BAPI BA/5467(-Z) Catalog Page

BA/5467(-Z)
Installation & Operations
21479_INS_5467-Z
Overview and Indentication
The BA/5467 is a room sensor specically designed to interface with a Siemens controller. It measures the temperature with a 10K Thermistor and has a built in setpoint with a cool/warm legend and an override button. It is connected via an RJ11 connector to the controller and has a built in communication jack under the cover for service connection to the controller communication bus. The BA/5467-Z is identical but without override.
Fig 1: Sensor
Board Face
Fig 2: Sensor
Isometric View
Mounting
JUNCTION BOX INSTRUCTIONS
2. Pull the wire through the hole in the base plate.
3. Secure the base to the box using the #6-32 x 3/4 inch mounting screw provided.
4. Terminate the unit according to the guidelines in Termination.
5. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place.
6. Secure the cover by backing out the lock-down screws using a 1/16” Allen wrench until they are ush with the bottom of the cover.
Controller
Connection
Fig 3: Sensor
Board Side
rev. 11/25/13
Fig 4: Sensor
Board Back View
DRYWALL MOUNTING INSTRUCTIONS
1. Place the base plate against the wall where you want to mount the unit.
2. Using a pencil mark out the two mounting holes and the area where the wires will come through the wall.
3. Drill two 3/16” holes in the center of each marked mounting hole. Insert a drywall anchor into each hole.
4. Drill one 1/2” hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out of the 1/2” hole, leaving about six inches free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
Fig. 5: Delta Enclosure Mounting
Mounting hardware is provided for both
junction box and drywall installation
(junction box installation shown)
8. Terminate the unit according to the guidelines in Termination.
9. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place.
10. Secure the cover by backing out the lock-down screws using a 1/16” Allen wrench.
NOTE: In a wall mount application, the wall temperature and the temperature of the air within the wall cavity can cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and premature failure of the sensor. To prevent these conditions, seal the conduit leading to the junction box and seal the hole in the drywall by using an adhesive backed, foam insulating pad (order part # BA/FOAMBACK-ROOM).
Specications subject to change without notice.
1 of 2
BA/5467(-Z)
Installation & Operations
21479_INS_5467-Z
rev. 11/25/13
Termination
All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as AC power wiring. BAPI’s tests show that uctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are experiencing any of these difculties, please contact your BAPI representative.
Service Tool
Connection
RJ11
Button on
BA/5467 only
Setpoint
Pot
To
Controller
RJ11
Cool Warm
Fig 5: Board Front
Diagnostics
Possible Problems:
Controller reports higher or lower than actual temperature
Specications
Sensor Thermistor, 10K @77ºF Accuracy ±0.36ºF (±0.2ºC) Dissipation 2.7mW/ºC Stability <0.02ºC/First 2 years
<0.1ºC over 10 years
Setpoint (SP) Potentiometer, 5K SP Control Wand at Bottom of Sensor SP Legend Cool/Warm, left to right
Fig 6: Board Side
Fig 7: Board Back
Possible Solutions:
- Conrm the input is set up correctly in the front end software
- Check wiring for proper termination
- Determine if the sensor is exposed to an external source different from room environment (conduit draft)
- Verify the sensor output is correct by comparing the sensor resistance to the appropriate temperature table on the BAPI website at “http://www.bapihvac.com”. Click on “Sensor Specs” on the left menu, then on the appropriate sensor table.
Override Side Pushbutton (BA/5467 Only) Comm. Jack 6 pin RJ11, Under the Cover, Pins 2, 5 & 6 Terminals None Connection 6 pin RJ11, Back Connection
Sensor: Pins 3 & 4 Override Button: Pins 3 & 4
Ambient 32 to 122ºF (0 to 50ºC) 0 to 95% RH Non-condensing
Enclosure ABS Plastic, UL94V-0 Dimensions 2.75"W x 4.5"H x 1"D (89.9 x 114.3 x 25.4 mm) Warranty Lifetime On Passive Sensors
Specications subject to change without notice.
2 of 2