Balluff COBALT-01 Usr Manual

CHAPTER 5: RFID TAGS
CHAPTER 5: RFID TAGS
RFID tags, which are also referred to as transponders, smart labels, or
inlays, come in a variety of sizes, memory capacities, read ranges,
frequencies, temperature survivability ranges and physical
Escort Memory Systems offers many different RFID tag models. Cobalt Controllers are capable of reading all Escort Memory Systems’ HMS
and LRP series RFID tags as well most of those produced by other
manufacturers. Our patented tags can be read through obstructions
such as water, wood, plastic and more. Our specialty high-temperature
(HT) models are capable of surviving temperatures of 415° F.
5.1 RFID STANDARDS
It is important to note that not all 13.56MHz RFID tags are compatible with Cobalt Controllers and even tags that are said to be compliant with ISO15693 or ISO14443 standards may not actually be compatible with RFID controllers adhering to the same standards. This is partially due to the fact that these ISO standards are so new that they leave many features open to the discretion and interpretation of the RFID equipment manufacturer to implement or define. When using another manufacturer’s tags, ensure compatibility of those tags with your RFID system provider.
5.1.1 ISO 14443A/B
RFID integrated circuits (ICs) designed to meet ISO 14443A and/or ISO 14443B standards were originally intended to be embedded in secure smart cards such as credit cards, passports, bus passes, ski lift tickets, etc. For this reason, there are many security authentication measures implemented within the air protocol between the RFID controller and the tag.
ISO 14443A/B compliant tags and controllers incorporate security authentication through the exchanging of software “keys.” The RFID controller and the tag must use the same security keys to authenticate communication before the transfer of data will begin. The Cobalt Controller’s operating system manages these security features, making their existence transparent to the user. However, it is important to understand the implications associated with ISO 14443 when using another manufacturer’s RFID tags. Because of these security “features,” an ISO 14443 tag made by one manufacturer may not necessarily be readable by a Cobalt Controller and, likewise, an Escort Memory Systems ISO 14443 compliant tag might not be readable by another manufacturer’s RFID controller. The Cobalt Controllers support Escort Memory Systems’ security keys for use on Philips mifare ISO 14443A tags.
Escort Memory Systems was one of the first companies to adopt ISO 14443 standards and has incorporated much of the technology into our products designed for industrial automation applications. But because most industrial environments do not require the same level of security that monetary or passport applications necessitate, some features have not been implemented in the Cobalt HF product line.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 51 OF 116
5.1.2 ISO 15693
ISO 15693 was established at a time when the RFID industry identified that the lack of standards was preventing the market from growing. Philips Semiconductor and Texas Instruments were, at that time, the major manufacturers producing RFID ICs for the Industrial, Scientific, and Medical (ISM) own unique protocol and modulation algorithm. Philips Semiconductor’s I-CODE® and Texas Instruments Tag-it® product lines were eventually standardized on the mutually compatible ISO 15693 standards. After the decision was made to standardize, the door was opened for other silicon manufacturers to enter the RFID business, many of which have since contributed to other RFID ISO definitions. This healthy competition has led to rapid growth in the RFID industry and has pushed the development of new standards, such as ISO 18000 for Electronic Product Code (EPC) applications.
5.1.3 ISO 18000-3.1
The ISO 18000 standard has not been implemented in the Cobalt HF product line at the time of publication of this manual. It is a planned product enhancement for future releases. The emerging ISO 18000 Standard will provide enhanced support for EPC and Unique Identification (UID) tag applications.
CHAPTER 5: RFID TAGS
frequency of 13.56MHz. However, each had their
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 52 OF 116
CHAPTER 5: RFID TAGS
5.2 RFID TAG COMPATIBILITY
The following RFID tags are compatible with the Cobalt HF Controller:
5.2.1 HMS Series RFID Tags
Integrated Circuits (ICs) used in Escort Memory Systems’ HMS-Series RFID tags include:
x Philips mifare Classic, 1 kilobyte (KB) + 32-bit Tag ID (ISO 14443A). One KB is
the total memory in the IC. Of this memory, 736 bytes are available for user data.
x Philips mifare Classic, 4 KB + 32-bit Tag ID (ISO 14443A). Four KB is the total
memory in the IC. Of this memory, 3,440 bytes are available for user data.
Figure 5-1: HMS125HT and HMS150HT RFID Tags
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 53 OF 116
CHAPTER 5: RFID TAGS
5.2.2 LRP Series RFID Tags
ICs used in Escort Memory Systems’ LRP-Series RFID tags include:
x Philips I•CODE 1, 48-byte + 64-bit Tag ID
x Philips I•CODE SLi, 112-byte + 64-bit Tag ID (ISO 15693)
x Texas Instruments Tag-it, 32-byte + 64-bit Tag ID (ISO 15693)
x Infineon My-D Vicinity, 1kb + 64-bit Tag ID (ISO 15693)
Figure 5-2: LRP125 and LRP250 RFID Tags
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 54 OF 116
CHAPTER 5: RFID TAGS
5.3 RFID TAG PERFORMANCE
Many factors can affect the performance between the controller’s antenna and the tag’s antenna. These include, but are not limited to: the tag integrated circuit (IC), the antenna coil design, the antenna conductor material, the antenna coil substrate, the bonding method between tag IC antenna coil, and the embodiment material.
Additionally, the mounting environment of the tag and controller can hinder performance due to other materials affecting the tuning of either antenna. Escort Memory Systems has undergone extensive testing to produce tags that obtain optimum performance with our RFID controllers. In most cases, optimal range will be obtained when mounting the tag and controller antenna in locations free from the influence of metals, ESD and EMI emitting devices.
5.4 RFID TAG EMBODIMENTS
RFID tags come in a variety of sizes and packages. The most common and cost effective tag embodiment is the RFID label.
5.4.1 RFID Labels
RFID Labels (inlays or inlets) are the lowest cost RFID tag solution and are typically used in an open system in which the tag leaves the facility attached to a product or is destroyed at the end of the process.
An inlay is a substrate (made of polyester or Mylar) with a printed, screened or etched antenna coil. Sometimes the coil consists of a wire that is laid down onto the substrate and is bonded to it with heat. Typically, the RFID IC is attached by means of flip-chip technology and the electrical connections are made by means of conductive epoxies.
RFID inlays are usually applied to sticker backed paper to create label tags which are manufactured in high volumes on roll-to-roll production equipment. Inlays can be laminated an used in smart credit cards, providing a low cost RFID tag with some protection from impact damage.
The materials and procedures used to manufacture an RFID label’s antenna coil are critically important. Low cost processes (such as printing or screening) produce low quality antenna coils which can exhibit poor conductivity and cracking when flexed.
Labels with copper wire wound coils are generally considered efficient conductors of RF energy and can usually survive considerable flexing, but are often more expensive due to more involved production processes.
RFID labels with etched copper antenna coils have been found to be the most reliable, semi-low cost tag solution. Etched inlay antenna coils are usually of consistent quality and can survive a great deal of flexing and bending. However, because etching is inherently a subtractive process, the cost per tag increases in part due to copper and other metals discarded during the fabrication process.
As RFID label manufacturing technology advances, there have been several new developments made in the areas of high volume, low cost, antenna coil manufacturing.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 55 OF 116
CHAPTER 5: RFID TAGS
One area, in particular, that has shown recent promise is the process of electroplating printed or screened antenna coils with an additional layer of copper to improve durability and conductivity.
5.4.2 Printed Circuit Board RFID Tags
RFID tags that incorporate Printed Circuit Board (PCB) technology are designed for encasement inside totes, pallets, or products that can provide the protection normally associated with injection-molded enclosures.
These tags are made primarily from etched copper PCB materials (FR-4, for example) and are die bonded by means of high quality wire bonding. This procedure ensures reliable electrical connections that are superior to flip-chip assembly methods. The RFID tag’s integrated circuit is then encapsulated in epoxy to protect it and the electrical connections.
5.4.3 Molded RFID Tags
Molded tags, which are PCB tags that have been protected with a durable resin overmolding, are the most rugged and reliable type of tag offered by Escort Memory Systems. These tags are designed for
closed loop applications where the tag is reused; thereby the cost of the tag can be amortized over the life of the production line.
Typically, molded tags will be mounted to a pallet or carrier which transports the product throughout the production process. Some of the applications for these tags include, but are not limited to: embedding the tag into concrete floors for location identification by forklifts and automatically guided vehicles (AGVs), shelf identification for storage and retrieval systems, and tool identification.
High temperature (HT) tags, using patented processes and specialized materials, allow tags to survive elevated temperatures, such as those found in automotive paint and plating applications. Escort Memory Systems offers a wide variety of molded tags that have been developed over the years for real world applications.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 56 OF 116
5.5 TAG M EMORY
Tag memory addressing begins at address 00 (0x0000), with the highest addressable memory location equal to one less than the total number of bytes in the tag. Each address is equal to one byte (8-bits), where the byte is the smallest addressable unit of data. So for example, writing 8-bytes to a tag beginning at address 00 will actually fill addresses 00 through 07 with 64-bits of data in all.
Depending on the manufacturer, RFID labels, molded tags and embedded PCBs can have differing memory storage capacities blocks of bytes that can vary in structure from manufacturer to manufacturer. Even when compliant to ISO standards, byte memory addressing can differ from one manufacturer to another. For example, tag memory can be organized in blocks of 4 or 8 bytes, depending on the RFID IC. Additionally, all bytes may not be available for data storage as some bytes may be used for security and access conditions. For more information regarding a specific RFID tag’s memory allocation, please refer to IC manufacturer’s published datasheet or Website.
Escort Memory Systems has taken great care to simplify tag memory addressing. The mapping from logical address to physical address is handled by the Cobalt Controller’s operating system. Users only need to indicate the starting address location on the tag and the number of bytes to be read or written.
CHAPTER 5: RFID TAGS
and organization. Tag memory is grouped into
Is it a Bit or a Byte?
Customers need to understand that there are some RFID tag manufacturers that measure and specify their tag memory size by the total number of bits, as this method generates a much larger (8X) overall number. Escort Memory Systems, on the other hand, prefers to specify total tag memory size in terms of bytes (rather than in bits), as this method more closely reflects how data is stored and retrieved from a tag and is typically what users really want to know.
5.5.1 Mapping Tag Memory
Creating an RFID Tag Memory Map
Creating a Tag Memory Map is much like creating a spreadsheet that outlines the actual data you plan to capture as well as the specific tag memory locations in which you wish to store said data. Tag Memory maps should be carefully planned, simple and straightforward. It is advisable to allow additional memory space than is initially required as inevitably a need will arise to store more data.
In the example below, 90-bytes of a 112-byte tag have been allocated to areas of the Memory Map (leaving roughly 20% free for future uses). Because a short paragraph of alphanumeric characters could quickly use all 90 bytes, creating an efficient mapping scheme which utilizes all 720-bits (out of the 90-bytes allocated) will provide a better use of tag space.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 57 OF 116
CHAPTER 5: RFID TAGS
TAG M EMORY M AP E XAMPLE
TAG ADDRESS USAGE
00 – 15
16 - 47
48 - 63
64 - 71
72 - 89
90 - 111
Serial #
Model #
Production Date
Lot #
Factory ID
Reserved for Future Use
Table 5-1: Tag Memory Map Example
5.5.2 Tag Memory Optimization
Data stored in tag memory is always written in binary (1’s and 0’s). Binary values are notated using the hexadecimal numbering system (otherwise it might be confusing viewing a page full of 1’s and 0’s).
Below is an example of how hexadecimal notation is used to simplify the process of expressing the decimal number 52,882.
Decimal Binary Hexadecimal
52,882 1100 1110 1001 0010 CE92
Rather than using five bytes to store the five individual ASCII characters representing the numerical values 5, 2, 8, 8, and 2 (ASCII bytes: 0x35, 0x32, 0x38, 0x38 and 0x32), by simply writing two Hex bytes (0xCE and 0x92), 60% less tag memory is required to store the same amount of information.
When an alphabetical character is to be written to a tag, the Hex equivalent of the ASCII value is written to the tag. So for example, to write a capital “D” (ASCII value 0x44), the Hex value 0x44 is written to the tag.
Additionally, if a database with look up values is used in the RFID application, the logic level of the individual bits within the tag can be used to further maximize tag memory.
(Note: refer to
Appendix D
in this document for a chart of ASCII characters, their
corresponding Hex values and their decimal value equivalents).
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 58 OF 116
CHAPTER 5: RFID TAGS
O PTIMIZING THE T AG
The following example illustrates how a single byte (8 bits) can be used to track an automobile’s inspection history at eight inspection stations. The number one (1) represents a required operation and the number zero (0) represents an operation that is not required for a particular vehicle.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 59 OF 116
CHAPTER 6: COMMAND PROTOCOLS
CHAPTER 6: COMMAND PROTOCOLS
6.1 COMMAND P ROTOCOL O VERVIEW
In order to correctly recognize and execute commands, the Cobalt HF and the host must be able to communicate using the same language. The language that is used to communicate is referred to as the Command Protocol.
There are two Command Protocols used by Cobalt HF RFID Controllers.
x ABx Fast Command Protocol
(-232, -422 and –USB models).
x CBx Command Protocol
drop (Subnet16) networks and Industrial Ethernet applications (-485 and –IND models).
These two Command Protocols have different packet structures and parameter settings, which are explained later in this chapter.
– for Point-to-Point, Host/Controller applications
– for multiple RFID controller configurations, Multi-
6.2 ABX F AST C OMMAND P ROTOCOL
The command protocol used by the Cobalt HF -232, -422 and -USB Controllers for Point­to-Point data transmission is known as the ABx Fast Command Protocol. ABx Fast has a single-byte oriented packet structure that permits the rapid execution of RFID commands while requiring the transfer of a minimal number of bytes.
ABx Fast supports the inclusion of an optional checksum byte. By default, the HF-CNTL­232, -422 and -USB controllers are configured to use ABx Fast without the checksum option. However, when increased data integrity is required, the checksum should be utilized. See Section 6.2.4 for more on using the checksum parameter.
6.2.1 ABx Fast - Command / Response Procedure
After an RFID command is issued by the host, a packet of data, called the “Command Packet” is sent to the Cobalt Controller. The command packet contains information that
instructs the controller to perform a certain task.
The Cobalt Controller automatically parses the incoming data packet, searching for a specific pair of start characters, known as the “Command Header.” (Note: in ABx Fast, the Command Header / Start Characters are 0x02, 0x02). When a Command Header is recognized, the controller then checks for proper formatting and the presence of a Terminator byte. (Note: in ABx Fast, the Terminator byte is 0x03).
Having identified a valid command, the controller will attempt to execute the instructions, after which it will generate a host-bound response message containing EITHER the results of the attempted command or an error code if the operation failed.
All commands will generate a response from the controller. Before sending another command, the host must first process (remove from memory) any pending response data.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 60 OF 116
CHAPTER 6: COMMAND PROTOCOLS
6.2.2 ABx Fast - Command Packet Structure
The packet structure of every ABx Fast command contains certain basic elements, including a Command Header, a number of command parameters and a Terminator.
COMMAND PACKET PARAMETER CONTENT SIZE
COMMAND HEADER:
The first two bytes of an ABx Fast Command Packet:
COMMAND SIZE:
This 2-byte value defines the number of bytes in the packet (excluding Header, Command Size, Checksum and Terminator).
COMMAND ID:
This single-byte value indicates the RFID command to execute.
START ADDRESS:
The 2-byte Start Address parameter indicates the location of tag memory where a read or write operation shall begin.
READ/WRITE LENGTH:
The 2-byte Read/Write Length parameter represents the number of bytes that are to be retrieved from or written to the RFID tag.
TIMEOUT VALUE:
This 2-byte integer indicates the maximum length of time for which the controller will attempt to complete the command. Measured in milliseconds, this value can have a range of 0x0001 to 0xFFFE or between 1 and 65,534 msecs (0x07D0 = 2000 x .001 = 2 seconds).
0x02, 0x02 2 bytes
0x0008
2-byte integer
0x06
1 byte
(Write Data)
0x0000
2-byte integer
0x0001
2-byte integer
0x07D0
2-byte integer
ADDITIONAL DATA:
This parameter uses one byte to hold a single character for fill operations and supports the use of multiple bytes when several characters are needed for write commands (when applicable).
CHECKSUM:
This optional parameter holds a single-byte checksum (only applicable when using ABx Fast with Checksum).
TERMINATOR:
0x00
One or more bytes (when applicable)
optional
1 byte (when applicable)
0x03 1 byte
Single-byte command packet terminator:
Table 6-1: ABx Fast - Command Packet Structure
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 61 OF 116
CHAPTER 6: COMMAND PROTOCOLS
6.2.3 ABx Fast - Response Packet Structure
After performing a command, the Cobalt HF will generate a host-bound response message. ABx Fast responses contain a Response Header, a number of response values (or retrieved data bytes), and a Terminator.
RESPONSE PACKET PARAMETER CONTENT SIZE
RESPONSE HEADER:
The first two bytes of an ABx Fast response packet.
RESPONSE SIZE:
This 2-byte integer defines the total number of bytes in the response packet (excluding Header, Response Size, Checksum and Terminator).
COMMAND ECHO:
The single-byte Command Echo parameter reiterates the Hex value of the command for which the response packet was generated.
RETRIEVED DATA:
This parameter is used to hold one or more bytes of data that was requested by the command (when applicable).
CHECKSUM:
This optional parameter holds a single-byte checksum (only applicable when using ABx Fast with Checksum).
0x02, 0x02 2 bytes
0x0001 2-byte integer
0x06 1 byte
Data
1 or more bytes (when applicable)
Optional
1 byte (when applicable)
TERMINATOR:
0x03 1 byte
Single-byte response packet terminator:
Table 6-2: ABx Fast - Response Packet Structure
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 62 OF 116
CHAPTER 6: COMMAND PROTOCOLS
6.2.4 ABx Fast - Command Packet Parameters
C OMMAND S IZE
Command Size = number
of bytes in these fields
The ABx Fast protocol requires that the byte count, known as the
Command Size
, be specified as a 2-byte integer. To calculate Command Size, add the total number of bytes within the command packet while excluding the two bytes for the Header, the two bytes for the Command Size, the one byte for the Checksum (if present) and the one byte for the Terminator (see example below).
PACKET PARAMETER
Header
Command Size
Command ID
Start Address
Read/Write Length
Timeout Value
Additional Data Bytes
Checksum
Terminator
# OF BYTES
INCLUDED IN COMMAND SIZE?
2 No
2 No
1 Yes
2 Yes
2 Yes
2 Yes
1 Yes
1 No
1 No
In the above command packet example, 8 bytes of data are located between the Command Size parameter and the Checksum parameter. Therefore, the Command Size for this example is 0x0008.
TART A DDRESS
S
The Start Address parameter is holds a two-byte integer representing the tag memory address location where a read or write operation will begin.
EAD/WRITE LENGTH
R
The two-byte Read/Write Length parameter indicates the number of bytes that are to be read from or written to the RFID tag.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 63 OF 116
CHAPTER 6: COMMAND PROTOCOLS
T IMEOUT V ALUE PARAMETER
ABx Fast commands include a two-byte Timeout Value parameter (measured in increments of one millisecond) that is used to limit the length of time that the Cobalt HF will attempt to complete a specified operation.
The maximum Timeout Value is 0xFFFE or 65,534 milliseconds (slightly longer than one minute). Setting a long Timeout Value does not necessarily mean that a command will take any longer to execute. This value only represents the period of time for which the Cobalt HF will attempt execution of the command.
IMPORTANT
During write commands, the tag must remain within the antenna’s RF field until the write operation completes successfully, or until the Timeout Value has expired.
If a write operation is not completed before the tag leaves the controller’s RF field, data may be incompletely written.
C HECKSUM P ARAMETER
The ABx Fast Command Protocol supports the inclusion of an additional checksum byte that is used to verify the integrity of data being transmitted between host and controller.
The checksum is calculated by adding together (summing) the byte values in the command packet (less the Header, Checksum and Terminator parameters), and then subtracting the total byte sum from 0xFF. Therefore, when the byte values of each parameter (from Command Size to Checksum) are added together, the byte value sum will equal 0xFF.
To enable the use of the checksum parameter, download the RFID Dashboard Utility
www.ems-rfid.com
from
, and use it to set the ABx Protocol parameter to ABx Fast with
Checksum.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 64 OF 116
CHAPTER 6: COMMAND PROTOCOLS
C HECKSUM E XAMPLE
The following example depicts Command 0x05 (Read Data) using a checksum.
Checksum = [0xFF – (sum of these fields)]
Add the byte values from the Command Size, Command ID, Start Address, Read Length and Timeout Value parameters together and subtract from 0xFF. Resulting value will be the checksum.
COMMAND
CONTENTS USED IN CHECKSUM
PARAMETER
Header 0x02, 0x02 n/a
Command Size 0x0007 0x00, 0x07
Command ID 0x05 0x05
Start Address 0x0001 0x00, 0x01
Read Length 0x0004 0x00, 0x04
Timeout Value 0x07D0 0x07, 0xD0
Checksum
0x17
n/a
Terminator 0x03 n/a
[0x07
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 65 OF 116
+ 0x05 + 0x01 + 0x04 + 0x07 + 0xD0] = 0xE8
The checksum equation is: [0xFF
– 0xE8] = 0x17
CHAPTER 6: COMMAND PROTOCOLS
6.3 CBX C OMMAND P ROTOCOL
The CBx Command Protocol, utilized by the Cobalt -485 and -IND models, includes Multi-drop Subnet16 networking support for use with Industrial Ethernet applications.
CBx is based on a double-byte oriented packet structure where commands always contain a minimum of six data “words,” even when one (or more) parameters are not applicable to the command. CBx does not support the inclusion of a checksum byte.
The CBx packet structures described herein are protocol independent and can be implemented the same for all Industrial Ethernet protocols (Ethernet/IP, Modbus TCP, etc.).
6.3.1 CBx – Command Procedure
C OBALT HF-CNTL-485-01 – COMMAND P ROCEDURE
Commands are initiated by a host PC or Programmable Logic Controller (PLC) and are distributed to the controller via a Subnet16 Gateway or Subnet16 Hub Interface Device that is connected to the host or PLC by standard Ethernet cabling.
After a command is sent, it is executed either directly by the interface device (Gateway or Hub) or is otherwise routed to the RFID controller specified in the command. Note that when issuing controller-bound commands, instructions are directed to the appropriate RFID controller by specifying the “Node ID Number” of the particular controller. Each Cobalt -485 Controller on a Multi-drop Subnet16 network is assigned an individual Node ID number.
OBALT HF-CNTL-IND-01 – COMMAND P ROCEDURE
C
Commands are initiated by a host PC or Programmable Logic Controller (PLC) and are distributed directly to the controller via an M12 D-Code to Ethernet cable.
After a command is sent, it is immediately executed by the Cobalt Controller. Note that instructions are directed to the controller by specifying in the command the “Node ID Number” of the Cobalt Controller. For the Cobalt HF-CNTL-IND-01, the Node ID will always be 01 (0x01).
6.3.2 CBx – Response Procedure
Following the execution of an RFID command, the controller will automatically generate a host-bound response message that contains EITHER the results of the attempted command or an error code if the operation could no be completed successfully.
Similar to ABx Fast, all CBx commands will generate a response from the controller. Before the host can send another command to the controller, it must first process (remove from memory) the controller’s pending response data.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 66 OF 116
CHAPTER 6: COMMAND PROTOCOLS
6.3.3 CBx - Command Packet Structure
As noted, CBx commands contain a minimum of six words. Below is the structure of a standard CBx command packet. For the Cobalt HF-CNTL-485-01 model, refer to the Subnet16 Gateway or Subnet16 Hub - Operator’s Manuals.
WORD#COMMAND PACKET PARAMETER MSB LSB
01
02
03
04
05
Overall Length: 2-byte integer indicating the number
of 16-bit “words” in the entire command packet. This value will always be at least 6, as each command has a minimum of 12-bytes (or 6 words). Overall Length will increase when additional data words are used in the command (for fills, writes, etc.).
AA in MSB
Command ID: single-byte value indicating command
to perform in LSB.
00 in MSB
Node ID: single-byte Node ID number of the controller
to which the command is intended. (Must be 0x01 for Cobalt -IND).
Timeout Value: 2-byte integer representing the length of time allowed for the completion of the command, measured in 1 millisecond units (when applicable).
Start Address: 2-byte integer indicating the location of tag memory where the Read/Write operation will begin (when applicable).
0x00
0x06 + (number of additional data words, if any)
0xAA Command ID
0x00 0x01
Timeout
Timeout LSB
MSB
Start MSB Start LSB
06
Read/Write Length: 2-byte integer indicating the
number of bytes that are to be Read/Written beginning
Length MSB
Length LSB
at the Start Address (when applicable).
07
Additional Data – (bytes 1 & 2) used to hold 2-bytes
D1 D2
of data used for writes and fills (when applicable).
08
Additional Data – (bytes 3 & 4): used to hold 2-bytes
D3 D4
of data for writes and fills (when applicable).
Table 6-3: CBx - Command Packet Structure
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 67 OF 116
CHAPTER 6: COMMAND PROTOCOLS
6.3.4 CBx - Response Packet Structure
After performing a command, the Cobalt HF RFID Controller will issue a host-bound response message. Below is the packet structure of a standard CBx response message.
WORD#RESPONSE PACKET
PARAMETER
01
Overall Length: 2-byte value indicating the
number of “words” in the response packet. This value will always be at least 6 words.
02
AA in MSB
Command Echo: single-byte value
indicating the command that was performed in LSB.
03
Instance Counter in MSB
(see description below)
Node ID Echo in LSB (will be 0x01 for the Cobalt -IND)
04
05
06
Month and Day timestamp Month DOM
Hour and Minute timestamp Hour Minutes
Second timestamp in MSB
MSB LSB
0x00
06 + (number of additional data words retrieved)
0xAA Command Echo
Instance
Node ID Echo
Counter
Seconds N-bytes
Number of Additional Data Bytes Retrieved in LSB
07
Retrieved Data – (bytes 1 & 2) used to hold
D1 D2
2-bytes of retrieved data (when applicable).
08
Retrieved Data – (bytes 3 & 4) used to hold
D3 D4
2-bytes of retrieved data (when applicable).
Table 6-4: CBx - Response Packet Structure
I
NSTANCE COUNTER
The Instance Counter is a one-byte value used by a Subnet16 Gateway or Subnet16 Hub to track the number of responses generated by a given Node ID number. The Gateway/Hub tallies in its internal RAM separate Instance Counter values for each Node ID. The Instance Counter value is incremented by one following each response. If, for example, 10 responses were generated by the controller assigned Node ID 01, its Instance Counter value will read 10. When the Gateway/Hub is power cycled or rebooted, all Instance Counter values will be reset to zero (0x00).
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 68 OF 116
CHAPTER 6: COMMAND PROTOCOLS
6.3.5 CBx - Command Example
In the example below, Command 0x05 (Read Data) is issued to the Cobalt Controller assigned to Node ID 01. The controller will be instructed to read 4 bytes of data from a tag beginning at tag address 0x20. The Timeout Value has been set to two seconds for the completion of this command (0x07D0 = 2000 x .001 = 2 seconds).
WORD # DESCRIPTION MSB LSB
01 Overall Length of Command
02 AA
03 00
04
05
in MSB
Command ID
in MSB
Node ID
2-byte
2-byte
in LSB: (0x01 for the Cobalt)
Timeout Value
Start Address
in LSB: (0x05: Read Data)
measured in ms
for the Read
Operation: (0x0020)
06
2-byte
Read Length
: (0x0004)
6.3.6 CBx - Response Example
Below is an example of a typical controller response after successfully executing the Read Data command (as issued in the previous example).
WORD # DESCRIPTION MSB LSB
01 Overall Length of Response
(in words)
02 AA
in MSB
Command Echo
(0x05 Read Data)
in LSB:
(in words)
0x00 0x06
0xAA 0x05
0x00 0x01
0x07 0xD0
0x00 0x20
0x00 0x04
0x00 0x08
0xAA 0x05
03 00
in MSB
Node ID Echo
04 Month
(March 19
05 Hour
and
and
in LSB
Day
th
)
Minute
timestamp:
timestamp
0x00 0x01
0x03 0x13
0x0A 0x0B
(10:11: AM)
06 Seconds
timestamp in MSB
0x24 0x04
(:36 seconds)
# of Additional Data Bytes Retrieved
07 Retrieved Data
08 Retrieved Data
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 69 OF 116
in LSB: (0x04)
(bytes 1 & 2)
(bytes 3 & 4)
0x01 0x02
0x03 0x04
CHAPTER 7: RFID COMMANDS
CHAPTER 7: RFID COMMANDS
Most RFID commands can be divided into two primary categories: READ and WRITE. Read commands retrieve data from a tag or obtain information from the controller. Write commands transfer information to a tag or update settings on the controller.
7.1 RFID COMMANDS TABLE
COMMAND ID
0x04
0x05
0x06
0x07
0x08
0x0D
0x35
0x38
COMMAND DESCRIPTION
Fill Tag
Read Data
Write Data
Read Tag ID
Tag Search
Start/Stop Continuous Read
Reset Controller
Get Controller Info
Writes a specified data byte to all defined tag addresses.
Reads a specified length of data from contiguous (sequential) areas of tag memory.
Writes a specified number of bytes to a contiguous area of tag memory.
Reads a tag’s unique tag ID number.
Instructs the controller to search for a tag in its RF field.
Instructs the controller to start or stop Continuous Read mode.
Resets power to the controller.
Reads hardware, firmware and serial number information from the controller.
Table 7-1: RFID Commands Table
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 70 OF 116
COMMAND 04: FILL TAG
Command 04 instructs the RFID controller to fill multiple contiguous addresses of an RFID tag with a single data byte value. This command is commonly used to clear sequential segments of tag memory by writing a one-byte value repeatedly across a specified range of tag addresses.
This command requires one Data Byte Value, a Start Address and a Fill Length. It will then proceed to fill the tag with the Data Byte Value, for the specified number of consecutive bytes, beginning at the Start Address.
When the Start Address is set to zero (0x0000), the fill will begin at the first available byte of tag memory. When the Fill Length is set to zero (0x0000), the controller will write fill data from the Start Address to the end of the tag’s memory. The Timeout Value is measured in 1-millisecond increments and can have a value of 0x0001 to 0xFFFE (1 ­65,534 milliseconds). If the Fill Length extends beyond the last byte in the tag, the controller will return an error.
OMMAND 04 (FILL TAG)-ABX F AST C OMMAND S TRUCTURE
C
CHAPTER 7: RFID COMMANDS
PARAMETER FIELD
Header
Command Size
Command ID
Start Address
Fill Length
Timeout Value
Data Byte Value
Checksum
Terminator
CONTENT
0x02, 0x02 (the header for all ABx Fast commands).
0x0008
1-byte Command ID Number (0x04).
2-byte value indicating tag address where fill will start.
2-byte value indicating the total number of bytes to be filled.
2-byte value (0x0001 – 0xFFFE).
1-byte value for the data byte to be used as fill.
Optional
0x03 (the terminator for all ABx Fast commands).
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 71 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 04 (FILL TAG)-ABX FAST C OMMAND E XAMPLE
This example instructs the Cobalt HF to fill an entire tag with the ASCII character 'A' (Data Byte Value 0x41) starting at the beginning of the tag (address 0x0000). A Timeout Value of 2 seconds (0x07D0) is set for the completion of the command.
Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
Command ID
Start Address
Fill Length
Timeout Value
Data Byte Value
Checksum
Terminator
0x02, 0x02
0x0008
0x04
0x0000
0x0000
0x07D0
0x41
Optional
0x03
Response from Controller
PARAMETER FIELD CONTENT
Header
Response Size
Command Echo
Checksum
0x02, 0x02
0x0001
0x04
Optional
Terminator
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 72 OF 116
0x03
CHAPTER 7: RFID COMMANDS
C OMMAND 04 (FILL TAG)-CBX C OMMAND E XAMPLE
This example instructs the Cobalt Controller to fill an entire tag with the ASCII character 'A' (Data Byte Value 0x41) starting at the beginning of the tag (address 0x0000). A Timeout Value of 2 seconds (0x07D0) is set for the completion of the command.
Command from Host
PARAMETER FIELD MSB LSB
Overall Length of Command
0x00 0x07
(in words)
in MSB
AA Command ID
in MSB
00 Node ID
2-byte
in LSB (Cobalt –IND = 01)
Timeout Value
in LSB: (0x04)
measured in
0xAA
0x04
0x00 0x01
0x07 0xD0
ms (0x07D0 = 2 seconds)
Start Address
Fill Length
Fill Byte 00
in MSB (A = 0x41)
in LSB
0x00 0x00
0x00 0x00
0x41 0x00
Note: The “Fill Length” in the Tag Fill Command represents the number of bytes to fill on the tag, not the length of the ‘fill byte data’ provided in the command, which is always just a single byte.
Response from Controller
DESCRIPTION MSB LSB
Overall Length of Response
0x00 0x06
(in words)
in MSB
AA Command Echo
in MSB
00 Node ID Echo
in LSB
in LSB (0x04)
0xAA
0x04
0x00 0x01
(Cobalt –IND = 0x01)
Month
Hour
and
and
Minute
Seconds
in LSB
00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 73 OF 116
timestamp
Day
timestamp
timestamp in MSB
Month DOM
Hour Minutes
Seconds 0x00
COMMAND 05: READ DATA
Command 05 instructs the controller to retrieve a specific number of bytes of data from a contiguous (sequential) area of an RFID tag’s memory.
When the Start Address is set to zero (0x0000), the controller will start reading at the beginning (or first accessible byte) of the tag. The minimum Read Length is one byte, the maximum is the entire read/write address space of the tag. Timeout Value is measured in 1-millisecond increments and can have a value of 0x0001 to 0xFFFE (1 to 65,534 milliseconds). If the Read Length exceeds beyond the last available tag address, the controller will return an error code.
OMMAND 05 (READ DATA )-ABX F AST C OMMAND S TRUCTURE
C
PARAMETER FIELD CONTENT
CHAPTER 7: RFID COMMANDS
Header
Command Size
Command ID
Start Address
Read Length
Timeout Value
Checksum
Terminator
0x02, 0x02
0x0007
1-byte Command ID (0x05).
2-byte value for the starting read address.
2-byte value for the number of bytes to read.
2-byte value measured in 1-ms units (0x0001 – 0xFFFE).
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 74 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 05 (READ D ATA)-ABX FAST C OMMAND E XAMPLE
This example instructs the controller to read four bytes of data from a tag starting at address 0x0001. A Timeout Value of 2 seconds (0x07D0 = 2000 x 1 millisecond increments) is set for the completion of the command.
Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
Command ID
Start Address
Read Length
Timeout Value
Checksum
Terminator
0x02, 0x02
0x0007
0x05
0x0001
0x0004
0x07D0
Optional
0x03
Response from Controller
PARAMETER FIELD CONTENT
Header
Response Size
Command Echo
Data from Address 0x0001
Data from Address 0x0002
0x02, 0x02
0x0005
0x05
0x05
0xAA
Data from Address 0x0003
Data from Address 0x0004
Checksum
Terminator
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 75 OF 116
0xE7
0x0A
Optional
0x03
CHAPTER 7: RFID COMMANDS
C OMMAND 05 (READ D ATA)-CBX C OMMAND E XAMPLE
This example instructs the controller to read four bytes of data from a tag starting at address 0x0001. A Timeout Value of 2 seconds (0x07D0 = 2000 x 1 millisecond increments) is set for the completion of the command.
Command from Host
PARAMETER FIELD MSB LSB
Overall Length of Command
in MSB
AA Command ID
in MSB
0x00 Node ID
2-byte
Timeout Value
in LSB (0x05)
in LSB (Cobalt -IND = 0x01)
measured in ms
(in words)
0x00 0x06
0xAA
0x05
0x00 0x01
0x07 0xD0
(0x07D0 = 2 seconds)
Start Address
Read Length
0x00 0x01
0x00 0x04
Response from Controller
PARAMETER FIELD MSB LSB
Overall Length of Response
in MSB
AA Command Echo
in MSB
00 Node ID Echo
in LSB
in LSB
(in words)
0x00 0x08
0xAA
0x05
0x00 0x01
Month
Hour
and
and
Seconds # of Bytes Read Data
Read Data
Read Data
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 76 OF 116
timestamp
Day
Minute
timestamp
timestamp in MSB
in LSB
(bytes 1 and 2)
(bytes 3 and 4)
Month DOM
Hour Minutes
Seconds 0x04
0x01 0x02
0x03 0x04
COMMAND 06: WRITE DATA
Command 06 instructs the controller to write information to an RFID tag. This command is used to store segments of data in contiguous tag memory locations. It is capable of transferring up to 100 bytes of data from the host to the tag with one command.
The shortest possible Write Length is one (0x0001). When the Start Address is set to zero (0x0000), the controller will begin writing to the first available byte of tag memory.
The Timeout Value is measured in 1-millisecond increments and can have a value of 0x0001 to 0xFFFE (1 to 65,534 milliseconds). If the Write Length exceeds beyond the last available tag address, the controller will return an error code.
OMMAND 06 (WRITE D ATA )-ABX FAST C OMMAND S TRUCTURE
C
PARAMETER FIELD CONTENT
CHAPTER 7: RFID COMMANDS
Header
Command Size
Command ID
Start Address
Write Length
Timeout Value
Data Byte Value
Checksum
Terminator
0x02, 0x02
0x0007 + N (where N = the number of Data Bytes to be written).
0x06
2-byte value for the tag address where the write will begin.
2-byte value for the number of bytes to write.
2-byte value measured in 1 millisecond units (0x0001 – 0xFFFE).
1-byte for each data value to be written to tag.
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 77 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 06 (WRITE D ATA )–ABX F AST C OMMAND E XAMPLE
This example writes the five ASCII characters H, E, L, L, O (Data Byte Values: 0x48, 0x45, 0x4C, 0x4C and 0x4F) to the tag starting at address 0x0000. A Timeout Value of 2 seconds (0x07D0 = 2000 x 1 millisecond increments) is set for the completion of this command.
Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
Command ID
Start Address
Write Length
Timeout Value
Data Byte Value = H
Data Byte Value = E
Data Byte Value = L
Data Byte Value = L
Data Byte Value = O
Terminator
0x02, 0x02
0x000C
0x06
0x0000
0x0005
0x07D0
0x48
0x45
0x4C
0x4C
0x4F
0x03
Response from Controller
PARAMETER FIELD CONTENT
Header
0x02, 0x02
Response Size
Command Echo
Terminator
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 78 OF 116
0x0001
0x06
0x03
CHAPTER 7: RFID COMMANDS
C OMMAND 06 (WRITE D ATA )–CBX C OMMAND EXAMPLE
This example writes the five ASCII characters H, E, L, L, O (Data Byte Values: 0x48, 0x45, 0x4C, 0x4C and 0x4F) to the tag starting at address 0x0000. A Timeout Value of 2 seconds (0x07D0 = 2000 x 1 millisecond increments) is set for the completion of this command.
Command from Host
PARAMETER FIELD MSB LSB
Overall Length of Command
in MSB
AA Command ID
in MSB
00 Node ID
2-byte
Timeout Value
in LSB (0x06)
in LSB (Cobalt -IND = 01)
measured in ms
Start Address
Length of Write
Write Data
Write Data
Write Data
in LSB
00
(in bytes)
(bytes 1 and 2)
(bytes 3 and 4)
(byte 5) in MSB
(in words)
0x00 0x09
0xAA
0x06
0x00 0x01
0x07 0xD0
0x00 0x00
0x00 0x05
0x48 0x45
0x4C 0x4C
0x4F 0x00
Response from Controller
PARAMETER FIELD MSB LSB
Overall Length of Response
(in words)
0x00 0x06
in MSB
AA Command Echo
in MSB
00 Node ID Echo
Month
Hour
Seconds 00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 79 OF 116
and
and
in LSB
Minute
timestamp in MSB
in LSB
in LSB (Cobalt = 01)
timestamp
Day
timestamp
0xAA
0x06
0x00 0x01
Month DOM
Hour Minutes
Seconds 0x00
COMMAND 07: READ TAG ID
This command instructs the RFID controller to locate a tag in RF range and retrieve its unique tag identification number.
RFID tags are assigned a unique tag ID number during the manufacturing process. After a tag ID number has been assigned to a tag, the value cannot be altered and is not considered part of the available read/write memory space of the tag.
x ISO 14443 compliant tags receive a 4-byte tag ID number. By using just four
x ISO 15693 compliant tags are given an 8-byte tag ID number. When using eight
OMMAND 07 (READ TAG ID) – ABX F AST C OMMAND S TRUCTURE
C
PARAMETER FIELD CONTENT
CHAPTER 7: RFID COMMANDS
bytes, tag manufacturers can generate over 4.2 billion possible ISO 14443 compliant tag ID numbers.
bytes, manufacturers can generate over 280 trillion possible tag ID numbers.
Header
Command Size
Command ID
Timeout Value
Checksum
Terminator
0x02, 0x02
0x0003
0x07
2-byte value, measured in 1 millisecond units. (0x0001 – 0xFFFE).
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 80 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 07 (READ TAG ID) – ABX FAST C OMMAND E XAMPLE
This example instructs the controller to retrieve a tag’s ID. In this example, the 8-byte tag ID number is E0040100002E16AD. A Timeout Value of two seconds is set for the completion of this command.
Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
Command ID
Timeout Value
Checksum
Terminator
0x02, 0x02
0x0003
0x07
0x07D0
Optional
0x03
Response from Controller
PARAMETER FIELD CONTENT
Header
Response Size
Command Echo
Tag ID
(bytes 1-8)
Checksum
0x02, 0x02
0x0009
0x07
0xE0 0x04 0x01 0x00 0x00 0x2E 0x16 0xAD
Optional
Terminator
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 81 OF 116
0x03
CHAPTER 7: RFID COMMANDS
C OMMAND 07 (READ TAG ID) – CBX C OMMAND E XAMPLE
This example instructs the controller to retrieve a tag’s ID. In this example the 8-byte tag ID number is E0040100002E16AD. A Timeout Value of 2 seconds is set for the completion of this command.
Command from Host
PARAMETER FIELD MSB LSB
Overall Length of Command
in MSB
AA Command ID
in MSB
00 Node ID
2-byte
Timeout Value
in LSB (0x07)
in LSB (Cobalt –IND = 01)
measured in ms
(in words)
0x00 0x06
0xAA
0x07
0x00 0x01
0x07 0xD0
(0x07D0 = 2 seconds)
Not Used:
Not Used:
(0x00, 0x00)
(0x00, 0x00)
0x00 0x00
0x00 0x00
Response from Controller
PARAMETER FIELD MSB LSB
Overall Length of Response
in MSB
AA Command Echo
in MSB
00 Node ID Echo
in LSB
in LSB
(in words)
0x00 0x0A
0xAA
0x
07
0x00 0x01
Month
Hour
Seconds
and
and
Minute
timestamp in MSB
Number of Tag ID Bytes Retrieved
Day
timestamp
timestamp
Month DOM
Hour Minutes
Seconds 0x08
in LSB
(0x08)
Tag ID
Tag ID
Tag ID
Tag ID
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 82 OF 116
(bytes 1 & 2)
(bytes 3 & 4)
(bytes 5 & 6)
(bytes 7 & 8)
0xE0 0x04
0x01 0x00
0x00 0x2E
0x16 0xAD
CHAPTER 7: RFID COMMANDS
Response if tag not found
PARAMETER FIELD MSB LSB
Overall Length of Response
Error Flag Command Echo
in MSB
00 Node ID Echo
Month
Hour
Seconds
in MSB
in LSB
in LSB
and
and
timestamp
Day
Minute
timestamp
timestamp in MSB
(in words)
# of Additional Data Bytes Retrieved
LSB
Error Code
in MSB (0x07 = “Tag Not
Found Error”)
in LSB
00
0x00 0x07
0xFF
0x07
0x00 0x01
Month DOM
Hour Minutes
Seconds 0x01
in
0x07 0x00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 83 OF 116
COMMAND 08: TAG SEARCH
Command 08 instructs the controller to search for the presence of a tag within RF range of the antenna. If the controller finds a tag it will return a Command Response to the host. The Timeout Value is measured in 1-millisecond increments and can have a value of 0x0001 to 0xFFFE (1 to 65,534 milliseconds).
OMMAND 08 (TAG S EARCH)–ABX F AST C OMMAND S TRUCTURE
C
PARAMETER FIELD CONTENT
CHAPTER 7: RFID COMMANDS
Header
Command Size
Command ID
Timeout Value
Checksum
Terminator
0x02, 0x02
0x0003 for this command
0x08
2-byte value measured in 1 millisecond units (0x0001 – 0xFFFE).
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 84 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 08 (TAG S EARCH)–ABX F AST C OMMAND E XAMPLE
This example checks for an RFID tag within range of the antenna. The checksum is enabled and the Timeout Value is set for 2 seconds (0x07D0 = 2000 milliseconds) for the completion of this command.
Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
Command ID
Timeout Value
Checksum
Terminator
0x02, 0x02
0x0003
0x08
0x07D0
0x1D
0x03
Response from Controller
PARAMETER FIELD CONTENT
Header
Response Size
Command Echo
Checksum
Terminator
0x02, 0x02
0x0001
0x08
0xF6
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 85 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 08 (TAG S EARCH)–CBX C OMMAND E XAMPLE
This command will instruct the controller to search for the presence of a tag within RF range of the antenna.
Command from Host
PARAMETER FIELD MSB LSB
Overall Length of Command
0x00 0x06
(in words)
in MSB
AA Command ID
in MSB
00 Node ID
2-byte
in LSB (Cobalt = 1)
Timeout Value
in LSB (0x08)
0xAA
0x08
0x00 0x01
0x07 0xD0 measured in ms (0x07D0 = 2 seconds)
Not Used:
Not Used:
(0x00, 0x00)
(0x00, 0x00)
0x00 0x00
0x00 0x00
Response from Controller
PARAMETER FIELD MSB LSB
Overall Length of Response
0x00 0x06 (in words)
in MSB
AA Command Echo
in LSB
0xAA
0x08
in MSB
00 Node ID Echo
Month
Hour
and
and
Seconds
in LSB
00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 86 OF 116
in LSB
timestamp
Day
Minute
timestamp
timestamp in MSB
0x00 0x01
Month DOM
Hour Minutes
Seconds 0x00
CHAPTER 7: RFID COMMANDS
Response if tag not found
PARAMETER FIELD MSB LSB
Overall Length of Response
(in words)
Error Flag Command Echo
in MSB
00 Node ID Echo
Month
Hour
Seconds
in MSB
in LSB
in LSB
and
and
timestamp
Day
Minute
timestamp
timestamp in MSB
Number of Additional Data
: 0x01
Bytes
Error Code
in MSB (0x07 =
“Tag Not Found Error”)
in LSB
00
0x00 0x07
0xFF
0x08
0x00 0x01
Month DOM
Hour Min
Seconds 0x01
0x07 0x00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 87 OF 116
CHAPTER 7: RFID COMMANDS
COMMAND 0D: START/STOP CONTINUOUS READ
Command 0D instructs the controller to start (or stop) Continuous Read Mode.
When the Cobalt Controller is in Continuous Read Mode, it will constantly emit RF energy in an attempt to read any tag that comes into range of the antenna. As a tag enters the antenna field, it is immediately read and the data is passed to the host. The controller will continue to read the tag but will not re-send the same data to the host until the tag has moved outside the RF field for a specified time period. This parameter is known as the
Delay Between Duplicate Reads
controller is in Continuous Read Mode.
If another RFID command is executed while the controller is in Continuous Read Mode, the Cobalt HF will temporarily stop Continuous Reading to execute the command, after which the controller will return to Continuous Read Mode.
The Start/Stop Continuous Read command contains three primary components: a Start Address, a Read Length and a Delay Between Duplicate Reads value.
, which prevents redundant data transmissions when the
x Start Address: The Start Address is a 2-byte integer indicating the tag address
location where the read will begin.
x Read Length: The Read Length is a 2-byte integer that represents the number
of tag data bytes of retrieve. By setting this parameter to one (0x01) or higher, Continuous Read Mode will be switched ON at the completion of the command. Setting the Read Length to zero (0x00) will turn Continuous Read Mode off.
x Delay Between Duplicate Reads: During Continuous Read Mode, any tag that
comes within range of the antenna will be constantly read and the requested data from the tag will be passed to the host. This single-byte delay parameter indicates the number of seconds that a tag must remain out of RF range before it can be re-read and have its data sent to the host for a second time. It is implemented to enable the operator to limit the volume of information sent by the controller. The Delay Between Duplicate Reads parameter can have a value of 0 to 60 seconds. When the Delay Between Duplicate Reads value is set to 0, the controller will continuously read AND transmit duplicate tag data to the host.
Continuous Read at Power-up
By default, Continuous Read Mode is not restarted if the controller is reset. However, through the use of the RFID Dashboard Utility, the Cobalt Controller can be configured to enter Continuous Read Mode automatically after a reset or power-up. See Section 3.1 for more information regarding the RFID Dashboard Utility or visit:
www.ems-rfid.com
.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 88 OF 116
CHAPTER 7: RFID COMMANDS
C ONTINUOUS R EAD M ODE LED BEHAVIOR
LED BEHAVIOR DESCRIPTION
PWR
COM
ON The controller is powered and functioning.
BLINKS ONCE Delay Between Duplicate Reads is set to 1 or
greater and a tag has entered the RF field.
COM
BLINKING Delay Between Duplicate Reads is set to 0 and a
tag is in the RF field.
RF
BLINKING Delay Between Duplicate Reads is set to 0 and a
tag is in the RF field.
RF
BLINKS ONCE Delay Between Duplicate Reads is set to 1 or
greater and a tag has entered the RF field.
RF
ON The controller is in Continuous Read Mode and no
tag is present.
Table 7-2: Continuous Read Mode - LED Behavior
OMMAND 0D (START/STOP C ONTINUOUS R EAD)–
C
X F AST C OMMAND S TRUCTURE
AB
PARAMETER FIELD CONTENT
Header
Command Size
0x02, 0x02
0x0006
Command ID 0x0D
Start Address
2-byte value for the tag address where the read will start.
Read Length
Delay Between Duplicate Reads
2-byte value for number of bytes to be read.
1-byte value for number of seconds a tag must be out of RF range before the controller will re­transmit data from same tag.
Checksum
Terminator
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 89 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 0D (START/STOP C ONTINUOUS R EAD)–
X F AST C OMMAND E XAMPLE
AB
This example places the controller in Continuous Read mode and reads four bytes of data from the tag starting at address 0x0001. The Delay Between Duplicate Reads is set to two seconds (0x02 = 2 x 1 second increments).
Starting Continuous Read - Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
0x02, 0x02
0x0006
Command ID 0x0D
Start Address
Read Length
Delay Between Duplicate Reads
Checksum
Terminator
0x0001
0x0004
0x02
Optional
0x03
Starting Continuous Read - Initial Response from Controller
PARAMETER FIELD CONTENT
Header
Response Size
0x02, 0x02
0x0001
Command Echo 0x0D
Checksum
Terminator
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 90 OF 116
CHAPTER 7: RFID COMMANDS
Continuous Read Mode Evoked - Response from Controller (after Tag Read)
PARAMETER FIELD CONTENT
Header
Response Size
0x02, 0x02
0x0005
Command Echo 0x0D
Data from address 0x0001
Data from address 0x0002
Data from address 0x0003
Data from address 0x0004
Checksum
Terminator
0x05
0xAA
0xE7
0x0A
Optional
0x03
To exit out of Continuous Read mode, issue Command 0D with zero (0x0000) in the Read Length parameter field.
Stopping Continuous Read - Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
0x02, 0x02
0x0006
Command ID 0x0D
Start Address
Read Length
Delay Between Duplicate Reads
Checksum
Terminator
0x0001
0x0000
0x02
Optional
0x03
Stopping Continuous Read - Response from Controller
PARAMETER FIELD CONTENT
Header
Response Size
0x02, 0x02
0x0001
Command Echo 0x0D
Checksum
Terminator
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 91 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 0D (START/STOP C ONTINUOUS R EAD)–
X C OMMAND E XAMPLE
CB
This example places the controller in Continuous Read Mode and reads 4 bytes of data from the tag starting at address 0x0001. The Delay Between Duplicate Reads is set to 2 seconds (0x02 = 2 x 1 second increments).
Starting Continuous Read - Command from Host
PARAMETER FIELD MSB LSB
Overall Length of Command
in MSB
AA Command ID
in MSB
00 Node ID
in MSB
00
1-byte
Delay Between Duplicate Reads
in LSB (0x0D)
in LSB (Cobalt -IND = 01)
(in words)
0x00 0x06
0xAA
0x0D
0x00 0x01
0x00 0x02
in LSB
Start Address
Read Length
(in bytes)
0x00 0x01
0x00 0x04
Starting Continuous Read - Initial Response from Controller
PARAMETER FIELD MSB LSB
Overall Length of Response
in MSB
AA Command Echo
in MSB
00 Node ID Echo
in LSB
in LSB
(in words)
0x00 0x06
0xAA
0x0D
0x00 0x01
Month
Hour
and
and
Seconds
in LSB
00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 92 OF 116
timestamp
Day
Minute
timestamp
timestamp in MSB
Month DOM
Hour Min
Seconds 0x00
CHAPTER 7: RFID COMMANDS
Continuous Read Mode Evoked - Response from Controller (after Tag Read)
PARAMETER FIELD MSB LSB
Overall Length of Response
in MSB
AA
in LSB
Day
in LSB
timestamp
timestamp
Command Echo
in MSB
00 Node ID Echo
Month
Hour
Seconds
and
and
Minute
timestamp in MSB
(in words)
0x00 0x08
0xAA
0x05
0x00 0x01
Month DOM
Hour Minutes
Seconds 0x04
# of Bytes Read Data
Read Data
Read Data
(bytes 1 & 2)
(bytes 3 & 4)
0x05 0xAA
0xE7 0x0A
To exit out of Continuous Read Mode, re-issue the command with zero (0x0000) for the Read Length.
Stopping Continuous Read - Command from Host
PARAMETER FIELD MSB LSB
Overall Length of Command
in MSB
AA Command ID
in LSB (0x0D)
(in words)
0x00 0x06
0xAA 0x0D
in MSB
00 Node ID
in MSB
00
1-byte
in LSB (Cobalt = 01)
Delay Between Duplicate Reads
0x00 0x01
0x00 0x02
in LSB
Start Address
Read Length
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 93 OF 116
(in bytes)
0x00 0x00
0x00 0x00
CHAPTER 7: RFID COMMANDS
Stopping Continuous Read - Response from Controller
PARAMETER FIELD MSB LSB
Overall Length of Response
(in words)
in MSB
AA
in LSB
timestamp
Day
in LSB
timestamp
Command Echo
in MSB
00 Node ID Echo
Month
Hour
Seconds 00
and
and
in LSB
Minute
timestamp in MSB
0x00 0x06
0xAA
0x0D
0x00 0x01
Month DOM
Hour Minutes
Seconds 0x00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 94 OF 116
COMMAND 35: RESET CONTROLLER
Command 35 will cause the controller to cycle power - effectively rebooting the device ­without clearing any stored configuration information. Command 35 will reset the controller’s configuration to default settings when a Configuration Tag is placed in the antenna’s RF field prior to execution.
OMMAND 35 (RESET CONTROLLER)–ABX F AST C OMMAND S TRUCTURE
C
PARAMETER FIELD CONTENT
CHAPTER 7: RFID COMMANDS
Header
Command Size
Command ID
Checksum
Terminator
C OMMAND 35 (RESET C ONTROLLER)–ABX F AST C OMMAND E XAMPLE
This example resets power to the controller.
Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
Command ID
Checksum
Terminator
0x02, 0x02
0x0001
0x35
optional
0x03
0x02, 0x02
0x0001
0x35
Optional
0x03
Response from Controller
PARAMETER FIELD CONTENT
Header
Response Size
Command Echo
Checksum
Terminator
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 95 OF 116
0x02, 0x02
0x0001
0x35
Optional
0x03
CHAPTER 7: RFID COMMANDS
C OMMAND 35 (RESET C ONTROLLER)–CBX C OMMAND E XAMPLE
Command from Host
DESCRIPTION MSB LSB
Overall Length of Command
0x00 0x06
(in words)
in MSB
AA Command ID
in MSB
00 Node ID
Not Used:
Not Used:
Not Used:
in LSB
(default: 0x00, 0x00)
(default: 0x00, 0x00)
(default: 0x00, 0x00)
in LSB
0xAA
0x35
0x00 0x01
0x00 0x00
0x00 0x00
0x00 0x00
Response from Controller
DESCRIPTION MSB LSB
Overall Length of Response
0x00 0x06
(in words)
in MSB
AA Command Echo
Instance Counter Node Echo
in LSB
in LSB
in MSB
0xAA
0x35
Instance Counter 0x01
Month
Hour
Seconds 00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 96 OF 116
and
and
timestamp in MSB
in LSB
Day
Minute
timestamp
timestamp
Month Day
Hour Min
Seconds 0x00
COMMAND 38:
GET CONTROLLER INFO
Command 38 is used to retrieve hardware version, serial number and installed firmware identification information from the controller.
OMMAND 38 (GET CONTROLLER I NFO)–
C
X F AST C OMMAND S TRUCTURE
AB
PARAMETER FIELD CONTENT
CHAPTER 7: RFID COMMANDS
Header
Command Size
Command ID
Checksum
Terminator
0x02, 0x02
0x0001
0x38
Optional
0x03
C OMMAND 38 (GET C ONTROLLER I NFO)–
X F AST C OMMAND E XAMPLE
AB
This example will query the Cobalt HF and retrieve specific internal hardware information.
Command from Host
PARAMETER FIELD CONTENT
Header
Command Size
Command ID
Checksum
Terminator
0x02, 0x02
0x0001
0x38
Optional
0x03
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 97 OF 116
Response from Controller
CHAPTER 7: RFID COMMANDS
PARAMETER FIELD
Header
Response Size
Command Echo
RF Controller Type
Major Release Digit
Minor Release Digit
Correction Release Digit
CONTENT DESCRIPTION CONTENT
SAMPLE
2-byte Response Header (0x02, 0x02) 0x02, 0x02
2-byte value for the total number of bytes in the
0x001B response packet, less Header, Command Size, Checksum and Terminator bytes.
0x38 0x38
Controller Type default = 1 (0x01) 0x01
The MAJOR release ASCII digit in the product
0x30 version number. Example product version number:
0.0t.14
.
Major Release Digit in this example = 0
The MINOR release ASCII digit in the product
0x30 version number. Example product version number:
0.0t.14
.
Minor Release Digit in this example = 0
The CORRECTION ASCII digit in the product
0x74 version number. Example product version number:
0.0t.14.
Correction Release Digit in this example = t
Point Release Digit
Hardware Version
Block 0, 1, and 2 CRC
Block 3, and 4 CRC
RC632 ID
RC632 RFU
RC632 Serial Number
RC632 Internal Information
The POINT RELEASE digit in the product version number. Example product version number:
0.0t.14.
Point Release Digit in this example = 14
Cobalt HF-xxx-01Hardware Version, default = 01 (0x01)
2-byte value for block 0, 1, and 2 CRC: (example: 986E)
2-byte value for block 3, and 4 CRC: (example: 986E)
5-byte value for the RC632 ID: (example: 30FFFF0F04)
3-byte value for the RC632 RFU. (example: 000000)
4-byte value for the RC632 Serial Number. (example: 05E19644)
2-byte value for the RC632 internal. (example: B669)
0x0E
0x01
0x986E
0x986E
0x30, 0xFF,
0xFF, 0x0F,
0x04
0x00, 0x00,
0x00
0x05, 0xE1,
0x96, 0x44
0xB669
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 98 OF 116
CHAPTER 7: RFID COMMANDS
RC632 RsMaxP
Single-byte value for the RC632 RsMaxP:
0x65 (example: 65)
RC632 Information CRC
Terminator
Single-byte value for the RC632 Information CRC. (example: A6)
0x03 0x03
0xA6
Controller Information (retrieved in the above example response)
RF Controller Type: 1
Product Version Number: 0.0T.5
Hardware Version: 01
Block 0, 1, and 2 CRC: 986E
Block 3, and 4 CRC: 986E
RC632 ID: 30FFFF0F04
RC632 RFU: 000000
RC632 Serial Number: 05E19644
RC632 internal: B669
RC632 RsMaxP: 65
RC632 Information CRC: A6
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 99 OF 116
CHAPTER 7: RFID COMMANDS
C OMMAND 38 (GET C ONTROLLER I NFO)–CBX C OMMAND E XAMPLE
Command from Host
DESCRIPTION MSB LSB
Overall Length of Command
in MSB
AA Command ID
in LSB (0x38:Get Controller
0x00 0x06
0xAA
0x38
Info)
in MSB
0x00 Node ID in LSB
Not Used:
Not Used:
Not Used:
(default: 0x00, 0x00)
(default: 0x00, 0x00)
(default: 0x00, 0x00)
(Cobalt –IND = 01)
0x00 0x01
0x00 0x00
0x00 0x00
0x00 0x00
Response from Controller
DESCRIPTION MSB LSB
Overall Length of Response
(in words)
0x00 0x06 + number of
additional data words retrieved
Command Echo
Instance Counter Node ID Echo
in LSB
in MSB
0xAA
Instance Counter
0x38
0x01
Month
Hour
and
and
Seconds
timestamp
Day
Minute
timestamp
timestamp in MSB
Month Day
Hour Min
Seconds N-bytes
Number of Additional Data Bytes Retrieved
Node Info:
in LSB
(bytes 1 & 2)
Node Info -
Node Info - byte 2
byte 1
Node Info:
(bytes 3 & 4) (…etc.)
Node Info -
Node Info - byte 4
byte 3
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 100 OF 116
CHAPTER 8: ERROR CODES
CHAPTER 8: ERROR CODES
If the Cobalt Controller encounters a fault during operation, the response that is generated will include a 1-byte error code. Entering an invalid Start Address for a Read Data command, for example, will generate Error Code 0x32 (Invalid Programming Address).
8.1 ERROR C ODE T ABLE
ERROR CODE
0x04
0x05
0x06
0x07
0x08
0x21
0x23
0x30
0x31
0x32
0x34
ERROR NAME DESCRIPTION
FILL TAG FAILED Fill Operation Failed
READ DATA FAILED Read Data Command Failed
WRITE DATA FAILED Write Data Command Failed
READ TAG ID FAILED Read Tag ID Command Failed
TAG SEARCH FAILED Tag Search Command Failed / No
Tag Found
INVALID SYNTAX Command Contained a Syntax
Error
INVALID TAG TYPE Invalid or Unsupported Tag Type
INTERNAL CONTROLLER ERROR
INVALID CONTROLLER TYPE Invalid Controller Type (when
INVALID PROGRAMMING ADDRESS
INVALID VERSION Invalid Software Version (when
Generic Internal Controller Error
Setting Configuration)
Invalid Tag Address Specified in the Command
Setting Configuration)
0x35
0x36
0x37
0x83
0x84
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 101 OF 116
INVALID RESET Invalid Hardware Reset
SET CONFIGURATION FAILED
GET CONFIGURATION FAILED
COMMAND INVALID OPCODE
COMMAND INVALID PARAMETER
Set Configuration Command Failed
Get Configuration Command Failed
An invalid Command ID number was specified in the command.
A parameter specified in the command was invalid.
CHAPTER 8: ERROR CODES
0x85
0x86
0x87
0x88
0x89
0x8A
0x8B
0x8C
COMMAND INVALID CONTROLLER ID
COMMAND INACTIVE CONTROLLER ID
SUBNET DEVICE SELECT FAILED
SUBNET DEVICE FAILED TO ACKNOWLEDGE
SUBNET RESPONSE MALFORMED
SUBNET RESPONSE TIMEOUT
SUBNET RESPONSE INVALID CHECKSUM
SUBNET DEVICE CONFLICT DETECTED
An invalid Node ID was specified in the command, or no controller was detected/present at the specified Node.
The Node ID specified in the command is currently inactive.
Internal Subnet Error – the specified Subnet device failed.
Internal Subnet Error - the specified Subnet device failed to respond to the Hub’s polling.
Internal Subnet Error – a controller returned a malformed response.
Internal Subnet Error – a controller was unable to generate a response before timeout was reached.
Internal Subnet Error – a controller generated a response that has an invalid checksum.
Internal Subnet Error – a Node ID conflict has been detected
0x8D
0x8E
0x92
0x93
0x94
0x95
BUFFER OVERFLOW Internal Error – buffer limit was
exceeded
FLASH FAILURE Internal Error – flash memory
failure
SUBNET16 ONLY COMMAND
MODBUS NODE MISMATCH ERROR
A Subnet16-only command was issued when in MUX32 mode.
The Node specified in the command did not match the Node to which the command was sent (MUX32 mode).
MODBUS CRC ERROR Internal Communications Error
(MUX32 mode)
MODBUS PROTOCOL ERROR
Internal Communications Error (MUX32 mode)
Table 8-1: Error Code Table
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 102 OF 116
8.2 ABX F AST:
RROR R ESPONSE P ACKET S TRUCTURE
E
For any ABx Fast error response, a single-byte Error Code always follows the 0xFF byte (Error Flag byte).
PARAMETER FIELD CONTENT
CHAPTER 8: ERROR CODES
Header
Response Size
Error Flag
Error Code
Checksum
Terminator
Table 8-2: ABx Fast - Error Response Structure
AB
X F AST -ERROR R ESPONSE E XAMPLE
Below is an example of an ABx Fast error response (with checksum) for a failed Write Data command (error code 0x06).
PARAMETER FIELD CONTENT
Header
Response Size
Error Flag
Error Code
Checksum
0x02, 0x02
0x0002
0xFF
1-byte error code
optional
0x03
0x02, 0x02
0x0002
0xFF
0x06
0xF8
Terminator
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 103 OF 116
0x03
8.3 CBX P ROTOCOL:
RROR R ESPONSE P ACKET S TRUCTURE
E
A one-byte Error Code will be returned in the MSB of the seventh data word in the error response packet (followed by a zero - 0x00 in the LSB).
PARAMETER FIELD MSB LSB
CHAPTER 8: ERROR CODES
Overall Length
the number of “words” in the Response Packet. This value will always be at least 7 words (6 + 1 for the error code).
Error Flag Byte
indicates that an error occurred.
Command ID Echo
LSB indicates the command that was attempted when the error occurred.
Instance Counter
tallies the number of responses from a given Node ID.
Node ID
the Node ID of the controller that experienced or generated the error. (Cobalt -IND = 01)
Month
Hour
Seconds # of Additional Bytes Retrieved
(0x01 for error responses).
Error Code 00
: 1-byte value in LSB indicates
and
and
in LSB
: 2-byte value indicating
: 0xFF in the MSB
: 1-byte value in the
: This 1-byte value
timestamp
Day
Minute
timestamp in MSB
timestamp
: 1-byte Error Code in MSB
in LSB
0x00 0x07
0xFF Command ID
Echo
Instance Counter 0x01
Month Day
Hour Minute
Seconds 0x01
Error Code 0x00
Table 8-3: CBx Error Response Structure
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 104 OF 116
CHAPTER 8: ERROR CODES
CBX -ERROR R ESPONSE E XAMPLE
Below is an example of a CBx error response (error code 0x08) for a failed Tag Search (Command ID: 0x08).
Command from Host
PARAMETER FIELD MSB LSB
in MSB
00 Overall Length of Command
in LSB
0x00 0x06
(in words)
in MSB
AA Command ID
in LSB:
0xAA 0x08
(0x08 – Tag Search)
in MSB
00 Node ID
2-byte
Timeout Value
in LSB (Cobalt –IND = 01)
measured in ms:
0x00 0x01
0x07 0xD0
(0x07D0 = 2 seconds)
Not Used:
Not Used:
(0x00, 0x00)
(0x00, 0x00)
0x00 0x00
0x00 0x00
Error Response (if no tag is found)
PARAMETER FIELD MSB LSB
in MSB
00 Overall Length of Response
in LSB
0x00 0x07
(in words)
Error Flag Command Echo
in MSB
00 Node ID Echo
Month
Hour
Seconds
in MSB
in LSB
in LSB
and
and
timestamp
Day
Minute
timestamp
timestamp in MSB
# of Additional Data Bytes
Error Code
in MSB:
: (0x01)
0xFF 0x08
0x00 0x01
Month DOM
Hour Minutes
Seconds 0x01
0x08 0x00
(0x08 = “Tag Search Failed”)
in LSB
00
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 105 OF 116
APPENDIX A:
COBALT HF SPECIFICATIONS
APPENDIX A: COBALT HF SPECIFICATIONS
ELECTRICAL
Supply Voltage: 10~30VDC
Power Consumption: 12W (450mA @ 24VDC)
COMMUNICATION
Communication Interfaces:
RFID Interface: Cobalt HF-Series RFID System
RF Output Power: 1W
Air Protocols: IǜCODE 1, ISO 15693, ISO 14443 A
Air Protocol Speed: 26.5kBaud/106kBaud with CRC error
RS232/RS422/485 Baud Rates: 9600 (default), 19.2k, 38.4k, 57.6k, 115.2k
MECHANICAL
Dimensions: Refer to Chapter 1, Section 1.4
Weight: .44 KG (1 lb. – 440 grams)
Enclosure: Powder-Coated Aluminum
ENVIRONMENTAL
Point-to-Point: RS232, RS422, USB
x
Multi-drop: Subnet16 (RS485)
x
Ethernet: Ethernet/IP, Modbus TCP,
x
TCP/IP
detection
Operating Temperature: -20° to 50°C (-4° to 122°F),
Storage Temperature: -40° to 85°C (-40° to 185°)
Humidity: 100%
Protection Class: IP66
Shock Resistance: IEC 68-2-27 Test EA 30g, 11milliseconds,
3 shocks each axis
Vibration Resistance IEC 68-2-6 Test FC 1.5mm; 10 to 55Hz;
2 hours each axis
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 106 OF 116
APPENDIX B:
MODELS & ACCESSORIES
APPENDIX B: MODELS & ACCESSORIES
C OBALT HF RFID CONTROLLER MODELS
There are five models of the Cobalt HF RFID Controller:
HF-CNTL-232-01
HF-CNTL-422-01
HF-CNTL-485-01
HF-CNTL-USB-01
HF-CNTL-IND-01
– for RS232 interface connections
– for RS422 interface connections
– for RS485 interface connections
– for USB interface connections
– for Industrial Ethernet interface connections
C OBALT HF ANTENNA MODELS
There are four models of the Cobalt HF Antenna:
HF-ANT-1010-01
HF-ANT-2020-01
HF-ANT-3030-01
HF-ANT-0750-01
– 10cm x 10cm
– 20cm x 20cm
– 30cm x 30cm
– 7cm x 50cm (for conveyor applications)
S UBNET16 GATEWAYS
GWY-01-TCP-01
Subnet16™ TCP/IP Gateway – for commercial TCP/IP environments
GWY-01-IND-01
Subnet16™ Industrial Ethernet Gateway – for Industrial Ethernet environments
S UBNET16 HUBS
HUB-04-TCP-01
Subnet16™ TCP/IP Hub (4-port) – for commercial TCP/IP environments
HUB-04-IND-01
Subnet16™ Industrial Ethernet Hub (4-port) – for Industrial Ethernet environments
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 107 OF 116
APPENDIX B:
MODELS & ACCESSORIES
P OWER S UPPLIES
00-1166: 24VDC, 1.88A max, 45W, Universal Input (90-264VAC, 47-63Hz), 5.5x2.5mm plug, positive tip; Note: Requires country specific power cord to mate to IEC 320 power cord receptacle.
00-1167:
plug, positive tip; Note: Requires country specific power cord to mate to IEC 320 power cord receptacle.
00-1168:
selectable, 47-63Hz) DIN Rail Mount; Note: AC wire receptacles are spring clamp for direct wire connection.
24VDC, 4.17A max, 100W, Universal Input (90-264VAC, 47-63Hz), 5.5x2.5mm
24VDC, 5.0A max, 120W, Universal Input (88-132VAC/176-264VAC switch
C OBALT HF SOFTWARE APPLICATIONS
RFID Dashboard: provides users with complete control over their Escort Memory Systems RFID system. The RFID Dashboard allows system operators to configure, monitor and control Cobalt HF-Series RFID devices from anywhere on their network.
C-MacroBuilder
save powerful RFID macros.
Cobalt HF-SDK:
Visual Studio® .Net). Contact your distributor.
Visit the Escort Memory Systems website (
: an easy to use GUI-driven utility that allows users to create, edit and
Cobalt HF Controller - Software Development Kit (requires Microsoft®
www.ems-rfid.com
) for download instructions.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 108 OF 116
APPENDIX B:
MODELS & ACCESSORIES
C OBALT C ABLES &CONNECTORS
CBL-1478 - RS232 Cable with DB9 Female Plug and 2.5mm DC Jack
CBL-1480-0.2
CBL-1480-02
CBL-1480-10
CBL-1481-0.2
CBL-1481-01
CBL-1481-02
CBL-1482-02
CBL-1482-10
CBL-1483
CBL-1484
CBL-1485
CBL-1486
CBL-1487
CBL-1488
CBL-1489
- Male/Female, ThickNet Trunk Cable, 10m
- Female w/ Bare Wire, ThickNet Trunk Cable, 2m
- ThickNet to ThinNet Drop-T
- ThinNet to ThinNet Drop-T
Straight Female M12 Field Mountable Connector
- M12-8, Female w/ Bare Wires Cable, 2m, (-232- & -422)
- Male 7/8-16 ThickNet 120-Ohm Termination Resistor Plug
- Male/Female, ThinNet Drop Cable, 0.2m
- Male/Female, ThinNet Drop Cable, 2m
- Male/Female, ThinNet Drop Cable, 10m (for Hubs only)
- Male/Male, ThinNet Drop Cable, 0.2m
- Male/Male, ThinNet Drop Cable, 1m
- Male/Male, ThinNet Drop Cable, 2m (Gateway to T)
- Male/90 Degree Female, ThinNet Drop, Cable, 2m
- Male/90 Degree Female, ThinNet Drop, Cable, 10m
CBL-1490
CBL-1491
CBL-1492
CBL-1493
CBL-1513
CBL-1514
CBL-1515-05
- Male M12 ThinNet 120-Ohm Termination Resistor Plug
- 90 Degree Female M12 Field Mountable Connector
- M12-8, 90 Degree Female w/ Bare Wires Cable, 2m, (-232 & -422)
- M12-8, Straight Female Field Mountable Connector
M12, 5-Pin, Male, Reverse Keyed to Type A, USB Cable 3M
M12, 5-Pin, Straight Male, Reverse Keyed Connector for USB
– Cable, Ethernet/M12, 5-Pin, Male, D-Code, 5M
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 109 OF 116
APPENDIX B:
MODELS & ACCESSORIES
RFID TAGS
Escort Memory Systems designs and manufactures several lines of RFID tags. LRP and HMS-Series passive read/write RFID tags are specially suited for the Cobalt HF Series product line.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 110 OF 116
APPENDIX C:
NETWORK DIAGRAMS
APPENDIX C: NETWORK DIAGRAMS
x Cobalt Ethernet Network
x Subnet16 Gateway ThickNet Network
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 111 OF 116
APPENDIX C:
NETWORK DIAGRAMS
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 112 OF 116
APPENDIX C:
NETWORK DIAGRAMS
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 113 OF 116
APPENDIX D: ASCII CHART
APPENDIX D: ASCII CHART
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 114 OF 116
APPENDIX D: ASCII CHART
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 115 OF 116
WARRANTY
WARRANTY
scort Memory Systems warrants that all products of its own manufacturing conform to Escort Memory Systems’ specifications and are free from defects in
E
within the service conditions for which they were furnished. The obligation of Escort Memory Systems hereunder shall expire one (1) year after delivery, unless otherwise specified, and is limited to repairing, or at its option, replacing without charge, any such product which in Escort Memory Systems’ sole opinion proves to be defective within the scope of this Warranty. In the event Escort Memory Systems is not able to repair or replace defective products or components within a reasonable time after receipt thereof, Buyers shall be credited for their value at the original purchase price. Escort Memory Systems must be notified in writing of the defect or nonconformity within the warranty period and the affected product returned to Escort Memory Systems factory or to an authorized service center within thirty (30) days after discovery of such defect or nonconformity. Shipment shall not be made without prior authorization by Escort Memory Systems.
This is Escort Memory Systems' sole warranty with respect to the products delivered hereunder. No statement, representation, agreement or understanding oral or written, made by an agent, distributor, representative, or employee of Escort Memory Systems which is not contained in this warranty, will be binding upon Escort Memory Systems, unless made in writing and executed by an authorized Escort Memory Systems employee.
material and workmanship when used under normal operating conditions and
Escort Memory Systems makes no other warranty of any kind what so ever, expressed or implied, and all implied warranties of merchantability and fitness for a particular use which exceed the aforementioned obligation are here by disclaimed by Escort Memory Systems and excluded from this agreement. Under no circumstances shall Escort Memory Systems be liable to Buyer, in contract or in tort, for any special, indirect, incidental, or consequential damages, expenses, losses or delay however caused. Equipment or parts which have been subject to abuse, misuse, accident, alteration, neglect, unauthorized repair or installation are not covered by warranty. Escort Memory Systems shall make the final determination as to the existence and cause of any alleged defect. No liability is assumed for expendable items such as lamps and fuses. No warranty is made with respect to equipment or products produced to Buyer’s specification except as specifically stated in writing by Escort Memory Systems in the contract for such custom equipment. This warranty is the only warranty made by Escort Memory Systems with respect to the goods delivered hereunder, and may be modified or amended only by a written instrument signed by a duly authorized officer of Escort Memory Systems and accepted by the Buyer.
Extended warranties of up to four years are available for purchase for most Escort Memory Systems products. Contact Escort Memory Systems or your distributor for more information.
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 116 OF 116
Loading...