the wallmount unit. See the latest revision of BG1000 Installation
Instructions 2100-672 for directions on connecting the
wall-mount units to the BG1000 controller.
Smoke Detector Unit Disable Option
The unit is equipped with an input that can be used
with a smoke detector or unit disable switch with a dry
contact. When this input indicates a smoke event, the
system will be shut down. The alarm will automatically
clear when the alarm condition is no longer present.
Inverter Option
The inverter is only used in applications where a
generator is not present and the wall-mount units must
run during a power loss event. The inverter will always
keep power available to the wall-mount units during a
power outage. In the event of a power outage, a power
loss relay in the FUSION-TEC
unit will be energized and will only allow the blower and
economizer to run while powering the controller. The
inverter converts either 24 VDC or 48 VDC, depending on
the model, to 230 VAC. A relay output from the inverter
will also communicate an alarm to the supervisory
controller in the event of an inverter failure. This variable
can be communicated through the Ethernet port for
integration into a building management system. The units
will continue to run in economizer-only operation until
power has been restored or the battery power has been
depleted.
When the FUSION-TEC
operating under inverter power, shelter economizer
cooling will only occur if outside temperatures fall below
indoor temperatures and blower speeds are slightly
reduced to conserve battery power.
HR Series
HR Series
wall-mount
wall-mount unit is
Manual 2100-670I
Page 35 of 47
Page 36
FUSION-TEC HR Series Wall-Mount Unit Control Board 8301-068-002*
Micro USB
Smoke Detector
Dirty Filter Switch
Compressor Alarm Relay
Damper Blade Switch
Airflow Switch
Digital Ground
Liquid Line Temp Sensor
Outdoor Air Temp Sensor
Return Air Temp Sensor
Supply Air Temp Sensor
Outdoor Humidity Sensor
Dust Sensor Board
Suction Temp Sensor
Analog Ground
24VDC to Outdoor Humidity Sensor
Liquid Pressure Transducer
Suction Pressure Transducer
Ground
Blower Motor Signal
Condenser Fan Motor
DI1
DI2
DI3
DI4
DI5
DI6
DI7
GND
B1
B2
B3
B4
B5
B6
B7
GND
+Vdc
B8
B9
GND
Y1
Y2
Y3
FIGURE 56
24VAC Hot24VAC Common
Control
Stand-by
BMS Card
EEV1
Rx+/Tx+
Rx-/Tx-
GND
FieldBus2
Jumper
NO8
NO9
+ Communication Wire
– Communication Wire
C1
NO1
NO2
NO3
C2
NO4
NO5
NO6
NO7
C7
NC7
C8
24VAC +
To CCM Y
Compressor Staging
Solenoid
24VAC +
Stage 1 Heat
24VAC +
Dirty Filter Light
Expansion Valve:
Purple, Yellow – 40 ohms
Red/White – 40 ohms
Red/Green – 40 ohms
White/Green – 80 ohms
Blue/Yellow – 83 ohms
* Asterisk represents letter at end of part number that designates software version (Example: 8301-068-002A).
Manual 2100-670I
Page 36 of 47
Page 37
TABLE 9
FUSION-TEC HR Series Wall-Mount Unit Control Board Terminals
TerminalFunctionTypeForm
Rx+/Tx+Communication
Rx-/Tx-Communication
DI1Smoke DetectorDigitalN/C
DI2Dirty Filter SwitchDigitalN/C
DI3Compressor Alarm RelayDigitalN/C
DI4Not Used
DI5Not Used
DI6Damper Blade SwitchDigitalN/C
DI7AirflowDigitalN/C
GNDDigital Ground
B1Liquid Line Temperature SensorAnalog Output10K Ohm Curve J
B2Outdoor Air Temperature SensorAnalog Output10K Ohm Type III (AN)
B3Return Air Temperature SensorAnalog Output10K Ohm Curve J
B4Supply Air Temperature SensorAnalog Output10K NTC Thermistor
B5Outdoor Humidity SensorAnalog Output
B6Dust Sensor BoardAnalog Output0-5VDC
B7Suction Temperature SensorAnalog Output10K Ohm Curve J
GNDAnalog Ground
+VDC24VDC to Outdoor Humidity Sensor
B8Liquid Pressure TransducerAnalog Output.5VDC to 4.5VDC
B9Suction Pressure TransducerAnalog Output.5VDC to 4.5VDC
Y1Blower Motor Signal
Y2Not Used
Y3Condenser Motor Signal
GNDGround
C124VAC+Power
NO1to CCM "Y"Relay Output
NO2Compressor Staging SolenoidRelay Output
NO3Not Used
C224VAC+Power
NO4Stage 1 HeatingRelay Output
NO5Not Used
NO6Not Used
NO7Not Used
C7Not Used
NC7Not Used
C824VAC+Power
NO8Dirty Filter LightRelay Output
GO24VAC Common
G24VAC Hot
Manual 2100-670I
Page 37 of 47
Page 38
FUSION-TEC HR Series Wall-Mount Unit Model Nomenclature
UNIT SERIES
MAXIMUM SENSIBLE CAPACITY
36 – 3 Ton 2 Stage Step Capacity
58 – 5 Ton 2 Stage Step Capacity
These units require R-410A refrigerant and
polyol ester oil.
General
1. Use separate service equipment to avoid cross
contamination of oil and refrigerants.
2. Use recovery equipment rated for R-410A
refrigerant.
3. Use manifold gauges rated for R-410A (800
PSI/250 PSI low).
4. R-410A is a binary blend of HFC-32 and HFC-
125.
5. R-410A is nearly azeotropic—similar to R-22 and
R-12. Although nearly azeotropic, charge with
liquid refrigerant.
6. R-410A operates at 40-70% higher pressure than
R-22, and systems designed for R-22 cannot
withstand this higher pressure.
7. R-410A has an ozone depletion potential of zero,
but must be reclaimed due to its global warming
potential.
8. R-410A compressors use polyol ester oil.
9. Polyol ester oil is hygroscopic; it will rapidly absorb
moisture and strongly hold this moisture in the oil.
10. A liquid line dryer must be used—even a deep
vacuum will not separate moisture from the oil.
11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug
compressor immediately after removal. Purge with
small amount of nitrogen when inserting plugs.
Topping Off System Charge
If a leak has occurred in the system, Bard
Manufacturing recommends reclaiming, evacuating
(see criteria above) and charging to the nameplate
charge. If done correctly, topping off the system charge
can be done without problems.
With R-410A, there are no significant changes in the
refrigerant composition during multiple leaks and
recharges. R-410A refrigerant is close to being an
azeotropic blend (it behaves like a pure compound or
single component refrigerant). The remaining refrigerant
charge in the system may be used after leaks have
occurred. “Top-off” the charge by utilizing the pressure
charts on the inner control panel cover as a guideline.
REFRIGERANT INFORMATION
REMEMBER: When adding R-410A refrigerant, it must
come out of the charging cylinder/tank as a liquid to
avoid any fractionation and to insure optimal system
performance. Refer to instructions for the cylinder that
is being utilized for proper method of liquid extraction.
Safety Practices
1. Never mix R-410A with other refrigerants.
2. Use gloves and safety glasses. Polyol ester oils can
be irritating to the skin, and liquid refrigerant will
freeze the skin.
3. Never use air and R-410A to leak check; the
mixture may become flammable.
4. Do not inhale R-410A—the vapor attacks
the nervous system, creating dizziness, loss
of coordination and slurred speech. Cardiac
irregularities, unconsciousness and ultimately
death can result from breathing this concentration.
5. Do not burn R-410A. This decomposition produces
hazardous vapors. Evacuate the area if exposed.
6. Use only cylinders rated DOT4BA/4BW 400.
7. Never fill cylinders over 80% of total capacity.
8. Store cylinders in a cool area, out of direct
sunlight.
9. Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge
lines or cylinders. R-410A expands significantly at
warmer temperatures. Once a cylinder or line is full
of liquid, any further rise in temperature will cause
it to burst.
Important Installer Note
For improved start-up performance, wash the indoor
coil with a dishwashing detergent.
R410-A Refrigerant Charge
This wall-mount unit was charged at the factory with
the quantity of refrigerant listed on the serial plate.
AHRI capacity and efficiency ratings were determined
by testing with this refrigerant charge quantity.
Table 10 on page 40 shows nominal pressures for the
units. Since many installation specific situations can
affect the pressure readings, this information should
only be used by certified technicians as a guide for
evaluating proper system performance. They shall not
be used to adjust charge. If charge is in doubt, reclaim,
evacuate and recharge the wall-mount unit to the serial
plate charge.
Manual 2100-670I
Page 39 of 47
Page 40
Pressure Service Ports
High and low pressure service ports are installed on all
wall-mount units so that the system operating pressures
can be observed. Pressures are shown in Table 10.
This unit employs high-flow Coremax valves instead of
the typical Schrader type valves.
TABLE 10
Cooling Pressures
Full Load CoolingAir Temperature Entering Outdoor Coil °F
WARNING! Do NOT use a Schrader valve core removal
tool with these valves. Use of such a tool could result
in eye injuries or refrigerant burns!
To change a Coremax valve without first removing the
refrigerant, a special tool is required which can be
obtained at www.fastestinc.com/en/SCCA07H. See the
replacement parts manual for replacement core part
numbers.
Model
HR36
HR58
Model
HR36
HR58
Return Air Temp
(DB/WB)
75/62
80/67
85/72
75/62
80/67
85/72
Part Load CoolingAir Temperature Entering Outdoor Coil °F
Return Air Temp
(DB/WB)
75/62
80/67
85/72
75/62
80/67
85/72
Pressure7580859095100 105 110 115 120 125
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Pressure7580859095100 105 110 115 120 125
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
130
290
139
297
144
307
129
318
138
326
143
337
119
268
127
275
131
285
135
283
144
290
149
300
131
312
140
320
145
331
130
340
139
349
144
361
125
288
134
295
139
305
136
304
145
312
150
323
132
334
141
343
146
355
131
365
140
374
145
387
131
308
140
316
145
327
136
327
145
335
150
347
134
359
143
368
148
381
132
389
141
399
146
413
136
331
145
339
150
351
137
350
146
359
151
372
135
384
144
394
149
408
133
414
142
425
147
440
140
354
150
363
155
376
137
375
147
385
152
398
136
411
145
422
150
437
134
440
143
451
148
467
143
378
153
388
158
402
138
402
148
412
153
426
137
439
147
450
152
466
136
467
145
479
150
496
146
405
156
415
161
430
138
428
148
439
154
454
138
468
148
480
153
497
137
495
146
508
151
526
148
432
158
443
164
459
140
456
150
468
155
484
139
498
149
511
154
529
137
527
147
537
152
556
149
460
159
472
165
489
141
486
151
498
156
515
140
530
150
544
155
563
139
553
149
567
154
587
150
490
160
503
166
521
142
416
152
529
157
548
142
564
152
578
157
598
140
584
150
599
155
620
149
522
159
535
165
554
143
547
153
561
158
581
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed and system evacuated and recharged to serial plate charge weight.
NOTE: Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check
condenser fan wiring. See “Condenser Fan Operation” on page 24.
Manual 2100-670I
Page 40 of 47
Page 41
MAINTENANCE
Standard Maintenance Procedures
!
WARNING
Electrical shock hazard.
Disconnect all power supplies before
servicing.
Failure to do so could result in electric shock
or death.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp
edges.
Failure to do so could result in personal
injury.
1. Disable system from LV1000 controller (see latest
revision of LV1000 Service Instructions 2100-
673).
2. Turn off AC breakers at wall-mount units.
3. Check inlet sides of condenser and evaporator coils
for obstructions/debris—clean if necessary using a
quality manufactured coil cleaning product specific
for the evaporator or condenser coil.
•
• Evaporator coil: Open filter access panels
Condenser coil: Remove the upper side panels
from the condenser section. This will give
clear access to the inlet side of the coil for
cleaning. Follow the coil cleaner manufacturer’s
directions for necessary safety gear and
precautions, as well as for application and use.
More than one application may be necessary.
Rinse thoroughly.
and remove filters. Apply specific evaporator
cleaner directly to the inlet side of coil, being
very careful not to overspray into insulation
or surrounding panels and wiring. Residual
cleaner and dissolved debris should drip into
the drain pan and leave the unit through the
condensate hose. More than one application
may be necessary. Rinse thoroughly.
4. Manually spin fan and blower motors to ensure
they turn freely. All motors are permanently
lubricated, so no oil is necessary.
5. Inspect free cooling damper actuator and linkage.
6. Install new air filter; check for additional filter
grilles internal to the structure.
7. Inspect the control panel of the system.
• Look for insect or rodent activity and remove
any nesting materials.
• Manually push contactor closed, observe for
movement—contactor points should have
minimal discoloration, no spalling or other
signs of arcing. Replace if doubtful.
• Check field and factory wiring for tightness and
look for signs of overheating (discoloration of
terminals or wire insulation).
8. Ensure that supply and return registers are not
obstructed, and more importantly, are not recycling
the air to one another. Adjust supply louvers if
necessary to direct discharge air away from any
direct route to the return grille.
Re-assemble wall-mount unit, turn breakers back on.
9.
10. Enable system to LV1000 controller (see latest
revision of LV1000 Service Instructions 2100-
673).
11. Repeat steps for additional wall-mount units.
Bard Guard Anti-Theft System Option
While the system is powered, push DISARM/RESET
button to disarm the system. Once the button is
pushed, the blue LED will illuminate. As long as
the blue LED is illuminated, the Bard Guard system
is disarmed and will remain disarmed depending
on the preset time for up to 250 minutes (default
approximatey 15 minutes). After the preset time
expires, the system will rearm automatically.
For situations that require an individual unit to be
disconnected from the Bard Guard security system for
an extended period of service time (longer than the
maximum 250 minutes disarm time), place a jumper
across the appropriate terminals on the BG1000
terminal block to temporarily remove the unit from the
security system. Be sure to remove the jumper from the
terminals after service has been completed.
See the latest revision of BG1000 Installation
Instructions 2100-672 for information on operating the
BG1000 controller.