A22
T1K Transmitter Room Unit
Temperature Sensors
Features & Options
Delta Style or BAPI-Stat 4 Enclosures
4 to 20 mA Temperature Output
Optional Display on the BAPI-Stat 4
Optional Override and Setpoint on the BAPI-Stat 4
Optional Communications Jack
Two Year Warranty
The T1K Transmitter Room Unit comes in the Delta style
and BAPI-Stat 4 style enclosures. They measure the room
temperature and output a 4 to 20mA signal per the custom
range selected at the time of order.
The BAPI-Stat 4 Style unit offers a full range of options
including setpoint, override, display, communication jack,
fi eld offset, fi eld ranging, ºF or ºC and a new stylish look.
For detailed specifi cations on the T1K
Transmitter, turn to the Sensors section
Rev. 09/01/16
BAPI-Stat 4
Units with white
and gray logo
plate.
Delta Style Unit
(Not available with
Display, Setpoint,
Override or Comm.
Jack.)
Specifi cations
Power:
12 to 30VDC (28 VDC max. recommended)
Transmitter Output:
4 to 20mA, 600Ω to 850Ω@24VDC
Power Consumption:
40 mA maximum
Sensing Element:
1KΩ Platinum RTD
Environmental Operation Range:
Temperature, Delta: 32 to 122ºF (0 to 50ºC)
Temperature, BS4: 15ºF to 130ºF, (-9º to 54ºC)
Humidity: 0 to 95%, non-condensing
Mounting: Standard 2” by 4” J-box or drywall mount
(mounting screws provided)
Wiring: 1 to 3 pair of 16 to 22AWG, plus comm. jack
Options:
Comm. Jack ........ Optional 3.5mm (1/8”) Phono
Jack or RJ11 Phone Jack
Setpoint............... BS2 & BS4, Resistive or 4 to 20mA
Display ................ BS4, 3.5 digit, 2”W x 1.1”H
External Sensor .. BS2 & BS4, Remote Mounted RTD
Material & Rating:
BAPI-Stat 4 ........ ABS Plastic, UL94 V-0
Delta Style ......... ABS Plastic, UL94 HB
Agency: RoHS
Delta Style
Enclosure
BAPI-Stat 4
Enclosure
T1K Transmitter Room Unit
Ordering Information T1K Temperature Transmitter Room Unit
Temperature Transmitter Type Must select one - Must include a Range
T1K[range]
1K Platinum RTD, 1,000 Ω @ 0 °C with 4 to 20 mA Output
$100 $_______
T1KM[range]
1K Platinum RTD, 1,000 Ω @ 0 °C with MATCHED* 4 to 20 mA Output
$280 $_______
Ranges for Temperature Transmitters
Custom temperature transmitter ranges are available. Common ranges are listed below
Enclosure Style Must select one
-R Delta Style Room Enclosure (Not available with Display, Setpoint, Override or Comm. Jack in the Delta Style Enclosure)
-B4S BAPI-Stat 4 Style Room Enclosure $50 $_______
LCD Display Must select one
D LCD Display (Only available for the BAPI-Stat 4 Style Enclosure) $35 $_______
Setpoint Display Options Must select one - Setpoint display only availablefor BAPI-Stat 4 units
- #
SETPOINT DISPLAY OPTIONS See page I3 for Additional Setpoint Display Ranges.
Designator
Desired Range
Designator
-2 to +2
P
65 to 80 °F or 18 to 27 °C
F
-3 to +3
A
45 to 96 °F or 7 to 36 °C
G
-5 to +5
B
70 to 74 °F or 21 to 23 °C
L
50 to 90 °F or 10 to 32 °C
C
60 to 85 °F or 15 to 30 °C
AA
55 to 85 °F or 13 to 30 °C
D
41 to 85 °F or 5 to 30 °C
CC
60 to 80 °F or 15 to 27 °C
E
No Setpoint Display
X
SETPOINT OUTPUT VALUE RANGE See page I2 for Additional Setpoint Output Ranges
$6 for $_______
16***
$60 for #16 $_______
-J Override as a Separate Input
$5 for any
$_______
-N Override in Parallel (//) with the Sensor (Only available for the BAPI-Stat 4 Style Units)
Override
-P Override in Parallel (//) with Setpoint
-C11L RJ11 (4 pin) Style Jack with Leads Attached $20 $_______
-C11LT RJ11 (4 pin) Style Jack with Leads and a Terminal Block Attached $20 $_______
-C35L 3.5 mm (3 pin) Phono Style Jack with Leads Attached $10 $_______
-C35LT 3.5 mm (3 pin) Phono Style Jack with Leads and a Terminal Block Attached $10 $_______
-DF Differential Inputs^ - Required for 4-20 mA setpoint
Optional External Sensor for BAPI-Stat 4
-ES External RTD Sensor (order separately)
BAPI-Stat 4 Logo Plate Color
-WMW Warm White Logo Plate Color
-GRY Gray Logo Plate Color
A23
Rev. 09/01/16
Temperature Sensors
Note: Setpoint display range cannot be larger than the Temperature Transmitter range selected above.
Optional Setpoint If setpoint is selected, you must select a Range and Legend)
Override Configuration Must select one - Override not available for Delta Style Units
Optional Comm. Jack Skip if not required - Not available for Delta Style units
Connection Configuration Must select one
EXAMPLE
BA/ T1K[65 TO 80F] -B4S D -P 25L6 -J -C35L -CG -GRY
Example Part Number: BA/T1K[65 TO 80F]-B4SD-P25L6-J-C35L-CG-GRY
Your Part Number:
Call BAPI if you have questions about the above ordering/pricing grid or the configuration of the product you are ordering.
*Matched transmitters use Class A & are matched at 25%, 50% & 75% of calibrated scale
**There is a common between the setpoint and override if the setpoint is resistive.
***If 4-20 mA setpoint output range (#16) is selected, then the bottom of a vertical slider equals a setpoint output of 4 mA and the top on a vertical slider equals a 20 mA
setpoint output. The 4-20 mA setpoint can only be used with the –B4S enclosure sensor and requires a –DF (differential input) designation.
^Setpoint and Override terminals do not share a common connection