Bard FC085V42A, FH110V60A, FH085V42A, FH110V48A, FLF085V42A Installation Instructions Manual

...
OIL FURNACE
INSTALLATION INSTRUCTIONS
MODELS
FC085V42A FH085V42A FH110V48A FH110V60A FLF085V42A FLF110V48A FLF110V60A FLR085V42A FLR110V48A FLR110V60A FLR140V60A
WARNING
READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION. THIS INSTALLATION MUST COMPLY WITH THESE INSTRUCTIONS AND THE REQUIREMENTS
OF ALL GOVERNING CODES AND ORDINANCES FOR THE INSTALLATION LOCATION. IT IS THE RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE
REQUIREMENTS. FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY DAMAGE, BODILY
INJURY OR DEATH.
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
IMPORTANT NOTICE
THIS FURNACE IS NOT INTENDED FOR USE AS A CONSTRUCTION HEATER. USE OF THIS FURNACE DURING CONSTRUCTION AND FINISHING PHASES OF A STRUCTURE IS CONSIDERED AS "OPERATION IN A CORROSIVE ATMOSPHERE" AND "UNUSUAL, NEGLIGENT OR IMPROPER USE" AND AS SUCH ARE CONSIDERED EXCLUSIONS BY THE BARD MANUFACTURING COMPANY LIMITED WARRANTY.
WARNING
CARBON MONOXIDE POISONING HAZARD
FAILURE TO FOLLOW THIS WARNING COULD RESULT IN PERSONAL INJURY OR DEATH.
Carbon Monoxide is invisible, orderless and toxic! Bard Manufacturing recommends a carbon monoxide alarm in your home, even if you do not own a gas appliance. Locate the carbon monoxide alarm in the living area of your home and away from doorways to attached garages. Follow the alarm manufacturer’s instructions included with the alarm.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual: 2100-540D Supersedes: 2100-540C File: VOL. I, TAB 3 Date: 04-24-13
Manual 2100-540D Page 1 of 45
CONTENTS
Getting Other Information and Publications ........ 3
Installation and Operating Instructions
Equipment Selection............................................. 4
Locating the Furnace ............................................ 4
Installing the Furnace ........................................... 8
Duct Work ............................................................. 8
Installing a Cooling Unit ........................................ 8
Wiring .............................................................. 9
Oil Line Piping..................................................... 12
Beckett AFG Oil Burner .............................. 12 & 13
Beckett “CleanCut” Oil Pump.............................. 13
Beckett Solid State Igniter................................... 13
Beckett GeniSys 7505 ...........................14 & 16-17
Burner States, Reset Button Op., Priming the Pump, Cad Cell Resistance Indicator, Reset Restricted Lockout
Troubleshooting GE ECM2.3......................... 21-23
Burner Setup and Adjustments ...................... 24-26
Short Form Adjustment Procedure ..................... 26
Combustion Air Requirements ............................ 30
Louvers and Grilles............................................. 35
Venting Options .................................................. 35
Thermostat.......................................................... 35
T ABLES
Table 1 Minimum Clearances.............................4
Table 2 Dimensions FLF/R Models ................... 5
Table 3 Electrical Data........................................9
Table A Reset Button Operation ....................... 15
Table B Status Lights ........................................15
Table C Heating Tap Select Settings................. 19
Table D Cooling Tap Select Settings .................19
Table E Adjustment Tap Selects ....................... 20
Table F Heating Delay Profile Taps .................. 20
Troubleshooting GE ECM2.3............... 21
Table 4 Furnace Data.......................................24
Table 5 Correlation of % of CO
Reserve Air .......................................... 29
, O2 and
2
Table 6 No. 2 Fuel Oil Efficiency Chart.............29
Table 7 Recommended Start-Up Settings ........29
Table 8 Sq.Ft. Required as
Unconfined Sp ace ............................... 32
Table 9 Minimum Ventilation Openings ............33
Table 10 Temperature Rise Ranges, Limit
Control Settings, and
Heating Blower Speeds ....................... 36
Table 11 Filter Sizes for Oil Furnaces ................ 37
Manual 2100-540D Page 2 of 45
Filters
Lo-Boy Models – Filter Locations.................37-38
Maintenance
Lubrication .......................................................... 39
Inspect Air Filter .................................................. 39
Final Inspection and Test .................................... 39
Service Hints....................................................... 39
Combination Combustion Chamber/Burner
Mounting System ................................................ 40
To Remove Burner Only ..................................... 41
To Remove Entire Combustion Chamber
Mounting System ................................................ 41
Common Causes of Trouble............................... 42
Care of Finish ..................................................... 42
Cleaning of the Heat Exchanger......................... 42
Wiring Diagrams ............................................43-45
FIGURES
Figure 1 FLF/R Models Dimensions ................ 5
Figure 2 FH Models Dimensions .....................6
Figure 3 FC Models Dimensions .....................7
Figure 4 Typical Unit Setup - FLF..................10
Figure 5 Typical Flue Inst allation
Requirements - FLF ........................ 11
Figure 6 Typical Single Inside
Tank Installation............................... 12
Figure 7 Electronic Blower Control ................18
Figure 8 Control Disassembly .......................23
Figure 9 Winding Test....................................23
Figure 10 Drip Loop......................................... 23
Figure 11 Typical Smoke-CO
Characteristic .. 27
2
Figure 12 Pressure Gauge Connection to
Bleed Port ....................................... 28
Figure 13A Electrode Adjustments-AFG............30
Figure 13B Electrode Adjustments-NX .............. 30
Figure 14 Combustion Air Boot Assembly .......31
Figure 15 All Air From Inside Building ............. 32
Figure 16 All Air From Outdoors ...................... 33
Figure 17 All Air From Outdoors Through
Ventilated Attic.................................34
Figure 18 All Air From Out doors - Inlet Air
From Ventilated Crawl Space and
Outlet Air to Ventilated Attic .............34
Figure 19 Typical Installation of FR26 and FR27.
Filter Rack ....................................... 37
Figure 20 Typical Inst allation of FR25 Filter
Kit ....................................................37
Figure 21 Filter Installation - Lo-Boy Models ... 38
Figure 22 Removal of Burner Only ..................40
Figure 23 Removal of Entire Combustion
Chamber Mounting System.............41
GETTING OTHER INFORMATION and PUBLICATIONS
These publications can help you install the furnace. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Fuel Gas Code.............. ANSI Z223.1/NFPA54
National Electrical Code.........................ANSI/NFPA 70
Standard for the Installation................. ANSI/NFPA 90A
of Air Conditioning and Ventilating Systems
Standard for Warm Air ........................ ANSI/NFPA 90B
Heating and Air Conditioning Systems
Standard for Chimneys, Fireplaces, Vents...... NFPA 211
and Solid Fuel Burning Appliances
Load Calculation for ..............................ACCA Manual J
Residential Winter and Summer Air Conditioning
FOR MORE INFORMATION, CONTACT THESE PUBLISHERS:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating Refrigerating,
and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
Duct Design for Residential................. ACCA Manual D
Winter and Summer Air Conditioning and Equipment Selection
NFPA National Fire Protection Association
Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-540D Page 3 of 45
INSTALLATION and OPERATING INSTRUCTIONS
EQUIPMENT SELECTION
An accurate heating load calculation must be conducted using American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) or Air Conditioning Contractors of America (ACCA) manuals. Do not add a large safety factor above the calculated value. If the calculated heating load requirement exceeds the heating capacity rating of a given model, use only the next larger size available. Never increase by any more than absolutely necessary based upon available equipment heating capacities. Always select based upon heat capacity (output), never use input capacities.
NOTE: It is the personal responsibility and obligation
of the purchaser to contract a qualified installer to assure that installation is adequate and is in conformance with governing codes and ordinances.
LOCATING THE FURNACE
When installing the furnace be sure to provide adequate space for easy service and maintenance. Locate the furnace as close to the chimney as practical, giving consideration to the accessibility of the oil burner, controls, and blower for service. Allow a minimum of 24 inches at front of furnace for servicing oil burner. Allow adequate room for filter and blower maintenance. Clearance from combustible material as
stated on the furnace and repeated in Table 1 must be maintained. For damp basement installations, a raised
concrete pad is recommended. This will help keep the bottom of the furnace dry and reduce the risk of rusting.
An oil burner must have a generous supply of combustion air to operate properly. The flow of combustion and ventilating air must not be obstructed from reaching the furnace. See “Combustion Air Requirements” section.
The furnace area must be kept clear and free of combustible materials, gasoline and other flammable vapors and liquids.
This unit is not designed for mobile home or trailer installations. Always install furnace in a level position.
TABLE 1
MINIMUM CLEARANCES
sehcnIsecanraelCnoitallatsnImuminiM
1
ledoM
A24V580CF 6 122229CN ** 42——
A24V580HF A84V011HF A06V011HF
4V011FLF
1
For the first three (3) feet from plenum. After three (3) feet, no clearance required.
C
Combustible flooring
NC
Noncombustible floor
*
Maintained on one side or the other to achieve filter access and/or blower service.
**
Floor must be noncombustible. For furnace only installation can be installed on combustible flooring only when installed on special base part no. CFB7 available from factory. When air conditioning coil cabinet DCB23-22 is used then use special base part no. CFB23.
4 4 4
A24V580FLF
6
A8
6 6
A06V011FLF
6
A24V580RLF
6
A84V011RLF A06V011RLF
6
A06V041RLF
6
1 1 1
0 0 0
81 81 81 81
2 2 2
2 2 2
2 2 2 2
2 2 2
2 2 2
2 2 2 2
2 2 2
2 2 2
2 2 2 2
tcuD
2 2 2
2 2 2
2 2 2 2
eulF epiProolFtnorFkcaBsediSpoTsediStnorFkcaBsediS
9 9 9
9 9 9
9 9 9 9
C C C
CN CN CN
CN CN CN CN
42
42
42
42 42 42
42 42 42 42
42 42 42
42 42 42 42
ecivreSmuminiM
secnaraelCecanruFmunelP
— — —
*81 *81 *81
*81 *81 *81 *81
Manual 2100-540D Page 4 of 45
Washable type filter 1” nom. thickness
ledoM
rebmuN
tenibaC
munelP
sgninepOnoitcennoCeulFsretliFriA 1
A
htdiW
B
htpeD
C
thgieH
ExD
ylppuS
FxD
nruteRnoitacoL
G
.aiDH
J eziS
.oN
desU
A24V580FLF
A24V580RLF
32
32
521.84
521.84
526.63
526.63
02x22
02x22
41x22
41x22
tnorF
raeR
6
6
526.13
526.13
521.5
521.5
1x02x61
1x02x61
1
1
A84V011FLF
A06V011FLF
A84V011RLF
A06V011RLF
323232
32
521.84
521.84
521.84
521.84
526.04
526.04
526.04
526.04
02x22
02x22
02x22
02x22
41x22
41x22
41x22
41x22
tnorF
tnorF
raeR
raeR
666
6
526.53
526.53
526.53
526.53
521.5
521.5
521.5
521.5
1x02x02
1x02x02
1x02x02
1x02x02
111
1
A06V041RLF62052.05526.7402x5261x52raeR6
521.24— 1x52x021
1
B
MIS-1815 A
RIGHT SIDE VIEWFRONT VIEWLEFT SIDE VIEW
TABLE 2
FLF/R MODELS DIMENSIONS (INCHES)
"FLF" FLUE
KNOCKOUT
LOW VOLTAGE
ENTRANCE
ENTRANCE
HIGH VOLTAGE
C
OPTIONAL
OIL ENTRANCE
FIGURE 1
A
FLF/R MODELS DIMENSIONS
SPECIFICATION SHEET
FLF/FLR 085, 110 AND 140
J
DUCT
SUPPLY
TOP VIEW
DUCT
RETURN
"FLF" FLUE
KNOCKOUT
EF
OIL
OPTIONAL
"FLF" FLUE
KNOCKOUT
G
D
REAR FLUE
OPTIONAL
ENTRANCE
HIGH VOLTAGE
ON "FLR" MODELS
ENTRANCE
LOW VOLTAGE
H
OIL
OPTIONAL
ENTRANCE
FILTER
ENTRANCE
FRESH AIR
KNOCKOUT
DOOR
Manual 2100-540D Page 5 of 45
FH085 AND FH110
SPECIFICATION SHEET
RETURN
OPENING
(CUT OUT)
MIS-1814 A
RIGHT SIDE VIEW
SUPPLY
OPENING
FIGURE 2
21 7/8"
FH MODELS DIMENSIONS
19 7/8"
TOP VIEW
30 1/2"
FLUE
KNOCKOUT
23"
FLUE
FLUE
KNOCKOUT
KNOCKOUT
OPTIONAL
HIGH VOLTAGE
HIGH
DOOR
REAR CLEANOUT
ENTRANCE
VOLTAGE
OPTIONAL
ENTRANCE
LOW VOLTAGE
ENTRANCE
53" (FH085)
OIL
OPTIONAL
ENTRANCE
LOW VOLTAGE
59" (FH110)
OIL
ENTRANCE
OPTIONAL
ENTRANCE
FRESH AIR
KNOCKOUT
OIL
ENTRANCE
DOOR
VESTIBULE
FRONT VIEW
Manual 2100-540D Page 6 of 45
19 1/4"
RETURN
OPENING
(CUT OUT)
16"
LEFT SIDE VIEW
COUNTERFLOW
FIGURE 3
FC085 MODEL DIMENSIONS
22"
20"
RETURN OPENING
SPECIFICATION
SHEET
FLUE
KNOCKOUT
OPTIONAL
HIGH VOLTAGE
ENTRANCE
OPTIONAL
LOW VOLTAGE
ENTRANCE
OIL ENTRANCE
OPTIONAL
OIL ENTRANCE
23"
30 5/8"
TOP VIEW
FLUE KNOCKOUT
54 1/4"
FLUE KNOCKOUT
REAR
CLEANOUT
DOOR
LOW VOLTAGE ENTRANCE
HIGH VOLTAGE ENTRANCE
FRESH AIR
KNOCKOUT
LEFT SIDE VIEW
SUPPLY OPENING
BOTTOM VIEW
FRONT VIEW
19 1/8"
OPTIONAL OIL ENTRANCE
RIGHT SIDE VIEW
18 1/8"
MIS-1826 A
Manual 2100-540D Page 7 of 45
INSTALLING THE FURNACE
INSTRUMENTS REQUIRED FOR PROPER SETUP OF THE FURNACE
It is important that a set of instruments capable of the following requirements be used for the setup of this furnace to ensure proper and safe operation:
1. Oil pump pressure gauge that measures up to 150 PSI.
2. Smoke gun to pull smoke samples from flue.
3. Draft gauge that will measure -.02" water column (W.C.)
4. Duct static pressure gauge 0-1.0" W.C. range.
5. Temperature gauge that can read from 50° F up to 700° F.
6. A gauge to measure CO2 or O2.
DUCT WORK
The air distribution system should be designed and installed in conformance with manuals published by Air Conditioning Contractors of America (ACCA) as set forth in Manual D, or ASHRAE publications.
IMPORTANT
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace This is to prevent drawing possible hazardous combustion products into the circulated air.
INSTALLATION
A typical installation is shown in Figures 4 and 5. All parts of the furnace installation (furnace, oil tank and piping systems, combustion and ventilation air, venting, etc.) must comply with NFPA31, Installation of Oil Burning Equipment -- latest edition. This drawing shows the typical connecting parts needed to correctly install this furnace. Make sure that all parts of the heating system comply with the local codes.
Check the furnace and your load calculation to verify that the unit is properly sized. (Refer to “Equipment Selection” section on Page 4.)
The correct size of unit needed may be substantially smaller than the unit being replaced due to home improvements and technology advancements since the initial installation.
INADEQUATE SUPPLY AIR and/or RETURN AIR DUCT SYSTEMS
Short cycling because of limit control operation can be created by incorrectly designed or installed supply and/ or return air duct systems.
The duct systems must be designed using ASHRAE or ACCA design manuals and the equipment CFM and external static pressure ratings to ensure proper air delivery capabilities.
On replacement installations, particularly if equipment is oversized, the duct systems can easily be undersized. Modifications may be required to assure that the equipment is operating within the approved
temperature rise range when under full rated input conditions, and that no short cycling on limit controls is
occurring.
INSTALLING A COOLING UNIT
When the furnace is used in connection with a cooling unit*, the furnace shall be installed parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering the furnace, and if manually operated, must be equipped with means to prevent operation of either unit, unless the damper is in the full heat or cool position.
* A cooling unit is an air conditioning coil, heat
pump coil or chilled water coil.
When installing a cooling unit above an FH or FL (below on an FC) series furnace, the coil must be spaced far enough from the furnace outlet to assure proper operation of the furnace. Bard supplied coils, when used with Bard supplied coil cabinets, are automatically positioned.
For top discharge FH and FL models, when coils are installed without using Bard coil cabinets or coils of another brand are used, the coil drain pan should be located a minimum of four (4) inches above the top of the furnace cabinet. If a greater clearance is specified by the coil manufacturer then it would apply.
NOTE: IF DRAIN PAN IS ANYTHING OTHER
THAN A STEEL PAN PARTICULAR ATTENTION MUST BE GIVEN TO THE INSTALLATION INSTRUCTIONS FOR THE COIL TO MAKE SURE IT IS ACCEPTABLE FOR USE WITH THESE OIL FURNACES HAVING MAXIMUM OUTLET AIR TEMPERATURE OF 200° F.
See Cooling Tap Select Table D (Page 19) for CFM at static pressures for additional information.
Manual 2100-540D Page 8 of 45
WIRING
FACTORY WIRING
All units are fully factory wired. Multispeed blowers are factory wired on high speed for cooling/manual fan operation. Heating speeds are wired for the largest input and may need lower speed for field installed low input nozzle. If replacement wire is necessary, use 105 degrees C minimum. See electrical data, Table 3.
ELECTRICAL DATA
FIELD WIRING
All wiring must conform to the National Electrical Code and all local codes. A separate fuse or breaker should be used for the furnace.
TABLE 3
rotoMrewolBrotoMrenruB
latoT
ledoMHP-ZH-stloV
A24V580CF1-06-5116.82/19.67/17.13.0151
A24V580HF1-06-5116.82/19.67/17.13.0151
A84V011HF1-06-5113.014/36.87/17.15.2151
A06V011HF1-06-5112.511
A24V580FLF1-06-5116.82/19.67/17.13.0151
A84V011FLF1-06-5113.014/36.87/17.15.2151
A06V011FLF1-06-5112.511
A24V580RLF1-06-5116.82/19.67/17.13.0151
A84V011RLF1-06-5113.014/36.87/17.15.2151
A06V011RLF1-06-5112.511
A06V041RLF1-06-5115.4118.217/17.17.7102
spmA
PHALFPHALF
5.317/17.16.8102
5.317/17.16.8102
5.317/17.16.8102
muminiM tiucriC
yticapmA
emiT.xaM
esuFyaleD
RCAHro
rekaerBtiucriC
Manual 2100-540D Page 9 of 45
FIGURE 4
TYPICAL UNIT SETUP
FLF UNIT SHOWN
WARNING
ALL WIRING MUST
CONFORM TO THE
NATIONAL ELECTRIC
!
CODE AND ALL LOCAL
Left side high voltage (unit power) entrance
Left side low voltage (thermostat) entrance
Left side oil line entrance for opt. air boot
Left side oil line entrance
CODES.
TYPICAL UNIT
SETUP
(FLF UNIT SHOWN)
Inspection door
Right side low voltage (thermostat) entrance
To thermostat and optional A/C unit
Oil line (see burner pump inst. for hookup info.)
Air Boot knockout (optional)
Control panel (junction box in FH units)
Manual 2100-540D Page 10 of 45
Right side high voltage (unit power) entrance
Right side oil line entrance
To power source
Shut off switch (if not fused, power line must include fuse or circuit breaker)
Power Wires: Black (HOT) White (NEUTRAL) Green (GROUND)
MIS-1836
FIGURE 5
TYPICAL FLUE INSTALLATION REQUIREMENTS
FRONT FLUE LO-BOY MODEL SHOWN
(REPRESENTS ALL MODELS)
L
i n e d
C
h
i
m
n
Thimble
1/4 inch per
1 foot rise
INSTALLER NOTE:
Follow all appropriate
standards for installing
needed venting system.
Draft Regulator (Be sure to follow installation inst. supplied with regulator).
90° Rotatable Flue Box on front flue models (remove appropriate cabinet knockout). Mounting screws located under flue box cover.
Flue Box Cover
Optional Flue Locations
e y
Clean-out Door (keep closed)
∨∨
∨∨
Note: This accessory is not currently available for Bard Models: FH110V48A, FH110V60A, FLF110V48A, FLF110V60A with NX Burners
Optional Fresh Air Boot (remove rect. knockout).
Oil Burner
MIS-1825
Manual 2100-540D Page 11 of 45
OIL LINE PIPING
First determine whether the pipe system is to be a single line system or a two line system. All connections must be absolutely air tight or you will have a malfunction of the burner. When installing the piping, a good oil filter should be installed close to the burner. A single line system is recommended for gravity feed.
A typical single inside tank installations shown in Figure 6. For installation details for this and other tank configurations, refer to NFPA31 -- latest edition. All tank and pipe setups must comply with NFPA31.
TYPICAL SINGLE INSIDE TANK INSTALLATION
Vent Cap
BECKETT AFG OR NX OIL BURNER
This furnace is equipped with a high static Beckett AFG or Beckett NX oil burner which is designed to produce adequate draft in nearly any vertically vented application. The burner employs the latest time tested controls of the highest quality. The controls consist of a high voltage Beckett solid state igniter, a Beckett “CleanCut” oil pump with an integral solenoid valve, and a Genisys 7505 primary control.
FIGURE 6
2" Cap
1-1/4" Vent Pipe
Oil Tank
2" Fill Pipe
Return Line
Guage
Bushing, 2" x 1-1/2" or 1-1/4"
Gate Valve 3/8" x 4"
nipple
6"
3/8" x 3/8" Adapter
Legs (either 1-1/4"x10" or 1-1/2"x10" nipples)
Manual 2100-540D Page 12 of 45
Bushing
Oil Filter
3/8" O.D. Copper Fuel Tubing
MIS-1823
These controls were selected for their proven high quality, dependability, and serviceability. With proper maintenance this burner assembly will provide many years of reliable service.
All units are shipped with the oil burner installed, and with high rate oil nozzle installed designed for use with No. 1 or No. 2 fuel oil. Inspect firepot refractory
before firing to be sure it has not been jarred out of position in shipment. Burner air tube must not extend beyond inside surface of firepot. Burner head should be centered on the combustion chamber opening.
WARNING
Never attempt to use gasoline in your furnace. Gasoline is more combustible than fuel oil and could result in a serious explosion causing damage, injury or death.
BECKETT SOLID STATE IGNITER
This igniter differs from the traditional iron core transformer in that it produces a 14,000 volt spark instead of a 10,000 volt spark of the iron core transformer. This hotter spark provides for cleaner, faster ignitions. Being solid state technology this igniter is less susceptible to problems caused by voltage variations. It also has a greater ability to ignite cold and/or inconsistent oil. The solid state igniter is wired to the primary control the same as an iron core transformer.
GENISYS 7505 PRIMARY CONTROL
The Genisys 7505 Interrupted Electronic Oil Primary is a line voltage, safety rated, interrupted ignition oil primary control for residential oil burners. The Genisys 7505 used with a cad cell flame sensor, operates the oil burner and oil valve. The primary controls fuel oil, senses flame, controls ignition spark and is designed to notify a remote alarm circuit before going into lockout when equipped with a flame monitoring system.
The following is a detailed explanation of each control included in the Beckett AFG Oil Burner, how each operates, how to set up the burner, and how to troubleshoot problems should they occur.
BECKETT “CLEANCUT” OIL PUMP
This oil pump is equipped with an oil solenoid valve installed in the pump housing. This feature provides quick cutoffs resulting in reduction in smoke after the burner shuts down. This is a time proven pump design and is capable of both one and two pipe systems. All installation and set up instructions are outlined in the “Oil Pump Specification” section of the installation instructions manual.
This primary control possesses the latest technology, is a very simple control to operate and provides additional troubleshooting features to ease service and reduce down time. The operational guide for the Genisys 7505 primary control is provided following on Page 14.
Manual 2100-540D Page 13 of 45
BECKETT GENISYS
MODEL 7505
MIS-2491
PRIMARY OPERATIONAL GUIDE
BECKETT GENISYS 7505
Sequence of Operation
BURNER STATES
1. Standby: The burner is idle, waiting for a call
for heat.
2. Valve-On Delay (Prepurge): The igniter and motor are on while the control delays turning on the oil solenoid valve for the programmed time.
3. Trial for Ignition: The fuel valve is opened. A flame should be established within the factory set trial for ignition time (“lockout time”).
4. Lockout: The control has shut the burner down for one of the following safety reasons:
• The trial for ignition (lockout) time expires without flame being established.
• The cad cell detects flame during Valve-On Delay.
• The Recycle mode 30-second time budget expires (see “Recycle” section for complete explanation of recycle time budget).
If the control locks out three times without completing a successful call for heat, the control enters Restricted (Hard) Lockout, and must be reset by a technician. Hold the reset button for 15 seconds until the red light shuts off to reset from Restricted Lockout.
5. Ignition Carryover: Once flame is established, the igniter remains on for 10 additional seconds to ensure flame stability.
6. Run: The flame is sustained until the call for heat is satisfied. The burner is then sent to Motor-Off Delay (Postpurge), if applicable, or it is shut down and sent to Standby.
7. Recycle: If the flame is lost while the burner is firing, the control shuts down the burner, enters a 60-second recycle delay and then repeats the ignition sequence. The control will continue to Recycle each time the flame is lost until the accumulated oil-flow-without-flame time reaches 30 seconds, at which point the control will go into lockout. This feature prevents excessive accumulation of oil in the appliance firing chamber.
8. Motor-Off Delay: If applicable, the fuel valve is closed and the control delays turning the motor off for the set motor-off delay time before the control returns to standby.
9. Pump Prime: The igniter and motor are on with the oil valve open for up to 4 minutes. During Pump Prime mode, the cad cell is disregarded, allowing the technician to prime the pump without having to jumper the cad cell.
RESET BUTTON OPERATION
• Table A explains what action the control
will take when the reset button is pressed for different lengths of time during the various burner operating states.
Manual 2100-540D Page 14 of 45
Loading...
+ 31 hidden pages