BAPI Water Leak Detector Catalog Page

Water Leak Detector
BA/LDT Accessories
Termination and Troubleshooting
26268_ins_LDT
Overview & Identication
Fig. 1:
Water Leak Detector with Internal Sensor Probe
rev. 11/16/18
Fig. 3:
Water Leak Detector with Remote Spot Sensor (right) and Water Rope Sensor (below)
Fig. 2:
Water Leak Detector with Built In Sensor and a 5 Amp Relay in a System Diagram (Side View)
Fig. 4:
Water Leak Detector with Remote Spot Sensor or optional Water Rope Sensor (not shown) and a 5 Amp Relay in a System Diagram (Side View)
Specications subject to change without notice.
1 of 6
BA/LDT Accessories
26268_ins_LDT
Mounting
Place the transmitter in a location where a water leak is likely to cause damage such as a cooling coil pan, a hot water tank pan, under a sink, under an elevated oor, or in a drop ceiling under pipes. The transmitter can be independently mounted in a visible location by using a remote water sensor and waterproof cable as shown in Fig. 4. Terminate the transmitter as shown in the termination section.
1. Set the transmitter where water is most likely to be a problem or in the collection pan under the water coil or heater (Fig. 5).
• Alternatively a water sensor or remote water sensor
can be attached to the pan edge with two set screws (Fig. 6). Do not over tighten or puncture the pan.
• Alternatively a remote water sensor can be attached
to the pan or oor with mounting tape (Fig. 7). Clean surface thoroughly before setting the sensor in place and push sensor down rmly. Mount the detector enclosure in a visible location within cable length of the remote water sensor.
• Alternatively a remote water sensor can be attached
to the oor with screws (Fig. 8). Mount the detector enclosure in a more visible location within cable length of the remote water sensor.
• Alternatively the rope water sensor can be laid on the
oor or under pipes as shown in Figs. 10, 11, 12 & 13. Cable clamps can be used to secure the sensor to the oor.
2. Adjust the depth screw on the sensor probe in the middle of the open enclosure to the alarm depth (Fig. 5). If using a remote water sensor, adjust the depth screw as shown in Fig. 9. The rope sensor detects water 1/8” off the oor and has no adjustment.
3. Run the cable to the transmitter location leaving enough slack to terminate and allow for some repositioning as needed. Use a strain relief on the entering cable so the wires do not tug on the terminals directly.
4. Terminate and congure in accordance with the termination section.
Water Leak Detector
Termination and Troubleshooting
rev. 11/16/18
Mounting
Nut
Sensor Probe
Screw
Fig. 5: Leak Detector with Sensor in a BAPI-Box
Detection depth
adjust screw
Pan edge
mounting
screws
Fig. 6: Water Sensor Pan Rim Mounting
Firmly push down
on clean surface
Fig. 7: Remote Water Sensor Tape Mount
Fig. 8: Remote
Water Sensor Floor Mount
Installer-provided mounting screws
Fig. 9: Remote Water Sensor
Up
Depth Adjusting
Detection depth adjust screw
Reference probe
Detection depth
adjust from 1/16”
to 1/2” depth
Specications subject to change without notice.
Down
1. Loosen wing nut.
2. Set the required depth of the sensor probe screw using a #2 Phillips screwdriver.
3. Hold the sensor probe screw stationary with the screwdriver.
4. Turn the wing nut down the probe screw until it engages the plastic.
5. Tighten the wing nut 1/4 turn into the plastic.
2 of 6
Loading...
+ 4 hidden pages