Bard D48L2P/BLD.10309, D36L2P/BLD.10305, D60A2P/BLD.10310, D60L2P/BLD.10303, D42A2P/BLD.10306 Installation And Service Instructions Manual

...
INSTALLATION AND SERVICE
INSTRUCTIONS
&
REPLACEMENT PARTS MANUAL
DC FREE COOLING UNIT SYSTEM
TWO (2) D-SERIES DUAL-TEC™
WALL-MOUNTED PACKAGE
AIR CONDITIONERS
&
ONE (1) BARD-LINKTM PLC
LEAD/LAG CONTROLLER
AIR CONDITIONER MODELS
D36A2P/BLD.10304 D36L2P/BLD.10305 D42A2P/BLD.10306 D42L2P/BLD.10307 D48A2P/BLD.10308 D48L2P/BLD.10309 D60A2P/BLD.10310 D60L2P/BLD.10303
CONTROLLER MODELS
LC1000-100/BLD.10293 LC1500-100/BLD.10291
NOTE: BARD-LINKTM LC1000-1000 or LC1500-100 Controllers must be used
with D-Series Wall-Mount Units
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual : 2100-620A Supersedes: 2100-620 Date: 3-25-15
Page 1 of 107
CONTENTS
SECTION 1: Installation Instructions ......................................................................................................... 7
List of Necessary Materials/Tools .........................................................................................................................8
Site Preparation .................................................................................................................................................9
Wall-Mount Unit Installation .............................................................................................................................11
Wall-Mount Unit Supply Wiring ..........................................................................................................................15
Preliminary Start-Up .........................................................................................................................................19
Bard-LinkTM Controller Installation .....................................................................................................................20
System Start-Up ..............................................................................................................................................36
SECTION 2: Service Instructions ............................................................................................................... 39
General Refrigerant Information .........................................................................................................................40
Sequence of Operation .....................................................................................................................................42
Advanced Programming ....................................................................................................................................49
Using the TEC-EYE ..........................................................................................................................................54
Componentry Specifications ..............................................................................................................................57
Maintenance and Troubleshooting ......................................................................................................................64
SECTION 3: Parts Manual ............................................................................................................................ 73
D-Series Wall-Mount Unit .................................................................................................................................74
Bard-LinkTM PLC Lead/Lag Controller ..................................................................................................................88
SECTION 4: Appendices .............................................................................................................................. 91
Appendix 1: LC-Series Controller Architecture .....................................................................................................92
Appendix 2: TEC-EYE Architecture ....................................................................................................................99
FIGURES AND TABLES
Figure 1.1 Wall-Mount Unit Model Nomenclature ......8
Figure 1.2 Dimensions ..........................................10
Figure 1.3 Mounting Instructions ...........................12
Figure 1.4 Electric Heat Clearance .........................13
Figure 1.5 Wall Mounting Instructions ....................13
Figure 1.6 Wall Mounting Instructions ....................14
Figure 1.7 Common Wall Mounting Installations ......14
Figure 1.8 Circuit Routing Label ............................16
Figure 1.9 WIRING: Figure 1.10 Adjusting the 230/208VAC Transformer ..17 Figure 1.11 WIRING:
Figure 1.12 Bard Polarity-Voltage Monitor .................18
Figure 1.13 WIRING:
Figure 1.14 Remote Temperature Sensor Install ........22
Figure 1.15 Additional Remote Temp Sensor Install ...23 Figure 1.16 Power and Signal Connections – Smoke ..24
Figure 1.17 Power/Signal Connections – Hydrogen ....25
Figure 1.18 LC1000/LC1500 Generator Run ............25
Figure 1.19 WIRING: Figure 1.20 WIRING:
Figure 1.21 WIRING: Communication Wiring ............28
Figure 1.22 WIRING: Communication Wiring:
Controller Termination ........................... 29
Figure 1.23 WIRING: Communication Wiring:
1st Unit Termination ............................. 30
Figure 1.24 WIRING: Communication Wiring:
2nd Unit Termination ............................ 31
Figure 1.25 Controller Circuit Install ........................32
Figure 1.26 Controller Grounding Posts ....................32
Figure 1.27 WIRING: Figure 1.28 WIRING:
Figure 1.29 Bard-LinkTM Controller Display ...............36
Figure 1.30 Clock/Scheduler Menu ..........................36
Figure 1.31 Status Display Showing Units "Online" ....36
Figure 1.32 Executing Run Test ............................... 37
VAC Supply Wiring Landing Points . 16
VDC Supply Wiring Landing Points . 17
Typical LC1000/LC1500 Wiring .. 20
LC1000 External Alarm Wiring .. 26 LC1500 External Alarm Wiring .. 27
LC1000/LC1500 Wiring Diagram .. 34 LC1500 Punch-Down Block Wiring 35
Figure 2.1 Refrigerant Sight Glass .........................41
Figure 2.2 Wall-Mount Unit Control Board ..............43
Figure 2.3 Controller Board and Terminal Block .......45
Figure 2.4 LC Series Controller Control Board .........46
Figure 2.5 Free Cooling Damper Operation ..............48
Figure 2.6 Bard-LinkTM Controller Display ...............49
Figure 2.7 Controller Status Display .......................50
Figure 2.8 TEC-EYE Display ..................................54
Figure 2.9 TEC-EYE Connection to Unit Control ......54
Figure 2.10 TEC-EYE Status Display ........................55
Figure 2.11 Fan Blade Setting .................................59
Figure 2.12 Dirty Filter Switch .................................59
Figure 2.13 Power Loss Relay Circuit .......................60
Figure 2.14 High Pressure Relay Circuit ...................60
Figure 2.15 Blower Motor Start Relay Circuit ............60
Figure 2.16 Unit Control Panel ................................61
Figure 2.17 WIRING: Unit Wiring Diagram ................62
Figure 2.18 Low Voltage Connections .......................63
Figure 2.19 Troubleshooting Motor Power Supply ......65
Figure 2.20 Troubleshooting Motor Start Command ...66
Figure 2.21 Troubleshooting Speed Voltage ...............66
Figure 2.22 VDC Polarity Check ...............................67
Figure 2.23 Verifying Incoming Voltage .....................68
Table 1.1 Electrical Specifications ..........................15
Table 1.2 Terminal Block Index ............................... 33
Table 1.3 Controller Default Settings .......................38
Table 2.1 Nominal Pressures ..................................41
Table 2.2 Blower Speed Voltage Chart .....................42
Table 2.3 Controller Default Settings .......................48
Table 2.4 Controller Programmable Features ............52
Table 2.5 Temp vs. Resistance of Temp Sensor. ........ 58
Table 2.6 Indoor Blower Performance ......................59
Table 2.7 Troubleshooting 48VDC Blower Motor ........65
Table 2.8 Blower Speed Voltage Chart .....................66
Manual 2100-620A Page 2 of 107
GENERAL INFORMATION
DC FREE COOLING UNIT SYSTEM (DC-FCU)
The Bard DC Free Cooling Unit system is composed of two (2) D-Series DUAL-TEC™ wall-mounted air conditioners matched with one (1) Bard-LinkTM PLC lead/lag controller. The D-Series, specifically engineered for the telecom market, can provide outdoor air cooling during power loss situations through the use of onsite -48VDC positive ground battery banks.
TM
NOTE: The Bard-Link
work together. The PLC controller cannot run other Bard models or other brands of systems, nor can other controllers or thermostats run the D-Series wall-mount units. They are a complete system, and must be used together.
WALL-MOUNT AIR CONDITIONER UNITS
The D-Series units operate on both VAC and VDC power under normal power supply conditions. If there is loss of VAC power supply (shore and/or back-up generator) the unit will continue to operate as free cooling or ventilation system using the shelter’s VDC power. The indoor blower and free cooling unit operate from -48VDC and no inverter is required.
The units will supply 100% of rated cooling airflow in free cooling mode with ability to exhaust the same amount through the unit itself without any additional relief openings in the shelter.
Each of these units are fully charged with refrigerant and have auxilliary heat installed.
BARD-LINKTM PLC CONTROLLER
Two models: LC1000-100 and LC1500-100 (controllers and accessories included with controllers shown below).
PLC lead/lag controller and the D-Series wall-mount units are designed specifically to
LC1000-100 Series – New Shelters Only
TEC-EYE Hand-Held Diagnostic Tool
Programmable Logic Controller
Remote Temperature
Sensor with 35' Cable
LC1500-100 Series – EOL and All HVAC Replacement Projects
TEC-EYE Hand-Held Diagnostic Tool
Programmable Logic Controller with Attached 66 Punch-Down Block
Remote Temperature
Sensor with 35' Cable
Communication
EMI Filters
Communication EMI Filters
VDC Smoke Detector
OPTIONAL 8301-061
VDC
Hydrogen
Detector
Manual 2100-620A Page 3 of 107
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the air cooled self-contained unit and the electrical wiring connections to the unit.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Page 3 for information on codes and standards.
Sizing of systems for proposed installation should be calculated by AT&T-specific methods/software using regional climatic data and standards. The air duct should be installed in accordance with the Standards
of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at
a variance with instructions, installer should adhere to local codes.
Shipping Damage
Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
These units must remain in upright position at all times.
ADDITIONAL PUBLICATIONS
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
National Electrical Code ...................... ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection
....................................................... ACCA Manual D
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI) 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE) 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA) Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
Manual 2100-620A Page 4 of 107
ANSI Z535.5 Definitions:
Danger: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.
Warning: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.
Caution: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.
Notice: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to “NOTICE” the word “CAUTION” without the safety alert symbol may be used to indicate a message not related to personal injury.
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
!
WARNING
Fire hazard.
Maintain minimum 1/4” clearance between the supply air duct and combustible materials in
the rst 3’ feet of ducting.
Failure to do so could result in re causing damage, injury or death.
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
!
CAUTION
Cut hazard.
Wear gloves to avoid contact with sharp edges.
Failure to do so could result in personal injury.
Manual 2100-620A Page 5 of 107
Manual 2100-620A Page 6 of 107
SECTION 1:
INSTALLATION
INSTRUCTIONS
Manual 2100-620A Page 7 of 107
LIST OF NECESSARY MATERIALS/TOOLS
Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must be sourced before installation. This list also includes tools needed for installation.
LIST OF MATERIALS/TOOLS
Personal protective equipment/safety devices
Supply/return grilles
Field-fabricated sleeves (if necessary)
5/16" diameter anchor/carriage/lag bolts
7/8" diameter washers
Caulking materials
Miscellaneous hand and power tools and jobsite or shop materials
Lifting equipment with the necessary capacity and rigging to safely move/install the systems
Electrical supplies
- Two (2) 20A circuit breakers for the shelter DC
power plant (one per wall-mount unit)
- One (1) 5A circuit breaker for the shelter DC
power plant (for the Bard-Link
TM
controller)
- Two (2) various size circuit breakers for
the shelter AC breaker box (see Table 1.1: Electrical Specifications on page 15)
- High-voltage wire of various gauges (see Table
1.1)
- Communication wire: 2-wire, 18 gauge,
shielded with drain
- 18 gauge non-shielded wire for connecting
smoke detector (and hydrogen detector and/or generator, if applicable) to controller
-
CAT 6 Ethernet cable of field-determined length (for remote communication, if applicable)
- Miscellaneous electrical supplies including rigid/flexible conduit and fittings, junction boxes, wire connectors and supports
The following are required and must be sourced prior to installation of these units.
• Two (2) 20A circuit breakers for the shelter DC power plant (one per wall-mount unit)
• One (1) 5A circuit breaker for the shelter DC
TM
power plant (for the Bard-Link
controller)
Circuit breakers for Emerson Network Power (ENP) power plants (used in most telecomm shelters built today) are available directly through the following distributors:
• Emerson Network Power: 440.288.1122
• Master Electronics: 888.473.5297 or
www.onlinecomponents.com
Emerson Network Power (ENP) Part Numbers
• 20A circuit breaker: P/N 101601
• 5A circuit breaker: P/N 101598
Always confirm the application before ordering.
D-Series DUAL-TEC™ Wall-Mount Unit Model Nomenclature
D 36 A 2 P A 05 4 P X X X J
MODEL
SERIES
CAPACITY
36 – 3 Ton
42 – 3½ Ton
48 – 4 Ton 60 – 5 Ton
A – Right Hand
L – Left Hand
REVISION
PLC
VOLTS & PHASE
A – 230/208-60-1 B – 230/208-60-3
05 – 5 KW 06 – 6 KW 09 – 9 KW
10 – 10 KW
Manual 2100-620A Page 8 of 107
KW
FIGURE 1.1
-48VDC
Free Cooling
Unit
CONTROL MODULES
J – High Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control, Alarm Contacts, Start Assist C – J Module + Compressor Crankcase Heater
COIL OPTIONS
X – Standard 3 – Phenolic Coated Evaporator and Condenser
SPECIAL FEATURES
COLOR OPTIONS
X – Beige 1 – White 4 – Buckeye Gray
FILTER OPTIONS
P – 2-Inch Pleated (MERV 8) M – 2-Inch Pleated (MERV 11)
SITE PREPARATION
NEW SHELTER INSTALLATION VS. RETROFIT INSTALLATION
These installation instructions cover both new shelter installations and retrofit installations. Each installation is unique and may require special accomodations and modifications. Although Bard Manufacturing follows a long-established tradition of manufacturing equipment using industry standard dimensions for building penetration, it is occasionally necessary to move or enlarge supply and return openings when replacing non-standardized equipment in a retrofit application.
MINIMUM CLEARANCE
D-Series wall-mount air conditioners are available in both right-hand access models and left-hand access models. Right-hand access models have the heat strip access panel, external circuit breakers access panel and internal controls access panel on the right side of the unit. Left-hand access models are a mirror image of the right-hand access models, and allow two wall­mount units to be placed in relatively close proximity and yet still allow complete acess for maintenance and repair.
On side-by-side installations, maintain a minimum of 26" clearance on control side to allow access to control panel and heat strips, and to allow proper airflow to the outdoor coil. For installations where units are installed with both control panels facing each other (inward), maintain a minimum of 36" clearance to allow access. Additional clearance may be required to meet local or national codes.
Care should be taken to ensure that the recirculation and obstruction of condenser discharge air does not occur. Recirculation of condenser discharge air can be from either a single unit or multiple units. Any object such as shrubbery, a building or a large object can cause obstructions to the condenser discharge air. Recirculation or reduced airflow caused by obstructions will result in reduced capacity, possible unit pressure safety lockouts and reduced unit service life.
For units with blow through condensers, such as the D-Series units, it is recommended there be a minimum distance of 10' between the front of the unit and any barrier or 20' between the fronts of two opposing (facing) units.
CLEARANCE TO COMBUSTIBLES
!
WARNING
Fire hazard.
Maintain minimum 1/4” clearance between the supply air duct and combustible materials in
the rst 3’ feet of ducting.
Failure to do so could result in re causing damage, injury or death.
The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 1.3 on page 12 for details on opening sizes.
Minimum Clearances Required to Combustible Materials
MODELS
All covered by this manual
SUPPLY AIR DUCT
FIRST 3'
1/4" 0"
CABINET
MODEL IDENTIFICATION
Identify the specific model using the model nomenclature information found in Figure 1.1 and/ or model/serial tag found on the unit on the opposite side of the control and access panels. See Figure 1.2 on page 10 for dimensions and critical installation requirements.
Clearances Required for Service Access and Adequate Condenser Airflow
MODELS LEFT SIDE RIGHT SIDE
All covered by this manual 26" 26"
Units with control panels facing each other (inward)
36" between units
Manual 2100-620A Page 9 of 107
FIGURE 1.2
DRAIN
ENTRANCE
4° PITCH
RAIN HOOD
BUILT IN
PANEL
ACCESS
HEATER
(LOCKABLE)
VENT HOOD
ACCESS PANEL
DISCONNECT
ENTRANCE
ELECTRICAL
LOW VOLTAGE
C. BREAKER/
HIGH VOLTAGE ELECTRICAL
SIDE VIEW
JDK
H
7"
C
2.13
I
ELECTRIC HEAT
Top Rain Flashing Shipping Location
DOOR
AIR
VENTILIATION
VENT HOOD
Cond.
Air
Inlet
FRONT VIEW
F
G
W
SUPPLY AIR
OPENING
OPENING
RETURN AIR
Brackets (Built In)
Mounting
Optional Electrical Entrances
Side Wall
BOTTOM INSTALLATION BRACKET
BACK VIEW
S
E
T
O
S
S
S
S
R
Air Outlet
Condenser
Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal)
Width
Depth
Model
D36A/L D42A/L
D48A/L D60A/L
(W)
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
Height
(D)
Supply Return
(H)
A B C B E F G I J K L M N O P Q R S T
All dimensions are in inches. Dimensional drawings are not to scale.
D**A
RIGHT
HAND
UNIT
D**L
F
G
FRONT VIEW
W
Condenser
Air Outlet
W
HEATER ACCESS PANEL
ELECTRIC HEAT
C. BREAKER/ DISCONNECT ACCESS PANEL (LOCKABLE)
VENT HOOD DOOR
VENTILIATION AIR
VENT HOOD
LOW VOLTAGE ELECTRICAL ENTRANCE
HIGH VOLTAGE ELECTRICAL ENTRANCE
2.13 A
7"
BUILT IN RAIN HOOD 4° PITCH
LEFT
HAND
UNIT
VENT HOOD DOOR
VENTILIATION
F
G
Condenser
Air Outlet
AIR
I
H
C
J
K
D
Cond.
Air
Inlet
Cond.
Air
Inlet
SIDE VIEW
BUILT IN RAIN HOOD 4° PITCH
2.13
I
C
JDK
DRAIN
HEATER ACCESS PANEL
ELECTRIC HEAT
C. BREAKER/ DISCONNECT ACCESS PANEL (LOCKABLE)
7"
VENT HOOD
LOW VOLTAGE ELECTRICAL ENTRANCE
HIGH VOLTAGE ELECTRICAL ENTRANCE
H
Side Wall Mounting Brackets (Built In)
Optional Electrical Entrances
Top Rain Flashing Shipping Location
Side Wall Mounting Brackets (Built In)
Top Rain Flashing Shipping Location
Optional Electrical Entrances
SUPPLY AIR
OPENING
RETURN AIR
OPENING
BACK VIEW
SUPPLY AIR
OPENING
RETURN AIR
OPENING
E O
E O
R
S
S
S
S
S
BOTTOM INSTALLATION BRACKET
S
S
S
S
S
T
R
BACK VIEW
Manual 2100-620A Page 10 of 107
SIDE VIEW
BACK VIEW
BOTTOM INSTALLATION BRACKET
MIS-3618
T
WALL-MOUNT UNIT INSTALLATION
MOUNTING THE UNITS
!
WARNING
Heavy item hazard.
Use more than one person to handle unit.
Failure to do so could result in unit damage or serious injury.
NOTE: It may be best to spot some electrical knockouts (such as those located on the back of the wall­mount unit) before units are mounted and access is unavailable or limited (see Figure 1.2 to locate pre­punched knockouts).
Two holes for the supply and return air openings must be cut through the wall as shown in Figure 1.3 on page
12. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
NOTICE
AT&T National Standards forbids the use of any adaptor or transitional curbs for use in the installation of wall-mount HVAC systems.
If existing supply and return penetrations do not match new requirements, those openings must be modied to meet the
needs of the new equipment.
2. The unit itself is suitable for 0" clearance, but the supply air duct flange and the first 3' of supply air duct require a minimum of 1/4" clearance to combustible material. However, it is generally recommended that a 1" clearance is used for ease of installation and maintaining the required clearance to combustible material. See Figure 1.3 for details on opening sizes.
3. Locate and mark lag bolt locations and location for optional bottom mounting bracket, if desired (see Figure 1.3).
4. Mount bottom mounting bracket (if used).
5. If desired, hook top rain flashing (attached to front­right of supply flange for shipping) under back bend of top.
6. Position unit in opening and secure with 5/16" lag/ anchor/carriage bolts; use 7/8" diameter flat washers on the lag bolts. It is recommended that a bead of silicone caulking be placed behind the side mounting flanges.
7. Secure optional rain flashing to wall and caulk across entire length of top (see Figure 1.3).
8. For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall.
9. A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage.
In retrofit (unit replacement) installations, the openings cut for the original equipment may not line up exactly with needs of this installation. Modifications may need to be made, such as increasing or decreasing the size of the wall cutouts. The existing bolt placement may not line up in which case the original bolts would need to be removed or cut away.
1. These units are secured by wall mounting flanges which secure the unit to the outside wall surface at both sides. A bottom mounting bracket, attached to skid for shipping, is provided for ease of installation, but is not required.
Manual 2100-620A Page 11 of 107
SUPPLIED
RAIN FLASHING
FOAM AIR SEAL
WALL STRUCTURE
1/4" CLEARANCE ON ALL
FOUR SIDES OF SUPPLY
AIR DUCT IS REQUIRED
MATERIALS
FROM COMBUSTABLE
PANEL
DUCT
SUPPLY AIR
RETURN AIR
OPENING
NOTES:
IT IS RECOMMENDED THAT A BEAD OF
SILICONE CAULKING BE PLACED BEHIND
THE SIDE MOUNTING FLANGES AND UNDER
MIS-3354
TOP FLASHING AT TIME OF INSTALLATION.
Right Side View
TOP.
FIGURE 1.3
SEAL WITH BEAD
OF CAULKING ALONG
ENTIRE LENGTH OF
Mounting Instructions
A B C D E
HEATER ACCESS
WALL
TOP
29
2
B
E
16"
6 1/4 1 1/4 29 3/4
10 1/2
30 1/2
32 12 5 1/2
A CC
Supply Opening
Return Opening
30"
"
1
2
6
"
7
8
"
1
8
3
4"
3"
3
"
1
8
2
"
1
2
Typ.
1"
4"
Typ.
" 6
1
2
6
Wall Opening and Hole Location View
1
D
16"
16"
16"
16"
1
16"
"
7
8
1
2
COMBUSTIBLE MATERIALS
1/4" MIN. CLEARANCE FROM
REQUIRED DIMENSIONS TO MAINTAIN
REQUIRED DIMENSIONS TO MAINTAIN
RECOMMENDED 1" CLEARANCE FROM
COMBUSTIBLE MATERIALS
Manual 2100-620A Page 12 of 107
FIGURE 1.4
DUCT
OPENING
RETURN AIR
SUPPLY AIR
WOOD FRAME WALL INSTALLATION
OPENING
WALL BEFORE
MOUNT ON UNIT
OPENING
BEFORE INSTALLATION
BOTTOM MOUNTING
CONCRETE BLOCK WALL INSTALLATION
BRACKET. MOUNT ON
OPENING
WOOD OR STEEL SIDING
OPENING
INSTALLING UNIT.
RETURN AIR
WALL STRUCTURE
RETURN AIR
SUPPLY AIR
FACTORY SUPPLIED
RAIN FLASHING.
SUPPLY AIR
MIS-548 A
SIDE VIEW
Electric Heat Clearance
Wall Mounting Instructions
See FIGURE 2 – Mounting Instructions
FIGURE 1.5
Manual 2100-620A Page 13 of 107
FIGURE 1.6
I
A
C
K
E + 1.000
B
1.000
SUPPLY DUCT
OVER FRAME
INTERIOR FINISHED WALL
ALL AROUND DUCT
FRAMING MATERIAL
EXTERIOR FINISH WALL
OPENING
FOR ACTUAL DIMENSIONS.
2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
ATTACH TO TOP
1.000" CLEARANCE
1.000" CLEARANCE
PLATE OF WALL
C
SEE UNIT DIMENSIONS, FIGURE 2,
OPENING
RETURN DUCT
2 x 6
ATTACH TO BOTTOM
OVER FRAME
PLATE OF WALL
L
THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL. A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS.
MIS-549 B
ALL AROUND DUCT
SUPPLY DUCT MAY BE LOCATED IN AN ATTIC
OPENING W/ GRILLE
SUPPLY AIR DUCT
RAFTERS
RAFTERS
RETURN AIR OPENING W/ GRILLE
DUCTED SUPPLY
OR BELOW CEILING RAFTERS AS SHOWN
FINISHED CEILING SURFACE
RAIN
FLASHING
RAIN
FLASHING
RETURN AT UNITNO DUCT
RETURN AIR
FINISHED CEILING SURFACE
FREE AIR FLOW
OUTSIDE
WALL
OUTSIDE
WALL
SUPPLY AIR DUCT W/ GRILLE
Wall Mounting Instructions
FIGURE 1.7
Common Wall Mounting Installations
Manual 2100-620A Page 14 of 107
WALL-MOUNT UNIT SUPPLY WIRING
All models covered by this installation instruction require dual power sources: VAC utility power to run the compressor, heat and outdoor fan motor and -48 VDC power to operate the indoor blower and DC free cooling damper.
!
WARNING
Electrical shock hazard.
Have a properly trained individual perform these tasks.
Failure to do so could result in electric shock or death.
These units require a positive ground
-48 VDC copper conductor field wire connection. Refer to the unit wiring diagram
for more information.
Refer to the unit rating plate or Table 1.1 for wire sizing information and maximum fuse or circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. The field wiring used must be sized to carry that amount of current. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.
TABLE 1.1
Electrical Specifications
AC POWER CIRCUIT DC POSITIVE GROUND POWER CIRCUIT
Model
D36A2PA05/D36L2PA05 D36A2PA10/D36L2PA10
D36A2PB06/D36L2PB06 D36A2PB09/D36L2PB09
D42A2PA05/D42L2PA05 D42A2PA10/D42L2PA10
D42A2PB06/D42L2PB06 D42A2PB09/D42L2PB09
D48A2PA05/D48L2PA05 D48A2PA10/D48L2PA10
D48A2PB06/D48L2PB06 D48A2PB09/D48L2PB09
D60A2PA05/D60L2PA05 D60A2PA10/D60L2PA10
D60A2PB06/D60L2PB06 D60A2PB09/D60L2PB09
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest version), Article 310 for power conductor sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to
note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors. Based on 75°C copper wire. All wiring must conform to the National Electric Code and all local codes.
Rated Volts,
Hertz & Phase
208/230-60-1
208/230-60-3
208/230-60-1
208/230-60-3
208/230-60-1
208/230-60-3
208/230-60-1
208/230-60-3
Minimum
Circuit
Ampacity
26 52
18
27.1
26 52
18.6
27.1
29 52
18.8
27.1
34.4 52
27.5
27.5
Maximum
External Fuse or
Ckt. Breaker
45 60
25 30
40 60
30 30
50 60
30 30
60 60
35 35
Field Power/ Ground Wire
Size
8 6
10 10
8 6
10 10
8 8
10 10
6 6
8 8
Minimum
Circuit
Ampacity
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
Maximum
External Fuse or
Ckt. Breaker
20 20
20 20
20 20
20 20
20 20
20 20
20 20
20 20
Field Power/ Ground Wire
Size
12 12
12 12
12 12
12 12
12 12
12 12
12 12
12 12
Manual 2100-620A Page 15 of 107
The electrical data lists fuse and wire sizes (75°C
NOTICE / AVIS
ROUTE ALL HIGH VOLTAGE FIELD
WIRES TO THE RIGHT OF THE WIRE
SHIELD AS SHOWN
ACHEMINER LES FILS HAUTE
TENSION SUR LA DROITE VERS LA
PROTECTION, COMME INDIQUÉ
VAC CIRCUIT BREAKER
/DISJONCTEUR
WIRE SHIELD /
PROTECTION
WHITE 3/16" LETTERING
7961-807
VDC CIRCUIT BREAKER
/DISJONCTEUR
copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay Relay Fuse” or circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.
Route all field wires to the right of the wire shield as shown in the circuit routing label found in Figure 1.8 (and also on the wall-mount units).
Factory
Wiring
FIGURE 1.9
VAC Supply Wiring Landing Points
Field Wiring
.
See Figure 1.9 to reference VAC landing points and Figure 1.11 to reference VDC landing points.
The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left-hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.
FIGURE 1.8
Circuit Routing Label
NOTE: Right-hand access model wiring landing points
are shown here; left-hand access models will mirror this image.
IMPORTANT
230/208V 1 phase and 3 phase equipment use dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. It is very important that the correct voltage tap is used. For 208V operation, reconnect from 240V to 208V tap (see Figure 1.10). The acceptable operating voltage range for the 240 and 208V taps are: 240V Tap (253 – 216) and 208 Tap (220 – 197).
Manual 2100-620A Page 16 of 107
FIGURE 1.10
Adjusting the 230/208 VAC Transformer
It is very important that the correct voltage tap (240V or 208V) is used
1. Verify incoming AC voltage: Multimeter set to VAC
.
Shelter supply breaker in ON position Bard
system breaker in OFF position
230V/208V Single Phase Voltage Range:
197VAC – 253VAC
230V/208V Three Phase Voltage Range:
197VAC – 253VAC
(not shown)
2. If incoming AC voltage is 220VAC or above...
...do not adjust transformer
230VAC
+
3. If incoming AC voltage is below 220VAC...
...shut off AC breaker to unit
and move factory "240V" wire to "208V" terminal
FIGURE 1.11
VDC Supply Wiring Landing Points
.
-
Factory
Wiring
NOTE: Right-hand access model wiring landing points are
shown here; left-hand access models will mirror of this image.
+
.
Field Wiring
+
Manual 2100-620A Page 17 of 107
FIGURE 1.12
Bard Polarity-Voltage Monitor
If the VDC wiring is not terminated correctly on the specific polarity-indicated terminals of the VDC terminal block, the VDC controls and motors will not activate and the wall-mounted unit will not function.
The Bard Polarity-Voltage Monitor continually monitors for correct polarity and voltage. If field wiring is connected improperly, or the voltage is outside of the system parameters, the Polarity-Voltage Monitor will not allow any VDC voltage to enter the system, protecting the internal controls and equipment.
+
When field wiring is correct in voltage and polarity, the green power (PWR) LED and yellow polarity (POL) LED will light, and system will operate normally.
If field wiring is incorrect in polarity, the red FAULT LED will light, and the monitor will not allow VDC voltage into the system.
If field wiring is correct in polarity but outside of the required 40VDC – 56VDC, the green PWR LED will not illuminate and the monitor not allow VDC voltage into the system.
If the Polarity-Voltage Monitor is showing a problem with polarity and/or voltage, see pages 67 and 68 of the Service section of this manual for instructions on checking VDC polarity and verifying incoming VDC voltage.
Manual 2100-620A Page 18 of 107
PRELIMINARY START-UP
RUNNING IN STAND ALONE (ORPHAN) MODE
With both AC and DC breakers turned on, each D-Series wall-mount system has the capability to run without the PLC controller attached—this feature is called Stand Alone or Orphan Mode, and it basically keeps the shelter between 60°F and 78°F by the use of the factory-installed return air sensor in each wall-mount unit.
During installation, this allows deactivation of one of the two existing, older wall-mount units, while keeping the shelter cool with the other unit still operating. Once the first of the two Bard wall-mount units is installed, Orphan Mode can be enabled early in the installation—keeping the climate inside the shelter stable and the installers comfortable while the remainder of the older equipment is removed and the second Bard wall-mount unit and PLC controller is installed.
Additionally, should either or both D-Series wall-mount units lose communication with the PLC controller (such as during maintenance), they will continue to serve the shelter's needs until a repair can be made.
Manual 2100-620A Page 19 of 107
BARD-LINKTM CONTROLLER INSTALLATION
FIGURE 1.13
Typical LC1000/LC1500 Wiring
RJ11 Cable
to Display
48VDC
Power Supply
24VDC
Power
to PLC
Ethernet Cable
PLC Board
Lag Unit
Running Relay
HVAC2 Fail
Alarm Relay
Smoke Alarm Relay
Hydrogen Alarm Relay
Generator Alarm Relay
Web Card
High Temp Alarm Relay
Low Temp Alarm Relay
-48VDC
Power Input
24VDC
Hydrogen
Power
Smoke Power
Manual 2100-620A Page 20 of 107
24VDC
Generator
Alarm Jumper
Remote Temp
Sensor
HVAC1 Fail Alarm Relay
RS485 Communication Cable
Alarm Block
Wiring
!
WARNING
Electrical shock hazard.
Disconnect both VAC and VDC power supplies
before servicing.
Failure to do so could result in electric shock or death.
LC1000-100/LC1500-100 CONTROLLER
The Bard-LinkTM LC1000-100 (or LC1500-100) controller is part of the DC Free Cooling Unit system. It is used to control two wall-mount air conditioners from one controller. The microprocessor control provides an easy-to-read interface with large LCD graphical display. It provides total redundancy for the structure and equal wear on both units. The Bard-LinkTM controller is configured for lead/lag/lead/lag sequence.
Differences Between the LC1000-100 and LC1500-100
There are two separate PLC lead-lag controllers to choose from and each one serves a specific application. The LC1000-100 controller comes pre-packaged with a TEC-EYE hand-held diagnostic tool, one remote temperature sensor and a pair of communication EMI filters. This controller is meant for new shelter construction only, and should never be used in the field as a retrofit replacement. The LC1500-100 controller comes pre-packaged with the TEC-EYE hand-held diagnostic tool, one remote temperature sensor, a pair of communication EMI filters and a smoke detector. (The optional 8301-061 hydrogen detector, if ordered from Bard, is also included with the LC1500-100 controller). The LC1500-100 has an umbilical cord and 66 punch-down block attached. The LC1500 controller is to be used in all retrofit applications, and all existing smoke detectors (and hydrogen detectors, if applicable) are to be removed in lieu of the new detectors.
Conduit is recommended for all wiring. Use separate conduits for communication and supply wiring.
1. Mounting the Controller
TM
Because the Bard-Link temperature sensor as opposed to one located in the controller box, the controller itself can be installed in any indoor location that is suitable, preferably at eye level. Four (4) mounting holes are provided for mounting to the wall and holes for conduit connections are provided in both the base, sides and top of the controller. If installing the LC1500-100, be sure to leave room to mount the 66 punch-down block (attached with an umbilical cord) near the controller.
controller utilizes a remote
Manual 2100-620A Page 21 of 107
2. Installing Remote Indoor Temperature Sensor(s)
A single remote indoor temperature sensor is included with the controller. This sensor must be installed for proper operation. Use the included 35' shielded cable to mount the temperature sensor in a location least likely to be affected by open doors, rack-mounted fans, radiant heat sources, etc. Locating the sensor between both return grilles is often the best location, but every installation is unique. Location height should be approximately 48" above the floor. The sensor should be installed on a 4" by 4" junction box to allow for control wire conduit (see Figure 1.14).
For proper operation, the remote indoor temperature sensors must be configured properly with the controller. If only the single remote indoor temperature sensor supplied with the controller is installed, the configuration setting is
FIGURE 1.14
Remote Indoor Temperature Sensor Installation
1. Connect wires from provided 35' shielded cable to terminals #11 and #12. The connection is not polarity-sensitive.
2. Connect the other end of the 35' shielded cable to either of the sensor terminals. These connections are also not polarity sensitive.
Sensor is best mounted on a junction box, and it is
recommended that the cable be in conduit.
Manual 2100-620A Page 22 of 107
"0". This is the default setting. For information on checking the remote indoor temperature sensor configuration, see Configuring Additional Remote Indoor Temperature Sensors on page 51.
For unique situations involving temperature flux within the shelter, up to two (2) additional sensors may be purchased and installed to provide temperature-averaging or highest-temperature protection (see Figure 1.15). Please see Configuring Additional Remote Indoor Temperature Sensors on page 51 in the Service section of this manual to set up the additional remotes.
FIGURE 1.15
Additional Remote Temperature Sensor Installation
Up to two (2) additional sensors may be purchased and installed for averaging or highest-temp mode. Use terminals #13, #14, #15 and #16. These connections are not polarity-sensitive.
Remote Sensor
Optional Additional Remote Sensor
Optional Additional Remote Sensor
Manual 2100-620A Page 23 of 107
3. Smoke, Hydrogen and Generator Alarms
The LC1500 PLC controller is shipped with a new smoke detector (and optional hydrogen detector if ordered from Bard) for use in existing shelters. The existing smoke detector (and hydrogen detector, if applicable) should be removed and disposed of properly. In cases where there are no existing detectors, follow the installation instructions provided with each detector for location and mounting practices. Both controllers have the capacity to provide power to a 24VDC smoke detector and a 24VDC hydrogen detector through fused power supply terminals. For proper power and alarm wiring, review the provided wiring diagrams (see Figures 1.16 and 1.17).
Please note that the provided smoke detector (and hydrogen detector, if applicable) has external testing buttons to artificially (and temporarily) create an alarm sequence. Additionally, should the desired NC contact closure need to be changed to the alternative contact closure, please refer to the Service section of this manual to reprogram the PLC control.
The generator run alarm (if desired) will be signaled through an existing (or field provided) relay attached to the site generator. The signal from the controller will route through a set of normally closed contacts. Should the generator start, the contacts will open, triggering the alarm and initiating “Generator Run Mode” (both compressors cannot operate concurrently). Since some sites do not have a generator present, there is a factory-installed jumper across terminals #9 and #10. If there is no generator, no action is necessary. If generator run alarm is desired, please remove the factory-installed jumper and wire per Figure 1.18.
FIGURE 1.16
Power and Signal Connections for Smoke Detector
-24VDC
+24VDC
See Terminal Block Index on page 33
-24VDC Return Signal
1. Using minimum 18 gauge, non-shielded wire, supply the new smoke detector with 24VDC from terminals 6 and 7 of the PLC controller.
2. Route a jumper wire from the -24VDC terminal on the new smoke detector to the common terminal of the on­board relay.
3. From the normally closed contact of the relay, return the
-24VDC signal to terminal #8 of the PLC controller.
Manual 2100-620A Page 24 of 107
NC
COM
FIGURE 1.17
Power and Signal Connections for Bard-Supplied Hydrogen Detector (If Applicable)
See Terminal Block Index on page 33
-24VDC Return
Signal
-24VDC
+24VDC
1. Using minimum 18 gauge, non-shielded wire, supply the new hydrogen detector with 24VDC from terminals 3 and 4 of the PLC controller.
2. Route a jumper wire from the -24VDC terminal on the new hydrogen detector to the common terminal of the on-board 2% relay.
-24VDC
+24VDC
3. From the normally closed contact of the relay, return the
-24VDC signal to terminal #5 of the PLC controller.
FIGURE 1.18
LC1000-100 and LC1500-100 Series Generator Run
-24VDC Return Signal
-24VDC
1. If there is a generator on site, remove the factory­installed jumper on Terminals #9 and #10. Using minimum 18 gauge, non-shielded wire, supply the common terminal on the existing generator relay with
-24VDC from terminal #9 on the PLC controller.
2. From the normally closed contact of the relay, return the -24VDC signal to terminal #10 of the PLC controller.
Manual 2100-620A Page 25 of 107
4. Connecting External Alarm Points
Both the LC1000 and LC1500 PLC controls have the capability to provide NC contacts for the following eight (8) alarms:
• Smoke
• Hydrogen
• Generator
• Lag Unit Run
• High Temp*
• Low Temp*
• HVAC 1 Fail
• HVAC 2 Fail
Before connecting the external alarm wiring, identify the model of the controller (see label inside of controller door). The LC1000 provides contacts for alarms at the internal terminal block (see Figure 1.19).
The LC1500 PLC control has a pre-installed, pre-wired 66 punch-down block to allow easy connection to these contacts outside of the controller box (see Figure 1.20).
FIGURE 1.19
LC1000-100 External Alarm Wiring
On the terminal strip of the LC1000 controller, there are eight (8) separate series of normally closed dry contacts for the following alarm scenarios…
• Smoke
• Hydrogen
• Generator
• Lag Unit Run
• High Temp*
• Low Temp*
• HVAC 1 Fail
• HVAC 2 Fail
* There is no longer any need for the
electro-mechanical coiled-bulb type thermostats—like the Johnson Penn A19-Series—for High/Low Temperature Alarms. Do not install in new sites, and remove them in retrofit applications.
Lag Unit Run Alarm Common
Lag Unit Run Alarm Contact
Generator Alarm Common
Generator Alarm Contact
Hydrogen Alarm Common
Hydrogen Alarm Contact
Smoke Alarm Common
Smoke Alarm Contact
High Temp Alarm Contact
High Temp Alarm Common
Low Temp Alarm Contact
Low Temp Alarm Common
HVAC 1 Fail Alarm Contact
HVAC 1 Fail Alarm Common
HVAC 2 Fail Alarm Contact
HVAC 2 Fail Alarm Common
Manual 2100-620A Page 26 of 107
FIGURE 1.20
LC1500-100 External Alarm Wiring
Before connecting the external alarm wiring, identify the model of the controller (see label on inside of controller door. The connections described below are for the LC1500-100 controller only.
The LC1500-100 has the same eight (8) separate series of normally closed dry contacts as the LC1000-100, but has a prewired 66 punch-down block to make external connections easier.
• Smoke
• Hydrogen
• Generator
• Lag Unit Run
• High Temp*
• Low Temp*
• HVAC 1 Fail
• HVAC 2 Fail
Field wiring for alarms
48” umbilical cord allows for mounting the 66 punch-down block to either side, top or bottom of PLC controller cox.
Bridge clips have been inserted for convenience.
* There is no longer any need for the electro-mechanical coiled-bulb type thermostats—like the Johnson Penn A19-
Series—for High/Low Temperature Alarms. Do not install in new sites, and remove them in retrofit applications.
Manual 2100-620A Page 27 of 107
5. Communication Wiring
Connect the communication wiring from the two wall-mount units to the controller in the manner shown in Figure
1.21. The communication wire should be 2-wire, 18 gauge shielded cable with drain. Any color can be used. Be sure to match "+" and "-" symbols on controller terminal blocks to prewired unit control terminal block (see Figures
1.23 and 1.24 on pages 30 and 31). Attach communication wire filters as shown below in Figure 1.22. Use separate
conduits for communication and supply wiring.
FIGURE 1.21
Communication Wiring
D-Series
Wall-Mount Unit
D-Series
Wall-Mount Unit
Bard-LinkTM
Controller
Manual 2100-620A Page 28 of 107
FIGURE 1.22
- +
G
Communication Wiring: Termination at the Controller
1. Using the field-provided shielded cable, make a small service loop after entering the controller and attach the provided EMI filter at the intersection of the loop.
2. Connect one wire to terminal #33 (negative), the other wire to terminal #34 (positive) and the drain wire to ground terminal #35.
To Wall-Mount Unit 1 Control Board RS485
Manual 2100-620A Page 29 of 107
RS485
R+T+ / R-T-
FIGURE 1.23
RS485
R+T+ / R-T-
Communication Wiring: Termination at the First Wall-Mount Unit
RS485
R+T+ / R-T-
Wall-Mount Unit 1
Control Board
1. From the controller, extend the shielded cable through a separate conduit and route to the provided terminal block next to the wall-mount control board.
Note that the terminal block label is clearly marked “+” and “-”. These
connections are polarity-sensitive. Two-wire communication from control board is prewired to terminal block. Make sure to match "+" and "-" symbols on controller terminal blocks.
From LC1000-100 or LC1500-100 Controller
2. Connect the wires matching the terminal designations (+/-) of the controller terminals. Leave the drain wire loose.
Wall-Mount Unit 1
Control Board
From LC1000-100 or LC1500-100 Controller
Wall-Mount Unit 1
Control Board
Manual 2100-620A Page 30 of 107
3. Connect another cable in a similar fashion (“daisy chain”) to route in conduit to the second wall-mount unit. Connect both drain wires with wire nut.
From LC1000-100 or LC1500-100 Controller
To Wall-Mount Unit 2 Control Board RS485
Loading...
+ 77 hidden pages