BAPI Refrigerant Sensor Catalog Page

Refrigerant Sensor
Mounting feet 4 typical
Ventilation holes, top and bottom DO NOT
block
________________________________________________________________________________________________________________________________________________________________
23983_ins_refrigerant
Overview
The BAPI Refrigerant Sensor measures the amount of R404a, R410A and/or R22 present.
Refrigerant Sensor measures leaks and spills; it is not intended for critical ppm measurements. Voltage trip levels for R22, R404A and R410A leaks and spills are shown in the
The sensor is temperature compensated for an
table.
accurate and reliable measurement.
Figure 1: BAPI Refrigerant Sensor
Installation and Operating Instructions
Rev 08/14/2012
Mounting
Figure 2: BAPI-Refrigerant Sensor Mounting
Mount the refrigerant sensor horizontally as shown in Figure 2. Make sure that there is an unobstructed path for a minimum of 12 inches above and below the sensor.
Hold the Refrigerant Sensor against the mounting surface. Mark the mounting feet and drill for #10 screws ´GULOO6FUHZWKH5HIULJHUDQW6HQVRUWRWKHPRXQWLQJVXUIDFH
____________________________________________________________________________________________________________________________________________________________________________________
Specifications subject to change without notice.
Page 1 of 2
Refrigerant Sensor
Possible Solutions
Check for correct power and wiring connections.
Check for correct wiring connections.
________________________________________________________________________________________________________________________________________________________________
23983_ins_refrigerant
Termination
Open the lid by pushing the latch away from the box and pulling the lid open. Close the lid by pushing the lid closed, pushing the latch away from the box and releasing the latch so it snaps into place.
Note: The male connectors that plug into the jacks on the board use a rising block screw terminal to hold the wires. It is possible for the block to be in a partially up position allowing the wire to be inserted under the block. Be sure that the male connector screws are turned fully counterclockwise before inserting the wire. Lightly tug on each wire after tightening to verify proper termination.
Installation and Operating Instructions
Rev 08/14/2012
Refrigerant Sensor
Vout
Temperature Sensor
GND Vin (Power)
Figure 3:
BAPI Refrigerant Sensor Electrical Connections
Operation
The BAPI Refrigerant Sensor has an element that changes its electrical resistance with changes in refrigerant concentrations. The change in resistance determines the output voltage.
Diagnostics
Possible Problem
Green LED is not on Output Incorrect
Specifications
Power: 9 to 40VDC at 120mA max
19 to 32 VAC at 5 VA
Output Impedance: 680 Ohms Output Voltage:
Refrigerant Voltage Trip Level
R22 2.5 VDC @ 500 ppm R134A 1.8 VDC @ 500 ppm R404A 4.5 VDC @ 500 ppm R410A 2.5 VDC @ 500 ppm