A14
*
BAPI Room Units Without LCD
Temperature Sensors
Features & Options
l BAPI-Stat 4, BAPI-Stat 2 and Delta Style Enclosures
l Optional Setpoint, Override, Comm. Jack and
Test & Balance Switch
l
Limited Lifetime Warranty
Setpoint & Legend
The optional setpoint is a linear slidepot adjustment that
comes in various ranges, reverse or direct acting. An
optional setpoint legend can be imprinted on the base of
the enclosure. Common Legends include “Cool/Warm”,
“55 to 85” and “5 to 30”.
Override
The optional override is a discreet momentary signal that
can be congured to be compatible with any controller.
Communication Jack
Available with RJ11 (4 pin), RJ12 (6 pin), RJ22 (4 pin) or
a 3.5 mm phono plug style jack.
Test and Balance Switch
A 3-position switch is available to change the sensor
output as follows: “Low” is a cold reading of ≈ 40°F,
“Normal” is the live sensor value, and “High” is a hot
reading of ≈ 105°F.
Rev. 02/24/15
BAPI-Stat 4 (above)
w/ Warm White and
Gray Logo Plates
BAPI-Stat 2
Unit
Delta Style with and
without Bi-Metal Indicator
Specications
Environmental Operation Range:
Temperature: 32 to 122
Humidity: 0 to 95%, non-condensing
Material & Rating: ABS Plastic, UL 94, V-0
Material Color: Warm White
Accuracy:
Standard Thermistor: ±0.2%°C (0 to 70°C)
Standard Plat. RTD: ±0.31%°C (@ 0°C)
Agency: RoHS, *CE (all Thermistors < 20KΩ are CE)
For detailed specications on the individual sensors,
turn to the Sensors section.
Delta Style
Enclosure
(High accuracy available, see ordering grid)
o
F (0 to 50 oC)
BAPI-Stat
4 Style
Enclosure
BAPI-Stat
2 Style
Enclosure
BAPI Room Units Without LCD
Ordering Information BAPI Room Temperature Sensors without Display
THERMISTORS RTDs Thermistors
3.25K
3.25K Ω @ 25 °C (T30 type)
1K
1K Ω Platinum @ 0 °C, 3.85 Ω/°C temp. coeff.
RTD's
3.3K
3.3K Ω @ 25 °C
2K
2K Ω Silicon @ 20 °C, 8 Ω/°C temp. coeff.
$25 Each
10K-2
10K Ω @ 25 °C
or $_______
10K-3
10K Ω @ 25 °C
$35 for 1K[NI]
10K-3[11K]
5,238 Ω @ 25 °C
20K
20K Ω @ 25 °C
334
LM334 Semiconductor Semi-
50K
50K Ω @ 25 °C
592
AD592 Semiconductor, 273 µA @ 0 °C
conductors
100K
100K Ω @ 25 °C
592-10K AD592 Semicond. w/ 10 kΩ shunt resistor, 2.73 V @ 0 °C $25 Each $_______
Enclosure Style (Must select one)
Setpoint If Setpoint is required, must select Range and Legend
SETPOINT OUTPUT VALUE RANGE (insert Designator #) $6 for $_______
Designator Desired Range Designator Setpoint
800 to 1200 Ω 25 15 k to 5 kΩ 61
## 909 to 1309 Ω 26 0 to 20 kΩ 80
2 k to 3 kΩ 42 10 k to 30 kΩ 84
0 to 10 kΩ 60 See App. Notes for other Setpoint Ranges
SETPOINT LEGEND (insert Designator #)
Legend Range Designator Legend Range Designator
-J Override as a Separate Input (Not available with voltage setpoint)
$5 $_______
-N Override in Parallel (//) with Sensor
$5 $_______
-P Override in Parallel (//) with Setpoint (Not available with voltage setpoint)
$5 $_______
-C35 3.5 mm Phono Style Jack $7 $_______
-C11 RJ11 (4 pin) Style Jack $7 $_______
-C12 RJ12 (6 pin) Style Jack $7 $_______
-C22 RJ22 (4 pin) Style Jack $12 $_______
-BM5090
$60 for any
$_______
Connection Configuration Must Select One
-CG Common Ground (Required for voltage setpoint)
Logo Plate Color for BAPI-Stat 4 Only Must select for BAPI-Stat 4
Optional Enclosure Color for BAPI-Stat 2 and Delta Style Only
Special Options Skip if not required
BA/ 10K-2 -B4 25L1 -J -C35 -CG
-WMW
Special order - call for price and availability.
Special order for Delta Style Units - call for price and availability.
Bi-Metal Indicator: 10 to 30 °C
High Accuracy
[XP] or [A]
Options
$10
A15
Rev. 02/24/15
BA/
Sensor Type (Must select one) Use the designator number (shown to the left in bold) to indicate the sensor
1.8K Ω @ 25 °C
3K Ω @ 25 °C
High Accuracy Thermistors (±0.1°C): 3K, 10K-2, 10K-3, 10K-3(11K), 20K & 100K Thermistors are available as high accuracy.
To order, add [XP] after the designator #. Example: BA/10K-2[XP]-B425L1-J-CG
High Accuracy RTDs (±0.156°C): 1K[375], 1K[NI] & 1K RTDs are available as high accuracy.
To order, add [A] after the designator #. Example BA/100[A]-B425L1-J-CG
-B4 BAPI-Stat 4 Style Room Enclosure
-R Delta Style Enclosure
1K Ω Platinum @ 0 °C, 3.75 Ω/°C temp. coeff.
1K Ω Nickel @ 21°C, 5 Ω/°C temp. coeff.
Temperature Sensors
2
5-30 C
55-85 F
60-85 F
Override Configuration Must select one
Optional Communication Jack Skip if not required
EXAMPLE
Example Part Number: BA/10K-2-B425L1-J-C35-CG-WMW
Your Part Number:
¹ The 100[3W] sensor is not available with Setpoint, Override, Communication Jack or Test & Balance switch options.
2
3
Call BAPI if you have questions about the above ordering/pricing grid or the configuration of the product you are ordering.
L1
L2
L4
Optional Bi-Metal Indicator (for Delta Style Enclosure only) Skip if not required
Bi-Metal Indicator: 50 to 90 °F
Optional Test & Balance Skip if not required
3 Position Switch - Low & High values vary, Normal is live sensor value.
2
68-70-72
COOL/WARM
WARM/COOL
No Legend
-WMW Warm White Logo Plate Color (standard)
-GRY Gray Logo Plate Color
-CPW Copla White Color (Warm White is Standard)
L5
L6
L0
-LED Separate Terminal Power
Foamback Insulator for Delta Style
-FOAM
Enclosure (Standard on BAPI-Stat)