LON Communicating Temperature Room Sensor
BA/LC, L-Temp Sensor
11797_ins_L_temp_set
Identication and Overview
BAPI’s Echelon® compatible “L-Temp” Room Unit features measurement
and display of local temperature (°C or °F), as well as display of outdoor
temperature and outdoor humidity – all in one aesthetically-pleasing
package.
An onboard Neuron® chip allows connection directly to a LonWorks® network
using star, bus, or loop topology. Additional options include Temperature
Setpoint and Local Override as well as Fan Speed Control for Fan Coils,
Heat Pumps, Unit Ventilators or other Terminal Units. The Fan Speed is
provided as a Network Variable and includes appropriate LCD Indicators.
Fig. 1:
L-Temp (BA/LC-RSOD)
LON Sensor w/Display,
Setpoint & Override
6
Mounting
JUNCTION BOX
1. Pull the wire through the wall and out of the junction box, leaving
about 6” free.
2. Pull the wire through the hole in the base plate and secure the base to
the box using the #6-32 x 1/2 inch mounting screw provided.
3. Terminate the unit according to the guidelines in the Termination
Section.
4. Attach Cover by latching it to the top of the base, rotating the cover
down and snapping it into place. Secure the cover by backing out the
lock-down screws using a 1/16” Allen wrench until they are ush with
the bottom of the cover.
Installation & Operating Instructions
rev. 06/26/15
DRYWALL MOUNTING
1. Place the base plate against the wall where you want to mount the
sensor. Use a pencil to mark the two mounting holes and the hole for
the wires on the wall.
2. Drill the two 3/16” mounting holes and insert a drywall anchor into
each hole.
3. Drill the 1/2” hole for the wires and pull the wire through the wall and
out of the 1/2” hole, leaving about 6” free.
4. Pull the wire through the hole in the base plate.
Fig. 2: Delta Room Sensor installation
Hardware for J-box or direct drywall
mount provided.
5. Secure the base to the drywall anchors using the #6 x 1 inch
mounting screws provided.
6. Terminate the unit according to the Termination guidelines in on pg 2.
7. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place.
8. Secure the cover by backing out the lock-down screws using a 1/16” Allen wrench until they are ush with the
bottom of the cover.
NOTE: In a wall-mount application, the wall temperature and the temperature of the air within the wall cavity
can cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to
condensation, erroneous readings and premature failure of the sensor.
To prevent these conditions, seal the
conduit leading to the junction box.
Specications subject to change without notice.
1 of 3
LON Communicating Temperature Room Sensor
BA/LC, L-Temp Sensor
Installation & Operating Instructions
11797_ins_L_temp_set
Wiring & Termination
BAPI recommends using twisted pair of at least 22AWG and sealant lled connectors for all wire connections.
Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and
local codes. Do NOT run this device’s wiring in the same conduit as AC power wiring.
For additional wiring information and requirements, please refer to Echelon® Corporation’s Bulletin titled “Junction
Box and Wiring Guidelines for Twisted Pair LonWorks® Networks” which can be found online at the following URL.
http://www.echelon.com/support/documentation/Bulletin/005-0023-01K.pdf
BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity, and
wiring connections are important to a successful installation. Not observing these recommendations may
damage the product and will void the warranty.
Service
Button
Terminal Description
NETB
Service
LED
..............Network B
NETA
..............Network A
V+
...................8 to 24VDC or 12 to 28VAC
GND
................Power Supply Ground
rev. 06/26/15
Communication Jack Termination
FRONT
Comm.
Jack
Fig. 4: Comm. Jack Location
Fig. 3: Termination &
Board layout
BACK
Fig. 5:
3.5mm Stereo Jack Pins
Specications subject to change without notice.
C35 Communication Jack Option
Plug ID Wire Color Pin #
Ground Black 1
Tip White 2
Ring Red 3
Table 1:
C35 Wiring ID