Bard D28A2PA, D36A2PA, D35A2PA, D28A2PB, D36A2PB Installation And Service Instructions Manual

...
SERVICE INSTRUCTIONS
DUAL-TEC™
WALL-MOUNT PACKAGE
AIR CONDITIONER
Models:
D25A2PA
D28A2PA D28A2PB
D35A2PA D35A2PB
D36A2PA D36A2PB
D42A2PA D42A2PB
D48A2PA D48A2PB
D60A2PA D60A2PB
D25L2PA D25L2PB
D28L2PA D28L2PB
D35L2PA D35L2PB
D36L2PA D36L2PB
Part of the Bard DC Free Cooling Unit System
NOTE: LC Series Controllers must be used with
D-Series Wall-Mount Units
D42L2PA D42L2PB
D48L2PA D48L2PB
D60L2PA D60L2PB
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 2100-643C Supersedes: 2100-643B Date: 7-28-16
Page 1 of 59
CONTENTS
SECTION 1: Installation Instructions ......................................................................................................... 5
List of Necessary Materials/Tools .........................................................................................................................6
Site Preparation .................................................................................................................................................7
Wall-Mount Unit Installation ...............................................................................................................................9
Wall-Mount Unit Supply Wiring ..........................................................................................................................15
Preliminary Start-Up .........................................................................................................................................19
SECTION 2: Service Instructions ............................................................................................................... 21
General Refrigerant Information .........................................................................................................................22
Sequence of Operation .....................................................................................................................................24
Using the TEC-EYE
Componentry Specifications ..............................................................................................................................30
Maintenance and Troubleshooting ......................................................................................................................38
SECTION 3: Appendix .................................................................................................................................. 45
Wall-Mount Unit Architecture ............................................................................................................................46
FIGURES AND TABLES
Figure 1.1 Wall-Mount Unit Model Nomenclature ......6
Figure 1.2 Dimensions ............................................8
Figure 1.3A D25A, D25L, D35A, D35L
Mounting Instructions ...........................10
Figure 1.3B D28A, D28L, D36A, D36L, D42A, D42L,
Mounting Instructions ...........................11
Figure 1.3C D48A, D48L, D60A, D60L
Mounting Instructions ...........................12
Figure 1.4 Electric Heat Clearance .........................13
Figure 1.5 Wall Mounting Instructions ....................13
Figure 1.6 Wall Mounting Instructions ....................14
Figure 1.7 Common Wall Mounting Installations ......14
Figure 1.8 Circuit Routing Label ............................15
Figure 1.9 WIRING: VAC and VDC Supply Wiring
Landing Points .....................................17
Figure 1.10 Adjusting the 230/208VAC Transformer ..17
Figure 1.11 Bard Polarity-Voltage Monitor .................18
Figure 2.1 Refrigerant Sight Glass .........................23
Figure 2.2 Wall-Mount Unit Control Board ..............25
Figure 2.3 TEC-EYE Figure 2.4 TEC-EYE Figure 2.5 TEC-EYE
Figure 2.6 Fan Blade Setting .................................32
Figure 2.7 Dirty Filter Switch .................................32
Figure 2.8 Power Loss Relay Circuit .......................33
Figure 2.9 High Pressure Relay Circuit ...................33
Figure 2.10 Blower Motor Start Relay Circuit ............33
Figure 2.11 D25A/L, D35A/L Unit Control Panel .......34
Figure 2.12 D28A/L, D36A/L, D42A/L, D48A/L,
D60A/L Unit Control Panel ....................35
Figure 2.13 WIRING: D25A/L, D35A/L
Unit Wiring Diagram .............................36
Figure 2.14 WIRING: D28A/L, D36A/L, D42A/L, ..........
D48A/L, D60A/L Unit Wiring Diagram ....37
Figure 2.15 Troubleshooting Motor Power Supply ......39
Figure 2.16 Troubleshooting Motor Start Command ...40
Figure 2.17 Troubleshooting Speed Voltage ...............40
Figure 2.18 VDC Polarity Check ...............................41
Figure 2.19 Verifying Incoming Voltage: VDC .............42
TM
........................................................................................................................................27
Table 1.1 Electrical Specifications ..........................16
Table 2.1 Nominal Pressures ..................................23
Table 2.2 Blower Speed Voltage Chart .....................24
Table 2.3 Temp vs. Resistance of Temp Sensor. ........31
Table 2.4 Indoor Blower Performance ......................32
Table 2.5 Troubleshooting 48VDC Blower Motor ........39
Table 2.6 Blower Speed Voltage Chart .....................40
TM
Display ................................27
TM
Connection to Unit Control ....27
TM
Status Display......................28
Manual 2100-643C Page 2 of 59
GENERAL INFORMATION
DC FREE COOLING UNIT SYSTEM
The Bard DC Free Cooling Unit system is composed of two (2) D-Series DUAL-TEC™ wall-mount air conditioners matched with one (1) LC Series lead/lag controller. The D-Series, specifically engineered for the telecom market, can provide outdoor air cooling during power loss situations through the use of onsite -48VDC positive ground battery banks.
NOTE: The LC Series lead/lag controller and the
D-Series wall-mount units are designed specifically to work together. The controller cannot run other Bard models or other brands of systems, nor can other controllers or thermostats run the D-Series wall-mount units. They are a complete system, and must be used together.
WALL-MOUNT AIR CONDITIONER UNITS
The D-Series units operate on both VAC and VDC power under normal power supply conditions. If there is loss of VAC power supply (shore and/or back-up generator) the unit will continue to operate as free cooling or ventilation system using the shelter’s VDC power. The indoor blower and free cooling unit operate from -48VDC and no inverter is required.
The units will supply 100% of rated cooling airflow in free cooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.
Each of these units are fully charged with refrigerant and have auxilliary heat installed.
GENERAL
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See ADDITIONAL PUBLICATIONS for information on codes and standards.
Sizing of systems for proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection
Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where
local regulations are at a variance with instructions, installer should adhere to local codes.
SHIPPING DAMAGE
Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
These units must remain in upright position at all times.
ADDITIONAL PUBLICATIONS
These publications can help when installing the air conditioning system. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection
....................................................... ACCA Manual D
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI)
11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
Manual 2100-643C Page 3 of 59
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE)
1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA)
Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
ANSI Z535.5 Definitions:
Danger: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
Warning: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
Caution: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
Notice: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to “NOTICE” the word “CAUTION” without the safety alert symbol may be used to indicate a message not related to personal injury.
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
!
WARNING
Fire hazard.
Maintain minimum 1/4” clearance between the supply air duct and combustible materials in
the rst 3’ feet of ducting.
Failure to do so could result in re causing damage, injury or death.
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
Manual 2100-643C Page 4 of 59
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.
SECTION 1:
INSTALLATION
INSTRUCTIONS
Manual 2100-643C Page 5 of 59
LIST OF NECESSARY MATERIALS/TOOLS
Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must be sourced before installation. This list also includes tools needed for installation.
LIST OF MATERIALS/TOOLS
Personal protective equipment/safety devices
Supply/return grilles
Field-fabricated sleeves (if necessary)
Fasteners sufficient for mounting the units such as 5/16" diameter anchor/carriage/lag bolts
7/8" diameter washers
Caulking materials
Miscellaneous hand and power tools and jobsite or shop materials
Lifting equipment with the necessary capacity and rigging to safely move/install the systems
Electrical supplies:
- Two (2) 20A circuit breakers for the shelter DC
power plant (one per wall-mount unit)
- Two (2) various size circuit breakers for
the shelter AC breaker box (see Table 1.1: Electrical Specifications on page 16)
- High-voltage wire of various gauges (see Table
1.1)
- Communication wire: 2-wire, 18 gauge,
shielded with drain
- Miscellaneous electrical supplies including
rigid/flexible conduit and fittings, junction boxes, wire connectors and supports
The following are required and must be sourced prior to installation of these units.
• Two (2) 20A circuit breakers for the shelter DC power plant (one per wall-mount unit)
Circuit breakers for Emerson Network Power (ENP) power plants (used in most telecomm shelters built today) are available directly through the following distributors:
• Emerson Network Power: 440.288.1122
• Master Electronics: 888.473.5297 or
www.onlinecomponents.com
Emerson Network Power (ENP) Part Number
• 20A circuit breaker: P/N 101601
Always confirm the application before ordering.
FIGURE 1.1
D-Series DUAL-TEC™ Wall-Mount Unit Model Nomenclature
D 25 A 2 P A 05 4 P X X X J
MODEL
SERIES
CAPACITY
25 – 2 Ton
28 – 2½ Ton
35 – 3 Ton 36 – 3 Ton
Manual 2100-643C Page 6 of 59
42 – 3½ Ton 48 – 4 Ton 60 – 5 Ton
A – Right Hand
L – Left Hand
REVISION
PLC
VOLTS & PHASE
A – 230/208-60-1 B – 230/208-60-3
KW
0Z – 0 KW 05 – 5 KW 06 – 6 KW
-48VDC
Free Cooling
Unit
COIL OPTIONS
X – Standard 3 – Phenolic Coated Evaporator and Condenser
SPECIAL FEATURES
COLOR OPTIONS
X – Beige 1 – White 4 – Buckeye Gray
FILTER OPTIONS
P – 2-Inch Pleated (MERV 8) M – 2-Inch Pleated (MERV 11)
CONTROL MODULES
J – High Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control, Alarm Contacts, Start Assist C – J Module + Compressor Crankcase Heater
SITE PREPARATION
NEW SHELTER INSTALLATION VS. RETROFIT INSTALLATION
These installation instructions cover both new shelter installations and retrofit installations. Each installation is unique and may require special accomodations and modifications. Although Bard Manufacturing follows a long-established tradition of manufacturing equipment using industry standard dimensions for building penetration, it is occasionally necessary to move or enlarge supply and return openings when replacing non-standardized equipment in a retrofit application.
MINIMUM CLEARANCE
D-Series wall-mount air conditioners are available in both right-hand access models and left-hand access models. Right-hand access models have the heat strip access panel, external circuit breakers access panel and internal controls access panel on the right side of the unit. Left-hand access models are a mirror image of the right-hand access models, and allow two wall­mount units to be placed in relatively close proximity and yet still allow complete access for maintenance and repair.
On side-by-side installations, maintain a minimum of 26" clearance on control side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. For installations where units are installed with both control panels facing each other (inward), maintain a minimum of 36" clearance to allow access. Additional clearance may be required to meet local or national codes.
Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or a large object can cause obstructions to the condenser discharge air. Recirculation or reduced airflow caused by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
For units with blow through condensers, such as the D-Series units, it is recommended there be a minimum distance of 10' between the front of the unit and any barrier or 20' between the fronts of two opposing (facing) units.
CLEARANCE TO COMBUSTIBLES
!
WARNING
Fire hazard.
Maintain minimum 1/4" clearance between the supply air duct and combustible materials in
the rst 3' of ducting.
Failure to do so could result in re causing damage, injury or death.
The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures 1.3A-C on pages 10-12 for details on opening sizes.
Minimum Clearances Required to Combustible Materials
MODELS
All covered by this manual
SUPPLY AIR DUCT
FIRST 3'
1/4" 0"
CABINET
MODEL IDENTIFICATION
Identify the specific model using the model nomenclature information found in Figure 1.1 and/ or model/serial tag found on the unit on the opposite side of the control and access panels. See Figure 1.2 on page 8 for dimensions and critical installation requirements.
Clearances Required for Service Access and Adequate Condenser Airflow
MODELS LEFT SIDE RIGHT SIDE
All covered by this manual 26" 26"
Units with control panels facing each other (inward)
36" between units
Manual 2100-643C Page 7 of 59
FIGURE 1.2
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
Width
Depth
Model
D25A/L D35A/L
D28A/L D36A/L D42A/L
D48A/L D60A/L
(W)
38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 4.19 12.00 9.00
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
Height
(D)
Supply Return
(H)
A B C B E F G I J K L M N O P Q R S T
All dimensions are in inches. Dimensional drawings are not to scale.
Side View
Built In Rain Hood 4° Pitch
D
1.250
Cond.
Air
Inlet
D
1.250
2.13
J
Drain
Electric Heat
A
I
C H
K
Heater Access Panel
C. Breaker/ Disconnect Access Panel (Lockable)
Econ. Hood
Side Wall Mounting
Brackets
(Built In)
Top Rain
Flashing Shipping Location
Optional
Electrical
Entrances
L
M
N
E O
Supply Air Opening
B
Return Air Opening
P
Back View
Q
W
D**A
RIGHT
HAND
UNIT
D**L LEFT
HAND
UNIT
Built In
Rain Hood
W
ECON Hood
F
Ventilation Air
Cond.
G
Air
Outlet
4° Pitch
Heater
Access
Panel
Electric
Heat
C. Breaker/ Disconnect
Access Panel
(Lockable)
7.000
Low Voltage
Electrical
Entrance
High Voltage
Electrical
Entrance
Front View
E
.44
R
S
S
O
Supply Air Opening
B
Side Wall Mounting Brackets (Built In)
Top Rain
Flashing Shipping Location
2.13
A
I
.44
Bottom Installation Bracket
MIS-3849
R
S
S
S
S
S
T
S
S
S
T
Drain
Return Air Opening
Bottom
Installation
Bracket
Back View
Manual 2100-643C Page 8 of 59
Optional Electrical Entrances
M
P
N
Q
C
Ventilation Air
H
K
L
Cond.
J
Air
Inlet
7.000
Low Voltage Electrical Entrance
High Voltage Electrical Entrance
Condenser
Air Outlet
Front ViewSide View
F
G
MIS-3848
WALL-MOUNT UNIT INSTALLATION
MOUNTING THE UNITS
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
NOTE: It may be best to spot some electrical knockouts (such as those located on the back of the wall­mount unit) before units are mounted and access is unavailable or limited (see Figure 1.2 to locate pre­punched knockouts).
Two holes for the supply and return air openings must be cut through the wall as shown in Figures 1.3A­C on pages 10-12. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
In retrofit (unit replacement) installations, the openings cut for the original equipment may not line up exactly with needs of this installation. Modifications may need to be made, such as increasing or decreasing the size of the wall cutouts. The existing bolt placement may not line up in which case the original bolts would need to be removed or cut away.
1. These units are secured by wall mounting flanges which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
2. The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figures
1.3A-C for details on opening sizes.
3. Locate and mark lag bolt locations and location for optional bottom mounting bracket, if desired (see Figures 1.3A-C).
4. Mount bottom mounting bracket (if used).
5. If desired, hook top rain flashing (attached to front­right of supply flange for shipping) under back bend of top.
6. Position unit in opening and secure with fasteners sufficient for the application such as 5/16" lag/ anchor/carriage bolts; use 7/8" diameter flat washers on the bolts. It is recommended that a bead of silicone caulking be placed behind the side mounting flanges.
7. Secure optional rain flashing to wall and caulk across entire length of top (see Figures 1.3A-C).
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
Manual 2100-643C Page 9 of 59
FOUR SIDES OF SUPPLY
Wall Opening and Hole Location View
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALSCRECOMMENDED 1" CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
AIR DUCT IS REQUIRED
1/4" CLEARANCE ON ALL
FROM COMBUSTABLE
MIS-3820
MATERIALS
FOAM AIR SEAL
SUPPLIED
RAIN FLASHING
SEAL WITH BEAD
FIGURE 1.3A
OF CAULKING ALONG
Mounting Instructions
ENTIRE LENGTH OF TOP.
D25A, D25L, D35A, D35L
ED
17 5/8
3 11/16
TOP
4 7/16
WALL STRUCTURE
WALL
SUPPLY AIR
DUCT
PANEL
HEATER ACCESS
B
TOP FLASHING AT TIME OF INSTALLATION.
IT IS RECOMMENDED THAT A BEAD OF
THE SIDE MOUNTING FLANGES AND UNDER
RETURN AIR
OPENING
NOTES:
SILICONE CAULKING BE PLACED BEHIND
W**A UNIT SHOWN, W**L UNIT
CONTROLS AND HEATER ACCESS
IS ON OPPOSITE (LEFT) SIDE.
Right Side View
"
7
8
4
E
14"
"
16
11
4
5 3/8
B
8 3/8A9 7/829 7/8
4 5/8 16 7/8
28 3/8
Manual 2100-643C Page 10 of 59
C
A
Supply Opening
Return Opening
28"
C
D
12"
12"
12"
12"
4"
"
Typ.
1
8
3
"
7
8
"
7
8
2
"
7
8
12"
4"
Typ.
"
1
16
9
"
16
11
4
D
16"
16"
16"
16"
16"
1
7
8
"
6
1
2
" 6
1
2
"
2
1
8
"
7
8
"
1"
3"
4"
Typ.
4"
Typ.
6
1
2
"
30"
E
16"
A CC
3
1
8
"
B
Wall Opening and Hole Location View
RETURN AIR
1
REQUIRED DIMENSIONS TO MAINTAIN
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
29
DUCT
COMBUSTIBLE MATERIALS
A B C DE
30 1/2
10 1/2
6 1/4 1 1/4 29 3/4
32 12 5 1/2
2
NOTES:
WALL STRUCTURE
1
SUPPLY AIR
IT IS RECOMMENDED THAT A BEAD OF
OPENING
Right Side View
RAIN FLASHING
SILICONE CAULKING BE PLACED BEHIND
RECOMMENDED 1" CLEARANCE FROM
THE SIDE MOUNTING FLANGES AND UNDER
TOP FLASHING AT TIME OF INSTALLATION.
TOP.
PANEL
HEATER ACCESS
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
FROM COMBUSTABLE
WALL
1/4" CLEARANCE ON ALL
MATERIALS
Supply Opening
FOAM AIR SEAL
SUPPLIED
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
1
Return Opening
MIS-416 E
Dimension is 21" on 95" tall units.
2
Dimension is 10" on T48H1 & T60H1.
2
Dimension is 6" on T48H1 & T60H1.
3
3
FIGURE 1.3B
Mounting Instructions
D28A, D28L, D36A, D36L, D42A, D42L
Manual 2100-643C Page 11 of 59
D
16"
16"
16"
16"
16"
2
"6
8
" 5
8 97
"
1"
3"
Typ.
1
4"
4"
Typ.
6
1
2
"
30"
E
16"
A CC
"
7
8
3
B
"
8
7
1
1
2
"6
1 1/430 1/2
1/4" CLEARANCE ON ALL
SUPPLIED
FOAM AIR SEAL
A
Supply Opening
SILICONE CAULKING BE PLACED BEHIND
DUCT
FOUR SIDES OF SUPPLY
FROM COMBUSTABLE
1/4" MIN. CLEARANCE FROM
COMBUSTIBLE MATERIALS
REQUIRED DIMENSIONS TO MAINTAIN
OPENING
COMBUSTIBLE MATERIALS
B D E
PANEL
AIR DUCT IS REQUIRED
32
10 1/2
Right Side View
SUPPLY AIR
RECOMMENDED 1" CLEARANCE FROM
MIS-3789
RAIN FLASHING
REQUIRED DIMENSIONS TO MAINTAIN
12
TOP.
MATERIALS
5 1/2
WALL STRUCTURE
2
6 1/4
29
29 3/4
IT IS RECOMMENDED THAT A BEAD OF
THE SIDE MOUNTING FLANGES AND UNDER
WALL
C
Wall Opening and Hole Location View
NOTES:
TOP FLASHING AT TIME OF INSTALLATION.
HEATER ACCESS
RETURN AIR
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
TOP
Return Opening
FIGURE 1.3C
Mounting Instructions
D48A, D48L, D60A, D60L
Manual 2100-643C Page 12 of 59
FIGURE 1.4
DUCT
OPENING
RETURN AIR
SUPPLY AIR
WOOD FRAME WALL INSTALLATION
OPENING
WALL BEFORE
MOUNT ON UNIT
OPENING
BEFORE INSTALLATION
BOTTOM MOUNTING
CONCRETE BLOCK WALL INSTALLATION
BRACKET. MOUNT ON
OPENING
WOOD OR STEEL SIDING
OPENING
INSTALLING UNIT.
RETURN AIR
WALL STRUCTURE
RETURN AIR
SUPPLY AIR
FACTORY SUPPLIED
RAIN FLASHING.
SUPPLY AIR
MIS-548 A
SIDE VIEW
Electric Heat Clearance
Wall Mounting Instructions
See FIGURE 2 – Mounting Instructions
FIGURE 1.5
Manual 2100-643C Page 13 of 59
FIGURE 1.6
I
A
C
K
E + 1.000
B
1.000
SUPPLY DUCT
OVER FRAME
INTERIOR FINISHED WALL
ALL AROUND DUCT
FRAMING MATERIAL
EXTERIOR FINISH WALL
OPENING
FOR ACTUAL DIMENSIONS.
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
ATTACH TO TOP
1.000" CLEARANCE
1.000" CLEARANCE
PLATE OF WALL
C
SEE UNIT DIMENSIONS, FIGURE 2,
OPENING
RETURN DUCT
2 x 6
ATTACH TO BOTTOM
OVER FRAME
PLATE OF WALL
L
THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.
MIS-549 B
ALL AROUND DUCT
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
OPENING W/ GRILLE
SUPPLY AIR DUCT
RAFTERS
RAFTERS
RETURN AIR OPENING W/ GRILLE
DUCTED SUPPLY
OR BELOW CEILING RAFTERS AS SHOWN
FINISHED CEILING SURFACE
RAIN
FLASHING
RAIN
FLASHING
RETURN AT UNITNO DUCT
RETURN AIR
FINISHED CEILING SURFACE
FREE AIR FLOW
OUTSIDE
WALL
OUTSIDE
WALL
SUPPLY AIR DUCT W/ GRILLE
Wall Mounting Instructions
SEE UNIT DIMENSIONS, FIGURE 1-2, FOR ACTUAL DIMENSIONS
FIGURE 1.7
Common Wall Mounting Installations
Manual 2100-643C Page 14 of 59
WALL-MOUNT UNIT SUPPLY WIRING
NOTICE / AVIS
ROUTE ALL HIGH VOLTAGE FIELD
WIRES TO THE RIGHT OF THE WIRE
SHIELD AS SHOWN
ACHEMINER LES FILS HAUTE
TENSION SUR LA DROITE VERS LA
PROTECTION, COMME INDIQUÉ
VAC CIRCUIT BREAKER
/DISJONCTEUR
WIRE SHIELD /
PROTECTION
WHITE 3/16" LETTERING
7961-807
VDC CIRCUIT BREAKER
/DISJONCTEUR
All models covered by this installation instruction require dual power sources: VAC utility power to run the compressor, heat and outdoor fan motor and -48 VDC power to operate the indoor blower and DC free cooling damper.
These units require a positive ground
-48 VDC copper conductor field wire connection. Refer to the unit wiring diagram
for more information.
!
WARNING
Route all field wires to the right of the wire shield as shown in the circuit routing label found in Figure 1.8 (and also on the wall-mount units).
Run communication wires in separate conduit whenever possible. If a unique installation occurs where it is not possible to isolate the communication wires, it is permissible to run communication wires in a conduit which contains a dedicated VDC voltage line. In all cases, the communication wires must be shielded, twisted wire and utilize proper filtration at the main communications board. It is never permissible to
run communication wires with VAC voltage lines.
FIGURE 1.8
Circuit Routing Label
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
Refer to the unit rating plate or Table 1.1 on page 16 for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. The field wiring used must be sized to carry models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
that amount of current. All
See Figure 1.9 on page 17 to reference VAC and VDC supply wiring landing points.
IMPORTANT: 230/208V 1 phase and 3 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. It is very important that the correct voltage tap is used. For 208V operation, reconnect from 240V to 208V tap (see Figure 1.10). The acceptable operating voltage range for the 240 and 208V taps are: 240V Tap (253 – 216) and 208 Tap (220 – 197).
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.
Manual 2100-643C Page 15 of 59
TABLE 1.1
Electrical Specifications
AC POWER CIRCUIT DC POSITIVE GROUND POWER CIRCUIT
Model
D25A2PA0Z/D25L2PA0Z 208/230-60-1 19 30 10/10 15.6 20 12
D25A2PA05/D25L2PA05 208/230-60-1 26 30 8/10 15.6 20 12
D35A2PA0Z/D35L2PA0Z 208/230-60-1 24 40 8/10 15.6 20 12
D35A2PA05/D35L2PA05 208/230-60-1 26 40 8/10 15.6 20 12
D35A2PB0Z/D35L2PB0Z 208/230-60-3 19 25 10/10 15.6 20 12
D35A2PB06/D35L2PB06 208/230-60-3 19 25 10/10 15.6 20 12
D28A2PA05/D28L2PA05 208/230-60-1 26 30 10/10 15.6 20 12
D28A2PB06/D28L2PB06 208/230-60-3 18 20 12/12 15.6 20 12
D36A2PA05/D36L2PA05 208/230-60-1 26 40 8/10 15.6 20 12
D36A2PB06/D36L2PB06 208/230-60-3 18 25 10/10 15.6 20 12
D42A2PA05/D42L2PA05 208/230-60-1 26 40 8/10 15.6 20 12
D42A2PB06/D42L2PB06 208/230-60-3 20 25 10/10 15.6 20 12
D48A2PA05/D48L2PA05 208/230-60-1 30 50 8/10 15.6 20 12
D48A2PB06/D48L2PB06 208/230-60-3 20 30 10/10 15.6 20 12
D60A2PA05/D60L2PA05 208/230-60-1 36 60 6/10 15.6 20 12
D60A2PB06/D60L2PB06 208/230-60-3 30 40 8/10 15.6 20 12
Rated Volts,
Hertz & Phase
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power/ Ground Wire
Size
Minimum
Circuit
Ampacity
Maximum
External Fuse
or Ckt. Breaker
Field Power/
Ground Wire
Size
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest version), Article 310 for power conductor sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention
to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors. Based on 75°C copper wire. All wiring must conform to the National Electric Code and all local codes.
Manual 2100-643C Page 16 of 59
FIGURE 1.9
VAC and VDC Supply Wiring Landing Points
.
Field Wiring
VDC
.
.
-
Factory
Wiring
VAC
Field Wiring
Factory
+
NOTE: Right-hand access model wiring landing points
are shown here; left-hand access models will mirror this image.
Wiring
NOTE: Right-hand access model wiring landing points
are shown here; left-hand access models will mirror this image.
FIGURE 1.10
Adjusting the 230/208 VAC Transformer
230/208V 1 phase and 3 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. It is very important that the correct voltage tap is used. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are: 240V Tap (253 – 216) and 208 Tap (220 – 197).
1. Verify incoming AC voltage: Multimeter set to VAC
2. If incoming AC voltage is 220VAC or above...
...do not adjust transformer
.
Shelter supply breaker in ON position
Bard system breaker in OFF position
230V/208V Single Phase Voltage Range:
197VAC – 253VAC
230V/208V Three Phase Voltage Range:
197VAC – 253VAC
(not shown)
230VAC
+
3. If incoming AC voltage is below 220VAC...
...shut off AC breaker to unit
and move factory "240V" wire to "208V" terminal
Manual 2100-643C Page 17 of 59
FIGURE 1.11
Bard Polarity-Voltage Monitor
If the VDC wiring is not terminated correctly on the specific polarity-indicated terminals of the VDC terminal block, the VDC controls and motors will not activate and the wall-mounted unit will not function.
The Bard Polarity-Voltage Monitor continually monitors for correct polarity and voltage. If field wiring is connected improperly, or the voltage is outside of the system parameters, the Polarity-Voltage Monitor will not allow any VDC voltage to enter the system, protecting the internal controls and equipment.
+
When field wiring is correct in voltage and polarity, the green power (PWR) LED and yellow polarity (POL) LED will light, and system will operate normally.
If field wiring is incorrect in polarity, the red FAULT LED will light, and the monitor will not allow VDC voltage into the system.
If field wiring is correct in polarity but outside of the required 40VDC – 56VDC, the green PWR LED will not illuminate and the monitor not allow VDC voltage into the system.
If the Polarity-Voltage Monitor is showing a problem with polarity and/or voltage, see pages 41 and 42 of the Service section of this manual for instructions on checking VDC polarity and verifying incoming VDC voltage.
Manual 2100-643C Page 18 of 59
Loading...
+ 41 hidden pages