BAPI Submersible Duct Temperature Sensors Catalog Page

Submersible Duct Temperature Sensors (BA/# -SD)
20905_ins_SubmersibleDuct_Passive_Passive
Overview and Identication
The Submersible Duct Unit is for duct mounting and temperature measurement of air across cooling coils or wet locations. The Stainless Steel probe tip is very small (1/8”) to t between coil ns and made in different lengths for a custom duct t.
The unit is available in multiple thermistor or RTD types as shown in the specications. Enclosure mounting styles come in plastic or metal for both NEMA 1 and NEMA 4 applications and are all plenum rated.
Installation & Operations
rev. 10/12/15
Fig 1: Duct Unit with No Box (NB)
Fig 2: Duct Unit with J-Box (Standard)
Fig 4: BAPI-Box (BB) Duct Unit
Fig 3: Weatherproof (WP) Duct Unit
Fig 5: BAPI-Box 2 (BB2) Duct
Specications subject to change without notice.
Fig 7: BAPI-Box 4 Enclosure (BB4) Duct Unit
(A Pierceable Knockout Plug is available from BAPI
for the open port in the BB4. Part #BA/PKP-100)
1 of 4
20905_ins_SubmersibleDuct_Passive_Passive
Mounting
Submersible Duct Temperature Sensors (BA/# -SD)
Installation & Operations
rev. 10/12/15
Fig 8: Cooling Coil Discharge Air
Temperature Application
Fig 9: Junction Box or No Box
(NB) Mounting Holes
Fig 12: Weather Tight (EU or
EUO) Enclosure Mounting Holes
Fig 10: BAPI-Box 2 (BB2)
Enclosure Mounting Holes
Fig 13: Weatherproof (WP)
Enclosure Mounting Holes
Fig 11: BAPI-Box (BB) Enclosure Mounting
Holes, Rotate 90° for Horizontal Mounting
Fig 14: BAPI-Box 4 (BB4) Enclosure
Mounting Holes
Specications subject to change without notice.
2 of 4
Submersible Duct Temperature Sensors (BA/# -SD)
Installation & Operations
20905_ins_SubmersibleDuct_Passive_Passive
Wiring & Termination
BAPI recommends using twisted pair of at least 22AWG and sealant lled connectors for all wire connections. Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as high or low voltage AC power wiring.
BAPI’s tests show that inaccurate signal levels are possible when AC power wiring is present in the same conduit as the sensor wires.
To Controller Analog Input (AI) (No Polarity)
Thermistor
or RTD Sensor
To Controller Analog Input (AI) (No Polarity)
rev. 10/12/15
Fig. 15: 2 Wire Lead Wire Termination for Thermistor or RTD
Fig. 17: Terminal Strip (-TS) Option for 2 Wire Sensors
Termination
Fig. 16: 3 Wire Lead Wire Termination for RTD
Fig. 18: Terminal Strip (-TS) Option for 3 Wire
Sensors Termination
Fig. 19: Test & Balance (-TB) Option for 2 Wire Sensors
Termination
Specications subject to change without notice.
Fig. 20: Test & Balance (-TB) Option for 3 Wire
Sensors Termination
3 of 4
20905_ins_SubmersibleDuct_Passive_Passive
Diagnostics
Submersible Duct Temperature Sensors (BA/# -SD)
Installation & Operations
rev. 10/12/15
Problems:
Controller reports higher or lower than actual temperature
Possible Solutions:
- Conrm the input is set up correctly in the front end software
- Check wiring for proper termination & continuity. (shorted or open)
- Disconnect wires and measure sensor resistance and verify the “Sensor” output is correct.
Specications
Sensor: Passive Thermistor, 2 wire RTD, 2 or 3 wire
Thermistor Thermal resistor (NTC) Temp. Output Resistance Per Order1 Accuracy (std) ±0.36ºF, (±0.2ºC) Accuracy
(Hi) ±0.18ºF, (±0.1ºC), [XP] option Stability 0.036ºF/Year, (<0.02ºC/Year) Heat dissipation 2.7 mW/ºC Temp. Drift <0.02ºC per year Probe range -40º to 221ºF (-40º to 105ºC)
RTD Resistance Temp Device (PTC) Platinum (Pt) 100Ω and 1KΩ @0ºC, 385 curve Platinum (Pt) 1KΩ @0ºC, 375 curve
Pt Accuracy (Std) 0.12% @Ref, or ±0.55ºF, (±0.3ºC) Pt Accuracy (Hi) 0.06% @Ref, or ±0.277ºF, (±0.15ºC), [A]option Pt Stability ±0.25ºF, (±0.14ºC) Pt Self Heating 0.4 ºC/mW @0ºC Pt Probe range -40º to 221ºF, (-40 to 105ºC) Nickel (Ni) 1000Ω @70ºF, JCI curve Ni Probe range -40º to 221ºF (-40 to 105ºC)
Sensitivity Approximate @ 32ºF (0ºC) Thermistor
Non-linier – Go to bapihvac.com click “Sensor Specs” RTD (Pt) 3.85Ω/ºC for 1KΩ RTD
0.385Ω/ºC for 100Ω RTD Nickel (Ni) 2.95Ω/ºF for the JCI RTD
Lead wire 22awg stranded
Insulation Etched Teon, Plenum rated Probe Stainless Steel,
Sheath 0.25” OD, probe 0.125
Probe Length 12” to 48”’ per order
Mounting Extension tabs (ears), 3/16” holes
Enclosure Types
J-Box -JB, w/eight ½” knockouts No Box -NB, intended for open wiring Weatherproof -WP, w/ two ½” FNPT entries, (Bell box) BAPI-Box -BB, w/ four ½” NPSM & one ½” drill-out BAPI-Box 2 -BB2, w/ three ½” NPSM & three ½” drill-outs
BAPI-Box 4: -BB4, w three ½” drill-outs & one ½” open port
Weather Tight -EU, -EUO, w/two ½” knockouts
Enclosure Ratings
J-Box -JB, NEMA 1 No Box -NB, No rating Weatherproof -WP, NEMA 3R, IP14 BAPI-Box -BB, NEMA 4X, IP66 BAPI-Box 2 -BB2, NEMA 4X, IP66
BAPI-Box 4 -BB4, IP10 (IP44 with Knockout Plug in the open port)
Weather Tight -EU, NEMA 4X, IP66 Weather Tight -EUO, NEMA 4X, IP66, UV rated
Enclosure Materials
2x4 J-Box -JB, Galvanized steel, UL94H-B No Box -NB, Nylon 66, UL94H-B Weatherproof -WP, Cast Aluminum, UV rated BAPI-Box -BB, Polycarbonate, UL94V-0, UV rated BAPI-Box 2 -BB2, Polycarbonate, UL94V-0, UV rated BAPI-Box 4: -BB4, Polycarbonate & Nylon, UL94V-0 Weather Tight -EU, ABS Plastic, UL94V-0 Weather Tight -EUO, ABS Plastic, UL94V-0, UV rated
Ambient (Encl.) 0 to 100% RH, Non-condensing All BAPI-Boxes -BB, BB2, BB4, -40 to 185ºF, (-40 to 85ºC) Weather Tight -EUO, EU, -40 to 185ºF, (-40 to 85ºC) J-Box & No Box -JB, NB, -40 to 212ºF, (-40 to 100ºC) Weatherproof -WP, -40ºF to 212ºF, (-40º to 100ºC)
Agency RoHS, *CE
PT= DIN43760, IEC Pub 751-1983,
JIS C1604-1989
*Passive Thermistors 20K and smaller are CE compliant
Specications subject to change without notice.