Table 1 Ventilation Air (CFM) ......................... 12
Manual 2100-512B
Page 2 of 15
Model Nomenclature Legend
Energy Recovery Ventilator
ERV F — A 3
2-Piece Front Door
Electrical Specifications
ModelVoltageAmps
ERVF-A3
CHERV-A3
ERVF-C3
CHERV-C3
230/2082.224V
4601.224V
Control
Voltage
General Description
The wall mount energy recovery ventilator was designed
to provide energy efficient, cost-effective ventilation
to meet IAQ (indoor air quality) requirements while
still maintaining good indoor comfort and humidity
control for a variety of applications such as schools,
classrooms, lounges, conference rooms, beauty salons
and others. It provides a constant supply of fresh air
for control of airborne pollutants including CO
radon, formaldehyde, excess moisture, virus and
bacteria.
The ventilator incorporates patented rotary heat
exchanger to remove both heat and moisture.
It is designed as a single package which can be
easily factory- or field-installed for new installations
or retrofit to the Bard W**A, W**H and C**H series
wall-mounted units. The package consists of a unique
rotary energy recovery cassette that can be easily
removed for cleaning or maintenance. The ERVF-*3/
CHERV-*3 has two 13” diameter heat transfer wheels.
The heat transfer wheels use a permanently bonded dry
desiccant coating for total heat recovery.
Ventilation is accomplished with two blower/motor
assemblies each consisting of a drive motor and dual
blowers for maximum ventilation at low sound levels.
The intake and exhaust blowers can be operated at the
same speed (airflow rate) or different speeds to allow
flexibility in maintaining desired building pressurization
conditions. Factory shipped on medium intake and low
exhaust. See Figure 6A on page 11 to change speeds.
The rotating energy wheels provide the heat transfer
effectively during both summer and winter conditions.
Provides required ventilation to meet the requirements
of ASHRAE 62.1 standard.
, smoke,
2
Wall Mount – Cabinet Size
Electrical
A = 230/208 volt
B = 230/208 volt
C = 460 volt
2 = W18-24A, L and H
3 = W30-36A, L and H
5 = W42-60A, L and H
NOTE: During operation below 5˚ F outdoor
temperature, freezing of moisture in the heat
transfer wheel can occur. Consult the factory if
this possibility exists.
General Information
The ventilator should only be installed by a trained
heating and air conditioning technician. These
instructions serve as a guide to the technician
installing the ventilator package. They are not
intended as a step-by-step procedure with which the
mechanically inclined owner can install the package.
The ventilator housing is shipped in one carton, which
contains the following:
1. Energy recovery ventilator
2. Service soor
3. Rain hood and mist eliminator
4. Installation instructions
Unpacking
Upon receipt of the equipment, be sure to compare the
model number found on the shipping label with the
accessory identification information on the ordering and
shipping document to verify that the correct accessory
has been shipped.
Inspect the carton housing of each ventilator as it is
received, and before signing the freight bill, verify that
all items have been received and that there is no visible
damage. Note any shortages or damage on all copies
of the freight bill. The receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent. Concealed
damage not discovered until after loading must be
reported to the carrier within 15 days of its receipt.
Manual 2100-512B
Page 3 of 15
Performance and Application Data – ERVF-*3/CHERV-*3
NOTE: All performance data is based on operating intake and exhaust blower on
the same speed.
Basic Installation
(Field Installation)
1. Unpack the ventilator assembly, which includes
the integral ventilator with attached electrical
harness and miscellaneous hardware.
!
WARNING
Open and lock unit disconnect switch before
installing this accessory to prevent injury or
death due to electrical shock or contact with
moving parts. Turn thermostat to OFF.
Model
ERVF-A3
CHERV-A3--
ERVF-C3
CHERV-C3--
!
Be sure the correct model and voltage energy
recovery ventilator is used with the correct air
conditioner or heat pump to ensure correct
voltage compatibility.
2. Remove the existing exterior blower access, filter
access and vent access panels on the Bard wall
mount unit. Save the blower access and filter
access panels and discard vent option access
panel (see Figure 1 on page 6).
3. Remove and save existing unit return air filter and
left side filter support bracket by removing two
screws from left side of unit. Remove and save top
four screws from front grille (see Figure 2 on page
7).
4. Remove and discard the exhaust cover plate (see
Figure 2).
For Use with the
Following Units
S26H*-A, -B
W30A*-A, -B
W36A*-A, -B
W30A*-C
W36A*-C
S30H*-A, -B
W30H*-A, -B
W36H*-A, -B
C24H*-A, -B
C30H*-A, -B
S26H*-C
S30H*-C
W30H*-C
W36H*-C
C24H*-C
C30H*-C
CAUTION
Electrical
230/208
1 or 3
phase
230/208
1 or 3
phase
460
3 phase
460
3 phase
5. Install ventilator by inserting the ventilator into
the unit to the far left side, clearing the right filter
bracket. Once the ventilator is fully inserted, slide
the ventilator to the right until it is tight against
the back of the control panel (see Figure 3 on page
8).
IMPORTANT NOTE: Position front lip of ventilator
under front grille and on top of condenser partition
(as shown in Figure 3 insert). This is important
to ensure proper drainage of any water entering
damper assembly.
6. Open control panel to gain access to unit low
voltage terminal block. (Be sure all power is OFF
prior to opening the control panel.)
7. Route four low voltage electrical leads through the
7/8" bushing in control panel (Figure 3) into low
voltage box.
8. Temporarily connect leads with fork terminals to
corresponding points on terminal strip to terminals
C, R, G and A or O1 depending whether unit is a
heat pump or air conditioner (see Figure 4 on page
9).
NOTE: These 24 volt control wires control the
starting and stopping of the energy recovery
ventilator and can be independently controlled
by an energy management control or timer. See
separate section on Control Wiring.
9. Remove female plug of high voltage wiring harness
from the heat recovery assembly and snap into unit
control panel from the inside of the control panel
in the hole provided. Wire to terminal block. See
Figure 4 and wiring diagram.
10. Plug male plug from ERVF-*3/CHERV-*3 assembly
into female connector at back of control panel (see
Figures 3 and 4).
11. Replace inner and outer control panel covers.
12. Ventilator checkout:
A. Resupply power to unit.
B. Energize the evaporator blower by
switching thermostat to the manual fan position with Heat/Cool in OFF position.
C. Ventilator heat transfer wheels should rotate
slowly (49 RPM). Intake and exhaust
blowers should run.
D. De-energize the evaporator blower. Energy
recovery heat transfer wheels and fresh air
and exhaust air blowers should stop.
E. This completes ventilator checkout.
14. Disconnect the wires temporarily connected in
Step 8.
15. Re-install the blower access and filter access
panels at top of unit and secure with sheet metal
screws.
Manual 2100-512B
Page 5 of 15
Loading...
+ 10 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.