Ballu AC-N006R, AC-N006RH, AC-T006R, AC-T006RH Service Manual

Service Manual
AC-N006R, AC-N006RH
AC-T006R, AC-T006RH
POSSIBLE CAUSE
SOLUTION
Water leakage
Rubber plug at the rear plate of the machine is out of place.
Water tube inside the machine is not in the place or broken. Water tube is of bad connection or broken.
Put back the rubber plug.
Check and reinstall or replace the water tube inside the machine. Check or replace the water tube.
Weak cooling Dusty filter
Dusty condenser.
Air vent is blocked. The room temperature is too high.
Too many windows or doors are open. Insufficient refrigerant or the refrigerant leaks out.. HEAT PUMP is broken.
Clean the filter. Use a high pressure air spray to clean the dust. *Do not touch the condenser directly, it is very hot now. Remove the blockade. It’s out of the working range of the machine. Close the windows/doors. Please check: Is the current/power consumption decreasing? Is the suction pressure of the machine too low? Is the temperature of the discharging tube too high? Is the suction tube frozen in ambient temperature?
7. Replace the heat pump.
Machine does not work at all.
Bad connection of the mains and plug. P.C. Board fused. P.C. Board or transformer breaks down. Bad connection of the wires.
Re-plug the power cord. Check and replace. Check and replace. Check and replace.
Compressor doesn’t work, only the fan to circulate the air.
Voltage/Frequency is too low. Overload protector of compressor breaks down. Compressor capacitor breaks down. Compressor breaks down. P.C. board breaks down. Room temperature is too low.
Check it by a voltmeter. Check and replace.
Check and replace. Check and replace. Check and replace. It is out of the working range of the machine.
1
PROBLEM POSSIBLE CAUSE SOLUTION
Compressor works but the fan doesn’t.
Bad connection of the wires. Fan motor breaks down. Fan motor capacitor breaks down. P.C. board breaks down. Fan blade is stuck.
Check and reconnect or replace. Check and replace. Check and replace. Check and replace. Fix it.
Big noise Screws/nuts of the fan for evaporator/
condenser come loose. Screws/nuts of the compressor come loose. Fan blade is blocked by something.
Check and fasten.
Check and fasten.
Remove the blockade.
Big vibration Screws/nuts of the compressor come loose.
Fan of the evaporator or condenser does not fix well or is deformed. The metal tubes inside the machine hit the other parts.
Check and fasten.
Check and replace.
Adjust the position of the tubes.
Motor doesn’t work. Wires problem.
Loose terminal connection. Motor breaks down. Motor capacitor breaks down. The fan blade is stuck.
Check and replace. Check and fasten. Check and replace. Check and replace. Fix it.
Auto-drainage system doesn’t work.
Wires problem. Pump motor breaks down. Bad installation of the water pump. Micro switch breaks down.
Check and replace. Check and replace. Re-install. Check and replace.
Suction pressure is too low while the suction temperature is too high.
Blocked capillary Blocked evaporator. Blocked refrigerant filter. Insufficient refrigerant or the refrigerant has been leaked.
Replace the capillary. Use high pressure N2 to clean the evaporator or replace it. Replace the refrigerant filter. Release the remained refrigerant, vacuum the unit (at least over 755mmHg). Recharge the unit. For correct refrigerant amount, please refer to the rating label at the back of the unit. The deviation should be within 3g.