BAPI Stainless Wallplate Catalog Page

Page 1
16068_ins_sp_rotary
Product Identication
Fig. 1: Wall Plate with Rotary
Mounting
Stainless Wallplate with Rotary Setpoint
Fig. 2: Wall Plate with Rotary
Setpoint and Pushbutton Override
Installation & Operating Instructions
rev. 08/01/18
Fig. 3: Doublegang Wall Plate with
Rotary Setpoint, Pushbutton Override and
Pressure Pickup Port
Ensure the plate does not touch the wall when it is mounted as this will lead to slower response rates when the environment changes.
Mounting hardware is provided for both junction box and drywall installation.
Junction Box
1. Pull the wire through the wall and out of the junction box, leaving about 6” free.
2. Terminate the unit according to the guidelines in Termination on page 1.
3. Secure the plate to the box using the #6-32 x 1/2” mounting screws provided or with security screws which are sold separately. (Call BAPI or visit the Accessories section of our website for security screw ordering.)
Verify visible
air gap
between plate
and wall.
Fig 4:
Side View of
Mounted Plate
Fig 5:
J-Box Mounting
4. Tighten screws until the foam gasket on the back plate is compressed about 50%. Ensure the plate doesn’t touch the wall (Fig 4).
Drywall Mounting
1. Place the plate against the wall where you want to mount the sensor and mark out the two mounting holes.
2. Drill two 3/16” holes in the center of each marked mounting hole. Insert a drywall anchor into each hole.
3. Cut hole between the mounting holes that clears the apparatus mounted on plate. Pull the wire through the wall hole cut in step 2, leaving about 6” free.
4. Terminate the unit according to the guidelines in Termination on page 1.
5. Secure the plate to the drywall anchors using the #6 x 1” mounting screws provided. Tighten screws until the foam gasket on the back plate is compressed about 50%. Ensure the plate doesn’t touch the wall.
Note: In any wall-mount application, the wall temperature and the temperature of the air within the wall cavity can cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and premature failure of the sensor. To prevent these conditions, seal the conduit leading to the junction box or ll the box with insulation.
Specications subject to change without notice.
1 of 4
Page 2
Stainless Wallplate with Rotary Setpoint
Installation & Operating Instructions
16068_ins_sp_rotary
J-Loop Termination Technique
Incorporating a “J-Loop” (also known as a drip loop) into all terminations adds an additional layer of protection against moisture and oxidation by directing moisture away from the connection. The idea is to place the wire junction as high as possible and form a “J” with the leadwires. The bottom of this “J” should be below the junction point. Any moisture that collects on the leadwires is pulled downward by gravity to the bottom of this loop and away from the junction.
J-Loop Technique J-Loop with Crimp-On SFC J-Loop with Twist-On SFC
Termination
rev. 08/01/18
Fig. 5
Wall Plate with Rotary
Static
Comm. Jack
Wall Plate with Rotary Setpoint and Override
Pressure Port
Override
Fig. 8
Doublegang Wall Plate with Rotary
Setpoint, Override, Pressure Pickup Port
and 3.5mm Comm. Jack
Override
Static Pressure Port
Override
Fig. 6
Fig. 7
Doublegang Wall Plate with Rotary Setpoint and Pressure Pickup Port
COMMON WIRING
PIN Function
SEN2 ....... Temperature, Resistance Output, To analog input of controller.
[Common Ground]
SEN1 ....... Temperature, Resistance Output, To analog input of controller.
OVR2 ....... Override, Normally OPEN, To analog or digital input of controller.
[Common Ground]
OVR1 ....... Override, Normally OPEN, To analog or digital input of controller.
SP+ .......... Setpoint voltage supply.
SET2........ Setpoint, To analog input of controller. [Common Ground]
SET1........ Setpoint, To analog input of controller.
Note: If unit is congured for common ground then SET2, OVR2 and
SEN2 are connected together.
Specications subject to change without notice.
2 of 4
Page 3
16068_ins_sp_rotary
Standard Override (O) 1 amp
Durable Override (O1) 250 milli-amps
Low Profile (O2) 125 milli-amps
Table 2 - Switch Contact Ratings
Termination continued...
Stainless Wallplate with Rotary Setpoint
Installation & Operating Instructions
rev. 08/01/18
Jumper Settings - J1 Options
Differential
Override in parallel with setpoint:
Override in parallel with sensor:
Override as a separate input:
Common Ground
Override in parallel with setpoint:
Override in parallel with sensor:
Override as a separate input:
Optional C35
Communications
Jack Pin Out
Pushbutton Override
Switch Wiring
The Wall Plate Pushbutton Override is a dry contact, normally-open switch. The contacts close for as long as you hold the switch down. All switches are for NEC Class 2 circuits only.
Standard and Durable Override:
The Standard Override (O) and Durable Override (O1) have two white wires attached to either side of the override switch.
Fig. 9: Comm. Jack Wiring
Fig. 10: Wiring for the
Standard (O) and Durable Pushbutton (O1) Override
Jumper Settings - J2 Options
Resistive Setpoint
Direct Action
Reverse Action
Voltage Setpoint
Direct Action
C35 Terminal Block
Terminal Connection
Tip ................. White (Pin 1)
Ring ..............Red (Pin 3)
Ground .......... Black (Pin 2)
Sensor
Wires
Override
Switch
Wires
Reverse Action
Fig. 11: Screw Terminals for
the Low Prole Pushbutton
(O2) Override. The center
terminal is not used.
Center Terminal
Not Used
Low Prole Override:
The Low Prole Override (O2) has three screw terminals that accommodate 16 to 28 gauge wire. The center terminal is not used.
Low Prole Override with LED:
The Low Prole Override with LED (O2G or O2R) has four screw terminals that accommodate 16 to 28 gauge wire. The terminals marked OVR are the dry contact output of the override switch, and the + and ­terminals are power for the LED.
Table 1 - Switch Contact Ratings
Fig. 12: Wiring Examples for the Low Prole Pushbutton Override with
5 VDC and 24 VAC/VDC LED (O2G5 & O2G24 or O2R5 & O2R24)
Specications subject to change without notice.
3 of 4
Page 4
16068_ins_sp_rotary
Diagnostics
Stainless Wallplate with Rotary Setpoint
Installation & Operating Instructions
rev. 08/01/18
POSSIBLE PROBLEMS:
General troubleshooting
Temperature reading is incorrect
Setpoint reading is incorrect
POSSIBLE SOLUTIONS:
- Make sure the input is set up correctly in the controller’s and building automation software.
- Check wiring for proper termination
- Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-strip the interconnecting wire and reapply the connection. In extreme cases, replace the controller, interconnecting wire and/or sensor.
- Label the terminals that the interconnecting wires are connected to at the sensor end and the controller end. Disconnect the interconnecting wires from the controller and the sensor and measure the resistance from wire-to-wire with a multimeter. The meter should read greater than 10 Meg-ohms, open or OL depending on the meter. Short the interconnecting wires together at one end. Go to the other end and measure the resistance from wire-to­wire with a multimeter. The meter should read less than 10 ohms (22 gauge or larger, 250 feet or less). If either test fails, replace the wire. Don’t forget to reconnect the wires.
- Make sure the sensor wires are connected to the correct controller input terminals.
- Check wiring for proper termination and make sure that leads are not touching.
- Measure the physical temperature at the sensor’s location using an accurate temperature standard. Disconnect the sensor wires and measure the resistance across the sensor output pins with an ohmmeter. Compare this resistance to the appropriate temperature sensor table on the BAPI website. If the measured resistance is different from the temperature table by more than 5%, call BAPI technical support. Find BAPI’s website at www.bapihvac.com; click on the button labeled SENSORS on the left of the screen and then click on the type of sensor you have. Don’t forget to reconnect the wires.
- Make sure that the setpoint output is correct. Remove the setpoint output wires and check the output for the correct resistance or voltage output. See the product label for your specic range.
Override is not working correctly
- Check that the resistance across the override output is less than 5 ohms when the override switch is pushed
- Make sure that the override jumper settings are correct.
Specications
Sensor: Passive Thermistor or RTD Thermistor: Thermal resistor (NTC)
Temp. Output:
Accuracy(std): Accuracy (High) Stability: Heat dissipation
Temp. Drift
Probe range:
RTD: Resistance Temperature Device (PTC)
Platinum (Pt) Platinum (Pt) Pt Accuracy (std) Pt Stability Pt Self Heating Pt Probe Range Nickel (Ni) Ni Probe Range
Mounting: 2x4” J-box or Direct Wall Lead Wire: 22AWG Stranded
........Resistance
........±0.36°F, (±0.2°C)
....±0.18°F, (±0.1°C), [XP] option
.................< 0.036°F/Year, (<0.02°C/Year)
....2.7 mW/°C
.............<0.02°C per year
.........-40° to 221º°F (-40° to 105°C)
.........100Ω and 1KΩ @0ºC, 385 curve,
.........1KΩ @0°C, 375 curve
...0.12% @Ref, or ±0.55°F, (±0.3°C)
.............±0.25°F, (±0.14°C)
......0.4 °C/mW @0°C
....-40° to 221°F, (-40 to 105°C)
.............1000Ω @70°F, JCI curve
....-40° to 221°F (-40 to 105°C)
Insulation: Etched Teon, Plenum rated Sensitivity: Approximate @ 32°F (0°C)
Thermistor: RTD (Plat)
0.385Ω/°C for 100Ω RTD
Nickel (NI): ........ 2.95Ω/°F for the JCI RTD
Enclosure: Stainless Steel Plate Foamback: 0.25” Closed Cell Foam Ambient (Encl.):
0 to 100% RH, Non-condensing, -40°F to 185°F, (-40° to 85°C)
Agency:
RoHS, CE, PT = DIN43760, Options: Override Switch
O ....................... N.O. switch, 115 VAC, 1 amp max
O1
..................... N.O. switch, 28 VDC, 250mA amp max
O2
..................... N.O. switch, 4 to 48 VDC, 150mA max
O2G & O2R
....... Non-linier (See bapihvac.com for specs)
........ 3.85Ω/°C for 1KΩ RTD
IEC Pub 751-1983, JIS C1604-1989
..... O2 Switch w/ green or red LED,
5V (11mA) or 24V (15mA) power
Specications subject to change without notice.
4 of 4
Loading...