Bard FUSION-TEC HR36APA, FUSION-TEC HR36APB, FUSION-TEC HR58APA, FUSION-TEC HR58APB Service Instructions Manual

SERVICE INSTRUCTIONS
®
FUSION-TEC
WALL-MOUNT
AIR CONDITIONER
Models:
HR36APA HR36APB HR58APA HR58APB
Part of the Bard Free Cooling System
multiple HR**AP* units are used.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com
Manual: 2100-670I Supersedes: 2100-670H Date: 9-26-18
Page 1 of 47
CONTENTS
Using the TEC-EYETM .................................................... 6
TEC-EYE Hand-Held Diagnostic Tool ............................6
TEC-EYE Menu Structure .....................................7
TEC-EYE
Main Status Screen .............................................7
Quick Menu .......................................................8
Setpoints ....................................................8
Information .................................................8
Staging Information ..............................8
Stand Alone Demand and Staging ..........8
Master Staging .....................................8
A/C Circuit Measurements ......................9
Last 24 Hour Operation .........................9
Software Version ...................................9
Alarm Log ...................................................9
Addressing Wall-Mount Units .............................10
Executing a Run Test ........................................10
Run Test Parameter Descriptions .................11
Reset to Factory Defaults ...................................11
Acronyms .............................................7
Operation .....................................................................12
Unit On/Off .............................................................12
Alarm Adjustment ..................................................12
Acknowledging Alarms.......................................12
Clearing Alarms ................................................12
Clearing Alarm Logs and Counters ......................12
Exporting Alarm Logs ........................................12
Exporting 7 Day Logs ........................................12
Stand Alone (Orphan) Mode ......................................12
Temperature/Humidity Control ...................................13
Temperature/Humidity Control Components .........13
Return Air Temperature Sensor ....................13
Return Air Temperature Alarm ..............13
Temperature/Humidity Control Operation .............13
Cooling .....................................................13
Cooling w/No Economizer ...........................13
Heating .....................................................15
Staging .....................................................15
Dehumidification .......................................15
Electronic Expansion Valve (EEV) ..............................15
EEV Components ..............................................15
Electronic Expansion Valve .........................15
EEV Instructions for Vacuum,
Reclaim, Charge Unit ..........................15
System Pressures ................................16
Suction Pressure Transducer .......................16
Troubleshooting the Suction
Pressure Transducer ............................17
Suction Pressure Alarm .......................17
Suction Temperature Sensor .......................17
Suction Temperature Alarm ..................17
EEV Operation ..................................................18
EEV Superheat Control ...............................18
Additional EEV Alarms ......................................18
Low Superheat Alarm .................................18
Indoor Airflow ..........................................................18
Indoor Airflow Components ................................18
Blower ......................................................18
Blower Status Switch ..........................19
Blower Status Alarm ............................20
Filters .......................................................20
Evaporator Freeze Condition Alarm ..........
17
Dirty Filter Switch ......................................20
Dirty Filter Alarm ................................20
Filter Indicator Light ..................................20
Freezestat .................................................20
Indoor Airflow Operation ....................................20
Blower Speed Control .................................20
Additional Indoor Airflow Alarms ........................22
Supply Air Temperature Alarm .....................22
Condenser Fan ........................................................22
Condenser Fan Components ...............................22
Condenser Fan ..........................................22
Liquid Line Pressure Transducer ..................22
Troubleshooting the Discharge/
Liquid Pressure Transducer ..................23
Discharge/Liquid Pressure
Transducer Alarm ................................23
Liquid Temperature Sensor .........................23
Condenser Fan Operation ...................................23
Condenser Fan Speed Control .....................23
Mechanical Cooling Only .....................23
Optimized Cooling (Concurrent Economizer and Mechanical
Cooling) .............................................23
High Pressure Control .................................24
Condenser Fan Speed ..........................24
Second Stage Drop Out .......................24
Low Ambient Control ..................................24
Additional Condenser Fan Alarms .......................24
Dirty Condenser Coil Alarm .........................24
Compressor .............................................................25
Compressor Components ...................................25
Compressor ...............................................25
Compressor Control Module (CCM) ..............25
Delay-on-Make Timer ...........................25
Short Cycle Protection/
Delay-on-Break ...................................25
High Pressure Detection ......................25
Test Mode ..........................................26
High Pressure Safety Switch .......................27
Refrigerant High Pressure Alarm ...........27
Phase Monitor ...........................................27
Compressor Operation .......................................27
Additional Compressor Alarms ............................28
Refrigerant Low Pressure Alarm ...................28
Economizer .............................................................28
Economizer Components ...................................28
Actuator ....................................................28
Dust Sensor ..............................................28
Dust Sensor Failure Alarm ...................29
High Dust Limit Alarm .........................29
Damper Blade ...........................................29
Damper Switch ..........................................29
Damper Failed to Open Alarm ..............30
Damper Failed to Close Alarm ..............30
Outdoor Temperature and Humidity
Combination Sensor ...................................30
Outdoor Temperature Sensor
Failure Alarm ......................................31
Outdoor Humidity Sensor
Failure Alarm ......................................31
Brownout Protection w/Adjustment ..........
26
Manual 2100-670I Page 2 of 47
Supply Temperature Sensor ........................31
Supply Temperature Sensor
Failure Alarm ......................................32
High Supply Air Temperature Alarm ......32
Low Supply Air Temperature Alarm .......32
Economizer Operation .......................................32
Emergency Cooling Mode..........................................34
Emergency Ventilation Mode .....................................34
Model/Serial Number Configuration ...........................34
Electric Heat Option ................................................34
Electric Heat Components .................................34
Electric Heating Element ............................34
Thermal Overload .......................................34
Electric Heat Operation .....................................34
Bard Guard Anti-Theft System Option ........................35
Smoke Detector Unit Disable Option ..........................35
Inverter Option ........................................................35
Refrigerant Information ...........................................39
General ...................................................................39
Topping Off System Charge .......................................39
Safety Practices .......................................................39
Important Installer Note ...........................................39
R410-A Refrigerant Charge .......................................39
Pressure Service Ports ..............................................40
Maintenance ................................................................ 41
Standard Maintenance Procedures ............................41
Bard Guard Anti-Theft System Option ........................41
Troubleshooting .........................................................42
8301-067 Outdoor Temperature/Humidity Sensor .......42
8408-044 Return Air Sensor/Suction Sensor ..............45
8301-066 Supply Air Sensor ....................................46
8
301-057 Blower Status Switch/Dirty Filter Switch ........
47
FIGURES AND TABLES
Figure 1 TEC-EYE Display and Interface ......................6
Figure 2 TEC-EYE Connection to Unit Control ..............6
Figure 3 Quick Menu Icons ........................................8
Figure 4 Cool and Heat Setpoints ...............................8
Figure 5 Stand Alone Demand and Staging .................8
Figure 6 Master Staging ............................................8
Figure 7 A/C Circuit Measurements .............................9
Figure 8 Last 24 Operation ........................................9
Figure 9 Software Version ..........................................9
Figure 10 Changing Unit Address ...............................10
Figure 11 Executing Run Test ....................................10
Figure 12 Run Test Summary .....................................10
Figure 13 Run Test: Motors & Sensors ........................11
Figure 14 Run Test: A/C Circuit ..................................11
Figure 15 Restoring Factory Default Settings ...............11
Figure 16 Clearing All Alarms ....................................12
Figure 17 Clearing Alarm Logs and Counters ...............12
Figure 18 Adjusting Return Air Sensor ........................13
Figure 19 Cooling w/Economizer ................................14
Figure 20 Cooling w/No Economizer ...........................14
Figure 21 Heating .....................................................14
Figure 22 Viewing Unit Stages ...................................15
Figure 23 Overriding EEV Output ...............................15
Figure 24 Electronic Expansion Valve (EEV) and
Service Tool ...............................................16
Figure 25 Adjusting Suction Sensor/Transducer
Pressure Values .........................................16
Figure 26 Voltage to Pressure: Suction Pressure
Transducer ................................................17
Figure 27 Adjusting Suction Temperature Sensor
Values.......................................................17
Figure 28 Adjusting Freeze Setpoint and Alarm Delay ..18 Figure 29 Figure 30
Figure 31 Verifying Differential Airflow Status ..............19
Figure 32 Adjusting Air Flow Alarm Delay ...................20
Figure 33 Dirty Filter Switch and Filter Indicator Light .21
Figure 34 Verifying Condenser Fan Output ..................22
Figure 35 Fan Blade Setting ......................................22
Figure 36 Adjusting Discharge/Liquid Transducer
Pressure Values .........................................23
Figure 37 Voltage to Pressure: Discharge/Liquid
Pressure Transducer ...................................23
Figure 38 Adjusting Discharge/Liquid Temperature
Input ........................................................23
Figure 39 Condenser Fan Speed Control .....................24
Figure 40 Adjusting Dirty Condenser Coil Alarm
Settings ....................................................25
Figure 41
Figure 42 Adjusting Compressor Delays ......................27
Figure 43
Figure 44 Damper Override ........................................28
Figure 45 Dust Sensor ..............................................29
Figure 46
Figure 47 Damper Switch ..........................................30
Figure 48 Adjusting Damper Alarm Delay ....................30
Figure 49 Outdoor Air Sensor .....................................31
Figure 50 Outdoor Humidity Sensor ............................31
Figure 51 Supply Air Sensor ......................................31
Figure 52 Adjusting Supply Air Temperature
Differential ................................................32
Figure 53 Economizer Setup ......................................32
Figure 54 Figure 55
Figure 56 Wall-Mount Unit Control Board ....................36
Figure 57 Wall-Mount Unit Model Nomenclature .........38
Figure 58 8301-067 Sensor Dip Switches and
Terminal Block ..........................................42
Figure 59
Table 1 Table 2
Table 3A HR36AP* Blower Speeds ...........................18
Table 3B HR58AP* Blower Speeds ...........................19
Table 4 Rated Airflow .............................................19
Table 5 Indoor Blower Performance .........................19
Table 6 Maximum ESP of Operation:
Electric Heat Only ......................................19
Table 7 Filter Switch Pressure Settings ....................21
Table 8 Economizer Default Settings .......................34
Table 9
Table 10 Cooling Pressures ......................................40
Table 11 8301-067 Sensor: Temp/Resistance ............43
Table 12 8301-067 Sensor: Humidity/mA .................44
Table 13 8408-044 Sensor:
Temperature/Resistance Curve J ..................42
Table 14
Putting Blower Output into Override Mode ......
Dirty Filter Switch/Blower Status Switch ........
8201-164 Compressor Control Module
Adjusting Low Pressure Alarm Settings ...........
Adjusting Dust Sensor Alarm Setpoint
Economizer Setup – Enthalpy Control ...........
Economizer Setup – TempHum Control ...........
8301-057 Air Differential Switch Terminals...
LV1000/TEC-EYE Passwords (Defaults)
Unit Status Messages ......................................
Wall-Mount Unit Control Board Terminals ......
8301-066 Sensor: Temperature/Resistance ...
...........26
............29
18 19
28
33 33
47
.............6
37
46
7
Manual 2100-670I Page 3 of 47
GENERAL INFORMATION
Free Cooling Unit System
This Bard Free Cooling Unit System is composed of FUSION-TEC HR Series wall-mounted air conditioners matched with an LV1000 lead/lag controller. The wall mounts are specifically engineered for telecom/motor control center rooms.
NOTE: The LV1000 lead/lag controller and FUSION-
TEC HR Series wall-mount units are designed specifically to work together. The controller cannot run other Bard models or other brands of systems, nor can other controllers run the FUSION-TEC HR Series wall-mount units. They are a complete system, and must be used together.
Wall-Mount Air Conditioner Units
The FUSION-TEC power.
The units will supply 100% of rated cooling airflow in free cooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.
Each of these units are fully charged with refrigerant and have optional auxiliary heat.
HR Series
units operate on VAC
General
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use without duct work. Flanges are provided for transition from unit to wall grilles.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Additional Publications for information on codes and standards.
Sizing of systems for proposed installation should be based on heat loss and heat gain calculations made according to methods of Air Conditioning Contractors of America (ACCA). The supply flange should be installed in accordance with the Standards of the National
Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with
instructions, installer should adhere to local codes.
Shipping Damage
Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
These units must remain in upright position at all times.
Additional Publications
These publications can help when installing the air conditioner. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI) 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE)
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA) Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-670I Page 4 of 47
ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
NOTICE: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to “NOTICE” the word “CAUTION” without the safety alert symbol may be used to indicate a message not related to personal injury.
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
!
WARNING
Fire hazard.
Maintain minimum 1/4" clearance between the
supply ange and combustible materials.
Failure to do so could result in re causing damage, injury or death.
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.
Manual 2100-670I Page 5 of 47
USING THE TEC-EYE
TEC-EYE (Bard P/N 8301-059) Display and Interface (Status Screen Shown)
TM
FIGURE 1
ALARM KEY
MENU KEY
ESCAPE KEY
ALARM KEY
Allows viewing of active alarms Silences audible alarms Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level Cancels a changed entry
TEC-EYE Hand-Held Service Tool
The TEC-EYE service tool is used to communicate with the FUSION-TEC unit logic board. By connecting directly to the logic board inside the unit control panel, it is possible to perform diagnostics on the unit, adjust certain settings and verify unit and economizer operation through a run test procedure. The TEC-EYE service tool is required for unit setup and operation. The TEC-EYE is supplied with the LV1000 controller but can also be ordered separately (Bard P/N 8301-059).
The menu driven interface provides users the ability to scroll through two menu levels: Quick Menu and Main Menu. The menus permit the user to easily view, control and configure the unit.
The controller is completely programmed at the factory; the default setpoints and their ranges are easily viewed and adjusted from the TEC-EYE display. The program and operating parameters are permanently stored on FLASH-MEMORY in case of power failure.
The TEC-EYE connects to the wall-mount unit control board via an RJ11 modular phone connector as shown in Figure 2.
When not being used, the TEC-EYE hand-held diagnostic tool should be stored inside or near the LV1000 controller. Do not let the TEC-EYE leave the shelter site.
UP KEY
ENTER KEY
DOWN KEY
UP KEY
Steps to next screen in the display menu Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field Advances cursor
DOWN KEY
Steps back to previous screen in the display menu Changes (decreases) the value of a modifiable field
FIGURE 2
TEC-EYE Connection to Unit Control
Modular Phone Connector for TEC-EYE Hand-Held Diagnostic Tool
TABLE 1
LV1000/TEC-EYE Passwords (Defaults)
User 2000
Technician 1313
Engineer 9254
Use UP or DOWN keys and ENTER key to enter password
Manual 2100-670I Page 6 of 47
TEC-EYE Screen Structure and Password Level
Quick Menu Setpoints (Stand Alone Temperature Control) Information Alarm Log Main Menu System Config: A1-A10 User (2000) Adv Sys Config: B1-B5 Technician (1313) I-O Config: C1-C16 Technician (1313) On/Off: User (2000) Alarm Logs: User (2000) Settings Date/Time: Technician (1313) Language: User (2000) Import/Export Parameter Config: Engineer (9254) Alarm Export: User (2000) Trend Log Export: User (2000) Initialization Clear Logs: User (2000) System Default: Engineer (9254) Serial Ports: Technician (1313) Change Passwords Logout
In addition to the menu structure above, there are also Status and Alarm screens.
TEC-EYE Acronyms
MAT – Mixed air temperature (calculated value) RAT – Return air temperature SAT – Supply air temperature OAT – Outdoor air temperature OAH – Outdoor air humidity ODP – Outdoor dew point (calculated value) Blower – Indoor blower speed Fan – Outdoor fan speed Damper – Free cooling damper position FC – Free cooling status CL1 – Compressor stage 1 status CL2 – Compressor stage 2 status H1 – Heater stage 1 status H2 – Heater stage 2 status ST – Number of start requests in last hour
NOTE: Digital refers to On/Off whereas analog is a
variable input.
Main Status Screen
The main Status screen is the default start-up screen and also the return screen after 5 minutes of no activity. The screen can be accessed at any time by pressing the ESCAPE key repeatedly.
The wall-mount unit address is displayed in the upper right corner on the main Status screen (see Figure
1). The main Status screen also shows the current date, time, return air temperature (RAT), mixed air temperature (MAT), supply air temperature (SAT) outdoor air temperature (OAT), outdoor air humidity (OAH) and outdoor dew point (ODP) conditions. Blower
speed, condenser fan speed, damper position and unit status are also displayed. See Table 2 for wall-mount unit status messages.
TABLE 2
Unit Status Messages
Message Description
Waiting...
Stand Alone
LV Online
Cont. Blower
Power Loss
Freecooling Unit is actively economizing.
Optimized Cool
Cooling Unit is actively mechanical cooling.
Heating Unit is actively heating.
Passive Dehum
Active Dehum
Self Test Unit is performing a self test.
Off by Alarm
Off by DI
Off by LV
Off by Keyboard
Override Active
Emergency Vent
Emergency Cool
Emergency Off
PLC is on and has not started running the application yet.
Unit is on and in orphan mode with no calls for heating or cooling.
Unit is on and communicating with the LV1000 with no heating or cooling calls.
Unit is operating with continuous blower when no heating or cooling calls are present.
Unit has experienced a loss of main utility power. Alarm only available with inverter units.
Unit is mechanical cooling while actively economizing.
Unit is taking measures to decrease humidity without using extra energy.
Unit is taking active measures to decrease humidity.
Unit has major fault preventing operation.
Unit is disabled by the local unit disable/smoke input.
Unit has been turned off by the supervisory controller.
Unit has been turned off by the local user.
There is an active override on the system.
Unit is in Emergency Ventilation. LV1000 has an active hydrogen alarm.
Unit is in Emergency Cooling. Indoor temperatures have exceded high temp alarms.
Unit is in Emergency Off. LV1000 has an active smoke alarm.
Manual 2100-670I Page 7 of 47
The Quick Menu is accessible from the main Status screen. Setpoints, Information and Alarm Log are available through the Quick Menu. Pressing the UP or DOWN keys while on the main Status screen will change the Quick Menu icon displayed (see Figure 3). Press the ENTER key when the desired icon is displayed.
FIGURE 3
Quick Menu Icons
Alarm Log Information
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
Quick Menu
Setpoints
From this screen, the local unit heating and cooling setpoints, used for stand alone operation only, can be changed.
Once the supervisory controller is connected, cooling and heating setpoints will be communicated and local cooling and heating setpoints will be replaced with the communicated cooling and heating setpoints.
If at any time the wall-mount unit(s) loses communication with the LV1000 controller, the wall-mount unit(s) will go into stand alone mode and operate using the last communicated setpoints.
To verify or change the wall-mount unit cooling and heating setpoints in stand alone mode:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the unit.
2. From the Status screen, press UP or DOWN key
until Quick Menu displays Setpoints icon. Press ENTER key.
3. Press ENTER key to scroll to the selected choice
(see Figure 4).
Setpoints
FIGURE 4
Cool and Heat Setpoints
4. Press UP or DOWN key on desired value until value displays correctly.
5. Press ENTER key to save and scroll to next parameter.
6. Press ESCAPE key until Main Menu screen is displayed.
Information
The information screens are used as a quick reference to show unit operational information such as staging, A/C circuit measurements, last 24 hour run times, component lifetime hours and software versioning.
Staging Information
Staging information is used to show any unit operation that should be taking place. The look of the staging display depends on if the unit is communicating with a supervisory controller.
Stand Alone Demand and Staging
If the unit is operating in a stand alone mode, the title will display as Unit Demand (see Figure 5). This signifies that the local unit has control of the unit heating and cooling stages.
FIGURE 5
Stand Alone Demand and Staging
Master Staging
If the unit is communicating with a supervisory controller, the title will display as Master Staging (see Figure 6). This signifies that the supervisory controller has control of the unit heating and cooling stages.
FIGURE 6
Master Staging
Manual 2100-670I Page 8 of 47
A/C Circuit Measurements
A/C Circuit Information can be found in two screens within the information menu (see Figure 7). The information and measurements provided are liquid line temperature, liquid line pressure, condensing saturated temperature, suction line temperature, suction line pressures, suction saturated temperature, super heat, sub-cooling and electronic expansion valve position.
Software Version
The Software Version screen displays the model number of the unit as well as all software version information for the PLC (see Figure 9). This information can be used to determine whether a software update may be required based on information found in the software change log. This change log can be found at http://www.bardhvac.com/software-download/.
FIGURE 7
A/C Circuit Measurements
FIGURE 9
Software Version
NOTICE
It is important to check the software version
during installation to ensure that the latest
version has been installed. Current software
versions, change log and installation
instructions are available on the Bard website at
http://www.bardhvac.com/software-download/
Last 24 Hour Operation
Last 24 Hour Operation information tracks the runtimes (Time) and start calls (Start) of different components or operations in the last 24 hour period (see Figure 8).
FIGURE 8
Last 24 Hour Operation
Alarm Log
The alarm log screens show a log of each alarm. There will be a log for when alarm occurred and if the alarm auto clears, it will show when the alarm cleared.
Manual 2100-670I Page 9 of 47
Addressing Wall-Mount Units
Each unit must have a unique address for the system to operate correctly with the LV controller (Ex: 1, 2, 3, 4 depending on the number of units). The wall-mount unit address is displayed in the upper right corner on the Status screen on the TEC-EYE display (see Figure 1 on page 6).
To change the unit address:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Unit Setup (A1) screen.
5. Press ENTER key to scroll to Controller Address (see Figure 10).
6. Press UP or DOWN keys to change the address to a value between 1 and 4.
7. Press ENTER key to save
FIGURE 10
Changing Unit Address
6. Press UP or DOWN key to change value to ON. The run test will begin and the screen will change to
Run Test Summary.
FIGURE 11
Executing Run Test
7. Press UP or DOWN key to scroll between Run Test Summary, Motors & Sensors and A/C Circuit
screens.
NOTE:
If the Run Test screens have been exited out of, they can be returned to by navigating to Run Test (A10) as provided in the instructions above, pressing ENTER key to scroll to Return to Screens, pressing UP or DOWN key to change value to YES and pressing ENTER key.
Executing a Run Test
This unit has the ability to perform a run test that will operate all available unit functions in order to quickly determine unit operation. Some unit parameters are adjustable.
To execute a run test:
1. Press MENU key to access the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Run Test (A10) screen.
5. Press ENTER key to scroll to Run Test Enable parameter (see Figure 11).
The Run Test Summary screen (Figure 12) contains a readout of the test that is currently taking place, and the Task the technician should be completing to verify operation.
FIGURE 12
Run Test Summary
The Motors & Sensors screen (Figure 13) displays output and estimated positional values for unit motors and actuators, and also temperature and humidity sensor values.
Manual 2100-670I Page 10 of 47
FIGURE 13
Run Test: Motors & Sensors
The A/C Circuit screen (Figure 14) displays all unit inputs, outputs and calculations associated with the A/C circuit operation.
FIGURE 14
Run Test: A/C Circuit
7. Press UP or DOWN key to change value to YES; press ENTER key.
8. System will restart with default values.
FIGURE 15
Restoring Factory Default Settings
Run Test Parameter Descriptions
Econ Stage Time: Amount of time (in seconds) allowed for damper blade movement in each direction.
Cool Stage Time: Amount of time (in seconds) allowed for each stage of cooling.
Heat Stage Time: Amount of time (in seconds) allowed for heating stage.
Reset to Factory Defaults
To reset to factory default settings:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter ENGINEER password 9254.
3. Press UP or DOWN keys to scroll to Settings; press ENTER key.
4. Press UP or DOWN keys to scroll to Initialization; press ENTER key.
5. Press UP or DOWN keys to scroll to the Default Installation screen; press ENTER key.
6. Press ENTER key to scroll to Reset to Factory Defaults (see Figure 15).
Manual 2100-670I Page 11 of 47
OPERATION
NOTE: Screenshots shown in this manual reflect
default settings (when applicable).
Unit On/Off
The wall-mount unit can be turned on and off from the TEC-EYE. Turning the unit off with the following instructions will disable all unit operation.
To turn the unit on or off:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to On/Off; press ENTER key.
4. Press UP or DOWN keys to change value from On to Off or from Off to On.
5. Press ESCAPE key several times to return to Main Menu screen.
The wall-mount unit may also be turned off by certain alarms such as the smoke alarm input on the wall­mount unit board or the return air temperature sensor failure when not connected to the LV1000.
Alarm Adjustment
Acknowledging Alarms
Alarm conditions activate a red LED indicator that backlights the ALARM function key. As an option, an alarm condition may also be enunciated by an audible alarm signal. An alarm is acknowledged by pressing the ALARM key. This calls up alarm display screen(s) that provide a text message detailing the alarm condition(s).
Clearing Alarms
Alarms can only be cleared after the alarm condition has been corrected. To clear a single alarm, press and hold the ALARM key for 3 seconds while viewing a specific alarm screen. To clear all alarms, navigate to the screen at the end of the alarm list (shown in Figure
16) and press and hold the ALARM key for 3 seconds.
FIGURE 16
Clearing All Alarms
Clearing Alarm Logs and Counters
To clear the alarm log and alarm counters:
1. Press MENU key to go to the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter USER password 2000.
3. Press UP or DOWN keys to scroll to Settings; press ENTER key.
4. Press UP or DOWN keys to scroll to Initialization; press ENTER key. (Alarm Management screen will be displayed.)
5. Press ENTER key to scroll to Clear Alarm Logs? (see Figure 17).
6. Press UP or DOWN key to change value to YES; press ENTER key.
7. Press ENTER key to scroll to Clear Counters.
8. Press UP or DOWN key to value to YES; press ENTER key.
FIGURE 17
Clearing Alarm Logs and Counters
Exporting Alarm Logs
See latest version of Supplemental Instructions manual 7960-815 for information on exporting alarm logs.
Exporting 7 Day Logs
See latest version of Supplemental Instructions manual 7960-816 for information on exporting 7 day I/O logs.
Stand Alone (Orphan) Mode
FUSION-TEC HR Series wall-mount units have the capability to run without the LV1000 controller attached—this feature is called stand alone or orphan mode. This keeps the shelter between 45°F and 79°F (factory default settings) by the use of the factory-installed return air sensor in each wall-mount unit. In stand alone mode, no auxiliary temperature measurement devices are required for operation. The wall-mount unit automatically uses a continuous blower setting to circulate room air into the return air inlet and
Manual 2100-670I Page 12 of 47
uses the return air temperature sensor to control room temperature.
To change default setpoints, refer to Setpoints on page 8.
During installation, the ability to run in stand alone mode allows deactivation of one of the existing, older wall-mount units, while keeping the shelter cool with the other unit still operating. Once the first of the Bard FUSION-TEC HR Series wall-mount units is installed and powered on, it will operate in orphan mode— keeping the climate inside the shelter stable and the installers comfortable while the remainder of the older equipment is removed and the remaining Bard FUSION-TEC HR Series wall-mount units and LV1000 controller are installed.
Additionally, should any or all of the FUSION-TEC HR Series wall-mount units lose communication with the LV1000 controller (such as during maintenance), they will continue to serve the shelter’s needs until a repair can be made.
Temperature/Humidity Control
Temperature/Humidity Control Components
Return Air Temperature Sensor
The unit is equipped with a return air temperature sensor to monitor the space temperature when the unit is in stand alone mode. The return air sensor is located in the upper part of the return opening in such a way that it is exposed to the entering airstream. An alarm signal will be sent to the LV controller if the return air temperature sensor is disconnected. The temperature is measured with a 10k ohm NTC thermistor.
This sensor can be verified and adjusted by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config; press ENTER key.
4. Press UP or DOWN keys to scroll to Return Air Sensor (C5); press ENTER key.
5. Verify the measurement displayed on screen is accurate (see Figure 18).
6. If the measurement needs to be adjusted, apply an offset value by pressing ENTER to scroll to Offset.
7. Press UP or DOWN keys to adjust the offset.
8. The update will not take effect until the cursor is moved out of the Offset parameter.
9. Once adjusted, press the ESCAPE key several times to return to Main Menu screen.
FIGURE 18
Adjusting Return Air Sensor
Return Air Temperature Alarm
When the return air temperature sensor value is out of range (-41.0 to 303.0°F), the controller will generate a sensor failure alarm to indicate the sensor is not working properly.
This alarm is fixed and cannot be adjusted.
Temperature/Humidity Control Operation
The unit utilizes a PID control loop for space control. This control will compare the space temperature to the space setpoint. Based on how far away from the setpoint the temperature is, the loop will output a cooling or heating capacity number between 0 and 100%. The unit will then take all of the available cooling methods and distribute them evenly across the 0-100% range. The stages are then brought on as the heating or cooling capacity reaches the percentage that brings the stages on or off. There are separate setpoints for cooling and heating.
To change or view the unit setpoint:
1. From the Status screen, press UP or DOWN key until Quick Menu displays Setpoints icon ( ). Press ENTER key.
2. Press ENTER key to scroll to Cool Setpoint or Heat Setpoint (see Figure 4 on page 8).
3. Press UP or DOWN keys to change the value to desired heating and/or cooling setpoint.
Cooling
The unit is equipped with 1 stage of freecooling and 2 stages of mechanical cooling (compressor and solenoid) for a total of 3 cooling stages (see Figure 19 on page
14).
Cooling w/No Economizer
The unit is equipped with 1 stage of freecooling and 2 stages of mechanical cooling (compressor and solenoid). However, the outdoor conditions are not favorable for economizer operation so there are a total of 2 cooling stages (see Figure 20 on page 14).
Manual 2100-670I Page 13 of 47
Freecooling
Compressor Stage 1
Compressor Stage 2
FIGURE 19
Cooling w/Economizer
-10% 0%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Off
Deadband On
110% 120%
Deadband(sometimes called a neutral zone or dead zone) is an interval of a signal domain or band where no action occurs
FIGURE 20
Cooling w/No Economizer
Compressor Stage 1
Compressor Stage 2
-10% 0%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Off
Deadband On
Deadband(sometimes called a neutral zone or dead zone) is an interval of a signal domain or band where no action occurs
110% 120%
Electric Heat
-10% 10% 30% 50% 70% 90% 110%
Deadband(sometimes called a neutral zone or dead zone) is an interval of a signal domain or band where no action occurs
Manual 2100-670I Page 14 of 47
Off
FIGURE 21
Heating
Deadband On
Heating
The unit is equipped with 1 stage of electric heat (see Figure 21).
Staging
The unit will stage the cooling components based on the cooling demand referenced in the temperature control. The unit will stage the economizer on first if the indoor and outdoor conditions are favorable. The compressor stage 1 will be enabled next as the demand increases. Finally, the compressor stage 2 will be enabled as the demand continues to increase.
The unit is only equipped with one stage of heat and will turn on based on the heating demand.
To view unit stages:
1. From the Status screen, press UP or DOWN key until Quick Menu displays Unit Information icon
( ). Press ENTER key.
2. The cooling and heating demand are visible on this screen. The unit stages will display here when active as FC, CL1, CL2 or H1 (see Figure 22).
FIGURE 22
Viewing Unit Stages
Electronic Expansion Valve (EEV)
EEV Components
Electronic Expansion Valve
The electronic expansion valve is a stepper motor that is controlled with a step output from the controller. The valve is capable of 480 steps represented by a 0-100% signal on the controller. The motor drives a needle valve that regulates the flow of refrigerant.
EEV Instructions for Vacuum, Reclaim, Charge Unit
The electronic expansion valve moves to the 20% open position when the unit is not actively cooling. The valve may need to be manually positioned for service or troubleshooting. The valve can be positioned by using a menu override.
To manually override the valve:
NOTE: The unit must be off to perform this override.
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config; press ENTER key.
4. Press UP or DOWN keys to scroll to TEEV Service (C16); press ENTER key.
Press ENTER key to scroll to Enable (see Figure 23).
5.
6.
Press UP or DOWN key to change Disable to Enable.
7. Press ENTER key to scroll to Position.
8. Press UP or DOWN keys to adjust to the desired value.
9. Press ENTER key to save.
Dehumidification
The unit uses a dehumidification sequence that does
not require the electric heat to run at the same time as the compressor. Instead, the unit will turn on the compressor to cool down to the heating setpoint. Once the lower setpoint has been reached, the unit will heat the space back up to the upper setpoint. This cycle continues until the humidity level in the shelter reaches an acceptable level. At this point, the unit will revert back to normal operation. The economizer will also be disabled while the unit is in the dehumidification mode.
NOTE: This feature is dependent upon the LV1000
indoor humidity sensors and a command from the LV to enter dehumidification mode. See the latest revision of LV1000 Service Instructions 2100-673 for adjustment of the dehumidification setpoint and differentials.
FIGURE 23
Overriding EEV Output
The valve can also be opened or closed using the EEV service tool (Bard Part # 2151-021). This magnetic EEV service tool (shown in Figure 24 on page 16) is used to manually open the EEV. To do this, remove the EEV stator coil (red color with retaining nut on top), slide the magnetic tool over the shaft where the stator was removed and turn in a clockwise direction to open the valve to the full open position (directional arrows
Manual 2100-670I Page 15 of 47
Loading...
+ 32 hidden pages