NOTE: These instructions are written to cover field-installed economizers,
but are also included with factory-installed economizers. For factoryinstalled economizers, all portions addressing “installation” are for
reference only.
Upon receipt of the equipment be sure to compare the
model number found on the shipping label with the
accessory identification information on the ordering and
shipping document to verify that the correct accessory
has been shipped.
Inspect the carton housing of each ventilator as it is
received, and before signing the freight bill, verify that
all items have been received and that there is no visible
damage (check parts list below). Note any shortages or
damage on all copies of the freight bill. The receiving
party must contact the last carrier immediately,
preferably in writing, requesting inspection by the
carrier’s agent. Concealed damage not discovered until
after loading must be reported to the carrier within 15
days of its receipt.
General
The economizer should only be installed by a trained
heating and air conditioning technician. These
instructions serve as a guide to the technician installing
the ventilator package. They are not intended as a stepby-step procedure with which the mechanically inclined
owner can install the package.
The economizer housing is shipped in one carton which
contains the electrical harness, miscellaneous hardware
and installation instructions.
Economizer kit includes:
(1) ECON-WD5 full flow economizer
(1) 1-910-1980 sensor assembly (ECON-WD5)
(1) 1-910-1898E sensor assembly (ECON-DB5)
(1) 910-2063 economizer control board assembly
(2) 7003-084 mist filters
(1) 7003-083 exhaust bug screen
(2) 1913-002-0808 8-1/2" foam strips
(4) 1913-002-0708 7-1/2" foam strips
(2) 539-405 intake sealing frames
(2) 543-223 lower block off plates
(1) 7950-12 push mount cable tie
(8) 7950-004 cable tie
(12) #10-16x1/2 screws
(4) #8-18x3/8 pan head screws
(1) 2100-697A installation instructions
Economizer Features
• One piece construction – easy to install.
• Exhaust air damper – built in with positive closed
position. Provides exhaust air capability to prevent
pressurization of tight buildings.
• Actuator motor – 24 volt, power open, spring return
with built in torque limiting switch.
TM
• JADE
• Proportioning-type control for maximum “free”
• Enthalpy or temperature only sensor to monitor
• Minimum Ventilation Position available for
• Mixed air sensor to monitor outdoor and return air
controller provides nearly limitless
customization on a solid, intuitive electronic
platform.
cooling economy and comfort with up to 100%
outside air.
outdoor air conditions.
required ventilation of occupants or dilution of
pollutants.
to automatically modulate damper position.
Description
The ECON-WD5 and ECON-DB5 ventilators are
designed to be used with the specific models with
"letter" revision codes as designated on the front page
of this installation instructions manual.
The economizer is an electromechanical vent system
designed to provide fresh air to meet indoor air quality
standards.
Models
When installed in the models listed on the front page,
ECON-WD5 and ECON-DB5 provide built-in exhaust
provisions. When the damper blade opens to bring
fresh air in, the damper also opens an exhaust relief.
The exhaust air will flow into the condenser section of
the unit. The condenser fan will help draw exhaust air
out when it is operating with compressor in cooling or
heat pump mode.
Manual 2100-697C
Page 3 of 33
Page 4
INSTALLATION OF FIELD-INSTALLED ECON-WD5/ECON-DB5
Basic Installation
!
WARNING
Electrical shock hazard.
Disconnect remote electrical power supply
or supplies before servicing.
Failure to do so could result in electric
shock or death.
!
WARNING
Exposed moving parts.
Disconnect electrical power before
servicing.
Failure to do so could result in severe
injury or amputation.
Remove both side grilles (see Figure 2).
FIGURE 2
Remove Side Grilles
Side Grille
Remove upper blower door, outer control panel cover
and front (lower) condenser grille (see Figure 3).
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp
edges.
Failure to do so could result in personal injury.
Disconnect all power to unit (see Figure 1).
FIGURE 1
Disconnect Power
Disconnect
Access Door
FIGURE 3
Remove Blower Door, Outer Control Panel Cover
and Condenser Grille
Upper Blower Door
Outer
Control Panel
Cover
Front (Lower)
Condenser Grill
Manual 2100-697C
Page 4 of 33
Page 5
Remove blank off plates (both sides) and discard (see
Figure 4). Retain screws for use with new vent.
Remove both air filters and the low voltage inner control
panel cover (see Figure 6).
FIGURE 4
Remove Blank Off Plates (Both Sides)
Blank Off Plate
Remove exhaust blank off plate through return or
through side intake openings and discard (see Figure 5).
FIGURE 5
Remove Exhaust Blank Off Plate
Exhaust Partition
FIGURE 6
Remove Air Filters and Low Voltage
Control Panel Cover
Air Filters (2)
Low Voltage Inner
Control Panel Cover
Electrical
Entrance Door
Install the 910-2063 control board assembly on the
left side of the control panel using four (4) #10 x 1/2
screws (provided) as shown in Figure 7 below (single
stage units) and Figure 8 on page 6 (2-stage units).
Snap the four wire connector into the opening next to
the low voltage box. Plug the 12 pin male connector
into the female plug in the low voltage box.
Remove wire channel cover and route four pin
connector mixed air sensor and outdoor sensor wires
inside channel; mixed air sensor and outdoor sensor
wires will be connected later.
Exhaust Blank Off
Plate
FIGURE 7
Install 910-2063 Control Board Assembly
(Single Stage Units)
JADE Control
Wire Channel
Single Stage:
For Balanced Climate,
disconnect this
connector (see Balanced
Climate on page 24).
Manual 2100-697C
Page 5 of 33
Page 6
2-Stage Units Only
For 2-stage units, balanced climate is unavailable.
Disconnect the 2-stage harness wire from blue jumper
wire secured to the low voltage box. Also, disconnect
the yellow and purple wires on the vent plug as shown
in Figures 8 and 9.
Connect the purple wire from the vent plug to the
2-stage harness (wire is blue for standard units and
orange/white for dehumidification units). Tape off the
yellow and blue wires that are not used as shown in
Figure 9.
FIGURE 8
Install 910-2063 Control Board Assembly
(W*SAC 2-Stage Units)
Balanced Climate is
unavailable in
2-stage units
Before installing the economizer, remove economizer
from packaging and verify there is no damage.
Install
the economizer as shown in Figure 10.
Set economizer on the exhaust partition (see Figure 5
on page 5) and slide in until flush with the side of the
wall mount.
FIGURE 10
Install Economizer
2-stage units:
Disconnect these two
connections.
FIGURE 9
W*SAC 2-Stage Unit Wire Connection
2-stage units:
Reconnect wires.
Standard: Blue Wire
Dehum: Orange/White Wire
Purple Wire
When the economizer is fully installed, the control plug
should be centered in the plug access opening on the
front panel of the economizer as shown in Figure 11.
FIGURE 11
Control Plug Centered in Plug Access Opening
Tape Off
Manual 2100-697C
Page 6 of 33
Page 7
From the front, through the filter opening, plug the
economizer power plug into the control panel plug (see
Figure 12).
IMPORTANT: Sharp edges--PPE required.
FIGURE 12
Connect Economizer Power Plug to
Control Panel Plug
Install the indoor mixed air sensor assembly in the
location shown in Figure 13, just to the right of
the indoor blower. Use two (2) #10-16x1/2 screws
(supplied) to mount the sensor.
Route the orange mixed air sensor wires up through the
control panel, circuit breaker panel and blower partition
as shown in Figure 14.
FIGURE 14
Route Orange Mixed Air Sensor Wires
FIGURE 13
Install Indoor Mixed Air Sensor Assembly
Indoor Mixed Air
Sensor Assembly
Indoor Blower
Secure wires with provided ladder ties (see Figure 15).
FIGURE 15
Secure Sensor Wires with Ladder Ties
Manual 2100-697C
Page 7 of 33
Page 8
Connect sensor plug as shown in Figure 16.
FIGURE 16
Connect Mixed Air Sensor Plug
Install the 910-1980 enthalpy sensor assembly (Figure
17) or 910-1898E temperature only sensor (Figure 18)
using two (2) #10-16x1/2 screws (supplied). Fasten
cable to the back with one (1) provided push wire tie.
Route wires over the top of the outdoor fan motor up
through the condenser partition wire bushing as shown
in Figure 19. Secure cable with provided ladder ties.
FIGURE 19
Route Wires and Secure with Ties
FIGURE 17
Enthalpy Sensor Assembly Installation
FIGURE 18
Temperature Only Sensor Assembly Installation
Route the cable up through the control panel bushing
and secure with provided ladder tie (see Figure 20).
FIGURE 20
Route Cable Through Control Panel Bushing
Manual 2100-697C
Page 8 of 33
Page 9
Route the cable into the wire channel (cover removed
earlier) and connect to the red and black wires from the
JADETM controller (see Figure 21).
FIGURE 21
Route Cable and Connect to Red and Black Wires
Re-install wire channel covers; make sure all wires are
contained inside the channel as shown in Figure 22.
Install the electrical entrance door and upper blower
door.
FIGURE 22
Wiring Connections Completed
The ECON-WD5 exhaust blade is fixed in the shipping
position by the latch located on the bottom of the
blade (see Figure 23). Access can be made through
the return air opening or through the opening under the
economizer. Turning the latch 1/4 turn will release the
blade.
FIGURE 23
Release the Exhaust Blade
Make sure the blade seats correctly over the exhaust
opening and that the latch is as shown in Figure 24.
FIGURE 24
Exhaust Blade and Latch
Manual 2100-697C
Page 9 of 33
Page 10
Install the 539-405 intake sealing frame and the 543223 lower block off plates (both sides) as shown in
Figure 25. Install two (2) 1913-002-0708 7-1/2" foam
gaskets below the intake sealing frame (both sides).
FIGURE 25
Install Intake Sealing Frame and
Lower Block Off Plates
Intake Sealing
Frame
Bend the two (2) sheet metal tabs in the condenser
partition up to hold the bottom of the bug screen in
place. Install two (2) 1913-002-0808 8-1/2" foam
gaskets to sides of cabinet (see Figure 27). Install the
7003-083 exhaust bug screen. Re-install front lower
(condenser) grille.
FIGURE 27
Install Bug Screen and Gaskets
Foam Gaskets
Lower Block
Off Plate
Install Gaskets Here
Bend the two (2) sheet metal tabs in the condenser
partition up to hold the bottom of the mist eliminator
in place.
Install 7003-084 mist filters on both sides (see Figure
26). Then re-install the side grilles removed earlier.
FIGURE 26
Install Mist Filters
Mist Filter
Exhaust Bug
Screen
Install both filters, then re-install the inner control
panel, outer control panel and upper blower door.
Restore power to unit.
Refer to Start-Up/Checkout Procedures.
Blade Adjustment for Desired
Ventilator Air
The amount of ventilation air supplied by the
commercial room ventilator is dependant on four
factors.
1. Return air duct static pressure drop.
2. Supply air duct static pressure drop.
3. Indoor blower motor speed.
4. Damper blade open position setting.
Refer to the appropriate graph on pages 29 – 31 to
determine minimum blade position settings.
Manual 2100-697C
Page 10 of 33
Page 11
START-UP/CHECKOUT PROCEDURES
JADE™ ECONOMIZER CONTROLLER
W7220 controller offers unparalleled flexibility and
expansion in a dependable and solid electronic
platform.
• Multiple economizer applications from one
controller.
• Nearly limitless customization of setpoints.
• Internal checkout menu provides fast performance
assessment.
• Alarms menu provides assistance in
troubleshooting.
Memory: User-defined setpoints remain in nonvolatile flash memory regardless of electrical outage
duration. Control voltage below 18V may cause erratic
performance.
FIGURE 28
JADETM Economizer Controller
2 LINE
LCD
will need to be changed to the values listed in Table 4
(see page 13).
The installing contractor can easily access the JADE™
programming by the integral keypad and LCD display.
There are six (6) basic MENU categories to navigate:
1. STATUS – provides real-time access to sensor
input, damper and equipment operation.
3. SYSTEM SETUP – customizable application
programming (see Revew/Customize System
Setup).
4. ADVANCED SETUP – further application and
operational options.
5. CHECKOUT – instantly activate and verify
economizer functions.
6. ALARMS – displays alarms and pinpoints problem
areas.
Review/Customize System Setup
Before being placed in service, the JADE™ economizer
controller programming should be reviewed/customized
through the following steps:
MENU UP
(EXIT)
BUTTON
From the factory, the JADE™ economizer controller
has been preset with “default” values that were predetermined as optimum for equipment buildings,
and these are shown in Tables 1 – 3. However, it is
important to review and/or customize these operational
values per owner specifications in order to guarantee
satisfactory performance.
If ECON-S* is installed in an H Series unit, the
"default" settings for "DRYBLB SET" and "MIN POS"
SCROLL
(UP/DOWN)
BUTTONS
SELECT (ENTER)
BUTTON
1. SYSTEM SETUP: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through the
six (6) basic menu items to the SYSTEM SETUP menu.
– Push the SELECT (ENTER) BUTTON to choose the
SYSTEM SETUP menu.
– Navigate through the multiple levels of SYSTEM
SETUP by pushing the SCROLL (UP/DOWN)
BUTTONS.
– To change a specific parameter in the SYSTEM
SETUP menu, press the SELECT (ENTER)
BUTTON to display its current value. Press the
SCROLL (UP/DOWN) BUTTONS to change or increase/decrease value. Press the SELECT
(ENTER) BUTTON to save the new customized
value—“CHANGE STORED” will be displayed.
Press the SELECT (ENTER) BUTTON again to
return to current menu parameter.
– For specific SYSTEM SETUP level information,
refer to Table 1 on page 12.
NOTE: During an extended level of inactivity, the
display of the JADE™ economizer controller will begin
to automatically scroll through the various levels of the
STATUS menu as a screensaver. Each level will stay for
approximately 5 seconds before changing to the next
level.
Manual 2100-697C
Page 11 of 33
Page 12
TABLE 1
System Setup Menu Levels
TABLE 2
Advanced Setup Menu Levels
Menu Level
INSTALL01/01/10
UNITS DEG°F°F / °C
EQUIPMENT HP(B)HP
AUX INHP(B)
FAN SPEED 1 Speed
FAN CFM5000
AUX OUTEXH2
OCCINPUT
FACTORY
DEFAULT
Default
Value
NO
RangeNotes
Display Order = MM/DD/YY
Setting Order = DD/MM/YY
Sets controller to read in
either measurements
Heat Pump HP
CONV = A/C
HP(O)
HP(B
1 Speed
2 Speed
100 to
15000
NONE
ERV
EXH2
SYS
INPUT or
ALWAYS
YES or NOResets to factory defaults if
Energize on Cool
Energize on Heat
Not applicable
Product can be used to
signal other devices
INPUT is for dedicated OCC
signal, ALWAYS is for all
other situations
changed to YES
*
*
* In SYS SETUP, the correct Equipment setting is HP
and for the AUX2 IN is HP (B) in all applications.
This is correct for both air conditioner and heat
pump equipment in order to have correct operating
sequences for the economizers. DO NOT change to
CONV = A/C setting just because the equipment is
an air conditioner and not a heat pump.
2. ADVANCED SETUP: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through
the six (6) basic menu items to the ADVANCED SETUP
menu.
– Push the SELECT (ENTER) BUTTON to choose the
ADVANCED SETUP menu.
– Navigate through the multiple levels of ADVANCED
SETUP by pushing the SCROLL (UP/DOWN)
BUTTONS.
– To change a specific parameter in the ADVANCED
SETUP menu, press the SELECT (ENTER)
BUTTON to display its current value. Press the
SCROLL (UP/DOWN) BUTTONS to change or increase/decrease value. Press the SELECT
(ENTER) BUTTON to save the new customized
value—“CHANGE STORED” will be displayed.
Press the SELECT (ENTER) BUTTON again to
return to current menu parameter.
Menu Level
MA
LOW
SET
FREEZE
POS
STG3
DLY
DMPR
POS
MA T
CAL
OA T
CAL
OAS H
CAL
Default
Value
45°F35-55°
CLO
15 MIN
CLO
0.0°F
0.0°F
0%
RangeNotes
CLO or
MIN
0 to 4.0h
or OFF
CLO or
OPN
+/-2.5°F
from
actual
reading
+/-2.5°F
from
actual
reading
+/-10%
from
actual
reading
Temp to activate freeze
protection — Close Damper
Damper position upon freeze
protection
Delay for 3rd Stage Cooling –
allows for 3 stages of cooling,
one stage for econ & two
stages for compressor
Where damper goes upon
shutdown signal
Mixed Air Sensor temperature
calibration
Outdoor Air Sensor
temperature calibration
Outdoor Air Humidity Sensor
calibration for economizers
using temp/humidity sensor
3. SETPOINTS: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through the
six (6) basic menu items to the SETPOINTS menu.
– Push the SELECT (ENTER) BUTTON to choose the
SETPOINTS menu.
– Navigate through the multiple levels of SETPOINTS
by pushing the SCROLL (UP/DOWN) BUTTONS.
– To change a specific parameter in the SETPOINTS
menu, press the SELECT (ENTER) BUTTON to
display its current value. Press the SCROLL (UP/DOWN) BUTTONS to change or increase/decrease
value. Press the SELECT (ENTER) BUTTON
to save the new customized value—“CHANGE
STORED”will be displayed. Press the SELECT
(ENTER) BUTTON again to return to current menu
parameter.
– For specific SETPOINTS level information, refer to
Table 3.
– For H Series unit SETPOINTS level information,
refer to Table 4.
– For specific ADVANCED SETUP level information,
refer to Table 2.
Manual 2100-697C
Page 12 of 33
Page 13
TABLE 3
Setpoints Menu Levels
Menu Level
MAT
SET
LOW T
LOCK
DRYBLB
SET
ENTH
CURVE
MIN
POS
EXH150%
EXH26%
DCV SET
(See NOTE
under Table
7 on page
14)
Default
Value
53°F
0°F
60°F
ES3
2V
1100
RangeNotes
38°F to
65°F
-45°F to
80°F
48°F to
80°F
ES1,
ES2,
ES3,
ES4 or
ES5
2 to 10
VDC
0 to
100%
0 to
100%
500 to
2000
Mixed Air Temperature setpoint
at which the economizer
damper will begin to modulate
to maintain setting
Low outdoor ambient
temperature for compressor
lockout
Maximum outdoor
temperature setting for “free”
economizer cooling
Enthalpy boundary “curves”
for economizers using temp/
humidity sensor, see “Enthalpy
Settings” explanation
Actuator voltage for Minimum
Position – see Minimum
Position Note
Setpoint for damper if exhaust
fan is powered by economizer
Setpoint for AUX output signal
Displays only if a CO
is connected. Setpoint for
Demand Control Ventilation
of space. Above the setpoint,
the OA dampers will modulate
open to bring in additional OA
to maintain a space ppm level
below the setpoint.
sensor
2
TABLE 4
H Series Setpoints Menu Levels*
Menu Level
MAT
SET
LOW T
LOCK
DRYBLB
SET
ENTH
CURVE
MIN
POS
EXH150%
EXH26%
* For DRYBLB SET and MIN POS, change default setting to
value shown
Default
Value
53°F
0°F
70°F
ES3
10V
RangeNotes
38°F to
65°F
-45°F to
80°F
48°F to
80°F
ES1,
ES2,
ES3,
ES4 or
ES5
2 to 10
VDC
0 to
100%
0 to
100%
Mixed Air Temperature setpoint
at which the economizer
damper will begin to modulate
to maintain setting
Low outdoor ambient
temperature for compressor
lockout
Maximum outdoor
temperature setting for “free”
economizer cooling
Enthalpy boundary “curves”
for economizers using temp/
humidity sensor, see “Enthalpy
Settings” explanation
Actuator voltage for Minimum
Position – see Minimum
Position Note
Setpoint for damper if exhaust
fan is powered by economizer
Setpoint for AUX output signal
MINIMUM POSITION NOTE: Minimum position
setting has been preset to 10V which when connected
to MC4002 Lead/Lag Controller System will allow
economizer to drive wide open per emergency ventilation
strategy as detailed in MC4002 Instructions. This may
require resetting to a lower value per job specifications.
4. CHECKOUT: from the main screen, press the
SCROLL (UP/DOWN) BUTTONS to navigate through the
six (6) basic menu items to the CHECKOUT menu.
– Push the SELECT (ENTER) BUTTON to choose the
CHECKOUT menu.
– Navigate through the multiple levels of CHECKOUT
by pushing the SCROLL (UP/DOWN) BUTTONS.
– To perform a specific test in the CHECKOUT menu,
press the SELECT (ENTER) BUTTON to choose a
particular exercise, “RUN?” will appear. Press the
SELECT (ENTER) BUTTON again to activate this
exercise. After a short pause, “IN PROGRESS” will
appear as the test activates. “DONE” will display
after the test is complete. Press the MENU UP (EXIT) BUTTON to end the test and/or turn off the
activated relay.
– For specific CHECKOUT level information, refer to
Table 5.
NOTE: CHECKOUT functions bypass the normal
5-minute delay for compressor protection. Be sure to
allow for enough time to pass between tests so the
compressor is not damaged from extreme short-cycling.
TABLE 5
Checkout Menu Levels
Menu LevelNotes
DAMPER VMIN-HS
DAMPER VMAX-HS
DAMPER OPEN
DAMPER CLOSE
CONNECT Y1-OForces Y1-OUTPUT to compressor
CONNECT Y2-OForces Y2-OUTPUT to compressor
CONNECT AUX
Positions damper to the minimum amount
of opening allowed by actuator
Opens damper to the MIN POS level
indicated in the SETPOINTS menu. See
Minimum Position Note above.
Forces damper to full open position, energizes
exhaust contacts
Positions damper to completely closed
position
Depending upon AUX OUT setting from
SETUP menu:
NONE – no action
ERV – 24VAC out for ERV & NOT
Economizer
SYS – 24VAC out for alarm
NOTE: Economizer assembly should be ready to
put into service. At any point during operation, in
economizer mode or idle, real-time information from
sensors and integral components can be accessed from
the STATUS menu.
Manual 2100-697C
Page 13 of 33
Page 14
5. STATUS: from the main screen, press the SCROLL (UP/DOWN) BUTTONS to navigate through the six (6)
basic menu items to the STATUS menu.
– Push the SELECT (ENTER) BUTTON to choose the
STATUS menu.
– Navigate through the multiple levels of STATUS by
pushing the SCROLL (UP/DOWN) BUTTONS.
– As the STATUS menu simply gives input/output
information in real-time, there is no way to
change or otherwise alter the displayed criteria.
It is simply a window into the operation of the
economizer controller.
– For specific STATUS level information, refer to
Table 6.
NOTE: Upon power-up (or after power failure or low
voltage condition), the controller will begin a 5-minute
time delay before enabling mechanical cooling.
TABLE 6
Status Menu Levels
Menu Level
ECON AVAILYES/NO
ECONOMIZINGYES/NO
OCCUPIEDYES/NO
HEAT PUMPCOOL/HEAT
COOL Y1-INON/OFF
COOL Y1-OUTON/OFF
COOL Y2-INON/OFF
COOL Y2-OUTON/OFF
MA TEMP0° to 140°F Current mixed air temp
OA TEMP
OA HUM0% to 100%
DAMPER OUT2.0 to 10.0 Displays voltage to actuator
ACT POS0 to 100% Current % of opening
ACT COUNTN/A
ACTUATOR OKYES/NOIndicates potential fault
EXH1 OUTON/OFFOutput of EXH1 Terminal
MECH COOL ON 0, 1, or 2
Default
Value
-40° to
140°F
Notes
Indicates if conditions are
favorable for economizing
Indicates if economizer is
actively economizing
Indicates if dedicated 24V
occupied signal is being received
on terminal OCC
Displays actual compressor use
if in HEAT PUMP mode
Indicates if 24V signal is being
received on terminal Y1-I
Displays if controller is
actively calling for mechanical
compressor cooling (24V on
Y1-O)
Indicates if 24V signal is being
received on terminal Y2-I
Displays if controller is actively
calling for Stg. 2 cooling
(24V on Y2-O)
Current outdoor air temp
Current outdoor air humidity
for economizers using temp/
humidity sensor
Current count of actuator cycles
from installation
Stages of mechanical cooling
currently active
NOTE: If there are any potential problems recognized
by the economizer controller, it may be registered
in the form of an alarm in the ALARM(S) menu. If
there is a period of inactivity AND there is an alarm
registering, the controller will randomly scroll through
the ALARM(S) menu items as a screensaver.
ALARM(S): from the main screen, press the SCROLL
(UP/DOWN) BUTTONS to navigate through the six (6)
basic menu items to the ALARM(S) menu.
– Push the SELECT (ENTER) BUTTON to choose the
ALARM(S) menu.
– Navigate through the current alarms in ALARM(S)
by pushing the SCROLL (UP/DOWN) BUTTONS.
–
Once the alarm has been identified, and the cause
has been removed (e.g., replaced faulty sensor), the
alarm may erase itself. If a manual alarm-erasing
is required, it can be cleared from the display by
navigating to the desired alarm and pressing the
SELECT (ENTER) BUTTON to choose that specific
alarm. “ERASE?” will display. Press the SELECT (ENTER) BUTTON again. “ALARM ERASED” will
appear. Press the MENU UP (EXIT) BUTTON to
complete the action and return to the previous menu.
– For specific ALARM(S) information, refer to
Table 7.
TABLE 7
Alarm Examples
Alarm(s)Notes
MA T SENS ERRMalfunctioning mixed air sensor
OA T SENS ERRMalfunctioning outdoor air sensor
ACT STALLED
SYS ALARM
NOTE: This is not a complete list of alarms. Additional alarms
will display depending upon the parameter settings and
configuration and attached equipment.
Actuator cannot reach desired percentage of
opening
If AUX is set to SYS in SETPOINTS menu,
SYS will display upon any registered alarm
NOTE: When using the Bard 8403-067 CO2 controller,
configure the sensor to 2-10VDC output (see CO2
sensor instructions).
The JADE controller default setting is 1100 PPM. The
economizer will modulate to maintain this CO
level
2
in the room. The default setting can be changed in
the SETPOINT menu in the DCV SET option. Default
settings and DCV MIN and DCV MAX will appear only
when the CO2 sensor is connected.
In the SETPOINT menu, change the MAX VENT setting
to 9.5 volts.
The CO
controller is active at any time the A terminal
2
is energized.
The status of the CO
input can be viewed at any time
2
in the STATUS menu.
Manual 2100-697C
Page 14 of 33
Page 15
Enthalpy Settings
If economizer is enthalpy-based and was shipped with
the temp/humidity sensor, the economizer must be
programmed for the specific enthalpy curve boundary
desired for “free” outdoor cooling. The available
enthalpy boundaries are all subject to specific OA
temperature, OA humidity and OA dew points. If all of
the OA conditions are below the specific points outlined
in each boundary, the conditions are good to economize
and economizer mode is set to “YES”. If some or all
the OA conditions are above the specific points outlined
in each boundary, the conditions are not good to
economize and the economizer mode is set to “NO”.
ES3 is factory default.
Manual 2100-697C
Page 15 of 33
Page 16
Completestat
Model #CS9B-THO or
Model #CS9BE-THO
FIGURE 29
Programmable Thermostat Connections for ECON-**5 with Single Stage Air Conditioners
SC
SC
SC
24V
COM
G
Y1Y2 O/BLDAGND
W2
W1/E
6
Thermostat
Bard #8403-060
Unit Low
Voltage
Term. Strip
1
12-Pin
Vent Plug
Factory installed jumper. Remove jumper and connect
1
to N.C fire alarm circuit if emergency shutdown required.
Wire not needed below 15KW.2
Wire required for dehumidificationmodels only.
3
4
Do not connect "A" from thermostat if optional CO2 controller is used
0-10 VDC modulating C02 control signal for modulating ventilation
5
control (optional for ECON only - see vent instruction manuals)
6
9
2357
ALL VENT OPTIONS PLUG IN HERE
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
B/W1
119
2
W1/E
2
7
W2CGRTY1Y2
W3
A
LO/BY2Y1RGCW2
4
LDA3
Change model configuration from heat pump to heat/cool. Must be configured to programmable
and fan set to be programmed fan for the "A" output to function during scheduled occupied
6
periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For
dehumidification, must be configured for "No Economizer" for YO/D to be active for humidity
control.
7
Install jumper for 1 stage electric heat on units with less than 15KW
Do not add these wires if setting up for modulating control. See note 7.
8
Factory installed jumper. Remove jumper to activate Balanced Climate
9
A 2-stage thermostat is recommended for Balanced Climate mode.
4
YO/D
3
5
Optional CO2 Controller
3
65421R
4
1012
Bard Part #8403-067
1
2
3
4
5
6
8
™
24VAC
CO2 OUT
TEMP-OUT
mode.
MIS-3974
A
Manual 2100-697C
Page 16 of 33
Page 17
FIGURE 30
Programmable Thermostat Connections for ECON-**5 with 2-Stage Air Conditioners
Completestat
Model #CS9B-THO or
Model #CS9BE-THO
6
Thermostat
Bard #8403-060
Unit Low
Voltage
Term. Strip
12-Pin
Vent Plug
Factory installed jumper. Remove jumper and connect
1
to N.C fire alarm circuit if emergency shut down required.
Wire not needed below 15K W.2
Wire required for dehumidification models only.
3
4
Do not connect "A" from thermostat if optional CO2 controller is used
0-10 VDC modulat ing C02 control si gnal for modulati ng ventilation
5
control (opti onal for ECON only - see vent instruction manuals)
SCSCSC
COM
24V
1
G
Y1Y2O/BLDAGND
Y365421R
9
6
2357
ALL VENT OPTIONS PLUG IN HERE
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
W1/E
W2
3
2
W1/E
LO/BY2Y1RGCW2
2
7
B/W1
119
W3
W2CGRTY1Y2
LDA3
Change model configuration from heat pump t o heat/cool. Must be configured to programmable
6
and fan set to be programmed fan for the "A" output to function during scheduled occupied
periods. Must be conf igured for multi-stage for Y1 output to be active 1st stage cooling. For
dehumidificat ion, must be configured for "No Economizer" for YO/D to be active for humidity
control.
7
Install jumper for 1 stage elect ric heat on units with less than 15KW
8
Do not add these wires if setting up f or modulating control. See note 7.
Factory installed jumper. Remove jumper to activate Balanced Cl imate
9
A 3-stage thermost at is recommended for Balanced Climate mode. Must not be
removed if Econ is installed.
4
Optional CO2 Controller
Bard Part #8403-067
YO/D
A
4
3
5
4
1012
1
24VAC
2
3
CO2 OUT
4
™
5
6
mode.
TEMP-OUT
MIS-4067
8
Manual 2100-697C
Page 17 of 33
Page 18
Completestat
Model #CS9B-THO or
Model #CS9BE-THO
6
Thermostat
Bard #8403-060
FIGURE 31
Programmable Thermostat Connections for ECON-**5 with Heat Pumps
SC
SC
SC
24V
COM
G
Y1Y2 O/BLDAGND
W2
W1/E
W1/E
3
2
LO/BY2Y1RGCW2
4
YO/D
A
Unit Low
Voltage
Term. Strip
1
12-Pin
Vent Plug
Factory installed jumper. Remove jumper and connect
1
to N.C fire alarm circuit if emergency shutdown required.
Wire not needed below 15KW.
2
Wire required for dehumidificationmodels only.
3
Do not connect "A" from thermostat if optional CO2 controller is used
4
0-10 VDC modulating C02 control signal for modulating ventilation
5
control (optional for ECON only - see vent instruction manuals)
6
8
2357
ALL VENT OPTIONS PLUG IN HERE
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
B/W1
119
2
4
3
W2CGRTY1Y2
LDA3
W3
4
Ensure model configuration is heat pump and not heat/cool. Must be configured to programmable
and fan set to be programmed fan for the "A" output to function during scheduled occupied
6
periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For
dehumidification, must be configured for "No Economizer" for YO/D to be active for humidity
control.
7
Do not add these wires if setting up for modulatingcontrol.
Factory installed jumper. Remove jumper to activate Balanced Climate
8
A 2-stage thermostat is recommended for Balanced Climate mode.
5
Optional CO2 Controller
Bard Part #8403-067
1
24VAC
2
CO2 OUT
3
TEMP-OUT
65421R
1012
4
5
6
7
mode.
™
MIS-4063 A
Manual 2100-697C
Page 18 of 33
Page 19
8403-057
9
(TH311OD1040)
or T4 Pro 8403-089
8403-058
(TH522OD1151)
8403-059
(TH522OD1219/U)
or T6 Pro 8403-090
7
FIGURE 32
Non-Programmable Thermostat Connections for ECON-**5 with Air Conditioners
Units With Dehumidification
WCRcYRG
WRcCRGYY2
B
O
8
W2
6
35
4
8403-038
Mechanical Humidist at
8403-047
Electronic H umidistat
10
Unit Low
Voltage
Term. Strip
1
12-Pin
Vent Plug
Factory installed jumper. Remove jumper and connect
1
to N.C fire alarm circuit if emergency shutdown required.
2A
Wire not needed below 15KW.
Install Jumper for 1 stage electric heat on units with more
2B
than 10KW.
Wire required for dehumidification models only.
3
For vent operation, add jumper if optional CO2 controller is not used.
4
Vent will run while blower is energized.
For ECON & CRV-V an additional wire change is required
See install Manual.
5
Do not add these wires if setting up for modulating control. See note 7.
6
2357
ALL VENT OPTIONS PLUG IN HERE
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
119
B/W1
2A
3
6
2B
W3
W2CGRTY1Y2
LDA3
4
4
0-10 VDC Modulating CO2 control signal for modulating ventilation control
6
(Optional for ECON Only) - See vent installation manual.
For 8403-058, change "system type", set up Function 1, From 5 (2 Heat/ 1 Cool heat Pump)
7
to 6 (2 Heat / 2 Cool Conventional). For 8403-059, No change required.
Jumper needs added.8
Thermostat will not work with units equipped with economizers.9
Factory installed jumper. Remove jumper to activate Balanced Climate™ Mode.
10
A 2-stage thermostat is recommended for Balanced Climate mode.
IMPORTANT NOTE
Optional CO2 Controller
Bard Part #8403-067
1
24VAC
2
3
CO2 OUT
4
65421R
5
TEMP-OUT
5
6
1012
MIS-3975 A
An additional wire change is required if jumper 4 is used which connects "A" to "G" (shown on Figures 32
and 30). The red/white wire on the blower interlock relay (located on the vent control plate) needs to be moved
from the "common" terminal to the "normally closed" terminal. If this change is not made, the relay will latch on once the "A" signal is received and the blower will not turn off. Refer to pages 32 and 33 to see the vent wiring
diagrams with this change called out.
Manual 2100-697C
Page 19 of 33
Page 20
8403-057
9
(TH311OD1040)
or T4 Pro 8403-089
8403-058
(TH522OD1151)
8403-059
(TH522OD1219/U)
or T6 Pro 8403-090
7
FIGURE 33
Non-Programmable Thermostat Connections for ECON-**5 with Heat Pumps
RGYY2
C
BCRcYRG
O/BRc
AUX
W
O
E
6
Units With Dehumidification
8403-038
Mechanical Humidist at
8
8403-047
35
4
Electronic H umidistat
10
Unit Low
Voltage
Term. Strip
1
12-Pin
Vent Plug
Factory installed jumper. Remove jumper and connect
1
to N.C fire alarm circuit if emergency shutdown required.
Wire not needed below 15KW.
2
Wire required for dehumidification models only.
3
For vent operation, add jumper if optional CO2 controller is not used.
4
Vent will run while blower is energized.
For ECON & CRV-V, an additional wire change is required.
See install manual
5
Do not add these wires if setting up for modulating control. See note 6.
6
2357
ALL VENT OPTIONS PLUG IN HERE
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
119
B/W1
2
3
W3
W2CGRTY1Y2
LDA3
6
4
4
0-10 VDC Modulating CO2 control signal for modulating ventilation control
6
(Optional for ECON Only) - See vent installation manual.
For 8403-058, change "system type", set up Function 1, From 5 (2 Heat/ 1 Cool heat Pump)
7
to 6 (2 Heat / 2 Cool Conventional). For 8403-059, No change required.
Jumper needs added.8
Thermostat will not work with units equipped with economizers.9
Factory installed jumper. Remove jumper to activate Balanced Climate™ Mode.
10
A 2-stage thermostat is recommended for Balanced Climate mode.
Optional CO2 Controller
Bard Part #8403-067
1
24VAC
2
3
CO2 OUT
4
65421R
5
TEMP-OUT
5
6
1012
MIS-4064 A
IMPORTANT NOTE
An additional wire change is required if jumper 4 is used which connects "A" to "G" (shown on Figures 32
and 33). The red/white wire on the blower interlock relay (located on the vent control plate) needs to be moved
from the "common" terminal to the "normally closed" terminal. If this change is not made, the relay will latch on once the "A" signal is received and the blower will not turn off. Refer to pages 32 and 33 to see the vent wiring
diagrams with this change called out.
Manual 2100-697C
Page 20 of 33
Page 21
ECONOMIZER SEQUENCE OF
OPERATION
Condition – Cool/Dry OA Conditions
st
Stage Cooling closes and sends signal to
• 1
JADE™ control. Since the air temperature outside
is cooler than the preset DRYBULB SET setting,
or is below the ENTH CURVE boundary in the
SETPOINTS menu, the actuator will power the
economizer damper to “economizer” mode as the
indoor blower motor starts. The mixed air sensor
senses a mixture of return air and cool outdoor
air and modulates opening to achieve preset MAT SET setting in SETPOINTS menu. Compressor
operation is inhibited (see Figure 34).
nd
• 2
• 3
Stage Cooling closes and sends a signal to
JADE™ control, which closes the Y1-O relay to
begin mechanical cooling. The economizer damper
REMAINS OPEN in tandem operation with the
compressor as long as the OA conditions do not drop below the preset DRYBULB SET/ENTH
CURVE settings in the SETPOINTS menu (see
Figure 35).
rd
Stage Cooling (if available) closes and sends a
signal to JADE™ control, which closes the Y2-O
relay to begin 2nd stage mechanical cooling. The
economizer damper REMAINS OPEN in tandem
operation with the compressor as long as the
temperature outside does not drop below the
preset DRYBULB SET setting in the SETPOINTS
menu (see Figure 35).
Condition – Warm/Humid OA Conditions
st
Stage Cooling closes and sends signal to
• 1
JADE™ control. Since the OA conditions are above
the preset DRYBULB SET/ENTH CURVE setting
in the SETPOINTS menu, the control will simply
close the Y1-O relay to initiate mechanical cooling.
The economizer damper will remain closed or in
a minimum ventilation setting depending upon
occupied status (see Figure 36 on page 22).
nd
• 2
Stage Cooling (if available) closes and sends a
signal to JADE™ control. Since the OA conditions
are still above than the preset DRYBULB SET/ENTH CURVE setting in the SETPOINTS menu,
the control will simply close the Y2-O relay
to initiate 2nd stage mechanical cooling. The
economizer damper will remain closed or in a
minimum ventilation setting depending upon
occupied status (see Figure 36).
FIGURE 34
100% Airflow
FIGURE 35
Mixed AIrflow Path
Manual 2100-697C
Page 21 of 33
Page 22
FIGURE 36
Call for Compressor or Fan Only with Ventilation Off
Manual 2100-697C
Page 22 of 33
Page 23
THERMOSTAT/CONTROL CALLS
FOR 1ST STAGE COOLING
OA CONDITIONS
ABOVE DRYBULB
OR ENTHALPY
CURVE SETPOINTS
OA CONDITIONS
BELOW DRYBULB
OR ENTHALPY
CURVE SETPOINT
ECONOMIZER ONLY
OPERATION, MAT
SENSOR ATTEMPTS
TO MAINTAIN
PRESET DISCHARGE
AIR TEMP.
IS ADDITIONAL
COOLING REQ’D?
MECHANICAL
COOLING BEGINS,
ECON. DAMPER
CLOSED OR MIN.
POSITION
CONDITIONED
SPACE LOAD IS
PICKED UP BY
MECHANICAL
COOLING
THERMOSTAT IS
SATISFIED AND
SYSTEM SHUTS
DOWN
CONDITIONED
SPACE LOAD IS
PICKED UP BY
ECONOMIZER
NO
YES
THERMOSTAT IS
SATISFIED AND
SYSTEM SHUTS
DOWN
MECHANICAL
COOLING BEGINS,
ECON DAMPER
REMAINS OPEN
CONDITIONED
SPACE LOAD IS
PICKED UP BY
ECONOMIZER AND
MECHANICAL COOL
THERMOSTAT IS
SATISFIED AND
SYSTEM SHUTS
DOWN
Economizer Operation for Single Stage:
Manual 2100-697C
Page 23 of 33
Page 24
Balanced Climate Mode – S, Y and Z Option
Economizer Sequence of Operation
Call for cooling and ECONOMIZER IS NOT AVAILABLE
(due to outdoor conditions):
Y1 energizes mechanical cooling and the Balance
Climate fan speed simultaneously. If the outdoor
conditions are not acceptable, the Y2 terminal will
energize full load compressor and increase the fan
speed to the rated airflow. When the temperature drops
below the Y2 setpoint, the unit will return to part load
and Balanced Climate fan speed. When the cooling
call is satisfied, the compressor will shut down and the
economizer will move to minimum position (ventilation
setting) and the fan will continue to run at RATED
airflow if A is energized on the low voltage terminal
strip.
Unit Operation with S (Part Flow), Y and Z (Full Flow) Economizer Options
Single Stage Compressor Units (Balanced Climate Available)
Call for cooling and ECONOMIZER IS AVAILABLE (due
to outdoor conditions):
Two stage cooling thermostat is required and connector
is disconnected at JADE
Balanced Climate mode (see Figure 7 on page 5).
Unit has a call for ventilation: Damper to Min position
and fan will run at RATED airflow. Y1 energizes
economizer and the Balance Climate fan speed
simultaneously. If the temperature continues to rise,
the Y2 terminal will energize part load compressor and
increase the fan speed to the RATED airflow. When the
temperature drops below the Y2 setpoint, the unit will
return to part load and Balanced Climate fan speed.
When the cooling call is satisfied, the compressor will
shut down and the economizer will move to minimum
position (ventilation setting) and the fan will increase
to run at RATED airflow if A is energized on the low
voltage terminal strip.
TABLE 8
TM
controller to enable
Unit
Operation
Fan OnlyYesXXXVentOffMin Pos
Fan OnlyNoXXVentOffClosed
BC CoolingYe sXXXXB ClimateEconMin Pos
BC CoolingNoXXXB ClimateEconClosed
Full Load CoolYesXXXXXXLo/Med/HiOnMin Pos
Full Load CoolNoXXXXXLo/Med/HiOnClosed
1st Stage HeatYe sXXXLo/Med/HiOffMin Pos
1st Stage HeatNoXXLo/Med/HiOffClosed
2nd Stage HeatYe sXXXXLo/Med/HiOffMin Pos
2nd Stage HeatNoXXXLo/Med/HiOffClosed
Dehumidify
Dehumidify
BC and B Climate − Balanced Climate
¹ Fan speed is selectable through the blower speed control terminal block. LO (default), MED or HI speeds can be used.
2
Dehumidification operation is disabled when a call for heating or cooling occurs. Unit runs at Balanced Climate speed
during dehumidification operation.
2
2
Occ.
Signal
GY1Y2W1 W2AD123-4-5
YesXXXXB ClimateOnMin Pos
NoXXXB ClimateOnClosed
Low Voltage 24VACSpeed Taps
Fan Speed
1
Comp.
Oper.
Damper
Manual 2100-697C
Page 24 of 33
Page 25
TABLE 9
Unit Operation with S (Part Flow), Y and Z (Full Flow) Economizer Options
2-Stage Compressor Units (Balanced Climate Unavailable)
Unit
Operation
Occ.
Signal
GY1Y2Y3W1 W2AD123-4-5
Low Voltage 24VACSpeed Taps
Fan
Speed
1
Comp.
Oper.
Damper
Blower OnlyYesXXXVentOffMin Pos
Blower OnlyNoXXVentOffClosed
Part Load CoolYesXXXXXPart LoadOnMin Pos
Part Load CoolNoXXXXPart LoadOnClosed
Full Load CoolYesXXXXXXXLo/Med/HiOnMin Pos
Full Load CoolNoXXXXXXLo/Med/HiOnClosed
1st Stage HeatYesXXXLo/Med/HiOffMin Pos
1st Stage HeatNoXXLo/Med/HiOffClosed
2nd Stage HeatYesXXXXLo/Med/HiOffMin Pos
2nd Stage HeatNoXXXLo/Med/HiOffClosed
Dehumidify
Dehumidify
¹ Fan speed is selectable through the blower speed control terminal block. LO (default), MED or HI speeds can be used.
2
Dehumidification operation is disabled when a call for heating or cooling occurs. Unit runs at part load speed during
2
2
YesXXXXPart LoadOnMin Pos
NoXXXPart LoadOnClosed
dehumidification operation.
Manual 2100-697C
Page 25 of 33
Page 26
Single Stage Compressor Units – Economizer Operation – Balanced Climate Mode
Connector disconnected from JADETM controller (see Figure 7 on page 5)
THERMOSTAT/CONTROL CALLS
FOR 1ST STAGE COOLING
OA CONDITIONS
ABOVE DRYBULB
OR ENTHALPY
CURVE SETPOINTS
MECHANICAL COOLING BEGINS,
FAN OPERATES IN BALANCED CLIMATE SPEED,
ECONOMIZER DAMPER CLOSED OR
MIN. POSITION
IS ADDITIONAL
COOLING REQ’D?
YES
THERMOSTAT CALLS
FOR 2ND STAGE COOLING,
BRINGS IN RATED
INDOOR FAN SPEED,
ECON DAMPER
CLOSED OR MIN
POSITION
CONDITIONED
SPACE LOAD IS
PICKED UP BY
COOLING
NO
CONDITIONED
SPACE LOAD IS
PICKED UP BY
MECHANICAL
COOLING
OA CONDITIONS
BELOW DRYBULB
OR ENTHALPY
CURVE SETPOINT
ECONOMIZER ONLY OPERATION,
FAN OPERATES AT RATED SPEED,
MAT SENSOR ATTEMPTS TO MAINTAIN
PRESET DISCHARGE AIR TEMP.
IS ADDITIONAL
COOLING REQ’D?
CONDITIONED
SPACE LOAD IS
PICKED UP BY
ECONOMIZER
THERMOSTAT IS
SATISFIED AND
SYSTEM SHUTS
DOWN
NO
YES
MECHANICAL COOLING
BEGINS IN BALANCED
CLIMATE SPEED,
ECON DAMPER REMAINS
IS ADDITIONAL
COOLING REQ’D?
NO
OPEN
YES
Manual 2100-697C
Page 26 of 33
THERMOSTAT IS
SATISFIED AND
SYSTEM SHUTS
DOWN
CONDITIONED
SPACE LOAD
IS PICKED UP BY
ECONOMIZER
AND
MECHANICAL
COOL
THERMOSTAT CALLS
FOR 2ND STAGE COOLING,
BRINGS IN RATED
INDOOR FAN SPEED
CONDITIONED SPACE LOAD
IS PICKED UP BY
ECONOMIZER AND
MECHANICAL COOL
THERMOSTAT IS SATISFIED
AND SYSTEM SHUTS DOWN
Page 27
2-Stage Compressor Units – Economizer Operation – Part and Full Load Operation
Balanced Climate Unavailable
Connector disconnected from JADETM controller and reconnected to 2-stage compressor harness (see Figures 8
and 9 on page 6)
THERMOSTAT/CONTROL CALLS
FOR 1ST STAGE COOLING
OA CONDITIONS
ABOVE DRYBULB
OR ENTHALPY
CURVE SETPOINTS
1ST STAGE MECHANICAL COOLING BEGINS,
FAN OPERATES IN PART LOAD SPEED,
ECONOMIZER DAMPER CLOSED OR
THERMOSTAT CALLS
FOR 2ND STAGE COOLING,
BRINGS IN RATED
INDOOR FAN SPEED,
ECON DAMPER
CLOSED OR MIN
POSITION
MIN. POSITION
YES
CONDITIONED
SPACE LOAD IS
PICKED UP BY
COOLING
IS ADDITIONAL
COOLING REQ’D?
NO
CONDITIONED
SPACE LOAD IS
PICKED UP BY
MECHANICAL
COOLING
OA CONDITIONS
BELOW DRYBULB
OR ENTHALPY
CURVE SETPOINT
ECONOMIZER ONLY OPERATION,
FAN OPERATES AT RATED SPEED,
MAT SENSOR ATTEMPTS TO MAINTAIN
PRESET DISCHARGE AIR TEMP.
IS ADDITIONAL
COOLING REQ’D?
CONDITIONED
SPACE LOAD IS
PICKED UP BY
ECONOMIZER
THERMOSTAT IS
SATISFIED AND
SYSTEM SHUTS
DOWN
NO
YES
1ST STAGE MECHANICAL
COOLING BEGINS IN
PART LOAD SPEED,
ECON DAMPER REMAINS
IS ADDITIONAL
COOLING REQ’D?
NO
OPEN
YES
THERMOSTAT IS
SATISFIED AND
SYSTEM SHUTS
DOWN
CONDITIONED
SPACE LOAD
IS PICKED UP BY
ECONOMIZER
AND
MECHANICAL
COOL
THERMOSTAT CALLS
FOR 2ND STAGE COOLING,
BRINGS IN RATED
INDOOR FAN SPEED
CONDITIONED SPACE LOAD
IS PICKED UP BY
ECONOMIZER AND
MECHANICAL COOL
THERMOSTAT IS SATISFIED
AND SYSTEM SHUTS DOWN
Manual 2100-697C
Page 27 of 33
Page 28
NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED
FIGURE 37
CO2 Sensor Default and Final Settings
Bard Part #8403-067 CO2 Controller
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
JUMPERS MUST BE
POSITIONED AS SHOWN
FOR PROPER OPERATION
Settings RecommendedDefault
Settings RecommendedDefault
RONNot Used
RONNot Used
ROFNot Used
ROFNot Used
DSPCCT
DSPCCT
UNIUSUS
UNIUSUS
COL7000
COL7000
COH15002000
COH15002000
TOLNot Used
TOLNot Used
TOHNot Used
TOHNot Used
BAR
BAR
CALUsed for Field Calibration
CALUsed for Field Calibration
See Instrution with Controller
See Instrution with Controller
For High Altitude Installations
For High Altitude Installations
Manual 2100-697C
Page 28 of 33
MIS-4025
Page 29
GRAPH 1
W3SAC ECON-WD/DB Ventilation Delivery
GRAPH 2
W/J42*C ECON-WD/DB Ventilation Delivery
Manual 2100-697C
Page 29 of 33
Page 30
GRAPH 3
W4SAC & W/J48*C ECON-WD/DB Ventilation Delivery
GRAPH 4
W5SAC & W/J60*C ECON-WD/DB Ventilation Delivery
Manual 2100-697C
Page 30 of 33
Page 31
GRAPH 5
W/J72AC ECON-WD/DB Ventilation Delivery
Manual 2100-697C
Page 31 of 33
Page 32
FIGURE 38
Wiring Diagram − Enthalpy Sensor
BROWN
BLACK
BROWN
1
MAT +
2
MAT -
3
OAT +
4
RED
OAT -
5
S-BUS
6
S-BUS
PLUG
PLUG
GRAY
1
IAQ +
2
IAQ -
3
IAQ24V
4
ACT +
5
ACT -
6
ACT 24V
ECONOMIZER CONTROL
RELAY
48
NCCOM
NO
ORANGE
ORANGE
MODULE
BROWN/WHITE
6
5
AUX2-I
4
OCC
3
E-GND
2
EXH1
1
AUX1-O
PLUG
PLUG
6
Y2-I
5
Y2-O
4
Y1-I
3
Y1-O
2
C
1
R
3
BLACK/WHITE
RED/WHITE
12 PIN PLUG
BLUE
BROWN/WHITE
GREEN
RED/YELLOW
GRAY
PURPLE/BLACK
PURPLE
YELLOW/BLACK
YELLOW/WHITE
BLACK/WHITE
RED/WHITE
ORANGE
12 PIN PLUG
MALE
MALE
7
12 PIN PLUG
8
FEMALE
1
RED
3
BLACK
2
BROWN
9
BROWN
8
BLACK
11
RED
12
ORANGE
5
ORANGE
6
CLOSE DAMPER INPUT
11
OCCUPIED SIGNAL INPUT
7
ECON OPEN OUTPUT
10
0-10 VDC CO2 CONTROL INPUT
4
2ND STAGE COOLING INPUT
5
2ND STAGE COOLING OUTPUT
1
1ST STAGE COOLI NG INPUT
2
COMPRESSOR OUTPUT
8
24V COMMON INPUT
6
24V HOT INPUT
9
3
DAMPER MOTOR
1
2
3
4
MIXED AIR
TEMPERATURE
SENSOR
3
OUTSIDE AIR
46
DIRECT PLUG-IN
INTO SIDE OF UNIT
CONTROL PANEL
ENTHALPY
SENSOR
2-STAGE COMPRESSOR
SINGLE STAGE COMPRESSOR
JUMPER DISCONNECTED FOR
BALANCED CLIMATE OPERATION.
SEE ECONOMIZER AND UNIT
INSTALLATION INSTRUCTIONS.
JUMPER MUST BE
DISCONNECTED,AND
PURPLE WIRE NEEDS
CONNECTED TO 2-STAGE
HARNESS WIRE,
(SEE FIGURE *)
Manual 2100-697C
Page 32 of 33
ORANGE
ECONOMIZER CONTROL PANEL
Move this RED/WHITE wire from
COM to NC if jumper is used
between A and G. See page 19 for
additional information.
4056-250 B
Page 33
FIGURE 39
Wiring Diagram − Temperature Only Sensor
BLACK
BROWN
BROWN
ORANGE
ORANGE
1
MAT +
2
MAT -
3
RED
OAT +
4
OAT -
5
S-BUS
6
S-BUS
PLUG
GRAY
1
IAQ +
2
IAQ -
3
IAQ24V
4
ACT +
5
ACT -
6
ACT 24V
ECONOMIZER CONTROL
RELAY
48
NC
NO
MODULE
BROWN/WHITE
COM
6
5
AUX2-I
4
OCC
3
E-GND
2
EXH1
1
AUX1-O
PLUGPLUG
PLUG
6
Y2-I
5
Y2-O
4
Y1-I
3
Y1-O
2
C
1
R
3
BLACK/WHITE
RED/WHITE
ORANGE
12 PIN PLUG
MALE
8
BLUE
BROWN/WHITE
GREEN
RED/YELLOW
GRAY
PURPLE/BLACK
PURPLE
YELLOW/BLACK
YELLOW/WHITE
BLACK/WHITE
RED/WHITE
ORANGE
12 PIN PLUG
MALE
7
ECONOMIZER CONTROL PANEL
12 PIN PLUG
FEMALE
1
RED
3
BLACK
2
BROWN
9
BROWN
8
BLACK
11
RED
12
ORANGE
5
ORANGE
6
CLOSE DAMPER INPUT
11
OCCUPIED SIGNAL INPUT
7
ECON OPEN OUTPUT
10
0-10 VDC CO2 CONTROL INPUT
4
2ND STAGE COOLING INPUT
5
2ND STAGE COOLING OUTPUT
1
1ST STAGE COOLI NG INPUT
2
COMPRESSOR OUTPUT
8
24V COMMON INPUT
6
24V HOT INPUT
9
3
TEMPERATURE
SINGLE STAGE COMPRESSOR
JUMPER DISCONNECTED FOR
BALANCED CLIMATE OPERATION.
SEE ECONOMIZER AND UNIT
INSTALLATION INSTRUCTIONS.
DAMPER MOTOR
1
2
3
4
MIXED AIR
SENSOR
46
DIRECT PLUG-IN
INTO SIDE OF UNIT
CONTROL PANEL
2-STAGE COMPRESSOR
3
OUTSIDE AIR
TEMPERATURE
SENSOR
JUMPER MUST BE
DISCONNECTED,AND
PURPLE WIRE NEEDS
CONNECTED TO 2-STAGE
HARNESS WIRE,
(SEE FIGURE *)
4056-254 B
Move this RED/WHITE wire from
COM to NC if jumper is used
between A and G. See page 19 for
additional information.
Manual 2100-697C
Page 33 of 33