BAPI ZPS-ACC07, ZPS-ACC09, ZPS-ACC08, ZPS-ACC05, ZPS-ACC06 Installation And Operation Instructions Manual

...
Static Pressure Accessories
Installation and Operation Instructions
13044_Ins_ZPS_ACC
Rev. 05/22/2017
The duct static pressure probe assembly consists of a static pressure probe, a six inch piece of silicon rubber tubing, a twelve inch piece of silicon rubber tubing, two self drilling sheet metal screws and a
pressure spike reducer.
Fig. 1: BAPI ZPS-ACC07
Mounting the Duct Static Pressure Probe, Hoses and Damper
Positioning the duct static pressure probe assembly to get the best results requires a little planning. Ideally the probe should be located 1/2 the distance from the fan to the end of the longest duct run. The probe should be a minimum of ve duct diameters from any vanes, straighteners, reducers or bends. The probe may be placed within 1/2 duct diameter of a lter as long as the lter is ve duct diameters from any other restriction.
Drill a 1/4 inch hole in the duct for the probe. Insert the 6 inch long section of the probe into the duct work and rotate so the air ow arrow is pointing in the same direction as the air ow in the duct. Using the two self drilling screws provided secure the probe to the duct. For round duct pick the two holes in the probe mounting ange that touch the duct surface. Position the probe so that it is at a right angle to the duct surface or at right angles to a line tangent to the duct surface for round duct. Being off by +/- 5 degrees angle is acceptable.
Long runs of tubing will damp out quick pressure uctuations. Where the ZPS unit must be located close to the static pressure tube BAPI provides a pressure spike reducer. The pressure spike reducer provides a slight restriction in the tubing. The volume of tubing after the pressure spike reducer determines the time constant, the longer the tubing the greater the pressure spike reduction.
Place the 6” tube towards the pressure source. Connect the 12” tube to your ZPS pressure transmitter. If you do not get the dampening that you desire, increase the tubing length from the blue plastic snubber to the pressure sensor.
Condensation running down the interior of the tubing will damage the sensor. Forming a drip loop in the tubing just before it enters the ZPS transmitter is good practice, see Fig 4. The distance from the bottom of the loop to the ZPS’s pressure port should be one to two inches (2.5 to 5 cm) greater than the highest air pressure, including error conditions, in the duct system.
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
Fig. 2:
ZPS-ACC08 Static
Tube
Fig. 3:
ZPS-ACC09
Hoses with
Pressure
Damper
1 of 3
Static Pressure Accessories
Installation and Operation Instructions
13044_Ins_ZPS_ACC
Typical Applications - Duct Static Pressure Probe
Fig. 4:
Measuring duct static pressure with pressure transmitter and static pressure probe
Fig. 5:
Measuring duct air lter pressure drop with pressure transmitter and two static pressure probes.
Mounting Wall & Ceiling Pressure Pickup Ports
Rev. 05/22/2017
Fig. 6: Ceiling Mount Cover
(ZPS-ACC05)
Mount the static pressure pickup port in an area that is representative of the zone near the center of the zone. Do not mount in a closet or other enclosed space, or in areas that are prone to drafts.
It is best to mount the wall pickup port using an electrical box. A simple hole in the wallboard may be used, but be sure that the foam gasket on the back of the pickup seals tightly against the wall. Attach tubing to the barbed tting on the back of the pickup port and run the tubing to the pressure sensor, forming a drip loop in the tubing just before connecting to the pressure sensor.
The ceiling pickups are sized to t through a standard 3/4-inch thick acoustic ceiling tile. Cut a 5/8 inch hole in the tile. Place the static pressure sensor on top of the tile with the lter into the hole. The lter should stick out slightly below the tile’s room surface. Attach tubing to the barbed tting on the back of pickup port and run the tubing to the pressure sensor, forming a drip loop in the tubing just before connecting the tubing to the pressure sensor.
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
Fig. 7: Ceiling Mount Cover &
J-Box (ZPS-ACC06)
Fig. 9: Wall Plate
(ZPS-ACC01)
Fig. 8: Delta Style Enclosure
(ZPS-ACC03)
Fig. 10: BAPI-Stat
“Quantum” (ZPS-ACC04)
2 of 3
Loading...
+ 1 hidden pages