The BAPI-Stat 3 is a multiple output transmitter for temperature and
humidity with setpoint capability for both and occupied/unoccupied
override switching. The large easy-to-read display is ideal for cross
room viewing and membrane pushbuttons are designed for easy
operation and cleaning.
A fully featured unit can have 4 active channel outputs, override and
a passive sensor output. All ranges are factory set, however each
temperature and humidity sensor channel has a local offset adjust for
ne tuning. The display can be locally customized to the customer’s
preference.
Fig. 1:
BAPI-Stat 3 with temperature and
humidity setpoint and override. (Units
without humidity setpoint will only have
three buttons.)
Specications
Installation & Operating Instructions
rev. 08/19/1535450_ins_BS3_JCI
Power Supply:
10 to 35 VDC (15 to 24 VDC Recommended) for 4 to 20 mA or 0 to 5 VDC Outputs
15 to 35 VDC (15 to 24 VDC Recommended) for 0 to 10 VDC Outputs
12 to 28 VAC (Requires a separate pair of shielded wires) for 0 to 5 VDC Outputs
15 to 28 VAC (Requires a separate pair of shielded wires) 0 to 10 VDC Output
Power Consumption:
60 mA maximum DC: 4 to 20 mA or 0 to 5 VDC Outputs
10 mA maximum DC: 0 to 10 VDC Output
1.44 VA maximum AC: 0 to 5 VDC Outputs
0.2 VA maximum AC: AC: 0 to 10 VDC Output
Outputs: 4 active output channels plus 1 passive temp. sensor
Volts 0 to 5 VDC or 0 to 10VDC, Imp. >10KΩ (CH 1, 2, 3, 4)Current0, 4-20 mA, Imp. <500 W @ 24 VDC (CH 1, 2)
ResistanceE-POT, 1K, 10K, 50K or 100KΩ, 5 VDC @ 5 mA max (CH 3, 4) - Factory selected per application
ContactN.O. reed switch, 250 mA @ 29 V max
Temp. Sensor Passive RTD, thermistor or semi-conductor (CH 5)
Sensing Elements: Active output and display
Temperature 10K-2 Thermistor,
Humidity Capacitive Polymer, ±2%RH
Ambient Specications:
Temperature: 32 to 122ºF (0 to 50ºC)
Humidity: 0 to 95%, non-condensing
Wiring:
2 to 5 pair of 16 to 22 AWG
(Conguration dependent)
Material: ABS Plastic
Material Rating: UL 94, V-0
Specications subject to change without notice.
1 of 6
“BAPI-Stat 3” JCI Room Sensor
Installation & Operating Instructions
rev. 08/19/1535450_ins_BS3_JCI
Mounting
JUNCTION BOX
1. Pull the wire through the wall and out of the junction box, leaving about six inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the backplate to the box using the #6-32 x 1/2 inch
mounting screws provided.
4. Terminate the unit according to the guidelines in the Termination
section.
5. Attach Cover by latching it to the top of the base, rotating the cover
down and snapping it into place.
6. Secure the cover by backing out the lock-down screw using a 1/16”
allen wrench until it is ush with the bottom of the cover.
DRYWALL MOUNTING
1. Place the base plate against the wall where you want to mount the
sensor.
2. Using a pencil, mark out the two mounting holes and the area
where the wires will come through the wall.
3. Drill two 3/16” holes in the center of each marked mounting hole.
Insert a drywall anchor into each hole.
4. Drill one 1/2” hole in the middle of the marked wiring area.
Mounting hardware is
provided for both junction
box and drywall installation
(Junction box installation
5. Pull the wire through the wall and out the 1/2” hole, leaving about
six inches free. Pull the wire through the hole in the base plate.
6. Secure the base to the drywall anchors using the #6 x 1” mounting screws provided.
7. Terminate the unit according to the guidelines in the Termination section.
8. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover
by backing out the lock-down screw using a 1/16” allen wrench until it is ush with the sides of the cover.
Fig. 2:
shown).
Note: In any wall-mount application, the wall temperature and the temperature of the air within the wall cavity can cause
erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous
readings and sensor failure. To prevent these conditions, BAPI recommends sealing the conduit leading to the junction
box with berglass insulation.
Front Panel Description
Humidity Setpoint: When the left set of s or t buttons are pressed, the relative humidity
setpoint will display. As the buttons are pressed again, the display will change in 1%
increments with each press. The setpoint will change only within the specied range ordered.
Temperature Setpoint: When the right set of s or t buttons are pressed, the temperature
setpoint will display. As the buttons are pressed again, the display will change in one degree
increments with each press. The setpoint will change only within the specied range ordered.
Pressing and holding any setpoint button will auto increment/decrement the setpoint value
The setpoint will change only within the specied range (as ordered).
Override: When the button is pressed, the Occupied/Unoccupied Icon will show
for a few seconds.
To retain the Occupied/Unoccupied Icon , you must energize J6*.
(*For more information on Occupied/Unoccupied Icon, see the “Termination” and the
“Display Occupancy Mode Termination” sections)
Fig. 3:
Front View of BAPI-Stat 3
Specications subject to change without notice.
2 of 6
“BAPI-Stat 3” JCI Room Sensor
Installation & Operating Instructions
rev. 08/19/1535450_ins_BS3_JCI
Termination
BAPI recommends using twisted pair of at least 22 AWG. Larger gauge wire may be required for long runs. All wiring
must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit
as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to supply highly inductive loads such
as motors, contactors and relays. BAPI’s tests show that uctuating and inaccurate signal levels are possible when AC
power wiring is present in the same conduit as the signal lines.
BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity, and wiring
connections are important to a successful installation. Not observing these recommendations may damage the
product and will void the warranty.
1. Only one variable and output type per channel. [CH3] and [CH4] can be
Occupied/
un-occupied
BAPI-Man
See Table 1
for terminal
description
power
(see Table 2,
Fig 5 & 6)
Factory
setup switch
Fig. 4: BAPI-Stat Circuit Board
Table 1: TerminationTable
Input Power
Terminal
Name
GND Pwr- & Sig- ------------- V+ DC or AC --------------
CH1CG X X X Sig+ mA + CH2CG X X X Sig+ mA+ CH3CG/DF* per order X X ^^E-POT Sig+ ^^*<100KΩ *E-POT CH4CG/DF* per order X X
TEMP+Sensor ^^^N.O ~ ~ N.O. Sensor V+
TEMP-CG/DF, S1-4** Sensor ^^^N.O. ~ ~ **N.O. Sensor ***V-
Supply
Power
Internal
Grounding
CG=Com. GND
DF=Isolated
Output Variable (See your unit label for your conguration)Output Signal (See your unit label for your conguration)
Temperature
Output
Sensor Power Connection---------
Sensor Power Connection---------
Humidity
Output
overridden.
2. The [GND] terminal is always the reference for [V+], [CH1] and [CH2]
terminals.
3. The temperature output range is limited to between 32º to 158ºF
(0º to 70ºC).
4. Humidity setpoint range is limited between 0 to 100% RH.
5. The override is available on [CH3], [CH4] and [TEMP+/TEMP-] only.
6. Voltage outputs are limited to between 0 to 10 VDC and are only
referenced to [GND].
7. Current outputs are limited to between 0 to 20 mA and are only referenced to [GND].
8. Resistive E-POT outputs are limited to a 1K, 10K, 50K or 100KW linier
POT, ±30%.
9. Resistive sensor [TEMP+/TEMP-] outputs may be any BAPI passive or
solid state sensor.
10. When using a 592/334 sensor, [TEMP+] is the supply (5 to 30 VDC)
[TEMP-] is the current output to the analog input @ 1µA/ºC and requires
S1-4 to be set for (DF). Reversal of the power will damage the sensor.
11.
The Test and Balance option (-TB) cannot be used with the 592/334 sensor.
12. If the BAPI-Stat has the external sensor option (-EXT), then it must be a
10K-2 thermistor purchased separately. The external sensor is wired to
the temp + and temp - terminals. A humidity signal or passive sensor are
not allowed in this conguration.
Temperature
Setpoint
Output
Humidity
Setpoint
Output
Sig- Sig- * ** ^ ** ***
Override
Output
^^E-POT/^N.O. Sig+
Voltage
Output
Current
Output
Resistive
Output
^^*<100KΩ *E-POT/^N.O.
Signal
Override
Contact
Passive
RTD or
Thermistor
Sensor
592/334
Solid
State
Sensor
* [CH3] and [CH4] are referenced to [GND] if (CG) is selected at time of order. [CH3] and [CH4] are referenced to each other if (DF) is selected at time of order.
** S1-4, Position (CG) connects [Temp-] terminal to the [GND] terminal internally. The (DF) position makes the [TEMP -] terminal oating. (See Fig.10)
*** This is the current output of the solid state sensor and must be congured as S1-4 set to (DF) to allow the 592 or 334 sensor to operate.
^ The reed contact to override [CH4] can be set up for (CG) which shorts the [CH4] output to [GND] or (DF) shorting the output terminals [CH3/CH4].
^^ The E-POT controls the output resistance setpoint and during override, the E-POT controls the resistance to <100 ohms for 3-5 seconds.
^^^ A reed dry contact across the sensor [TEMP+/-] is congured at time of order as a (-61) option.
~ The [TEMP] terminals are used for an external 10K-2 thermistor connection if the [EXT option] is selected. (wire=25’ max)
When the override button is pushed, the override output is active
for 3 to 5 seconds. Simultaneously, the outline and center of the
HUMAN ICON on the display will be lled in for 3 to 5 seconds and
then go blank.
If you need visual indication of the override on the LCD display, the
controller must have a digital output connected to the sensor’s threepin EXT OVR terminal block, J6.
When appropriate power is connected between the EXT OVR
common and either 5 VDC or 24 VDC/
VAC, both the outline and center of the
HUMAN ICON will be lled in. When the external override is canceled, the HUMAN ICON’S
outline will remain lled in to show that the external override was used.
Human Icon
Filled In
Human Icon
Outline
If power to the sensor is removed, the outline will be blank until the next time the external
override is used. This input is optically isolated from the rest of the device’s circuitry.
“BAPI-Stat 3” JCI Room Sensor
Installation & Operating Instructions
rev. 08/19/1535450_ins_BS3_JCI
Terminal
Name
COMMON
5VDC
24V DC/VAC
Table 2: Override Display Termination Table
This [COMMON] is isolated from the other [GND]
terminal. See Figures 5 & 6 for more details.
ICONON
5VDC
-
+
ICON ON
24VDC
-~N
+
ICON ON
24VAC
~H
Controller Output OPEN
=
Fig. 5: 5VDC Wiring Example
Controller
Digital
EXT OVR Display Input
Optional Communication Jack Wiring
Optional Communication Jack Termination Wiring
Fig. 7: RJ12 JCI Jack
Fig. 8: C35 Jack
Output
5VDC Customer
Power Supply
Table: 3 RJ12 Wiring
Comm Jack Pin Wire Color
1 Black
2 Yellow
3 Green
4 Red
5 Not Connected
6 Not Connected
Table: 4 C35 Female Jack Wiring
Comm Jack Pin Wire Color
Ground Black
Tip White
Ring Red
Note: Male Jack shown for clarity
Controller Output CLOSED (Override) =
Fig. 6: 24VDC/VAC Wiring Example
EXT OVR Display Input
Fig. 9:
View of
BAPI-Stat 3
wallplate
RJ12
Controller
Digital
Output
24DC/AC
Customer
Power Supply
C35
Optional Test & Balance Switch (SW1), For Passive Sensor Ouput Only (Output at Temp+ and Temp- Terminals)
1000 RTD1.02K(41.2°F)1.15K(101.5°F)
3000
Thermistor7.87K(39.8°F)1.50K(106.8°F)
10K-2 Thermistor30.1K
10K-3 Thermistor26.7K
Specications subject to change without notice.
(34.9°F)4.75K(109.1°F)
(35.9°F)5.11K(108.4°F)
4 of 6
“BAPI-Stat 3” JCI Room Sensor
Installation & Operating Instructions
Optional Technician Adjustments
The four DIP switches on the bottom of the board called S1 congure four different parameters (see Fig: 10).
1) Fahrenheit or Celsius temperature display “F/C” Switch.
2) Display Reading Offset “Mode” Switch for temperature and humidity appearance and output offset.
3) User Setpoint Lockout Enable “SPLO” Switch.
4) Passive temperature sensor differential ground or common ground conguration “TEMP” Switch.
ADJUSTMENT PROCEDURE FOR EACH DIP SWITCH IN S1:
°F OR °C DISPLAY SELECTION [F/C Switch]
The “F/C” Switch allows for either °F or °C operation. Remove the cover from the
backplate and set the switch to the desired position.
The Display Reading Offset “Mode” Switch lets you adjust the reading of the BAPIStat display. For example if the display reads 70° but you wish it to display and
send a signal to your controller of 70.5°, you will enter an adjustment of 0.5. If the
display reads 40 %RH and you wish it to display and send a signal to your controller of 38% RH, you will enter -2.0.
1) Remove cover from backplate & slide the “MODE” switch on S1 to the “OFFSET” position.
The screen in gure 11 will appear on the display. If you previously entered an offset, the offset
you entered will show on the display. Either the F or C annunciator will be lit depending on the
position of “F/C” Switch
2) Press the Override button on the front of the sensor to advance to the screen for the parameter
you wish to change.
a. TEMPERATURE OFFSET - Screen P26 (gure 11)
b. HUMIDITY OFFSET - Screen P27 (gure 12)
c. DISPLAY MODE - Screen P28 (gure 13)
d. ACTIVE TEST & BALANCE MODE - Screen P29 (gures 14 & 15)
3) Use the Temperature Setpoint up and down arrows on the front of the sensor to select the
calibration needed.
a. TEMPERATURE OFFSET - Adjust the temperature ± 5°in 0.1° increments
b. HUMIDITY OFFSET - Adjust the humidity ± 5% in 0.1% increments
c. DISPLAY MODE - Adjust to 0 through 7 depending on the display mode you desire.
0 - Temperature in the main portion and %RH in the upper section
1 - %RH in the main portion and Temperature in the upper section
2 - The LCD toggles the locations at a ~5 second rate
3 - Temperature Only.
4 - Setpoint Display Only (SDO), Temp Setpoint in the main portion and %RH Setpoint in
the upper section
5 - Setpoint Display Only (SDO), %RH Setpoint in the main portion and Temp Setpoint in
the upper section
6 - Setpoint Display Only (SDO), The LCD toggles the setpoints between the locations at a
~5 second rate
7 - Setpoint Display Only (SDO), Temperature Setpoint only.
(Note: Selecting options 1, 2, 5 or 6 with units without %RH will default to mode 0)
d. ACTIVE TEST & BALANCE MODE - Setpoint buttons up or down toggles between ‘LO’
and ‘HI’ on the LCD. This mode is active only for models which use Channel 1 as a
temperature output. ‘LO’ will drive Channel 1 to it’s lowest voltage or current output. ‘HI’
will drive Channel 1 to it’s highest voltage or current output. (gures 14 & 15)
4) Press the Override button on the front of the sensor to ‘enter’ and store the change. Set the
“MODE” switch on S1 back to “RUN” and put the cover on the backplate.
Fig. 10: Conguration Switches S1
Fig. 11: Temp Offset
Fig. 12: %RH Offset
Fig. 13: Display Mode
Fig. 14: T&B Mode Lo
rev. 08/19/1535450_ins_BS3_JCI
SETPOINT LOCK OUT [SPLO Switch]
The “SPLO” Switch allows the setpoint buttons to be disabled. A switch setting of “ON” disables the
buttons.
PASSIVE TEMPERATURE SENSOR GROUNDING [TEMP switch]
Adjust DIP switch to “CG” for [TEMP –] connected to common ground [GND]
Adjust DIP switch to “DF” for [TEMP –] differential oating without connection to any ground.
Fig. 15: T&B Mode Hi
5 of 6
Diagnostics
POSSIBLE PROBLEMS
General Diagnostics
“BAPI-Stat 3” JCI Room Sensor
Installation & Operating Instructions
rev. 08/19/1535450_ins_BS3_JCI
POSSIBLE SOLUTIONS:
- Determine that the input is set up correctly in the controller’s and building automation
software.
- Check wiring for proper termination
- Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-strip
the interconnecting wire and reapply the connection. In extreme cases, replace the
controller, interconnecting wire and/or sensor.
- Label the terminals that the interconnecting wires are connected to at the sensor end
and the controller end. Disconnect the interconnecting wires from the controller and the
sensor. With the interconnecting wires separated at both ends measure the resistance
from wire-to-wire with a multimeter. The meter should read greater than 10 Meg-ohms,
open or OL depending on the meter you have. Short the interconnecting wires together
at one end. Go to the other end and measure the resistance from wire-to-wire with a
multimeter. The meter should read less than 10 ohms (22 gauge or larger, 250 feet or
less). If either test fails, replace the wire.
Unit does not operate
- Check power for proper polarity.
- Disconnect the power wires at the controller. Measure controller output for proper
power (see specications), if the voltage is outside the limits troubleshoot controller.
Reconnect power wires to controller when nished. If the measured voltage is above the
specication limit, you may have damaged the unit, contact your BAPI representative.
- Disconnect the power wires at the sensor. Measure the wires for the same voltage
as at controller. If the voltage is different from that measured at the controller, then
troubleshoot the wire. Reconnect power wires to sensor when nished.
- Measure the power at the sensor with the power connected for proper power (see
specications). If the voltage is outside the specication limits, call your BAPI
representative.
Specications subject to change without notice.
6 of 6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.