BAPI BAPI-Stat 4 Sensor Catalog Page

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
Product Identication and Overview
The BAPI-Stat 4M room temperature sensor features a large format LCD and pushbutton setpoint adjustment. Additonal options include pushbutton override, fan speed and mode adjustments.
The setpoint is available as a resistance or voltage output. The override is a momentary closure signal that can be congured in parallel with the sensor or setpoint, or as a separate momentary or latching contact output. A 3.5mm (1/8”), RJ11 or RJ22 communication jack can also be mounted in the unit’s base to provide direct access to the network.
BA/BS4M Temperature Sensor
Installation & Operating Instructions
rev. 01/18/1625188_ins_BS4M
Fig. 2: 2 Button Unit
Fig. 1: BAPI-Stat 4M
Override, Fan and Mode
Control.
Note: BAPI-Stat 4M shown with ve buttons. Two, three or ve buttons may be present. See “Front Panel & Control” section.
Mounting
JUNCTION BOX
1. Pull the wire through the wall and out of the junction box, leaving about 6 inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the base to the box using the #6-32 x 1/2 inch mounting screw provided.
4. Terminate the unit according to the guidelines in the Termination section.
5. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place.
6. Secure the cover by backing out the lock-down screws using a 1/16” Allen wrench until they are ush with the bottom of the cover.
DRYWALL MOUNTING
1. Place the base plate against the wall where you want to mount the sensor.
2. Using a pencil, mark out the two mounting holes and the area where the wires will come through the wall.
3. Drill two 3/16” holes in the center of each marked mounting hole. Insert a drywall anchor into each hole.
4. Drill one 1/2” hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out the 1/2” hole, leaving about 6” free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8. Terminate the unit according to the guidelines in the Termination section.
9. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover by backing out the lock-down screws using a 1/16” Allen wrench until they are ush with the bottom of the cover.
Fig. 5: Mounting hardware is provided
for both J-Box and drywall installation
(J-Box installation shown)
Fig. 3: 3 Button Unit
Fig. 4: 5 Button Unit
NOTE: In a wall-mount application, the mixing of room air and air from within the wall cavity can lead to erroneous
readings, condensation, and premature failure of the sensor. To prevent this condition, plug the conduit hole with insulation in the junction box.
Specications subject to change without notice.
1 of 8
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
BA/BS4M Temperature Sensor
Installation & Operating Instructions
rev. 01/18/1625188_ins_BS4M
Termination
BAPI recommends using twisted pair of at least 22AWG and sealant lled connectors for all wire connections. Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as AC power wiring. BAPI’s tests show uctuating and inaccurate signals are possible when AC power wiring is in the same conduit as the signal lines. If you are experiencing any of these difculties, please contact your BAPI representative.
BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and void the warranty.
TERMINAL DESCRIPTION
GND ........................Power Supply Ground (Common to the controller)
V+
........................... Power Supply Hot (See specications for voltage
details)
.........................Fan Speed/System Mode (Resistive Output)
FAN
EXT OVR
SEN1 & SEN2
SET1 & SET2 ......... A) Setpoint output per order (resistive). *If the unit
B) Setpoint output per order (voltage). SET1 is
OVR1 & OVR2
Fig. 6: BAPI-Stat 4M Circuit Board
*Grounding Note:
Common Ground (-CG) or Differential Ground (-DF) congurations are selected per order. The Differential Ground conguration (-DF) indicates that SEN2, SET2, OVR2 and RSEN2 must all be wired separately (No internal common connection). The Common Ground conguration (-CG) indicates that SEN2, SET2, OVR2 and RSEN2 are connected to GND internally (All internally common). This is true of all Common Ground units except when ordered with the Override as a Latching Switch option (-L#). In this case, OVR2 is isolated and not internally connected to SEN2, SET2 and RSEN2.
RSEN1 & RSEN2
................BAPI-Man Occ/Un-Occ indicator Input.
Ground terminal to ll in the BAPI-Man icon for Occupied.
........Sensor output per order (resistive). No polarity. *If
the unit is a common ground conguration (-CG), see “Grounding Note” below.
is a common ground conguration (-CG), see “Grounding Note” below.
“+”, SET2 is “-”. *If the unit is a common ground conguration (-CG), see “Grounding Note” below.
........Override output (Dry contact) The contact can be
ordered as a momentary shunt across the sensor (-N) or as a momentary shunt across the setpoint (-P) or as a separate momentary contact (-J) or as a separate latching contact (-L#). *If the unit is a common ground conguration (-CG), see “Grounding Note” below.
... Remote sensor option (-ES). No polarity. *If the
unit is a common ground conguration (-CG), see “Grounding Note” below. A 10K-2 thermistor sensor must be ordered separately and the temperature value is displayed on the LCD. Note: If a temperature reading is needed at the controller, then a second sensor must be ordered and wired independently.
Specications subject to change without notice.
2 of 8
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
Low Temp (40° F)
High Temp (105°F)
3000Ω Thermistor 7.87KΩ (39.8°F) 1.5KΩ (106.8°F)
10K-3(11K) Thermistor 7.32KΩ (43.7°F) 3.65Ω (105.2°F)
HCF 5KΩ 10KΩ 15KΩ 20KΩ 25KΩ 30KΩ
Option Heat Cool Auto Off
Option OFF AUTO LO MED HI ON
XLD 5KΩ 10KΩ 15KΩ 20KΩ 25KΩ
X02 2KΩ 4KΩ 6KΩ 8KΩ 10KΩ
X06 6.5KΩ 8.5KΩ 10.5KΩ 12KΩ
Optional Communication Jack Wiring
BA/BS4M Temperature Sensor
Installation & Operating Instructions
rev. 01/18/1625188_ins_BS4M
Fig. 7:
Back Plate Comm. Jack Locations
C35L
C11L/
C22L
Fig. 8: C35L Comm. Jack (3.5mm plug
shown for
clarity)
Fig. 9:
C11/C22
Comm.
Jack
C35L Comm. Jack Wiring
Location WIRE COLOR
Ground Black
Tip White
Ring Red
C11L/C22L Comm. Jack Wiring
PIN # WIRE COLOR
1 Not Connected 2 Black 3 Red 4 Yellow 5 Green 6 Not Connected
Optional Test and Balance Switch (S1)
On the Test and Balance Switch, the NORM position allows the real sensor to be monitored. The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading (see Table below).
Test and Balance Switch (S1)
LOW: Sets the sensor value low
Sensor Type
Resistance Value
Resistance Value
1000Ω RTD 1.02KΩ (41.20°F) 1.15KΩ (101.5°F)
NORM: Sensor operates normally
HIGH: Sets the sensor value high
Optional Fan Speed and System Mode Control
The unit is available with optional Fan Speed and
Option Heat/Auto Off /Auto Cool/Auto Heat/On Off/On Cool/On
System Mode Control. The resistive outputs for
H01 2KΩ 4KΩ 6KΩ 8KΩ 10KΩ
the various options is shown in the table at right. The option is selected at
H02 5KΩ 10KΩ 15KΩ 20KΩ
the time of order and the resistive value is output to the FAN terminal.
X01 4.89KΩ 2.33KΩ 10.63KΩ 13.24KΩ 16.33K
X03 5KΩ 10KΩ 15KΩ X05 4.89KΩ 2.33KΩ 15.8KΩ
X07 5KΩ 15KΩ X08 12.68KΩ 11.86KΩ 13.86KΩ
10K-2 Thermistor 30.1KΩ (34.9°F) 4.75Ω (109.1°F) 10K-3 Thermistor 26.7KΩ (35.9°F) 5.11KΩ (108.4°F)
Specications subject to change without notice.
3 of 8
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
Front Panel & Control Descriptions
A display is standard for all BA/BS4M units. It is available with an optional override button, setpoint buttons, fan control or system control buttons or any option combination. Fig. 10 shows a fully featured sensor.
NUMERICAL DISPLAY:
The default display shows current temperature. When the up/down buttons are pushed, then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds. The unit can also be set up to display setpoint only or for setpoint lockout. See “Optional Technicians Adjustments” section.
BAPI-MAN ICON: The BAPI-Man Icon shows the status of the room – Solid for Occupied, Hollow for “Unoccupied” (Fig. 11).
Note: The unit must receive a conrmation (ground) signal on the “EXT OVR” terminal for the BAPI-Man to remain visible on the screen. Pressing the Override button will light the BAPI-Man icon; however, if no conrmation signal is received, then the BAPI-Man will go blank (disappear) after 5 seconds.
Upon receiving a rst conrmation (ground) signal on the “EXT OVR” terminal, the BAPI-Man will show occupied (Solid). The BAPI-Man will then show unoccupied (Hollow) whenever the conrmation signal is removed and occupied when the signal is returned. The only way to blank the BAPI-Man from the display at this point is to cycle power.
Fan and Speed Indicator
Occupied or Unoccupied Icon
Automatic System Mode
BA/BS4M Temperature Sensor
Heat Mode
Cool Mode
System Mode Button
Override Button
Fan Speed Button
Fig. 10: BAPI-Stat 4M unit with Override, Setpoint, Fan
Note: BAPI-Stat 4M shown with ve buttons. Two,
three or ve buttons may be present.
Solid
equals
“Occupied”
Fig. 11: BAPI-Man Icon
Installation & Operating Instructions
& System Buttons.
Hollow
equals
“Unoccupied”
rev. 01/18/1625188_ins_BS4M
Engineering Units
Temperature Display in .5 Increments
Override On
Override Off
Setpoint Up/Down Buttons
Fan Speed
Low
Fan Speed
Medium
Fan Speed
High
Fig. 12: Fan Speed
Indicator
FRONT PANEL BUTTONS
SETPOINT:
When pressed, the setpoint will display for three to four seconds. When pressed again, the setpoint will change in one degree increments. It will only change within the setpoint range that was ordered.
OVERRIDE: When the override button is pressed, the BAPI-Man will be displayed as “Solid” for 3-5 seconds and the override output will shunt or short for 3 seconds depending on the override option selected. (-N Option = Momentary Temperature Sensor Shunt to <15Ω, -P Option = Momentary Setpoint Shunt to <15Ω, -J Option = Momentary Override as a Separate Shorting Contact Output, -L# Option = Override as a Latching Switch, See “Latching Override Operation” on pg. 5.) If the occupied input (EXT OVR) terminal is grounded, then the BAPI-Man will stay lled in, indicating an occupied state. If the input is open, then the BAPI-Man will revert to hollow, indicating unoccupied (or the icon will disappear completely if there has never been a ground on the EXT OVR terminal).
MODE:
Cycles through ‘HEAT’, ‘OFF’ and ‘COOL’.
FAN:
Cycles through ‘AUTO’, ‘ON’ and Fan Speed (see Fig. 12).
Specications subject to change without notice.
4 of 8
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
BA/BS4M Temperature Sensor
Installation & Operating Instructions
rev. 01/18/1625188_ins_BS4M
Optional Technician Adjustments (The sensor set-up is factory set per your order. Set-up adjustments are not required)
The unit is shipped ready to install per the order and does not requires any special setup or programming. The following Setup or Program Menu Changes are available if the installer decides to change the factory settings. Pushing the button (S2) on the lower right side of the termination board allows the user to change the display from Celsius to Fahrenheit and back again (See Fig. 6).
ENTERING PROGRAM MODE AND MAKING CHANGES:
1. Remove cover and install the shunt jumper across the J16 pins (see Fig. 13).
2. Use the Up and Down Setpoint Pushbuttons on the front of the sensor to advance
to the parameter you wish to adjust. (Moves up or down from page to page or from setting to setting.)
3. Push the Override Pushbutton on the front of the unit to select the menu adjust
Jumper Off
Run Mode
parameter. This selects the currently displayed menu.
4. Use the Up and Down pushbuttons to adjust the parameter
Fig. 13: J16 Program
5. Push the Override Pushbutton to select the newly adjusted parameter value.
6. You can quit by removing J16 or move to the next parameter using the Up/Down Setpoint buttons.
Note: If your unit does not have the necessary front Up/Down/Override buttons for
adjustment you can remove the board from the housing and use the three buttons that are on the back of the board. Removing the board requires removing the centered board mounting screw. The buttons are identied as S3 = Enter (Override), S5 = Up Adjust and S6 = Down Adjust. (See Fig. 14) After adjustment, place the board back into the cover and insert the center mounting screw. Do not over tighten.
Jumper On
Program Mode
Jumper
MODE MENUS:
The setup mode consists of menu pages P1 through P6 for conguring the sensor. The following adjustments can be done with the program jumper J16 installed.
P1 = Temperature offset: Adjust Up or Down, -5 to 5° in 0.1° increments
P2 = Setpoint Lockout: Adjust the value to dene the Setpoint mode
0 = Enable Setpoint adjustment (Normal mode) 1 = Disable Setpoint adjustment (No setpoint adjust)
Enter
2 = Display Setpoint Only (No room temperature displayed) 3 = No Setpoint Displayed (Rarely used with pushbutton setpoint units)
P3 = Latching Display (see Fig. 15)
-1 = Override Disabled 0 = Momentary Contact, Hollow Man/Solid Man (Typically the normal setting)
1 = Latching Contact: Off/On, No Fan/Fan, Solid Man 2 = Latching Contact: Off/On, No Fan/Fan, No BAPI-Man 3 = Latching Contact: Off/On, Solid Man 4 = Latching Contact: Off/On, No BAPI-Man
Fig. 14: Setup Switch
locations on the circuit board.
5 = Latching Contact: On/Off, Fan/No Fan, Solid Man 6 = Latching Contact: On/Off, Fan/No Fan, No BAPI-Man 7 = Latching Contact: On/Off, Solid Man 8 = Latching Contact: On/Off, No BAPI-Man 9 = Latching Contact: Hollow Man/Solid Man 10 = Non-Latching
See “Latching Override Operation” and “Momentary Override Operation” descriptions for further details.
P4 = Temperature Display: Adjust value to the display increments desired 0 = Display in whole digits only 1 = Display in 0.5° increments, F or C as chosen on switch S2 2 = Display in 0.1° increments, F or C as chosen on switch S2
P5 = Setpoint Display Low: Adjust the Low temperature of the desired setpoint range between -9 to 99°.
P6 = Setpoint Display High: Adjust the High temperature of the desired setpoint range between -9 to 99°.
Up
Down
5 of 8
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
BA/BS4M Temperature Sensor
Latching Override Operation
The unit can be ordered with an “Override as a Latching Switch” by selecting the -L# option. The # (1-10) represents the display the user may want to use and is shown below. This can be changed by a technicians adjustment.
In the “Override as Latching Switch” Option, pressing the Override button closes the override relay contacts (Terminals OVR1 & OVR2). They will remain closed until the “Override” button is pressed again, then they will open and remain open until the Override button is pressed again. See Fig. 16 below for examples of “Override as a Latching Switch” circuits.
Ten display options (Fig. 15) are available to indicate when the latching relay is open and when the latching relay is closed. Note: If one of the “Fan Speed/ Mode” options is selected from the ordering grid, then you MUST use the latching display Option 9.
BAPI-MAN ICON
On Options 2, 4, 6, 8 & 10, the BAPI-Man Icon is disabled and will not show on the display, even when the Override button is pushed.
On Options 1, 3, 5 & 7, the BAPI-Man Icon is lled or solid for 3 to 5 seconds after the Override button is pushed, but it will only remain solid or lled when there is a ground signal to the EXT OVR terminal of the unit.
For Option 9, the BAPI-Man Icon stays lled or solid when the relay is closed and hollow when the relay is open.
For Option 10, the BAPI-Man Icon is disabled but the “ON” or “OFF” Dot on the display is controlled by the EXT OVR terminal. When there is a ground signal at the EXT OVR terminal, the “ON” dot is lit. Otherwise the “OFF” and hollow dot are lit. Note: The Override Terminals OVR1 and OVR2 are NOT latching in
Option 10. These terminals close MOMENTARILY in this option.
Installation & Operating Instructions
rev. 01/18/1625188_ins_BS4M
Latching Switch with
External Load Circuit
Latching Switch as Direct Controller Input Circuit
Fig. 16: Latching Switch Wiring Diagrams
In the “Override as Latching Switch” conguration, terminals OVR1 & OVR2 act as a latching switch with a maximum capacity of 24 VAC/VDC at 800 mA resistive. Pressing the Override button latches or unlatches the OVR1 & OVR2 terminals. These diagrams show how to wire the latching switch with an External Load and as a Direct Controller Input
Fig. 15: Latching Switch Display Options
The 10 “Override as a Latching Switch” display options are shown above for when the relay is open and when the relay is closed.
Note 1: If the unit is ordered with “Fan Speed/Mode” Options, then you must use the latching display Option 9.
Note 2: On Options 1, 3, 5 & 7, the BAPI-Man Icon is lled or solid for 3 to 5 seconds after the Override button is pushed, but it will only remain solid or lled when there is a ground signal to the EXT OVR terminal of the unit.
6 of 8
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
BA/BS4M Temperature Sensor
Installation & Operating Instructions
rev. 01/18/1625188_ins_BS4M
Momentary Override Operation (Non-Latching)
When the Override pushbutton is pressed, the BAPI-Man (Fig. 11) will be displayed as “Solid” for 3-5 seconds and the override output will shunt or short for 3 seconds depending on the override option selected. The various options are described below.
-N Option = Momentary Temperature Sensor Shunt to < 15Ω
-P Option = Momentary Setpoint Shunt to <15Ω
-J Option = Momentary Override as a Separate Shorting Contact Output on OVR1 & OVR2
BAPI-MAN ICON: The BAPI-Man Icon shows the status of the room – Solid for Occupied, Hollow for “Unoccupied” (Fig. 11). The unit must receive a conrmation (ground) signal on the “EXT OVR” terminal for the BAPI-Man to remain visible on the screen. Pressing the Override button will light the BAPI-Man icon; however, if no conrmation signal is received, then the BAPI­Man will go blank (disappear) after 5 seconds. Upon receiving a rst conrmation (ground) signal on the “EXT OVR” terminal, the BAPI-Man will show occupied (Solid). The BAPI-Man will then show unoccupied (Hollow) whenever the conrmation signal is removed and occupied when the signal is returned. The only way to blank or remove the BAPI-Man from the display after receiving a conrmation signal is to cycle power.
General Diagnostics
POSSIBLE PROBLEM: POSSIBLE SOLUTIONS:
Temperature reading is incorrect - Verify that the input is set up correctly in the controller’s and building
automation software.
- Check wiring for proper termination and check for opens or shorts.
- Measure the room temperature at the sensor’s location using an accurate temperature standard. Disconnect the temperature sensor wires and measure the temperature sensor’s resistance across the sensor output pins with an ohmmeter. Compare the temperature sensor’s resistance to the appropriate temperature sensor table on the BAPI website. If the measured resistance varies by more than 5% from the temperature table, call BAPI technical support. To view the temperature table, go to the BAPI website (www.bapihvac.com), click on “Resource Library” and “Sensor Specs”, then click on the type of sensor you have.
- If the unit has a test and balance switch, make sure that it is in the correct position.
Setpoint reading is incorrect - Make sure that the setpoint output is correct. Remove the setpoint output
wire and check the output for the correct resistance or voltage output. See the product label for your specic range.
Override is not working correctly - Check that the resistance across the override output is less than 5Ω when
the override is pushed.
Fan Mode not correct - Make sure that the fan mode output is correct. Remove the fan mode
output wire and check the output for the correct resistance. See the product label for your specic range and compare it to the resistance chart at the bottom of page 3. Don’t forget to reconnect the wire.
Specications subject to change without notice.
7 of 8
BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control
BA/BS4M Temperature Sensor
Installation & Operating Instructions
Specications
Power for 5 VDC Power Units:
0 to 5 VDC Setpoint or Resistive Setpoint ....5V ±1% (5 VDC nominal, Input regulation affects accuracy)
Power for 24 VDC Power Units:
0 to 5 VDC Setpoint or Resistive Setpoint ...9 to 40 VDC (24 VDC nominal) 0 to 10 VDC Setpoint or Resistive Setpoint ..15 to 40 VDC (24 VDC nominal)
Any Allowed Setpoint ....................................15 to 28 VAC (24 VAC nomimal)
Note: AC power requires a separate pair of shielded wires
Power Consumption: .....................................7 mA max DC; .17 VA maximum AC
Wiring: ................... See Wiring & Termination Section, 22 to 14AWG
Mounting: .............. Standard 2 x 4” box or drywall direct, Screws provided
Outputs:
Passive Sensor....See order grid for thermistor or RTD
Thermistor, ±0.36ºF (±0.2ºC), [XP] ±0.18ºF (±0.1ºC) Platinum RTD, ±0.12%, [A] ±0.06% Nickel RTD, 1000Ω @70ºF, JCI curve
External Sensor ...10K-2 thermistor (-ES), (Purchased separately) Wired 25’ maximum from sensor
Setpoint ...............Resistive per order or voltage (0 to 10VDC limit per order)
Isolated Contact ..24VDC @500mA resistive
Inputs: ....................Dry contact (24V, <1mA)
Occupied .............EXT OVR “Grounded”
Unoccupied .........EXT OVR “Open to Ground”
Display: .................LCD, Overall, 2”W x 1.1”H (Temp/Setpoint/Occupied)
LCD ....................3.5 Digits @0.6”H
Occ/Unocc ..........BAPI-Man Icon, (Filled in man is occupied)
Display Limits ......1.0º, 0.5° and 0.1° (F/C) increments, Setpoints in 1º steps
Range .................-40 to 185°F (-40 to 85°C)
Display Setup ......Temp. & Setpoint, Temp. only, or Setpoint only, ºF or ºC
Optional ............... Fan Speed, System Mode, Override
Button Options: .... Factory set options
Setpoint ..............Up & Down buttons
Override .............. Pushbutton
Override .............. Factory set to Momentary shunt across sensor, Momentary shunt across setpoint,
Momentary isolated contact or Latching isolated contact
Fan Speed ...........Off, Auto, Lo, Med, Hi
System Mode ......Heat/Off/Cool, Auto/On Fan
Setup Options:
Offset ...................±5º
Temp Display .......Display in ºF or ºC
Setpoint ...............Disabled or Setpoint display only
Resolution ...........Display in 1.0°, 0.5º or 0.1º increments
Other Options:
Comm. jack .........3.5mm phone jack, 3 wires (-C35) • RJ11 jack, 4 wires (-C11) • RJ22 jack, 4 wires (-C22)
Test & Balance .... Three position switch (-TB), (High Temp/Normal/Low Temp)
Common Ground .Internal common connection (-CG) Differential GND. .Each output terminal is isolated (-DF)
Environmental Ambient:
Temperature ........32 to 122ºF (0 to 50ºC)
Humidity ..............0 to 95% RH Non-condensing
Storage ................32 to 185°F (0 to 85°C)
Encl. Material: ....... ABS Plastic, UL94V-0
Agency: .................RoHS, CE* (*Units with passive Thermistors 20KΩ and smaller are CE compliant.)
Specications subject to change without notice.
rev. 01/18/1625188_ins_BS4M
8 of 8
Loading...