Bard EIFM-3B, EIFM-2B User Manual

INSTALLATION INSTRUCTIONS
ECONOMIZERS WITH EXHAUST
MODELS
EIFM-2B EIFM-3B
For Use with Bard 1-1/2 thru 3 Ton
Wall Mount Air Conditioners
and Heat Pumps
Bard Manufacturing Company Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual : 2100-390 Supersedes: File: Volume III T ab 19 Date: 04-26-01
© Copyright 2001
CONTENTS
GENERAL
General Information ................................................. 1
Unpacking................................................................ 1
Description ............................................................... 1
INSTALLATION
Basic Installation ...................................................... 2
Economizers – WA, WH & WL Series.................... 8
FIGURES
Figure 1 ................................................................ 2
Figure 2 ................................................................ 3
Figure 3 ................................................................ 4
Figure 4 ................................................................ 5
Figure 5 ................................................................ 6
Figure 6 ................................................................ 8
Figure 7 ................................................................ 9
Figure 8 .............................................................. 10
TABLES
Table 1 ................................................................ 1
Table 2 ................................................................ 7
Manufactured under U.S. patent number 5,301,744.
Other patents pending.
COPYRIGHT APRIL 2001
BARD MANUFACTURING COMPANY
BRYAN, OHIO USA 43506
GENERAL
GENERAL INFORMATION
The economizer should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the economizer package. They are not intended as a step by step procedure with which the mechanically inclined owner can install the package.
The economizer housing is shipped in one carton which contains the electrical harness, miscellaneous hardware and installation instructions.
The economizer installation requires an additional two stage cooling thermostat in place of the normal single stage cooling thermostat. Also additional low voltage wire will be required to transmit the second call (Y2) for cool. (I.E. use 6 conductor thermostat wire for an air conditioning unit and 9 conductor thermostat wire for heat pumps.) See Page 8 for required thermostats.
If using a Bard master controller, the MC91AE master controller is designed specifically to control two (2) redundant Bard wall mount units equipped with economizers.
Any wall mount unit equipped with an economizer must also have a low ambient control installed. This control can be factory installed or field installed. If field installed, use kit CMA-6 (air conditioner models) or CMH-7 (heat pump models).
UNPACKING
Upon receipt of the equipment be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
Inspect the carton housing of each economizer as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt.
DESCRIPTION
The EIFM-2 and EIFM-3 economizers are designed to be used with Bard 1-1/2 thru 3 ton wall mount series air conditioners and heat pumps with low ambient fan cycling controls. They are electromechanical economizer systems designed to provide “free” cooling where the outdoor air temperature is cool enough to provide the needed cooling without running the compressor. When cooling is needed, the system automatically takes advantage of the could outdoor air when available and uses it for first stage cooling. This then reduces the need to runt the air conditioning compressor providing lower operating costs and increasing the service life of the equipment. If the outdoor air gets too warm or humid to be helpful, the enthalpy control detects the condition and automatically closes the outdoor air and exhaust damper, opens the return air damper and switches to the compressor operation. This is all done automatically to achieve maximum savings without attention for the user. See Figure 1, Page 9, for a block diagram of the economizer operation logic flow. The unit is equipped with a full modulating type damper motor which controls the damper position to a factory set minimum supply air temperature.
TABLE 1
)1(
LEDOM
B2-MFIE142HW,381HW,152AW,142LW/AW,181LW/AW
B3-MFIE173AW,163HW,103HW,163LW/AW,103LW/AW
(1) Low ambient is required with Economizer for low
pressure compressor operation.
EIFM models not suitable for use with hot gas bypass models.
HTIWESUROF
STINUGNIWOLLOF
Manual 2100-390 Page 1
INSTALLATION
BASIC INSTALLATION
1. Unpack the economizer assembly which includes the integral economizer with attached electrical harness, mixed air thermistor, miscellaneous hardware and installation instructions.
WARNING
Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to OFF.
2. Remove and save the existing exterior blower access and service access panels on the Bard wall mount unit. (See Figure 1.)
FIGURE 1
Manual 2100-390 Page 2
MIS-344