Table 1 Ventilation Air (CFM) ......................... 12
Manual 2100-512B
Page 2 of 15
Page 3
Model Nomenclature Legend
Energy Recovery Ventilator
ERV F — A 3
2-Piece Front Door
Electrical Specifications
ModelVoltageAmps
ERVF-A3
CHERV-A3
ERVF-C3
CHERV-C3
230/2082.224V
4601.224V
Control
Voltage
General Description
The wall mount energy recovery ventilator was designed
to provide energy efficient, cost-effective ventilation
to meet IAQ (indoor air quality) requirements while
still maintaining good indoor comfort and humidity
control for a variety of applications such as schools,
classrooms, lounges, conference rooms, beauty salons
and others. It provides a constant supply of fresh air
for control of airborne pollutants including CO
radon, formaldehyde, excess moisture, virus and
bacteria.
The ventilator incorporates patented rotary heat
exchanger to remove both heat and moisture.
It is designed as a single package which can be
easily factory- or field-installed for new installations
or retrofit to the Bard W**A, W**H and C**H series
wall-mounted units. The package consists of a unique
rotary energy recovery cassette that can be easily
removed for cleaning or maintenance. The ERVF-*3/
CHERV-*3 has two 13” diameter heat transfer wheels.
The heat transfer wheels use a permanently bonded dry
desiccant coating for total heat recovery.
Ventilation is accomplished with two blower/motor
assemblies each consisting of a drive motor and dual
blowers for maximum ventilation at low sound levels.
The intake and exhaust blowers can be operated at the
same speed (airflow rate) or different speeds to allow
flexibility in maintaining desired building pressurization
conditions. Factory shipped on medium intake and low
exhaust. See Figure 6A on page 11 to change speeds.
The rotating energy wheels provide the heat transfer
effectively during both summer and winter conditions.
Provides required ventilation to meet the requirements
of ASHRAE 62.1 standard.
, smoke,
2
Wall Mount – Cabinet Size
Electrical
A = 230/208 volt
B = 230/208 volt
C = 460 volt
2 = W18-24A, L and H
3 = W30-36A, L and H
5 = W42-60A, L and H
NOTE: During operation below 5˚ F outdoor
temperature, freezing of moisture in the heat
transfer wheel can occur. Consult the factory if
this possibility exists.
General Information
The ventilator should only be installed by a trained
heating and air conditioning technician. These
instructions serve as a guide to the technician
installing the ventilator package. They are not
intended as a step-by-step procedure with which the
mechanically inclined owner can install the package.
The ventilator housing is shipped in one carton, which
contains the following:
1. Energy recovery ventilator
2. Service soor
3. Rain hood and mist eliminator
4. Installation instructions
Unpacking
Upon receipt of the equipment, be sure to compare the
model number found on the shipping label with the
accessory identification information on the ordering and
shipping document to verify that the correct accessory
has been shipped.
Inspect the carton housing of each ventilator as it is
received, and before signing the freight bill, verify that
all items have been received and that there is no visible
damage. Note any shortages or damage on all copies
of the freight bill. The receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent. Concealed
damage not discovered until after loading must be
reported to the carrier within 15 days of its receipt.
Manual 2100-512B
Page 3 of 15
Page 4
Performance and Application Data – ERVF-*3/CHERV-*3
NOTE: All performance data is based on operating intake and exhaust blower on
the same speed.
Page 5
Basic Installation
(Field Installation)
1. Unpack the ventilator assembly, which includes
the integral ventilator with attached electrical
harness and miscellaneous hardware.
!
WARNING
Open and lock unit disconnect switch before
installing this accessory to prevent injury or
death due to electrical shock or contact with
moving parts. Turn thermostat to OFF.
Model
ERVF-A3
CHERV-A3--
ERVF-C3
CHERV-C3--
!
Be sure the correct model and voltage energy
recovery ventilator is used with the correct air
conditioner or heat pump to ensure correct
voltage compatibility.
2. Remove the existing exterior blower access, filter
access and vent access panels on the Bard wall
mount unit. Save the blower access and filter
access panels and discard vent option access
panel (see Figure 1 on page 6).
3. Remove and save existing unit return air filter and
left side filter support bracket by removing two
screws from left side of unit. Remove and save top
four screws from front grille (see Figure 2 on page
7).
4. Remove and discard the exhaust cover plate (see
Figure 2).
For Use with the
Following Units
S26H*-A, -B
W30A*-A, -B
W36A*-A, -B
W30A*-C
W36A*-C
S30H*-A, -B
W30H*-A, -B
W36H*-A, -B
C24H*-A, -B
C30H*-A, -B
S26H*-C
S30H*-C
W30H*-C
W36H*-C
C24H*-C
C30H*-C
CAUTION
Electrical
230/208
1 or 3
phase
230/208
1 or 3
phase
460
3 phase
460
3 phase
5. Install ventilator by inserting the ventilator into
the unit to the far left side, clearing the right filter
bracket. Once the ventilator is fully inserted, slide
the ventilator to the right until it is tight against
the back of the control panel (see Figure 3 on page
8).
IMPORTANT NOTE: Position front lip of ventilator
under front grille and on top of condenser partition
(as shown in Figure 3 insert). This is important
to ensure proper drainage of any water entering
damper assembly.
6. Open control panel to gain access to unit low
voltage terminal block. (Be sure all power is OFF
prior to opening the control panel.)
7. Route four low voltage electrical leads through the
7/8" bushing in control panel (Figure 3) into low
voltage box.
8. Temporarily connect leads with fork terminals to
corresponding points on terminal strip to terminals
C, R, G and A or O1 depending whether unit is a
heat pump or air conditioner (see Figure 4 on page
9).
NOTE: These 24 volt control wires control the
starting and stopping of the energy recovery
ventilator and can be independently controlled
by an energy management control or timer. See
separate section on Control Wiring.
9. Remove female plug of high voltage wiring harness
from the heat recovery assembly and snap into unit
control panel from the inside of the control panel
in the hole provided. Wire to terminal block. See
Figure 4 and wiring diagram.
10. Plug male plug from ERVF-*3/CHERV-*3 assembly
into female connector at back of control panel (see
Figures 3 and 4).
11. Replace inner and outer control panel covers.
12. Ventilator checkout:
A. Resupply power to unit.
B. Energize the evaporator blower by
switching thermostat to the manual fan position with Heat/Cool in OFF position.
C. Ventilator heat transfer wheels should rotate
slowly (49 RPM). Intake and exhaust
blowers should run.
D. De-energize the evaporator blower. Energy
recovery heat transfer wheels and fresh air
and exhaust air blowers should stop.
E. This completes ventilator checkout.
14. Disconnect the wires temporarily connected in
Step 8.
15. Re-install the blower access and filter access
panels at top of unit and secure with sheet metal
screws.
Manual 2100-512B
Page 5 of 15
Page 6
16. Replace the vent option access panel with the new
panel provided. Attach air intake hood with screws
provided (see Figure 5 on page 10). Be sure to
insert the top flange of the air intake hood into and
through the slot in the service door and between
the door and insulation to prevent bowing of the
door.
17. Apply Certification label, included with installation
instructions, next to unit serial plate.
18. Ventilator is now ready for operation.
FIGURE 1
Removing Access Panels
Basic Installation
(Factory-Installed Models)
1. Remove blower access, filter access and vent
option panels. Remove filter bracket from shipping
location and install on left side. Remove filter
located above air circulation blowers. Install filter.
2. Remove air intake hood from shipping location and
install air intake hood on vent option panel. Refer
to the Control Wiring Section for suggested control
schemes. After wiring, replace all panels.
REMOVE & SAVE
Manual 2100-512B
Page 6 of 15
REMOVE & DISCARD
Page 7
FIGURE 2
Removing Filter and Grille
REMOVE & DISCARD
Manual 2100-512B
Page 7 of 15
Page 8
FIGURE 3
Running Wiring
FIGURE 3 –
INSET
SIDE VIEW -
SEE STEP 5 OF
INSTRUCTIONS
Manual 2100-512B
Page 8 of 15
Page 9
MIS-2641
INSTALL 1-480701-0 CAP
AS SHOWN AND WIRE
PER WIRING DIAGRAM
FROM HEAT RECOVERY
ASSEMBLY.
LOW VOLTAGE WIRES
TEMPORARY CONNECTION
FOR TESTING. SEE
RECOMMENDED CONTROL
SEQUENCES
FIGURE 4
Control Panel
Manual 2100-512B
Page 9 of 15
Page 10
FIGURE 5
Replacing Access Panel
Manual 2100-512B
Page 10 of 15
Page 11
FIGURE 6
Airflow Diagram
FIGURE 6A – Speed Tap Label
Manual 2100-512B
Page 11 of 15
Page 12
Control Wiring
The ERVF-*3/CHERV-*3 comes from the factory with
the low voltage control wires not wired into the wall
mount low voltage terminal strip. Care must be taken
when deciding how to control the operation of the
ventilator. When designing the control circuit for the
ventilator the following requirements must be met.
Control Requirements
1. Indoor blower motor must be run whenever the
ERVF-*3/CHERV-*3 is run.
2. Select the correct motor speed tap in the
ERVF-*3/CHERV-*3. Using Table 1 to determine
the motor speed needed to get the desired amount
of ventilation air needed. For instance, do not use
the high speed tap on a ERVF-A3 if only 250 CFM
of ventilation air is needed; use the low speed
tap. Using the high speed tap would serve no
useful purpose and significantly affect the overall
efficiency of the air conditioning system. System
operating cost would also increase.
3. Run the ERVF-*3/CHERV-*3 only during periods
when the conditioned space is occupied. Running
the ERVF-*3/CHERV-*3 during unoccupied periods
wastes energy, decreases the expected life of
the ERVF-*3/CHERV-*3 and can result in a large
moisture buildup in the structure. The ERVF-*3/
CHERV-*3 removes 60 to 70% of the moisture
in the incoming air, not 100% of it. Running
the ERVF-*3/CHERV-*3 when the structure is
unoccupied allows moisture to build up in the
structure because there is little or no cooling load.
Thus, the air conditioner is not running enough to
remove the excess moisture being brought in. Use
a control system that in some way can control the
system based on occupancy.
IMPORTANT
2. Use a motion sensor in conjunction with a
mechanical thermostat to determine occupancy in
the structure. Bard markets the CS2000A for this
use.
3. Use a DDC control system to control the ERVF-*3/
CHERV-*3 based on a room occupancy schedule to
control the ERVF-*3/CHERV-*3.
4. Tie the operation of the ERVF-*3/CHERV-*3 into
the light switch. The lights in a room are usually on
only when occupied.
5. Use a manual timer that the occupants turn to
energize the ERVF-*3/CHERV-*3 for a specific
number of hours.
6. Use a programmable mechanical timer to energize
the ERVF-*3/CHERV-*3 and indoor blower during
occupied periods of the day.
Ventilation Airflow
The ERVF-*3 and CHERV-*3 are equipped with a
3-speed motor to provide the capability of adjusting
the ventilation rates to the requirements of the specific
application by simply changing motor speeds.
TABLE 1
Ventilation Air (CFM)
High
Model
ERVF-A3
CHERV-A3
ERVF-C3
CHERV-C3
The units are set from the factory with the exhaust
blower on the low speed and the intake blower on
medium speed. Moving the speed taps located in the
control panel can change the blower speed of the
intake and exhaust. See Figure 6A on page 11.
Speed
(Black)
400325250
Medium
Speed
(Blue)
Low
Speed
(Red)
Operating the ERVF-*3/CHERV-*3 during
unoccupied periods can result in a build up of
moisture in the structure.
Recommended Control Sequences
Several possible control scenarios are listed below:
1. Use a programmable electronic thermostat
with auxiliary terminal to control the ERVF-*3/
CHERV-*3 based on daily programmed occupance
periods. Bard markets and recommends the Bard
Part No. 8403-060 programmable electronic
thermostat for air conditioner and heat pump
applications.
Manual 2100-512B
Page 12 of 15
!
WARNING
Open disconnect to shut all power OFF before
making adjustments to the speed taps. Failure
to do so could result in injury or death due to
electric shock.
Page 13
Energy Recovery Ventilator
Maintenance
General Information
The ability to clean exposed surfaces within air moving
systems is an important design consideration for the
maintenance of system performance and air quality.
The need for periodic cleaning will be a function of
operating schedule, climate and contaminants in the
indoor air being exhausted and in the outdoor air being
supplied to the building. All components exposed to
the airstream, including energy recovery wheels, may
require cleaning in most applications.
Rotary counterflow heat exchanges (heat wheels) with
laminar airflow are “self-cleaning” with respect to
dry particles. Smaller particles pass through; larger
particles land on the surface and are blown clear
as the flow direction is reversed. For this reason,
the primary need for cleaning is to remove films of
oil-based aerosols that have condensed on energy
transfer surfaces. Buildup of material over time may
eventually reduce airflow. Most importantly, in the
case of desiccant coated (enthalpy) wheels, such films
can close off micron-sized pores at the surface of the
desiccant material, reducing the efficiency, with which
the desiccant can absorb and desorb moisture.
Frequency
In a reasonably clean indoor environment such as a
school, office building or home, experience shows that
reductions of airflow or loss of sensible (temperature)
effectiveness may not occur for 10 or more years.
However, experience also shows that measurable
changes in latent energy (water vapor) transfer can
occur in shorter periods of time in commercial,
institutional and residential applications experiencing
moderate occupant smoking or with cooking facilities.
In applications experiencing unusually high levels
of occupant smoking, such as smoking lounges,
nightclubs, bars and restaurants, washing of energy
transfer surfaces, as frequently as every 6 months,
may be necessary to maintain latent transfer efficiency.
Similar washing cycles may also be appropriate for
industrial applications involving the ventilation of high
levels of smoke or oil-based aerosols such as those
found in welding or machining operations, for example.
In these applications, latent efficiency losses of as
much as 40% or more may develop over a period of 1
to 3 years.
Cleanability and Performance
In order to maintain energy recovery ventilation
systems, energy transfer surfaces must be accessible
for washing to remove oils, grease, tars and dirt that
can impede performance or generate odors. Washing
of the desiccant surfaces is required to remove
contaminate buildups that can reduce adsorption of
water molecules. The continued ability of an enthalpy
wheel to transfer latent energy depends upon the
permanence of the bond between the desiccant and
the energy transfer surfaces.
Bard wheels feature silica gel desiccant permanently
bonded to the heat exchange surface without
adhesives; the desiccant will not be lost in the washing
process. Proper cleaning of the Bard energy recovery
wheel will restore latent effectiveness to near original
performance.
Maintenance Procedures
NOTE: Local conditions can vary and affect the
required time between routine maintenance
procedures. Therefore, all sites (or specific
units at a site) may not have the same
schedule to maintain acceptable performance.
The following timetables are recommended and
can be altered based on local experience.
Quarterly Maintenance
1. Inspect mist eliminator/prefilter and clean if
necessary. This filter is located in the fresh air
intake hood on the front of the unit. This is an
aluminum mesh filter and can be cleaned with
water and any detergent not harmful to aluminum.
2. Inspect wall mount unit filter and clean or replace
as necessary. This filter is located either in the
unit, in a return air filter grille assembly, or both.
If in the unit, it can be accessed by removing the
lower service door on the front of the unit. If in a
return air filter grille, it can be accessed by hinging
the grille open to gain access.
3. Inspect energy recovery ventilator for proper wheel
rotation and dirt buildup. This can be done in
conjunction with Step 2 above. Energize the energy
recovery ventilator after inspecting the filter and
observe for proper rotation and/or dirt buildup.
4. For recommended energy recovery wheel cleaning
procedures, follow Steps 5 through 8.
5. Disconnect all power to unit. Remove the lower
service door of the wall mount unit to gain access
to the energy recovery ventilator.
6. Remove the front access panel on the ventilator.
Unplug amp connectors to cassette motors. Slide
energy recovery cassette out of ventilator.
7. Use a shop vacuum with brush attachment to clean
both sides of the energy recovery wheels.
8. Reverse shop vacuum to use as a blower and blow
out any residual dry debris from the wheel.
NOTE: Discoloration and staining of the wheel
does not affect its performance. Only
excessive buildup of foreign material needs
to be removed.
9. If any belt chirping or squealing noise is present,
apply a small amount of LPS-1 or equivalent dry
film lubricant to the belt.
Manual 2100-512B
Page 13 of 15
Page 14
Belt Replacement
Instructions
MIS-1890
Route this part of replacement
belt in bottom groove of pulley.
Route this part of replacement
belt in top groove of pulley.
If belt "squeaks" or "chirps"
lubricate lightly with LPS-1
or equivalent "dry film"
lubricant.
Annual Maintenance
1. Inspect and conduct the same procedures as
outlined under Quarterly Maintenance.
2. To maintain peak latent (moisture) removal
capacity, it is recommended that the energy
recovery wheels be sprayed with a diluted nonacid
based evaporator coil cleaner or alkaline detergent
solution such as 409.
NOTE: Do not use acid-based cleaners, aromatic
solvents, temperatures in excess of 170°F or
steam. Damage to the wheel may result.
Do not disassemble and immerse the entire
heat wheel in a soaking solution, as bearing
and other damage may result.
3. Rinse wheel thoroughly after application of the
cleaning solution and allow to drain before reinstalling.
Belt Replacement Instructions
(Two Wheel Cassette Only)
4. No re-lubrication is required to heat wheel bearings
of the drive motor, or to the intake and exhaust
blower motors.
5. If any belt chirping or squealing noise is present,
apply a small amount of LPS-1 or equivalent dry
film lubricant to the belt.
FIGURE 7
Manual 2100-512B
Page 14 of 15
Page 15
FIGURE 8
Hub Assembly with Ball Bearings
Manual 2100-512B
Page 15 of 15
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.