
YI/10K-3-RSOC
Sensor Termination and Troubleshooting
9511_ins_york_rsoc
Termination
BAPI recommends using twisted pair of at least 22 AWG and crimp type connectors for all wire
connections. Also, it is recommended that wiring NOT be run in the same conduit as line voltage
wiring or with wiring used to supply highly inductive loads such as motors, generators, and coils.
Printed October 29, 2003
Jumper Settings
Factory Settings:
Override in parallel
with sensor: J4=
Common Ground
J2-Pins 2,4,6: J4=
Note: For other types of devices, connect to the
device based on the terminals Function
Setpoint Direct
Acting (DA): J5=

9511_ins_york_rsoc
Troubleshooting
YI/10K-3-RSOC
Sensor Termination and Troubleshooting
Printed October 29, 2003
Problems:
Temperature sensor in front end software is reading
high
Temperature sensor in front end software is reading
low
Setpoint is not working correctly
Possible Solutions:
- Is the input set up correctly in the front end software
- Is thermistor physically shorted
- Check wiring for proper termination
- Is the Sensor output correct from (J2) Pin 1 to Pin 2
Refer to table below for proper reading
- Make sure thermistor is installed in sensor
- Check wiring for proper termination
- Is the Sensor output correct from (J2) Pin 1 to Pin 2
Refer to table below for proper reading
- Is the Setpoint output correct from (J2)
Pin 5 to Pin 6.
- Are J4 and J5 set up correctly
- Check wiring for proper termination