D6
VOC Duct and Rough Service Sensor
Air Quality Sensors
Rev. 01/19/16
Features & Options
Corresponds to ASHRAE’s CO2-Based DCV Algorithm
Quick Response Sensor with Aspiration Tube or Ventilated BAPI-Box
0 to 5 VDC or 0 to 10 VDC Output
Humans respirate Volatile Organic Compounds (VOCs) as well as CO
The BAPI sensor measures these VOCs and indicates when a space is
occupied just as well as a CO
sensor.
2
The advantage of the VOC sensor is that it measures air contaminants
from other sources besides respiration, such as building materials,
cleaners, perfumes and furniture and carpet off-gassing. Using this
sensor for Demand Controlled Ventilation then is a way of achieving true
indoor air quality, rather than just CO
dilution.
2
A further benefi t is that it requires no additional work on your part. That’s
because the sensor converts the VOC reading to a CO
This lets you use ASHRAE’s CO
(More information on the CO
-based VRP schedule to ventilate.
2
equivalent output is available on our
2
equivalent level.
2
website at www.bapihvac.com, or in the Application Notes at the end of
this section of the catalog.)
BAPI’s VOC Duct Sensor samples duct air using an aspiration tube. Moving air from the duct enters
the tube, is forced into the BAPI-Box enclosure and exits through the other half of the tube. As long
as there is air movement in the duct, air is continuously exchanged.
The Rough Service unit features a ventilated BAPI-Box and is ideal for rough service areas such as
outdoor air plenums, equipment rooms, attics, green houses and warehouses.
.
2
VOC Duct (top) and
Rough Service Sensors
Specifi cations
Power:
12 to 24 VDC, 200 mA Peak
18 to 24 VAC, 12 VA Peak
Analog Outputs:
0 to 5VDC or 0 to 10VDC, >10KΩ impedance
VOC Contaminants: 0 to 2,000 PPM CO2 Equivalent
Sensing Element:
VOCs: Micro-machined Metal Oxide
VOC Detection Range: 0 to 100%
Response Time: Less Than 60 Seconds
Start-Up Time: 15 minutes
Operating Environment:
32 to 122°F (0 to 50°C)
0 to 95%RH non-condensing
Dimension: 4.91”H x 3.21”W x 1.20”D
(124.6 x 81.5 x 30.5 mm)
Enclosure Rating:
Unventilated BAPI-Box: NEMA 4, IP66
Enclosure Material:
Polycarbonate, UL94 V-O
Certifi cations: RoHS
Warranty: Two years from manufacture date
VOC
Rough
Service
Sensor
VOC Duct Sensor
Ordering Information VOC Duct Sensor in the BAPI-Box Enclosure
VOC Output Must Select One
VOC05 VOCs Transmitted as 0 to 2,000 ppm CO2 Equivalent, 0 to 5 VDC output
VOC10 VOCs Transmitted as 0 to 2,000 ppm CO2 Equivalent, 0 to 10 VDC output
Enclosure Required Selection
Example Part Number: BA/VOC05-D-BB
BAPI-Box - IP66 rated, UV-resistant polycarbonate, aspiration probe
VOC Duct and Rough Service Sensor
D7
Rev. 01/19/16
BAPI-Box - UV-resistant polycarbonate, ventilated
Your Part Number:
Call BAPI if you have questions about the above ordering grid.
Air Quality Sensors