Bard EIFM-3C User Manual

INSTALLATION INSTRUCTIONS
ECONOMIZERS WITH EXHAUST
Models
EIFM-3C
For Use with Bard 2-1/2 through 3 Ton
Wall Mount Air Conditioners
Produced in 2005 and Later
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual : 2100-449A Supersedes: 2100-449 File: Volume III Tab 19 Date: 03-14-08
© Copyright 2004
Manual 2100-449A Page 1 of 13
CONTENTS
GENERAL
General Information ................................................. 3
Unpacking................................................................ 3
Description ............................................................... 3
INST ALLATION
Basic Installation ............................................ 4 – 7, 9
Economizers – WA, WL & WH Series .................. 10
Wall Thermostats................................................... 12
FIGURES
Figure 1 ................................................................ 4
Figure 2 ................................................................ 5
Figure 3 ................................................................ 6
Figure 4 ................................................................ 7
Figure 5 ................................................................ 8
Figure 6 .............................................................. 10
Figure 7 ............................................................... 11
Figure 8 .............................................................. 12
Wiring Diagram ...................................................... 13
TABLES
Table 1 EIFM ........................................................... 3
Table 2 Enthalpy Control Setting ............................. 9
Manual 2100-449A Page 2 of 13
Manufactured under U.S. Patent number 5,301,744.
Other patents pending.
COPYRIGHT DECEMBER 2004
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO USA 43506
GENERAL
GENERAL INFORMATION
The economizer should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the economizer package. They are not intended as a step by step procedure with which the mechanically inclined owner can install the package.
The economizer housing is shipped in one carton which contains the electrical harness, miscellaneous hardware and installation instructions.
The economizer installation requires an additional two stage cooling thermostat in place of the normal single stage cooling thermostat. Also additional low voltage wire will be required to transmit the second call (Y2) for cool. (I.E. use 6 conductor thermostat wire for an air conditioning unit and 9 conductor thermostat wire for heat pumps.) See Page 12 for required thermostats.
If using a Bard master controller, the MC3000 Master Controller is designed specifically to control two (2) redundant Bard wall mount units equipped with economizers.
Any wall mount unit equipped with an economizer must also have a low ambient control installed. This control can be factory installed or field installed. If field installed, use kit CMA-6 (air conditioner models) or CMH-7 (heat pump models).
UNPACKING
Upon receipt of the equipment be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
Inspect the carton housing of each economizer as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt.
DESCRIPTION
The EIFM-3C economizer is designed to be used with Bard 2-1/2 through 3 ton wall mount series air conditioners and heat pumps with low ambient fan cycling controls. They are electromechanical economizer systems designed to provide “free” cooling where the outdoor air temperature is cool enough to provide the needed cooling without running the compressor. When cooling is needed, the system automatically takes advantage of the could outdoor air when available and uses it for first stage cooling. This then reduces the need to run the air conditioning compressor providing lower operating costs and increasing the service life of the equipment. If the outdoor air gets too warm or humid to be helpful, the enthalpy control detects the condition and automatically closes the outdoor air and exhaust damper, opens the return air damper and switches to the compressor operation. This is all done automatically to achieve maximum savings without attention for the user. See Figure 6 & 7, Pages 10 & 11, for a block diagram of the economizer operation logic flow. The unit is equipped with a full modulating type damper motor which controls the damper position to a factory set minimum supply air temperature.
EIFM models not suitable for use with hot gas bypass models.
TABLE 1
EIFM USED ON THIS MODEL
HTIWESUROF
LEDOM
C3-MFIE 13HS,73AW,62HS,73AW,63HW,03HW,63LW/AW,03LW/AW
(1) Low ambient is required with Economizer for low pressure compressor operation.
STINUGNIWOLLOF
Manual 2100-449A Page 3 of 13
INSTALLATION
BASIC INSTALLATION
1. Unpack the economizer assembly which includes the integral economizer with attached electrical harness, mixed air thermistor, miscellaneous hardware and installation instructions.
WARNING
Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to OFF.
2. Remove and save the existing exterior blower access and service access panels on the Bard wall mount unit. (See Figure 1.)
FIGURE 1