BAPI LM334 Room Sensors Catalog Page

LM334 Room Sensors
Sensor Termination and T roubleshooting
9613_ins_LM334_Room
Termination
BAPI recommends using twisted pair of at least 22 AWG and crimp type connectors for all wire connections. Also, it is recommended that wiring NOT be run in the same conduit as line voltage wiring or with wiring used to supply highly inductive loads such as motors, generators, and coils.
11/22/06rev.
LM334 (2 Wire) sensors
1. Install a 10K 0.1% resistor between the sensor Output (terminal 2) and Ground (GND).
2. Make sure that the resistor is connected between the analog input (A.I.) point and
Ground.
3. Connect the sensor Output to the A.I. point.
4. Connect the 5 to 30 VDC wire last.
SENS
R1
R2
1 2 3
+5 to +30 VDC [To Power of Controller or Supply]
Sensor output (1mV/°K) [To Analog Input of Controller]
10K 0.1%
GND(Common) [To GND(Common) of Controller]
LM334-10K (3 Wire) sensors
1. All LM334-10K (3 wire) sensors have a 10K
0.1% resistor built in.
2. Connect the Ground (terminal 3) wire first.
3. Connect the Sensor Output wire second.
4. Connect the 5 to 30 VDC wire last.
SENS
R1
R2
1 2 3
+5 to +30 VDC [To Power of Controller or Supply]
Sensor output (1mV/°K) [To Analog Input of Controller]
GND(Common) [To GND(Common) of Controller]
Offsetting
All LM334 sensors will have the following information provided on a label:
Therm Reading_______
The actual temperature reading according to a thermometer that is certified traceable to recognized standards by the National Institute of Standards and Technology (NIST).
To correct the Sensor Reading, simply add the offset value to the sensor reading so that it equals the thermometer reading.
e.g. Therm Reading 74.6 Sensor Reading 73.0 Offset +1.6
Correction: Add (+1.6) °F to the sensor for an accurate reading: 73 + 1.6 = 74.6°F
e.g. Therm Reading 75.4 Sensor Reading 77.2 Offset -1.8
Correction: Add (-1.6) °F to the sensor for an accurate reading: 77.2 + (-1.8) = 75.4°F
Sensor Reading ______
The temperature reading according to the LM334 sensor, using the output in either mA or mV and converting the output to a Fahrenheit temperature.
Offset_______
The difference between the Thermometer Reading and the Sensor Reading
1
9613_ins_LM334_Room
Troubleshooting
LM334 Room Sensors
Sensor Termination and T roubleshooting
11/22/06rev.
Problems:
Temperature sensor in front end software is reading high
Temperature sensor in front end software is reading low
Temp. LM334
°F °C (µA) (V) 50 10 283.2 2.83 60 15.56 288.7 2.89 62 16.67 289.8 2.90 64 17.78 290.94 2.91
Possible Solutions:
- Confirm the input is set up correctly in the front end software
- Check wiring for proper termination
- Verify the “Sensor” output is correct from Pin 2 to Pin 3 Refer to table below for proper reading
- Determine if the semiconductor appears physically shorted
- Check wiring for proper termination
- Verify the “Sensor” output is correct from Pin 2 to Pin 3 Refer to table below for proper reading
66 18.89 292.1 2.92 68 20 293.2 2.93 70 21.11 294.3 2.94 72 22.22 295.4 2.95 74 23.33 296.5 2.97 76 24.44 297.6 2.98 77 25 298.2 2.98 78 25.56 298.7 2.99 80 26.67 299.8 3.00 82 27.78 300.9 3.01 84 28.89 302.1 3.02 86 30 303.2 3.03 88 31.11 304.3 3.04 90 32.22 305.4 3.05 100 37.78 310.9 3.10
2
Loading...