Baldor ZD18H201–E, ZD18H401–E, ZD18H501–E, ZD18H201–W, ZD18H401–W Installation & Operating Manual

...
VECTOR DRIVE
AC Flux Vector Control
SERIES 18H
Installation
9/97 MN718
& Operating Manual
Table of Contents
Section 1 Quick Start Guide
Overview 1-1
Quick Quick
Section General Information 2-1.
Section Receiving & Installation
2
Overview 2-1 Limited Warranty 2-2. Safety
Notice
3
Receiving Physical Control Through Optional Electrical
Input AC
Wire AC
Optional
Encoder Home Buffered
Location
Installation
the W Remote Keypad Installation
Installation System Line
Impedance Line Reactors 3-7. Load Reactors 3-7. Current Requirements
Main Circuit
Protection Devices 3-10. Power
Size and Protection Devices
Line Connections
380-400 VAC Configuration Three Single Single Size
A and B Single Phase Power Installation Size
C and D Single Phase Power Installation Size
E Single Phase Power Installation Size
F Single Phase Power Installation
Dynamic Brake Hardware Physical Electrical
Installation
(Orient) Switch Input
Encoder Output
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Checklist Start Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
& Inspection
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
all Mounting
Grounding
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Disconnect
Phase Input Power
Phase Input Power Considerations
Phase Control Derating
Installation
Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1.
1-1. 1-2.
2-3.
3-1. 3-1. 3-1. 3-2. 3-2. 3-3. 3-4. 3-4. 3-6.
3-9.
3-10.
3-10. 3-10. 3-13. 3-13. 3-15. 3-18. 3-18. 3-18. 3-20. 3-22. 3-24. 3-26. 3-26. 3-27. 3-30. 3-32. 3-32.
MN718
of Contents i
Section 1 General Information
Control Circuit Connections
Keypad Standard 15 Fan Fan Bipolar Process Specific
Analog
Analog
Analog External T Opto-Isolated Opto-Isolated Pre-Operation Power-Up
Section Programming and Operation 4-1.
4
Overview 4-1 Display
Adjusting
Display
Display
Fault Log Access 4-5. Program
Parameter
Changing
Reset
Initialize Parameter
Mode Connections
Run 3 Wire Mode Connections
Speed 2-Wire Mode Connections
Pump 2 Wire Control Mode Pump 3 Wire Control Mode
Speed and T
Mode Connections
Process Mode Outputs
Inputs and Outputs
Inputs Outputs
rip Input
Inputs Outputs
Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mode
Mode Screens Screens & Diagnostic Information Access
Mode
Parameters to Factory Settings
New Firmware
Definitions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checklist
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Contrast
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blocks Access for Programming
Parameter V
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
orque Mode Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
alues when Security Code Not Used
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-33. 3-33. 3-35. 3-37. 3-39. 3-40. 3-41. 3-43. 3-45. 3-47. 3-47. 3-50. 3-51. 3-51. 3-53. 3-55. 3-56.
4-2. 4-2. 4-3. 4-4.
4-6. 4-6. 4-7. 4-8. 4-9.
4-10.
ii T
able of Contents
MN718
Section 1 General Information
Section 5 Troubleshooting 5-1.
No
Keypad Display - Display Contrast Adjustment
How
to Access the Fault Log
How
to Clear the Fault Log
How
Electrical
Causes Special Drive Radio Transmitters 5-14. Control
Special Wiring Practices 5-16. Optical Plant
Section Manual Tuning the Series 18H Control
Manually T
Isolation
Ground
6
Motor
Slip
Current
Current
Speed
Speed
PI
Controller
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
to Access Diagnostic Information
Noise Considerations
and Cures
Drive Situations
Power Lines
Enclosures Motor Considerations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
uning the Control
Mag Amps Parameter
Frequency Parameter
Prop Gain Parameter
Int Gain Parameter Prop Gain Parameter Int Gain Parameter
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1. 5-3. 5-3.
5-4. 5-11. 5-11.
5-14. 5-14.
5-15. 5-15.
5-17. 5-17.
6-1.
6-1.
6-1.
6-1.
6-1.
6-2.
6-2.
6-2.
6-3.
MN718
of Contents iii
Section 1 General Information
Section 7 Specifications, Ratings & Dimensions
Specifications 7-1
Operating Keypad Control Differential Analog Digital Digital
Diagnostic Ratings 7-4 Terminal T Dimensions 7-10
Size
Size
Size
Size
Size
Size
Size
Size
Size
Size
Size
Appendix
Appendix
Appendix
A
Dynamic
RGA
RBA
RTA
B
Parameter Values B-1.
C
Remote
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conditions
Display
Specifications
Analog Input
Outputs Inputs Outputs
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ightening T
A Control A Control – Through–W B Control B Control – Through–W C Control D Control E Control E Control – Through–W F Control F Control – Through–W G Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Braking (DB) Hardware
Assemblies
Assemblies
Assemblies
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keypad Mounting T
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
orque Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
emplate C-2.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
all Mounting
all Mounting
all Mounting
all Mounting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1.
7-1. 7-2. 7-2. 7-2. 7-3. 7-3. 7-3. 7-3.
7-6.
7-10.
7-11. 7-12. 7-13. 7-14. 7-15. 7-16. 7-17. 7-19. 7-20. 7-22.
A-1. A-1. A-4. A-5. A-6. B-1.
C-1.
iv T
able of Contents
MN718
Section 1 Quick Start Guide
Overview
Quick Start Checklist
If you are an experienced user of Baldor controls, you are probably already familiar with the keypad programming and keypad operation methods. If so, this quick start guide has been prepared for you. This procedure will help get your system up and running in the keypad mode quickly procedure assumes that the Control, Motor and Dynamic Brake hardware are correctly installed (see Section 3 for procedures) and that you have an understanding of the keypad programming & operation procedures. It is not necessary to wire the terminal strip to operate in the Keypad mode (Section 3 describes terminal strip wiring procedures). The quick start procedure is as follows:
1.
Read the Safety Notice and Precautions in section 2 of this manual.
2.
Mount the control. Refer to Section 3 “Physical Location” procedure.
3.
Connect AC power
4.
Connect the motor, refer to Section 3 “Three Phase Input Power”.
5.
Connect the encoder
6.
Install Dynamic brake hardware, if required. Refer to Section 3 “Optional Dynamic Brake Hardware”.
Check of electrical items.
CAUTION: After completing the installation but before you apply power
1. V
erify AC line voltage at source matches control rating.
2.
Inspect all power connections for accuracy as compliance to codes.
3. V
erify control and motor are grounded to each other and the control is
connected to earth ground.
4.
Check all signal wiring for accuracy
5.
Be certain all brake coils, contactors and relay coils have noise suppression. This should be an R-C filter for AC coils and reverse polarity diodes for DC coils. MOV type transient suppression is not adequate.
. This will allow motor and control operation to be verified. This
, refer to Section 3 “AC Line Connections”.
, refer to Section 3 “Encoder Installation”.
, be
sure to check the following items.
, workmanship and torques as well
.
W
ARNING: Make sure that unexpected operation of the motor shaft during start
up will not cause injury to personnel or damage to equipment.
Check of Motors and Couplings
1. V
erify freedom of motion for all motor shafts and that all motor couplings are
tight without backlash.
2. V
erify the holding brakes if any, are properly adjusted to fully release and set to
the desired torque value.
MN718
Quick
Start Guide 1-1
Section 1 General Information
Quick Start Procedure
Initial Conditions
Be sure the Control, Motor and Dynamic Brake hardware are wired according to the procedures described in section 3 of this manual. Become familiar with the keypad programming and keypad operation of the control as described in Section 4 of this manual.
1. V
erify that any enable inputs to J1-8 are open.
2. T
urn power on. Be sure there are no faults.
3.
Set the Level 1 Input block, Operating Mode to “KEYP
4.
Be sure the Level 2 Protection block, Local Enable INP parameter is OFF and the Level 2 Protection block, External T
5.
Set the Level 2 Output Limits block, “OPERA (STD CONST TQ, STD V
6.
Enter the following motor data in the Level 2 Motor Data block parameters: Motor V Motor Rated Amps (FLA) Motor Rated Speed (base speed) Motor Rated Frequency Motor Mag Amps (no load current) Encoder Counts
7.
Go to Level 2 Motor Data block, press ENTER, at CALC PRESETS select YES (using the Y key) and let the control calculate preset values for the parameters that are necessary for control operation.
8.
Disconnect the motor from the load (including coupling or inertia wheels). If the load cannot be disconnected, refer to Section 6 and manually tune the control. After manual tuning, perform steps 10, 1
oltage (input)
AR TQ, QUIET CONST TQ or QUIET V
rip parameter is OFF
TING ZONE” parameter as desired
1, 15, 16 and 17.
AD”.
.
AR TQ).
W
ARNING: The motor shaft will rotate during this procedure. Be certain that
unexpected motor shaft movement will not cause injury to personnel or damage to equipment.
9.
Go to Level 2 Autotune block, and do the following tests:
CMD OFFSET TRIM CUR LOOP COMP STAT
OR R1 FLUX CUR SETTING ENCODER TESTS SLIP FREQ TEST
10.
Set the Level 2 Output Limits block, “MIN OUTPUT SPEED” parameter
11.
Set the Level 2 Output Limits block, “MAX OUTPUT SPEED” parameter
12.
Remove all power from the control.
13.
Couple the motor to its load.
14. T
urn power on. Be sure no errors are displayed.
15.
Go to Level 2 Autotune block and perform the SPD CNTRLR CALC test.
16.
Run the drive from the keypad using one of the following: the arrow keys for direct speed control, a keypad entered speed or the JOG mode.
17.
Select and program additional parameters to suit your application.
The control is now ready for use the in keypad mode. If a dif desired, refer to Section 3 Control Connections and Section 4 Programming and Operation.
ferent operating mode is
.
.
1-2
Quick Start Guide
MN718
Section 2 General Information
Overview
The Baldor Series 18H PWM control uses flux vector technology (sometimes referred to as Field Oriented Control) is a closed loop control scheme using an algorithm to adjust the frequency and phase of voltage and current applied to a three phase induction motor torque producing components. These components are independently adjusted and vectorially added to maintain a 90 degree relationship between them. This produces maximum torque from base speed down to and including zero speed. Above base speed, the flux component is reduced for constant horsepower operation. In addition to the current, the electrical frequency must also be controlled. The frequency of the voltage applied to the motor is calculated from the slip frequency and the mechanical speed of the rotor phasing in response to speed and position feedback from an encoder mounted to the motors’ shaft.
The control’s rated horsepower is based on the use of a NEMA design B four pole motor and 60Hz operation at nominal rated input voltage. If any other type of motor is used, the control should be sized to the motor using the rated current stated on the motor nameplate.
The Baldor Series 18H control may be used in many dif programmed by the user to operate in four dif constant torque or variable torque. It can also be configured to operate in a number of modes depending upon the application requirements and user preference.
It is the responsibility of the user to determine the optimum operating zone and mode to interface the control to the application. These choices are made with the keypad as explained in Section 4 of this manual.
. The vector control separates the motor current into it’
. This provides instantaneous adjustment of the voltage and current
ferent applications. It may be
ferent operating zones; standard or quiet
. Flux vector technology
s flux and
MN718
General
Information 2-1
Limited Warranty
For
a period of two (2) years from the date of original purchase, BALDOR will repair or replace without charge controls and accessories which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized persons, misused, abused, or improperly installed and has been used in accordance lieu of any other warranty or guarantee expressed or implied. BALDOR shall not be held responsible for any expense (including installation and removal), person or property caused by items of our manufacture or sale. (Some states do not allow exclusion or limitation of incidental or consequential damages, total liability, under all circumstances, shall not exceed the full purchase price of the control. Claims for purchase price refunds, repairs, or replacements defect, the date purchased, the task performed by the control, and the problem fuses.
Goods may be returned only with written notification including a BALDOR Return
with the instructions and/or ratings supplied.
inconvenience, or consequential damage, including injury to
so the above exclusion may not apply
.) In any event, BALDOR’
This warranty is in
any
must be referred to BALDOR with all pertinent data as to the
encountered. No liability is assumed for expendable items such as
Authorization Number and any return shipments must be prepaid.
s
2-2 General Information
MN718
Safety Notice This
can cause serious or fatal injury procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts that are driven by this equipment. Improper use can cause serious or fatal injury qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
PRECAUTIONS
equipment contains voltages that may be as high as 1000 volts! Electrical shock
. Only qualified personnel should attempt the start–up
. Only
W
ARNING:
Do not touch any circuit board, power device or electrical connection before you first ensure that power has been disconnected and there is no high voltage present from this equipment or other equipment to which it is connected. Electrical shock can cause serious or fatal injury
. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
W
ARNING:
Be sure that you are completely familiar with the safe operation of this equipment. This equipment may be connected to other machines that have rotating parts or parts that are controlled by this equipment. Improper use can cause serious or fatal injury Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
W
ARNING: This unit has an automatic restart feature that will start the motor
whenever input power is applied and a RUN (FWD or REV) command is issued. If an automatic restart of the motor could cause injury to personnel, the automatic restart feature should be disabled by changing the Level 2 Miscellaneous block, Restart Auto/Man parameter to Manual.
W
ARNING:
Be sure the system is properly grounded before applying power Do not apply AC power before you ensure that all grounding instructions have been followed. Electrical shock can cause
W
ARNING:
serious or fatal injury Do not remove cover for at least five (5) minutes after AC power is
.
disconnected to allow capacitors to discharge. Dangerous voltages are present inside the equipment. Electrical shock can cause serious or fatal injury
W
ARNING: Improper operation of control may cause violent motion of the
.
motor shaft and driven equipment. Be certain that unexpected motor shaft movement will not cause injury to personnel or damage to equipment. Certain failure modes of the control can produce peak torque of several times the rated motor torque.
W
ARNING:
Motor circuit may have high voltage present whenever AC power is applied, even when motor is not rotating. Electrical shock can
W
ARNING:
cause serious or fatal injury Dynamic brake resistors may generate enough heat to ignite
.
combustible materials. Keep all combustible materials and flammable vapors away from brake resistors.
W
ARNING: The motor shaft will rotate during the autotune procedure. Be
certain that unexpected motor shaft movement will not cause injury to personnel or damage to equipment.
.
.
Continued on next page
MN718
General Information 2-3
Section 1 General Information
Caution: T
Caution: Disconnect motor leads (T1, T2 and T3) from control before you
Caution: Do not connect AC power to the Motor terminals T1, T2 and T3.
Caution: Baldor recommends not using “Grounded Leg Delta” transformer
Caution: Do not supply any power to the External Trip (motor thermostat)
o prevent equipment damage, be certain that the electrical service is not capable of delivering more than the maximum line short circuit current amperes listed for 230 V control rating.
perform a “Megger” test on the motor. Failure to disconnect motor from the control will result in extensive damage to the control. The control is tested at the factory for high voltage / leakage resistance as part of Underwriter Laboratory requirements.
Connecting AC power to these terminals may result in damage to the control.
power leads that may create ground loops and degrade system performance. Instead, we recommend using a four wire W
leads at J1-16 and 17. Power on these leads can damage the control. Use a dry contact type that requires no external power to operate.
AC, 460 V
AC or 575 V
ye.
AC
2-4
General Information
MN718
Section 3 Receiving & Installation
Receiving & Inspection The
for shipment. When you receive your control, there are several things you should do immediately.
Physical Location The
from direct sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration. Exposure to these elements can reduce the operating life and degrade performance of the control.
Several other factors should be carefully evaluated when selecting a location for installation:
Series 18H V
1.
Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control.
2. V number listed on your purchase order
3.
If the control is to be stored for several weeks before use, be sure that it is stored in a location that conforms to published storage specifications. (Refer to Section 7 of this manual).
location of the 18H is important. It should be installed in an area that is protected
1.
For ef on a flat, smooth, non-flammable vertical surface. T Loss ratings for enclosure sizing.
2.
At least two inches clearance must be provided on all sides for air flow
3.
Front access must be provided to allow the control cover to be opened or removed for service and to allow viewing of the Keypad Display may optionally be remote mounted up to 100 feet from the control.)
Controls installed in a floor mounted enclosure must be positioned with clearance to open the enclosure door suf
4. Altitude derating 3300 ft, derate the continuous and peak output current by 2% for each 1000 ft.
5. T the continuous and peak output current by 2% per °C. Maximum ambient is 55°C.
ector Control is thoroughly tested at the factory and carefully packaged
erify that the part number of the control you received is the same as the part
.
fective cooling and maintenance, the control should be mounted vertically
ficient air space for cooling.
. Up to 3300 feet (1000 meters) no derating required. Above
emperature derating
. Up to 40°C no derating required. Above 40°C, derate
able 3-1 lists the W
. (The keypad
. This clearance will also provide
atts
.
Table 3-1 Series 18H Watts Loss Ratings
Enclosure
A and B
C, D, E, and F
MN718
Size
G
2.5KHz PWM
14 W
Amp
12 W
Amp
230 V
atts/
atts/
AC
8.0KHz PWM
17 W
15 W
atts/
Amp
atts/
Amp
2.5KHz PWM
17 W
Amp
15 W
Amp
15 W
Amp
460 V
atts/
atts/
atts/
AC
8.0KHz PWM
26 W
Amp
23Watts/
Amp
atts/
2.5KHz PWM
18 W
atts/
Amp
19Watts/
Amp
Receiving
575 V
AC
8.0KHz PWM
28 W
atts/
Amp
29 W
atts/
Amp
& Installation 3-1
Section 1 General Information
Control Installation The
control must be securely fastened to the mounting surface. Use the four (4)
mounting holes to fasten the control to the mounting surface or enclosure.
Shock Mounting
If the control will be subjected to levels of vibration greater than 0.5G at 10 to 60Hz, the control should be shock mounted. Excessive vibration within the control could cause internal connections to loosen and cause component failure or electrical shock hazard.
Through the Wall MountingControl
control through the wall, a Through the W are:
Kit No. Description
KT0000A00 KT0001A00 V0083991 V0084001
Procedure:
1.
2.
3.
4.
5.
6.
sizes E and F are designed for panel or through the wall installation. T
all mounting kit must be purchased. These kits
Size A control through the wall mounting kit. Size B control through the wall mounting kit. Size E control through the wall mounting kit. Size F control through the wall mounting kit.
Refer to Section 7 of this manual for drawings and dimensions of the through the wall mounting kits. Use the information contained in these drawings to layout the appropriate size hole on your enclosure and wall.
Cut the holes in your enclosure and wall. Locate and drill holes for mounting hardware as shown in the drawings. Cut foam tape and apply to perimeter of opening as shown. Secure the four (4) brackets to the exterior of the customers panel with the
hardware provided. Secure the control to the customers panel using the hardware provided.
o mount a
3-2
Receiving & Installation
MN718
Section 1 General Information
Optional Remote Keypad Installation
extension cable. The keypad assembly (white - DC00005A-01; grey - DC00005A-02) comes complete with the screws and gasket required to mount it to an enclosure. When the keypad is properly mounted to a NEMA T 4X indoor rating.
Tools Required:
Mounting Instructions: For tapped mounting holes
Mounting Instructions:
For clearance mounting holes
The keypad may be remotely mounted using the optional Baldor keypad
Center punch, tap handle, screwdrivers (Phillips and straight) and crescent wrench.
8-32 tap and #29 drill bit (for tapped mounting holes) or #19 drill (for clearance mounting holes).
1-1/4″
R
1.
2.
3.
4.
5.
6.
7.
8.
9.
1.
2.
3.
4.
5.
6.
7.
8.
9.
standard knockout punch (1-11/16″
TV sealant. (4) 8-32 nuts and lock washers. Extended 8-32 screws (socket fillister) are required if the mounting surface is
thicker than 12 gauge and is not tapped (clearance mounting holes). Remote keypad mounting template. A tear out copy is provided at the end of
this manual for your convenience.
Locate a flat 4″ wide x 5.5″ minimum high mounting surface. Material should be suf
ficient thickness (14 gauge minimum). Place the template on the mounting surface or mark the holes as shown. Accurately center punch the 4 mounting holes (marked A) and the large
knockout (marked B). Drill four #29 mounting holes (A). Thread each hole using an 8-32 tap. Locate the 1-1/4″
instructions. Debur knockout and mounting holes making sure the panel stays clean and flat. Apply R Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers. From the inside of the panel, apply R
and nuts. Cover a 3/4″ encapsulate the nut and washer
Locate a flat 4″ wide x 5.5″ minimum high mounting surface. Material should be suf
Place the template on the mounting surface or mark the holes as shown on the template.
Accurately center punch the 4 mounting holes (marked A) and the large knockout (marked B).
Drill four #19 clearance holes (A). Locate the 1-1/4″
instructions. Debur knockout and mounting holes making sure the panel stays clean and flat. Apply R Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers. From the inside of the panel, apply R
and nuts. Cover a 3/4″ encapsulate the nut and washer
TV to the 4 holes marked (A).
ficient thickness (14 gauge minimum).
TV to the 4 holes marked (A).
ype 4X indoor enclosure, it retains the T
nominal diameter).
knockout center (B) and punch using the manufacturers
TV over each of the four mounting screws
area around each screw while making sure to completely
.
knockout center (B) and punch using the manufacturers
TV over each of the four mounting screws
area around each screw while making sure to completely
.
ype
MN718
Receiving
& Installation 3-3
Section 1 General Information
Electrical Installation Interconnection
host control and any operator interface stations. Use listed closed loop connectors that are of appropriate size for wire gauge being used. Connectors are to be installed using crimp tool specified by the manufacturer of the connector used.
Baldor Series H controls feature UL approved adjustable motor overload protection suitable for motors rated at no less than 50% of the output rating of the control. Other governing agencies such as NEC may require separate over–current protection. The installer of this equipment is responsible for complying with the National Electric Code and any applicable local codes which govern such practices as wiring protection, grounding, disconnects and other current protection.
System Grounding
Baldor Controls are designed to be powered from standard three phase lines that are electrically symmetrical with respect to ground. System grounding is an important step in the overall installation to prevent problems. The recommended grounding method is shown in Figure 3-1.
Caution: Baldor recommends not using “Grounded Leg Delta” transformer
Figure 3-1 Recommended System Grounding
wiring is required between the motor control, AC power source, motor
. Only Class 1 wiring should be
power leads that may create ground loops and degrade system performance. Instead, we recommend using a four wire W
ye.
,
AC Main Supply
Safety
Ground
Driven Earth Ground Rod
(Plant Ground)
L1
L2
L3 Earth
Four Wire
“Wye”
Route all 4 wires L1, L2, L3 and Earth (Ground) together in conduit or cable.
Route all 4 wires T1, T2, T3 and Motor Ground together in conduit or cable.
Optional Line Reactor
LOCAL
JOG
DISP
FWD
SHIFT
REV
RESET
STOP
Series H
L1
L2 L3 T1 T2 T3
PROG
ENTER
Note: Wiring shown for clarity of grounding
method only. Not representative of actual terminal block location.
Optional
Load
Reactor
Ground
per NEC and
Local codes.
Connect all wires (including motor ground) inside the motor terminal box.
3-4
Receiving & Installation
MN718
Section 1 General Information
Ungrounded Distribution System
With an ungrounded power distribution system it is possible to have a continuous current path to ground through the MOV devices. T transformer with a grounded secondary is recommended. This provides three phase AC power that is symmetrical with respect ground.
Input Power Conditioning
Baldor controls are designed for direct connection to standard three phase lines that are electrically symmetrical with respect to ground. Certain power line conditions must be avoided. An AC line reactor or an isolation transformer may be required for some power conditions.
S
Baldor Series H controls require a minimum line impedance of 3%. Refer to “Line Impedance” for additional information.
S
If the feeder or branch circuit that provides power to the control has permanently connected power factor correction capacitors, an input AC line reactor or an isolation transformer must be connected between the power factor correction capacitors and the control.
S
If the feeder or branch circuit that provides power to the control has power factor correction capacitors that are switched on line and of must not be switched while the control is connected to the AC power line. If the capacitors are switched on line while the control is still connected to the AC power line, additional protection is required. TVSS (T Suppressor) of the proper rating must be installed between the AC line reactor or an isolation transformer and the AC input to the control.
o avoid equipment damage, an Isolation
f line, the capacitors
ransient V
oltage Surge
MN718
Receiving
& Installation 3-5
Section 1 General Information
Line Impedance
The Baldor Series 18H control requires a minimum line impedance of 3% (voltage drop across the reactor is 3% when the control draws rated input current). If the incoming power line has less than 3% impedance, a 3 phase line reactor can be used to provide the needed impedance in most cases. Line reactors are optional and are available from Baldor.
The input impedance of the power lines can be determined in two ways:
1.
Measure the line to line voltage at no load and at full rated load. Use these measured values to calculate impedance as follows:
(Volts
%Impedance+
2.
Calculate the short circuit current capacity of the power line. If the short circuit
NoLoadSpeed
(Volts
*Volts
NoLoadSpeed
FullLoadSpeed
)
)
100
current capacity is greater than the published maximum short circuit current ratings for the control, a line reactor should be installed.
T
wo methods of calculating short circuit current capacity are provided:
A.
Method 1 Calculate short circuit current as follows:
SC
+
(KVA
I
Example: 50KV
SC
(50 1000 100)
+
B.
I
Method 2 Step 1: Calculate KV
KVA
SC
+
(%Z
A transformer with 2.75% impedance @ 460V
(2.75 460 3Ǹ)
1000 100)
XFMR
V
XFMR
A short circuit as follows:
(KVA
XFMR
%Z
XFMR
(
)
100
3Ǹ)
L*L
AC
+2282Amps
)
+
50
ǒ
.0275
Ǔ
+1818.2KVA
Step 2: Calculate short circuit current as follows:
SC
(KVASC 1000)
+
(V
L*L
3Ǹ)
I
1818.2 1000
+
460 3
+2282Amps
Ǹ
where:
KVA
XFMR
=T
ransformer KV
A Isc=short circuit current Z
=T
XFMR
V
L–L
ransformer Impedance
=Input volts measured line to line
3-6
Receiving & Installation
MN718
Section 1 General Information
Line Reactors
Load
Reactors
Three phase line reactors are available from Baldor the *Quad Rated HP of the control. If providing your own line reactor formula to calculate the minimum inductance required. T
. The line reactor to order is based on
, use the following
able 3-3 lists the input current
required for this calculation, for each control size.
(V
0.03)
L
LL
(I 3 377)
Where:
L Minimum inductance in Henries. V
L–L
0.03 Desired percentage of input impedance. I Input current rating of control. 377 Constant used with 60Hz power.
Line reactors may be used at the control output to the motor
Input volts measured line to line.
Use 314 if input power is 50Hz.
. When used this way
, they
are called Load Reactors. Load reactors serve several functions that include:
S
Protect the control from a short circuit at the motor
S
Limit the rate of rise of motor surge currents.
S
Slowing the rate of change of power the control delivers to the motor
.
.
Load reactors should be installed as close to the control as possible. Selection should be based on the motor nameplate FLA value.
*Quad Rated HP of the control refers to the four (4) dif
ferent HP ratings of the control that are based on operating in Standard (2.5KHz PWM) or Quiet (8.0KHz PWM) in either Constant T
orque or V
ariable T
orque. The ratings are provided in Section 7 of this
manual.
MN718
Receiving
& Installation 3-7
Section 1 General Information
Table 3-2 Short Circuit Current Ratings
230VAC 460VAC 575VAC
Catalog Numbers Max. Line
Short Circuit
Amps
ZD18H201–E 250 ZD18H401–E 150 ZD18H501–E 50 ZD18H201–W 350 ZD18H401–W 200 ZD18H502–E 100 ZD18H202–E 350 ZD18H402–E 200 ZD18H503–E 150 ZD18H202–W 550 ZD18H402–W 300 ZD18H505–E 200 ZD18H203–E or W 550 ZD18H403–E or W 300 ZD18H507–E 300 ZD18H205–E 550 ZD18H405–E 300 ZD18H510–E 400 ZD18H205–W 1000 ZD18H405–W 500 ZD18H515–E, EO or ER 600 ZD18H207–E or W 1000 ZD18H407–E or W 500 ZD18H520–EO or ER 1000 ZD18H210–E 1000 ZD18H410–E 500 ZD18H525–EO or ER 1100 ZD18H210L–ER 1500 ZD18H410L–ER 800 ZD18H530–EO or ER 1500 ZD18H215–E, EO or ER 1900 ZD18H415–E, EO or ER 1000 ZD18H540–EO or ER 1800 ZD18H215L–ER 1900 ZD18H415L–ER 1000 ZD18H550–EO or ER 2200 ZD18H220–EO or ER 2400 ZD18H420–EO or ER 1200 ZD18H560–EO or ER 2700 ZD18H220L–ER 2100 ZD18H420L–ER 1200 ZD18H575–EO or ER 3300 ZD18H225–EO or ER 2800 ZD18H425–EO or ER 1400 ZD18H5100–EO or ER 4200 ZD18H225L–ER 2500 ZD18H425L–ER 1400 ZD18H5150V–EO or ER 4800 ZD18H230V–EO or ER 3600 ZD18H430V–EO or ER 1800 ZD18H230–EO or ER 3600 ZD18H430–EO or ER 1800 ZD18H230L–ER 3600 ZD18H430L–ER 1800 ZD18H240–MO or MR 4500 ZD18H440–MO or MR 2300 ZD18H240L–MR 4000 ZD18H440L–MR 2300 ZD18H250V–MO or MR 4500 ZD18H450–EO or ER 2800 ZD18H250–MO or MR 4500 ZD18H450L–ER 2800
Catalog Numbers Max. Line
Short Circuit
Amps
ZD18H460–EO or ER 3500 ZD18H460V–EO or ER 3500 ZD18H460L–ER 3500 ZD18H475–EO 4300 ZD18H475L–EO 4300 ZD18H4100–EO 5500 ZD18H4150V–EO 6200 ZD18H4150–EO 8300 ZD18H4200–EO 11000 ZD18H4250–EO 13800 ZD18H4300–EO 16600 ZD18H4350–EO 19900 ZD18H4400–EO 19900 ZD18H4450–EO 25000
Catalog Numbers Max. Line
Short Circuit
Amps
3-8
Receiving & Installation
MN718
Section 1
230 VAC Control
Input
460 VAC Control
Input
575 VAC Control
Input
General Information
Input Current Requirements
Table 3-3 Input Current Requirements
230 VAC Control Input 460 VAC Control Input 575 VAC Control Input
Catalog Numbers
ZD18H201-E or W 6.8 ZD18H401-E or W 3.4 ZD18H501-E 2.7 ZD18H202-E or W 9.6 ZD18H402-E or W 4.8 ZD18H502-E 4.0 ZD18H203-E or W 15.2 ZD18H403-E or W 7.6 ZD18H503-E 6.1 ZD18H205-E 15.2 ZD18H405-E or W 11 ZD18H505-E 11 ZD18H205-W 22 ZD18H407-E 11 ZD18H507-E 11 ZD18H207-E or W 28 ZD18H407-W 14 ZD18H510-E 11 ZD18H210-E 28 ZD18H410-E 21 ZD18H515-EO or ER 22 ZD18H210L-ER 42 ZD18H410L-ER 21 ZD18H520-EO or ER 27 ZD18H215-E 42 ZD18H415-E 21 ZD18H525-EO or ER 32 ZD18H215-EO or ER 54 ZD18H415-EO or ER 27 ZD18H530-EO or ER 41 ZD18H220-EO or ER 68 ZD18H415L-ER 27 ZD18H540-EO or ER 52 ZD18H220L-ER 60 ZD18H420-E or ER 34 ZD18H550-EO or ER 62 ZD18H225-EO or ER 80 ZD18H420L-ER 30 ZD18H560-EO or ER 62 ZD18H225L-ER 75 ZD18H425-EO or ER 40 ZD18H575-EO 100 ZD18H230-EO or ER 104 ZD18H425L-ER 38 ZD18H5100-EO 125 ZD18H230V-EO or ER 104 ZD18H430-EO or ER 52 ZD18H5150V-EO 145 ZD18H230L-ER 104 ZD18H430L-ER 52 ZD18H240-MO or MR 130 ZD18H430V-EO or ER 52 ZD18H240L-MR 115 ZD18H430L-ER 52 ZD18H250-MO or MR 130 ZD18H440-EO or ER 65 ZD18H250V-MR 130 ZD18H440L-ER 60
Amps
Catalog Numbers
ZD18H450-EO or ER 80 ZD18H450L-ER 80 ZD18H460-EO or ER 100 ZD18H460V-EO or ER 100 ZD18H460L-ER 100 ZD18H475-EO 125 ZD18H475L-EO 125 ZD18H4100-EO 160 ZD18H4150-EO 240 ZD18H4150V-EO 180 ZD18H4200-EO 310 ZD18H4250-EO 370 ZD18H4300-EO 420 ZD18H4350-EO 480 ZD18H4400-EO 540 ZD18H4450-EO 590
Amps
Catalog Numbers
Amps
MN718
Receiving
& Installation 3-9
Section 1
Control Output
I
I
Wi
p
p
General Information
AC Main Circuit
Protection Devices Be
Power Disconnect A
Wire Size and Protection Devices
Table 3-4 Wire Size and Protection Devices - 230 VAC Controls
sure a suitable input power protection device is installed. Use the recommended circuit breaker or fuses listed in Tables 3-4 through 3-6 (Wire Size and Protection Devices). Wire sizes rating power from the control will be less than the maximum, the sizes of the wire and protective devices Input
and output wire size is based on
table
is specified for NEMA B motors.
Circuit Breaker: 1 phase, thermal magnetic.
Fast Action Fuses: 230 VAC, Buss KTN
Very Fast Action: 230 VAC, Buss JJN
Time Delay Fuses: 230 VAC, Buss FRN
power
a
fail safe method to disconnect power
all
input power is removed from the control and the internal bus voltage is depleted.
and protective device specifications are based on the controls’ maximum output power
for the operating zone. Refer to Quad ratings in Section 7 of this manual.
may be adjusted accordingly
. Be sure to follow NEC, UL and other applicable codes.
If the output
the use of copper conductor wire rated at 75 °C. The
Equal to GE type THQ or TEB for 230 VAC 3 phase, thermal magnetic. Equal to GE type THQ or TEB for 230 VAC or GE type TED for 460 VAC and 575 VAC.
460 VAC, Buss KTS to 600A (KTU 601 - 1200A) 575VAC, Buss FRS
460 VAC, Buss JJS 575 VAC, , Buss JJS
460 VAC, Buss FRS to 600A (KTU 601 - 1200A) 575 VAC, Buss FRS to 600A (KTU 601 - 1200A)
disconnect should be installed between the input power service and the control for
. The control will remain in a powered-up condition until
Note: All
Power Rating
1 5A 5A 5A 14 2.5 2 10A 10A 8A 14 2.5 3 15A 15A 12A 14 2.5 5 20A 25A 12.5A 14 2.5
7.5 25A 30A 25A 12 4 10 35A 40A 35A 10 10 15 50A 60A 50A 8 10 20 60A 80A 60A 4 25 25 80A 100A 80A 4 25 30 100A 125A 100A 3 30 40 125A 150A 125A 1 50 50 150A 200A 150A 2/0 70
nput Breaker
Fast Acting Time Delay AWG mm
wire sizes based on 75°C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
nput Fuse
re Gauge
used per NEC and local codes. Recommended fuses/breakers are based on 25°C ambient, maximum continuous control output current and no harmonic current.
2
3-10
Receiving & Installation
MN718
Section 1
Control Output
I
I
Wi
p
p
General Information
Table 3-5 Wire Size and Protection Devices - 460 VAC Controls
Power Rating
1 4A 4A 3A 14 2.5 2 10A 5A 4A 14 2.5 3 10A 8A 6A 14 2.5 5 10A 12A 9A 14 2.5
7.5 15A 20A 15A 14 2.5 10 20A 25A 17.5A 12 4 15 25A 30A 25A 10 6 20 30A 40A 30A 8 10 25 40A 50A 40A 8 10 30 45A 60A 45A 6 16 40 60A 80A 60A 4 25 50 70A 100A 75A 4 25 60 90A 125A 90A 2 35 75 125A 150A 125A 1/0 54
100 150A 200A 150A 2/0 70 125 175A 250A 175A 2/0 70 150 200A 300A 200A 4/0 120 200 250A 350A 250A (2)1/0 (2)54 250 350A 450A 350A (2)3/0 (2)95 300 400A 500A 400A (2)4/0 (2)120 350 500A 600A 500A (3)4/0 (3)120 400 600A 800A 600A (3)250 mcm (3)125 450 600A 800A 600A (3)250 mcm (3)125 500 800A 1000A 800A (3)350 mcm (3)185
nput
Breaker
Fast Acting Time Delay AWG mm
nput Fuse
re Gauge
2
Note: All
wire sizes based on 75°C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 25°C ambient, maximum continuous control output current and no harmonic current.
Receiving
& Installation 3-1
1MN718
Section 1
Control Output
I
I
Wi
p
p
General Information
Table 3-6 Wire Size and Protection Devices - 575 VAC Controls
Note: All
Power Rating
1 5A 5A 4A 14 2.5 2 10A 5A 4A 14 2.5 3 10A 6A 5A 14 2.5 5 10A 10A 7A 14 2.5
7.5 10A 15A 10A 14 2.5 10 15A 15A 12A 14 2.5 15 20A 25A 20A 12 4 20 25A 35A 25A 10 6 25 30A 40A 30A 8 10 30 35A 50A 35A 8 10 40 45A 60A 45A 6 16 50 60A 80A 60A 4 25 60 70A 90A 70A 4 25 75 120A 150A 120A 3 27
100 120A 150A 120A 1/0 54 125 150A 200A 150A 2/0 70 150 175A 225A 175A 2/0 70
nput
Breaker
Fast Acting Time Delay AWG mm
wire sizes based on 75°C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
nput Fuse
re Gauge
used per NEC and local codes. Recommended fuses/breakers are based on 25°C ambient, maximum continuous control output current and no harmonic current.
2
3-12
Receiving & Installation
MN718
Section 1 General Information
AC Line Connections Be
applied to the control, wait at least 5 minutes after power disconnect for residual voltage across bus capacitors to discharge.
Reduced Input Voltage Derating
All 460 or 575V reduced input voltage. The amount of reduction is the ratio of the voltage change.
Examples:
For example, a 10HP of 9.04HP
10HP
Likewise, a 10HP
8.26HP 10HP
T
380-400 VAC Configuration
control modification is not necessary Size C, D, E, F and G controls all require modification for operation on the reduced line
voltage (380-400V
T
sure all power to the control is disconnected before proceeding. If power has been
power ratings stated in Section 7 are for the stated nominal AC input voltages (230,
AC). The power rating of the control must be reduced when operating at a
, 230V
AC control operating at 208V
.
208VAC 230VAC
.
380VAC 460VAC
o obtain the full output rating of 10HP in either case requires a 15HP Control.
Size A and B controls may be used directly with a 380-400 V
ap Change Procedure
1.
Be sure drive operation is terminated and control is disabled.
2.
Remove all power sources from the control. If power has been applied, wait at least 5 minutes for bus capacitors to discharge.
3.
Remove or open the front cover
4.
Remove the wire from terminal 5.
5.
Place the wire that was removed from terminal 5 onto terminal 4.
6.
Install or close the front cover
9.04HP
, 460V
AC control operating at 380V
8.26HP
.
AC).
(size C, D, E and F controls).
.
.
AC has a reduced power rating
AC has a reduced power rating of
AC power source,
MN718
Receiving
& Installation 3-13
Section 1 General Information
Figure 3-2 Configuring the Control Transformer Terminal Block for 380 - 400 VAC (Size G)
T
ap Change Procedure
1.
Be sure drive operation is terminated and control is disabled.
2.
Remove all power sources from the control. If power has been applied, wait at least 5 minutes for bus capacitors to discharge.
3.
Remove or open the front cover
4.
Remove the wires from the two right side terminals.
5.
Place the wires on the center terminals as shown.
6.
Install or close the front cover
(size G controls). See Figure 3-2.
.
.
460VAC 380-400VAC
3-14
Receiving & Installation
MN718
Section 1 General Information
Three Phase Input Power
Three
phase AC power and motor connections are shown in Figure 3-3. Overloads are not required. The 18H control has an electronic I2t motor overload protection. If motor overloads are desired, they should be sized according to the manufacturers specifications and installed between the motor and the T1, T2 and T3 terminals of the control.
Caution: Do not connect AC power to the Motor terminals T1, T2 and T3.
Connecting AC power to these terminals may result in damage to the control.
Caution: Baldor recommends not using “Grounded Leg Delta” transformer
power leads that may create ground loops and degrade system performance. Instead, we recommend using a four wire W
1.
Connect the incoming AC power wires from the protection devices to L1, L2 and L3 at the Main Circuit T control is not phase sensitive.
2.
* Connect earth ground to the “ ” of the control. Be sure to comply with local codes.
Note:
Use same gauge wire for earth ground as is used for L1, L2 and L3 connections. Refer to the Wire Size and Protection Devices tables shown previously in this section.
erminals. The phase rotation is not important as the
ye.
3.
Connect the three phase power leads of the AC motor to terminals T1, T2, and T3 of the Main Circuit T
4.
* Connect motor ground wire to the “ all applicable codes.
*
Grounding by using conduit or panel connection is not adequate. A separate conductor of the proper size must be used as a ground conductor
erminals.
” of the control. Be sure to comply with
.
MN718
Receiving
& Installation 3-15
Section 1 General Information
Figure 3-3 Three Phase AC Power and Motor Connections
L1 L2 L3
Note 1
Note 2
* Circuit Breaker
A1 B1 C1
Earth
Alternate *
Fuse
Connection
L1 L2 L3
Note 1
A1 B1 C1
Note 4
Note 2
Note 3
Note 4
Note 3
*Optional
Line
Reactor
*Optional
Load
Reactor
A2 B2 C2
L1 L2 L3
Baldor
Series
Control
T1 T2 T3
A1 B1 C1
A2 B2 C2
T2 T3
T1
18H
G
* Optional components not provided with 18H Control.
Notes:
1. See
2.
3.
4.
5.
“Protective Devices” described previously in this section. Shield wires inside a metal conduit. Metal conduit should be used to shield output wires (between
control and motor). Connect conduits so the use of Load Reactor or RC Device does not interrupt EMI/RFI shielding.
See Line/Load Reactors described later in this section. A motor circuit contactor is recommended to provide a positive
disconnect and prevent motor rotation which could pose a safety hazard. Connect the M-Contactor as shown. The contactor should open the enable input at J1-8 at least 20 msec before the main M-contacts open to prevent arcing at contacts. This greatly increases contactor life and allows use of IEC rated contactors.
Note 3
*Optional
Note 4
Load
Reactor
Note 3
M=Contacts of optional M-Contactor
3-16
Receiving & Installation
* AC Motor
T1 T2 T3
A1 B1 C1
A2 B2 C2
MMM
T2 T3
T1
* Motor
See Recommended Tightening Torques in Section 7.
Optional Connection of
Load Reactor and M-Contactor
G
To Power Source
(Rated Coil
Voltage)
J1
*
M Enable
7 8 9
Note 5
* M-Contactor
Note: Close “Enable” after “M” contact closure.
* Optional
RC Device
Electrocube
RG1781-3
MN718
Section 1
p
p
p
p
General Information
Table 3-7 Single Phase Rating Wire Size and Protection Devices - 230 VAC Controls
Control Output
Power Rating
1 15A 5A 5A 14 2.5 2 15A 10A 10A 14 2.5 3 15A 15A 15A 14 2.5 5 30A 30A 30A 12 4
7.5 25A 25A 25A 14 2.5 10 40A 30A 30A 12 4 15 50A 45A 45A 10 6 20 60A 45A 45A 8 10 25 70A 70A 70A 8 10 30 80A 80A 80A 6 16 40 100A 100A 100A 4 25 50 125A 125A 125A 4 25
Input Breaker Input Fuse Wire Gauge
Fast Acting Time Delay AWG mm
2
Table 3-8 Single Phase Rating Wire Size and Protection Devices - 460 VAC Controls
Control Output
Power Rating
1 15A 4A 4A 14 2.5 2 15A 8A 8A 14 2.5 3 15A 10A 10A 14 2.5 5 15A 15A 15A 14 2.5
7.5 15A 15A 15A 14 2.5 10 20A 15A 15A 14 2.5 15 25A 25A 25A 14 2.5 20 30A 30A 30A 14 2.5 25 35A 30A 30A 14 2.5 30 40A 40A 40A 10 6 40 60A 50A 50A 8 10 50 70A 60A 60A 8 10 60 80A 80A 80A 6 16
Input Breaker Input Fuse Wire Gauge
Fast Acting Time Delay AWG mm
2
Note: All
wire sizes based on 75°C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 25°C ambient, maximum continuous control output current and no harmonic current.
MN718
Receiving
& Installation 3-17
Single
Phase Input Power Considerations
Caution: Do not connect AC power to the Motor terminals T1, T2 and T3.
Connecting AC power to these terminals may result in damage to the control.
Caution: Baldor recommends not using “Grounded Leg Delta” transformer
power leads that may create ground loops and degrade system performance. Instead, we recommend using a four wire W
Single phase AC input power can be used to power the control instead of three phase for control sizes A, B, C, D, E and F
. Single phase operation of G size controls is not possible. The specifications and control sizes are listed in Section 7 of this manual. If single phase power is to be used, the rated Horsepower of the control may have to be reduced (derated). In addition, power wiring and jumper changes are required.
Single phase rating wire size and protection devices are listed in T
ables 3-7 and 3-8.
Single Phase Control Derating: Single phase power derating requires that the continuous and peak current ratings
of the control be reduced by the following percentages:
1.
1-2 HP 230 and 460 V
AC controls:
No derating required.
2.
3-15 HP (Size B) 230 and 460 V
AC controls:
Derate HP by 40% of the nameplate rating.
3.
15 HP (Size C) and Larger 230 and 460 V
AC controls:
Derate HP by 50% of the nameplate rating.
ye.
Size A and B Single Phase Power Installation
Jumper Configuration
Size A and B controls, no jumper changes required.
Power and Control Connections
The
single phase power and motor connections are shown in Figure 3-4.
1.
Connect the incoming power wires to Main Circuit T
2.
Place a jumper across control power input terminals L2 and L3. Use the same size wire for the jumper as the incoming power wires on L1 and L2.
3.
Connect earth ground to the “ codes.
Note:
Use same gauge wire for earth ground as is used for L1, L2 and L3 connections. Refer to the Wire Size and Protection Devices tables shown previously in this section.
4.
Connect the three phase power leads of the AC motor to terminals T1, T2, and T3 of the Main Circuit T
5.
Connect motor ground wire to the “ applicable codes.
Note:
In steps 3 and 5 grounding by using conduit or panel connection is not adequate. A separate conductor of the proper size must be used as a ground conductor.
erminals L1 and L2.
” of the control. Be sure to comply with local
erminals.
” of the control. Be sure to comply with all
3-18 Receiving & Installation
MN718
Section 1 General Information
Figure 3-4 Size A & B Single Phase 230/460VAC Power and Motor Connections
Note 1
* Circuit Breaker
L1 L2
Earth
* Fuse
Connection
L1 L2
Note 1
Note 2
Note 4
Note 2
Note 3
Note 5
Note 3
*Optional
Line
Reactor
*Optional
Load
Reactor
A1 B1
A2 B2
L1 L2 L3
Baldor
Series
Control
T1 T2 T3
A1 B1 C1
A2 B2 C2
T2 T3
T1
18H
G
A1 B1
* Optional
components not provided with 18H Control.
Notes:
1. See
2.
3.
“Protective Devices” described previously in this section. Shield wires inside a metal conduit. Metal conduit should be used to shield output wires (between
control and motor).
4.
See “Line Impedance” described previously in this section.
5.
See Line/Load Reactors described previously in this section.
6.
A motor circuit contactor is recommended to provide a positive disconnect and prevent motor rotation which could pose a safety hazard. Connect the M-Contactor as shown. The contactor should open the enable input at J1-8 at least 20 msec before the main M-contacts open to prevent arcing at contacts. This greatly increases contactor life and allows use of IEC rated contactors.
Note 3
Note 5
Note 3
M=Contacts of optional M-Contactor
*Optional
Load
Reactor
Note 6
MN718
* AC Motor
T1 T2 T3
A1 B1 C1
A2 B2 C2
MMM
T2 T3
T1
* Motor
See
Recommended T
Optional Connection of
Load Reactor and M-Contactor
To Power Source
Note 6
G
ightening T
M Enable
orques in Section 7.
(Rated Coil
Voltage)
*
Note 6
* M-Contactor
J1
7 8 9
* Optional RC Device
Electrocube
RG1781-3
Note: Close “Enable” after “M” contact closure.
Receiving & Installation 3-19
Size C and D Single Phase Power Installation
Figure 3-5
Place JP2 on pins 1 & 2 for control single phase operation.
Place JP3 in position B for fan single phase operation.
Gate Drive Circuit Board
Jumper Configuration
J2
J3
JP2
Pins 1 & 2 = Single Phase Pins 2 & 3 = Three Phase
8380
J4 J5
R24
R27
JP2 1
JP3
Position A = Three Phase Position B = Single Phase
R35
R36
R58
JP3
A
B
Power and Control Connections
The
single phase power and motor connections are shown in Figure 3-4.
1.
Connect the incoming power wires to Main Circuit T
2.
Place a jumper across control power input terminals L1 and L2. Use the same size wire for the jumper as the incoming power wires on L2 and L3.
erminals L2 and L3.
1
JP1
J14J12
J13
AC INPUT
3.
Connect earth ground to the “ codes.
Note:
4.
Connect the three phase power leads of the AC motor to terminals T1, T2, and T3 of the Main Circuit T
5.
Connect motor ground wire to the “ applicable codes.
Note:
3-20
Receiving & Installation
” of the control. Be sure to comply with local
Use same gauge wire for earth ground as is used for L1, L2 and L3 connections. Refer to the Wire Size and Protection Devices tables shown previously in this section.
erminals.
” of the control. Be sure to comply with all
In steps 3 and 5 grounding by using conduit or panel connection is not adequate. A separate conductor of the proper size must be used as a ground conductor.
MN718
Section 1 General Information
Figure 3-6 Size C & D Single Phase 230/460VAC Power and Motor Connections
Note 1
* Circuit Breaker
L1 L2
Earth
* Fuse
Connection
L1 L2
Note 1
Note 2
Note 4
Note 2
Note 3
Note 5
Note 3
*Optional
Load
Reactor
B1 C1
*Optional
Line
Reactor
B2 C2
L1 L2 L3
Baldor
Series
Control
T1 T2 T3
A1 B1 C1
A2 B2 C2
T1
18H
T2 T3
B1 C1
* Optional
components not provided with 18H Control.
Notes:
1. See
2.
3.
“Protective Devices” described previously in this section. Shield wires inside a metal conduit. Metal conduit should be used to shield output wires (between
control and motor).
4.
See “Line Impedance” described previously in this section.
5.
See Line/Load Reactors described previously in this section.
6.
A motor circuit contactor is recommended to provide a positive disconnect and prevent motor rotation which could pose a safety hazard. Connect the M-Contactor as shown. The contactor should open the enable input at J1-8 at least 20 msec before the main M-contacts open to prevent arcing at contacts. This greatly increases contactor life and allows use of IEC rated contactors.
G
Note 3
Note 5
Note 3
M=Contacts of optional M-Contactor
*Optional
Load
Reactor
Note 6
MN718
* AC Motor
T1 T2 T3
A1 B1 C1
A2 B2 C2
MMM
T2 T3
T1
* Motor
See
Recommended T
Optional Connection of
Load Reactor and M-Contactor
To Power Source
Note 6
G
ightening T
M Enable
orques in Section 7.
(Rated Coil
Voltage)
*
Note 6
* M-Contactor
J1
7 8 9
* Optional RC Device
Electrocube
RG1781-3
Note: Close “Enable” after “M” contact closure.
Receiving & Installation 3-21
Size E Single Phase Power Installation
Place
JP1 on the High V
1
JP2
ANS
DUAL 230V
FANS
SINGLE
230V F
CNTRL XFMR
400V PRI
CNTRL XFMR
460V PRI
AC INPUT J2
8470
Figure 3-7 Jumper Configuration
oltage Circuit Board across pins 1 and 2.
High Voltage Circuit Board (100 - 150HP E Size)
1
JP1
JP1
Pins 1 & 2 = Single Phase Pins 2 & 3 = Three Phase
J7
J8
Power and Control Connections
The
single phase power and motor connections are shown in Figure 3-8.
1.
Connect the incoming power wires to Main Circuit T
2.
Place a jumper across control power input terminals L2 and L3. Use the same size wire for the jumper as the incoming power wires on L1 and L2.
3.
Connect earth ground to the “
” of the control. Be sure to comply with local
codes. Note:
Use same gauge wire for earth ground as is used for L1, L2 and L3 connections. Refer to the Wire Size and Protection Devices tables shown previously in this section.
4.
Connect the three phase power leads of the AC motor to terminals T1, T2, and T3 of the Main Circuit T
5.
Connect motor ground wire to the “
erminals.
” of the control. Be sure to comply with all
applicable codes.
Note:
In steps 3 and 5 grounding by using conduit or panel connection is not adequate. A separate conductor of the proper size must be used as a ground conductor.
erminals L1 and L2.
3-22
Receiving & Installation
MN718
Section 1 General Information
Figure 3-8 Size E Single Phase 230/460VAC Power and Motor Connections
Note 1
* Circuit Breaker
L1 L2
Earth
* Fuse
Connection
L1 L2
Note 1
Note 2
Note 4
Note 2
Note 3
Note 5
Note 3
*Optional
Line
Reactor
*Optional
Load
Reactor
A1 B1
A2 B2
L1 L2 L3
Baldor
Series
Control
T1 T2 T3
A1 B1 C1
A2 B2 C2
T2 T3
T1
18H
G
A1 B1
* Optional
components not provided with 18H Control.
Notes:
1. See
2.
3.
“Protective Devices” described previously in this section. Shield wires inside a metal conduit. Metal conduit should be used to shield output wires (between
control and motor).
4.
See “Line Impedance” described previously in this section.
5.
See Line/Load Reactors described previously in this section.
6.
A motor circuit contactor is recommended to provide a positive disconnect and prevent motor rotation which could pose a safety hazard. Connect the M-Contactor as shown. The contactor should open the enable input at J1-8 at least 20 msec before the main M-contacts open to prevent arcing at contacts. This greatly increases contactor life and allows use of IEC rated contactors.
Note 3
Note 5
Note 3
M=Contacts of optional M-Contactor
*Optional
Load
Reactor
Note 6
MN718
* AC Motor
T1 T2 T3
A1 B1 C1
A2 B2 C2
MMM
T2 T3
T1
* Motor
See
Recommended T
Optional Connection of
Load Reactor and M-Contactor
To Power Source
Note 6
G
ightening T
M Enable
orques in Section 7.
(Rated Coil
Voltage)
*
Note 6
* M-Contactor
J1
7 8 9
* Optional RC Device
Electrocube
RG1781-3
Note: Close “Enable” after “M” contact closure.
Receiving & Installation 3-23
Size F Single Phase Power Installation
Place JP2 on the High Voltage Circuit Board across pins 1 and 2.
High Voltage Circuit Board (150 - 250HP F Size)
Figure 3-9 Jumper Configuration
J5
JP1
JP2
1
JP2
Pins 1 & 2 = Single Phase Pins 2 & 3 = Three Phase
J1 J4J3
Power and Control Connections
The
single phase power and motor connections are shown in Figure 3-10.
1.
Connect the incoming power wires to Main Circuit T
2.
Place a jumper across control power input terminals L1 and L3. Use the same size wire for the jumper as the incoming power wires on L2 and L3.
erminals L2 and L3.
J2
3.
Connect earth ground to the “ codes.
Note:
4.
Connect the three phase power leads of the AC motor to terminals T1, T2, and T3 of the Main Circuit T
5.
Connect motor ground wire to the “ applicable codes.
Note:
3-24
Receiving & Installation
” of the control. Be sure to comply with local
Use same gauge wire for earth ground as is used for L1, L2 and L3 connections. Refer to the Wire Size and Protection Devices tables shown previously in this section.
erminals.
” of the control. Be sure to comply with all
In steps 3 and 5 grounding by using conduit or panel connection is not adequate. A separate conductor of the proper size must be used as a ground conductor.
MN718
Section 1 General Information
Figure 3-10 Size F Single Phase 230/460VAC Power and Motor Connections
Note 1
* Circuit Breaker
L1 L2
Earth
* Fuse
Connection
L1 L2
Note 1
Note 2
Note 4
Note 2
Note 3
Note 5
Note 3
*Optional
Load
Reactor
B1 C1
*Optional
Line
Reactor
B2 C2
L1 L2 L3
Baldor
Series
Control
T1 T2 T3
A1 B1 C1
A2 B2 C2
T1
18H
T2 T3
B1 C1
* Optional
components not provided with 18H Control.
Notes:
1. See
2.
3.
“Protective Devices” described previously in this section. Shield wires inside a metal conduit. Metal conduit should be used to shield output wires (between
control and motor).
4.
See “Line Impedance” described previously in this section.
5.
See Line/Load Reactors described previously in this section.
6.
A motor circuit contactor is recommended to provide a positive disconnect and prevent motor rotation which could pose a safety hazard. Connect the M-Contactor as shown. The contactor should open the enable input at J1-8 at least 20 msec before the main M-contacts open to prevent arcing at contacts. This greatly increases contactor life and allows use of IEC rated contactors.
G
Note 3
Note 5
Note 3
M=Contacts of optional M-Contactor
*Optional
Load
Reactor
Note 6
MN718
* AC Motor
T1 T2 T3
A1 B1 C1
A2 B2 C2
MMM
T2 T3
T1
* Motor
See
Recommended T
Optional Connection of
Load Reactor and M-Contactor
To Power Source
Note 6
G
ightening T
M Enable
orques in Section 7.
(Rated Coil
Voltage)
*
Note 60
* M-Contactor
J1
7 8 9
* Optional RC Device
Electrocube
RG1781-3
Note: Close “Enable” after “M” contact closure.
Receiving & Installation 3-25
Section 1 General Information
Optional Dynamic Brake Hardware
W
ARNING:
Resistors may generate enough heat to ignite combustible materials. T
o avoid fire hazard, keep all combustible materials and
flammable vapors away from brake resistors.
Physical Installation Dynamic
surface to obtain ef exceed 80
1.
Caution: If the DB hardware mounting is in any position other than vertical
2.
Figure 3-11 DB Hardware Installation
Brake (DB) Hardware must be installed on a flat, non-flammable, vertical
fective cooling and operation. The ambient temperature must not
°C.
Select a clean
VERTICAL
surface that is free from corrosive gasses, liquids,
vibration, dust and metallic particles.
(Figure 3-1
1), the DB hardware must be derated by 35% of its rated
capacity.
Mount the DB hardware as shown in Figure 3-1
Maximum
temperatures
near wall.
80°C
70°C
65°C
70°C
Maximum temperatures above the enclosure.
85°C
115°C
115°C
200°C
12
48
36
24
1.
75°C
Heat shield inside RBA units must be in this vertical direction to protect transistor and circuit board.
3-26
Receiving & Installation
MN718
Section 1 General Information
Electrical Installation Terminal
(E, EO, ER or MO). See Figure 3-12 for terminal identification.
Figure 3-12 DB Terminal Identification
“E” or “W” suffix
“EO” or “MO” suffix
“ER” suffix
Figure 3-13 Wiring for RGA Assembly
MOTOR
GND
connections for DB hardware is determined by 18H Control model number suf
R2 B+/R1 B–
B+ B– GND D1 D2 GND
R2 B+/R1 B– GND
Control
Terminals
GND
R2
B+/R1
T3
T2
T1
T3 T2
T1
DB
Terminals
R2 R1
Optional
Dynamic Brake
(RGA)
fix
Optional Customer Supplied Breaker or Fuse Protection -
Subject to Local Codes
50/60 Hz 3 Phase Power
Note: Although
and motor leads.
L3 L2 L1
GND
See recommended Terminal Tightening Torques in Table 3-10.
not shown, metal conduit should be used to shield all power wires
MN718
Receiving
& Installation 3-27
Section 1 General Information
Figure 3-14 Wiring for RBA Assembly
Optional Customer Supplied
Breaker or Fuse Protection -
Subject to Local Codes
See recommended Terminal Tightening Torques in Section 7.
DB
Terminals
D1 D2
Dynamic Brake
B– B+
MOTOR
GND
50/60 Hz 3 Phase Power
Control
Terminals
T3
T2
T1
D1 D2
GND
B–
B+
T3 T2
T1
L3 L2 L1
Shielded Twisted Pair
See recommended Terminal Tightening Torques in Table 3-9.
Note: Although
GND
not shown, metal conduit should be used to shield all power wires
and motor leads.
Figure 3-15 Wiring for RTA Assembly
MOTOR
GND
D1 D2
GND
B– B+
T3 T2
T1
Shielded Twisted Pair
Control
Terminals
T3
T2
T1
DB
Terminals
D1 D2
B– B+
Optional
(RBA)
Optional
Dynamic Brake
(RTA)
R2R1
R2R1
50/60 Hz 3 Phase Power
Optional Customer Supplied Breaker or Fuse Protection -
Subject to Local Codes
See recommended Terminal Tightening Torques in Section 7.
Note: Although
3-28
Receiving & Installation
L3 L2 L1
GND
not shown, metal conduit should be used to shield all power wires
and motor leads.
Optional
RGA
Assembly
See recommended Terminal
T
Tightening
orques in Table 3-10.
MN718
Section 1
Control
Braking
g
General Information
Table 3-9 Terminal Torques & Wire Size for Model No. Suffix E or W
Table 3-10 Terminal Torques & Wire Size for Model No. Suffix EO, MO, or ER
B+ / B– / R1 / R2 /
Control Voltage Rating
VAC
230, 460, 575 10 6 600 2.26 20
Wire SIze
AWG mm
Terminals
Volt
2
Tightening
Torque
Nm Lb–in
B+ / B– and R1 / R2 /
Control Braking
Voltage Rating
VAC
230 <10,000 10 6 600 2.26 32 20-22 0.5 600 0.4 3.5 230 >10,000 8 10 600 2.26 32 20-22 0.5 600 0.4 3.5 460 <20,000 10 6 600 2.26 32 20-22 0.5 600 0.4 3.5 460 >20,000 8 10 600 2.26 32 20-22 0.5 600 0.4 3.5 575 <20,000 10 6 600 2.26 32 20-22 0.5 600 0.4 3.5 575 >20,000 8 10 600 2.26 32 20-22 0.5 600 0.4 3.5
Option
Watts Rating
Terminals
Wire SIze
AWG mm
Tightening
Volt
2
Torque
Nm Lb–in AWG mm
Wire SIze
D1 / D2 / Terminals
Volt
2
Table 3-11 DB Terminal Torques (All)
Tightening Torque
Nm Lb–in
2.26 32
Tightening
Torque
Nm Lb–in
MN718
Receiving
& Installation 3-29
Section 1 General Information
Encoder Installation
Electrical isolation of the encoder shaft and housing from the motor is required. Electrical isolation prevents capacitive coupling of motor noise that will corrupt the encoder signals. See electrical noise considerations in Section 7 of this manual.
Cable Preparation
Encoder wiring must be shielded twisted pairs, #22 A 200
(60m) maximum, with an insulated overall shield.
Control End (See Figure 3-16.)
1.
Strip the outside jacket approximately 0.375″ (9.5mm) from the end.
2.
Solder a #22 A
3.
Connect all shields to J1-30. T to the wire soldered to the braided shield in step 2.
4.
Insulate or tape of conductors or ground.
Encoder End
1.
Strip the outside jacket approximately 0.375″ (9.5mm) from the end.
2.
Identify each of the four twisted pair and label or use the color codes shown in Figure 3-17 for the optional Baldor Encoder Cable.
3.
Insulate or tape of prevent contact with other conductors or ground.
CAUTION:
Do not connect any shields to the encoder case or motor frame. The encoder +5VDC supply at J1-29 is referenced to circuit board common. Do not connect any shields to ground or another power supply or damage to the control may result.
WG (0.34mm2) wire to the braided shield.
o do this, solder a “Drain Wire” from each shield
f ungrounded end of shields to prevent contact with other
f ungrounded end of shields and unused conductors to
WG (0.34mm2) minimum size,
Figure 3-16 Encoder Cables
No.
9891
3-30
Receiving & Installation
MN718
Section 1 General Information
Figure 3-17 Encoder Connections
H
GJC
FED
No Connection
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
Encoder Cable Connection
Encoder cable must wires. Encoder cables that cross power wires must cross at a 90° angle only wires must be #22 A have an overall shield.
Note:
Be careful not to pinch the wires’ insulation in J1 terminals as proper electrical connection may not be made.
be separated by at least 3” (76mm) from parallel runs of power
WG (0.34mm2) minimum, 200 feet (60m) maximum length and must
AB
K
. Encoder
1.
Feed the control end of the cable through one of the “Knock-out” holes in the control case so connections can be made inside the control.
2. Differential Connections Connect the cable braided shield to J1-30 at control end.
Connect the cable ends as follows: (See Figure 3-17.)
Encoder End
Control End
A J1-23 (A) H
J1-24 (A
) B J1-25 (B) J C K D F E
3.
Single Ended Connections
Dif
ferential inputs are recommended for best noise immunity
J1–26 (B
) J1–27 Index(C) J1–28 Index(C
) J1–29 (+5VDC) J1–30 (Common) No Connection
. If only single ended encoder signals are available, connect them to A, B, and INDEX (C) (J1-23, J1-25 and J1-27 respectively).
MN718
Receiving
& Installation 3-31
Section 1 General Information
Home (Orient) Switch InputThe
position. The homing function allows shaft rotation in the drive forward direction only The home position is located when a machine mounted switch or the encoder “Index” pulse is activated (closed). Home is defined by a rising signal edge at terminal J1-27. The shaft will continue to rotate only in a “Drive Forward” direction for a user defined of
fset value. The of parameter Miscellaneous Homing Speed parameter
A machine mounted switch may be used to define the Home position in place of the encoder index channel. A dif preferred for best noise immunity J1-28.
A single ended solid-state switch or limit switch should be wired as shown in Figure 3-18. Regardless of the type of switch used, clean rising and falling edges at J1-27 are required for accurate positioning.
Figure 3-18 Typical Home or Orient Switch Connections
+5V Input
Output Common
Home or Orient function causes the motor shaft to rotate to a predefined home
fset is programmed in the Level 2 Miscellaneous Homing Of
fset
. The speed at which the motor will “Home” or orient is set with the Level 2
.
ferential line driver output from a solid state switch is
. Connect this dif
Note:
Control requires dynamic brake hardware for Orient (Homing) function to
ferential output to terminals J1-27 and
work. Control will trip without dynamic brake hardware installed. Size A and B controls ( “–E” suf
fix) are shipped with factory installed dynamic brake
hardware.
J1
27 28 29
30
INDEX INDEX +5V Common
J1
27 28 29
30
INDEX INDEX +5V Common
.
Buffered Encoder Output The
3-19. This output may be used by external hardware to monitor the encoder signals. It is recommended that this output only drive one output circuit load.
From Processor
Terminal 7 lb–in (0.8 Nm) maximum.
tightening torque is
Limit Switch (Closed at HOME).5VDC Proximity Switch
Terminal Tightening Torque = 7 Lb-in. (0.8 Nm).
control provides a buffered encoder output on pins J1-31 to J1-38 as shown in Figure
Figure 3-19 Buffered Encoder Output
J1
29
+5VDC
30
COMMON
31
A
IN A
IN IN C IN D
B
26LS31
E
A A B B
C
C D D
E
32 33 34 35 36 37 38
A B
B INDEX INDEX Not Used
COMMON
Buffered Encoder Output
3-32
Receiving & Installation
MN718
Section 1 General Information
Control Circuit Connections
Eight dif operating modes define the basic motor control setup and the operation of the input and output terminals. After the circuit connections are completed, the operating mode is selected by programming the Operating Mode parameter in the Level 1 Input programming Block. A
ferent operating modes are available in the Series 18H vector control. These
vailable operating modes include:
Keypad Control
Standard Run, 3 Wire Control
15 Speed, 2 Wire Control
Fan Pump 2 Wire Control
Fan Pump 3 Wire Control
Bipolar Speed or T
Process Control
Serial
Note:
The Serial operating mode requires one of the optional Serial Interface expansion boards (RS232 or 422/485). Installation and operation information for these serial expansion boards is provided in Serial Communications expansion board manual MN1310. This manual is shipped with the serial expansion boards.
orque
Keypad Mode Connections
To to Keypad. In this mode, only the External T 2 Protection block, External T active. Connections are made as shown in Figure 3-20.
operate in the Keypad mode, set the Level 1 Input block, Operating Mode parameter
rip Opto Input at J1-16 is active (if the Level
rip parameter is set to ON). Both analog outputs remain
The ST
S Press ST
S Press ST
OP key can operate in either of two ways:
OP key one time to brake or coast to stop (as set in the Level 1
Keypad Setup block, Keypad Stop Mode parameter).
OP key two times to disable control.
MN718
Receiving
& Installation 3-33
Section 1
J
General Information
Note 1
Notes:
1. Refer
2.
3.
4.
Programmable 0–5V Output (Factory Preset: Speed)
Programmable 0–5V Output (Factory Preset: Current)
to Analog Outputs. Refer to Opto Isolated Outputs. Refer to Encoder Installation. Refer to Buf
fered Encoder Outputs.
Refer to Figure NO
Figure 3-20 Keypad Control Connection Diagram
1
No Connections Required
No Connections (Inactive)
TAG.
Note 2
ANALOG GND
ANALOG INPUT 1
POT REFERENCE ANALOG INPUT +2 ANALOG INPUT –2
ANALOG OUT 1 ANALOG OUT 2
EXTERNAL TRIP
O INPUT COMMON
OPT
OPT
O OUT COMMON
OPTO OUT #1 OPTO OUT #2 OPTO OUT #3 OPTO OUT #4
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
ENABLE INPUT #1 INPUT #2 INPUT #3 INPUT #4 INPUT #5
INPUT #7
1
23
2
24
3
25
4
26
5
27
6
28
7
29
8
30
9
31
10
32
11
33
12
34
13
6
35
14
36
15
37
16
38
17
39
18
40
19
41
20
42
21
43
22
44
A A B B INDEX INDEX +5VDC
COMMON A A B B INDEX INDEX Not Used COMMON +24VDC
OPTO IN POWER OPTO OUT #1 RETURN
OPTO OUT #2 RETURN OPTO OUT #3 RETURN OPTO OUT #4 RETURN
Encoder Input Note 3
Buffered Encoder Output Note 4INPUT #1
J1-8 Optional, is active when Level 2 Protection block, Local Enable INP parameter is set to
ON. OPEN disables the control and motor coasts to a stop. CLOSED allows current to flow in the motor and produce torque.
J1-16 OPEN causes an external trip to be received by control. The control will disable and
J1-39 & 40 Jumper as shown to power the Opto Inputs from the internal +24VDC supply.
display external trip when programmed “ON”. When this occurs, the motor stop command is issued, drive operation is terminated and an external trip fault is displayed on the keypad display (also logged into the fault log). If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
3-34
Receiving & Installation
MN718
Section 1 General Information
Standard Run 3 Wire Mode Connections
In
Standard Run mode, the control is operated by the opto Isolated inputs at J1-8 through J1-16 and the analog command input. The opto inputs can be switches as shown in Figure 3-21 or logic signals from another device. The External T active if connected as shown and the Level 2 Protection block, External Trip parameter is set to ON.
rip opto input at J1-16 is
MN718
Receiving
& Installation 3-35
Section 1 General Information
Figure 3-21 Standard Run 3-Wire Connection Diagram
Note 1
Note 4
Note 2
Notes:
1. Refer
2.
3.
4.
5.
6.
Programmable 0–5V Output (Factory Preset: Speed) Programmable 0–5V Output (Factory Preset: Current)
to Analog Inputs. Refer to Analog Outputs. Refer to Opto Isolated Outputs. Refer to Figure NO TAG for 4-20mA. Refer to Encoder installation. Refer to Buf
fered Encoder Output.
Refer to Figure NO
5kW Command Pot
±5VDC, ±10VDC or 4-20mA
TAG.
Note 3
ANALOG GND
ANALOG INPUT 1
POT REFERENCE ANALOG INPUT +2 ANALOG INPUT –2
ANALOG OUT 1 ANALOG OUT 2
FORWARD RUN
REVERSE RUN
ACCEL/DECEL
PRESET SPEED #1
FAULT RESET
EXTERNAL TRIP
O INPUT COMMON
OPT
OPT
O OUT COMMON
OPTO OUT #1 OPTO OUT #2 OPTO OUT #3 OPTO OUT #4
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
ENABLE
STOP
JOG
1 2 3 4 5
7 8
9 10 11 12 13 14 15
16 17 18
19 20 21 22
J1
23
A
24
A B
25
B
26
INDEX
27
6
INDEX
28
+5VDC
29
30
COMMON A
31
A
32
B
33
B
34
INDEX
35
INDEX
36
Not Used
37 38
COMMON
39
+24VDC
40
OPTO IN POWER
41
OPTO OUT #1 RETURN
42
OPTO OUT #2 RETURN
43
OPTO OUT #3 RETURN
44
OPTO OUT #4 RETURN
Encoder Input Note 5
Buffered Encoder Output Note 6
J1-8 OPEN disables the control and motor coasts to a stop.
CLOSED allows current to flow in the motor and produce torque.
J1-9 MOMENTARY CLOSED starts motor operation in the Forward direction. In JOG mode
(J1-12 CLOSED), continuous CLOSED jogs motor in the Forward direction.
J1-10 MOMENTARY CLOSED starts motor operation in the Reverse direction. In JOG mode
(J1-12 CLOSED), CONTINUOUS closed JOGS motor in the Reverse direction.
J1-11 MOMENTARY OPEN causes motor to decel to stop (depending on Keypad Stop Mode
parameter setting). Motor current continues to be applied to the motor.
J1-12 CLOSED places control in JOG mode, Forward and Reverse run are used to jog the
motor.
J1-13 OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J1-14 CLOSED selects preset speed #1, (J1-12, will override this preset speed).
OPEN allows speed command from Analog input #1 or #2 or Jog.
J1-15 CLOSED to reset fault condition.
OPEN to run.
J1-16 OPEN causes an external trip to be received by control. The control will disable and
J1–39 & 40 Jumper as shown to power the Opto Inputs from the internal +24VDC supply.
display external trip when programmed “ON”. When this occurs, the motor stop command is issued, drive operation is terminated and an external trip fault is displayed on the keypad display (also logged into the fault log). If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
3-36
Receiving & Installation
MN718
Section 1 General Information
15 Speed 2-Wire Mode Connections
Operation in the 15 Speed 2-Wire mode is controlled by the Opto Isolated inputs at J1-8 through J1-16. The Opto inputs can be switches as shown in Figure 3-22 or logic signals from another device. The External T shown and the Level 2 Protection block, External T
Switched inputs at J1-11 through J1-14 allow selection of 15 preset speeds and provide Fault Reset as defined in T
Table 3-12 Switch Truth Table for 15 Speed, 2 Wire Control Mode
Function J1-11 J1-12 J1-13 J1-14
Preset 1 Open Open Open Open Preset 2 Closed Open Open Open Preset 3 Open Closed Open Open Preset 4 Closed Closed Open Open Preset 5 Open Open Closed Open Preset 6 Closed Open Closed Open Preset 7 Open Closed Closed Open Preset 8 Closed Closed Closed Open Preset 9 Open Open Open Closed
Preset 10 Closed Open Open Closed
Preset 11 Open Closed Open Closed Preset 12 Closed Closed Open Closed Preset 13 Open Open Closed Closed Preset 14 Closed Open Closed Closed Preset 15 Open Closed Closed Closed
Fault Reset Closed Closed Closed Closed
Switch T
ruth T
able is defined in T
able 3-12.
able 3-12.
rip Opto Input at J1-16 is active if connected as
rip parameter is set to ON.
MN718
Receiving
& Installation 3-37
Section 1 General Information
Figure 3-22 15 Speed 2-Wire Control Connection Diagram
Note 1
Notes:
1. Refer
2.
Refer to Opto Isolated Outputs.
3.
Refer to Encoder installation.
4.
Refer to Buf
* Refer to truth table, Table 3-12.
Programmable 0–5V Output (Factory Preset: Speed) Programmable 0–5V Output (Factory Preset: Current)
Both CLOSED= Forward
Both OPEN = Stop
* All CLOSED= Fault
to Analog Outputs.
fered Encoder Output.
Refer to Figure NO
No Connections
Reset
TAG.
Note 2
ANALOG GND
ANALOG INPUT 1
POT REFERENCE ANALOG INPUT +2 ANALOG INPUT –2
ANALOG OUT 1 ANALOG OUT 2
ENABLE
FORWARD RUN
REVERSE RUN
* SWITCH 1 * SWITCH 2 * SWITCH 3 * SWITCH 4
ACC/DEC/“S” SELECT 1
EXTERNAL TRIP
O INPUT COMMON
OPT
OPT
O OUT COMMON
OPTO OUT #1 OPTO OUT #2 OPTO OUT #3 OPTO OUT #4
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
1 2 3 4 5
7 8
9 10 11 12 13 14 15
16 17 18
19 20 21 22
J1
23
A
24
A B
25
B
26
INDEX
27
6
INDEX
28
+5VDC
29
30
COMMON A
31
A
32
B
33
B
34
INDEX
35
INDEX
36
Not Used
37 38
COMMON
39
+24VDC
40
OPTO IN POWER
41
OPTO OUT #1 RETURN
42
OPTO OUT #2 RETURN
43
OPTO OUT #3 RETURN
44
OPTO OUT #4 RETURN
Encoder Input Note 3
Buffered Encoder Output Note 4
J1-8 OPEN disables the control & motor coasts to a stop. CLOSED allows current to flow in
the motor and produce torque.
J1-9 CLOSED operates the motor in the Forward direction (with J1-10 open).
OPEN motor decels to stop (depending on Keypad Stop mode parameter setting).
J1-10 CLOSED operates motor in the Reverse direction (with J1-9 open).
OPEN motor decels to stop depending on Keypad Stop mode parameter setting.
J1-11 to Selects programmed preset speeds as defined J1-14 in Table 3-12.
J1-15 Selects ACC/DEC group. OPEN selects group 1. CLOSED selects group 2. J1-16 OPEN causes an external trip to be received by control. The control will disable and
J1-39 & Jumper as shown to power the Opto Inputs from the internal +24VDC supply. 40
display external trip when programmed “ON”. When this occurs, the motor stop command is issued, drive operation is terminated and an external trip fault is displayed on the keypad display (also logged into the fault log). If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
3-38
Receiving & Installation
MN718
Section 1 General Information
Fan Pump 2 Wire Control Mode
Figure 3-23 Fan Pump, 2 Wire Control Connection Diagram
Note 1
Notes 1 and 2
Note 3
Notes:
1. Refer
2.
3.
4.
5.
6.
7.
Programmable 0–5v Output (Factory Preset: Speed) Programmable 0–5v Output (Factory Preset: Current)
Both CLOSED=
Fault Reset
Note 4
Refer Figure
to Analog Inputs.
NO T AG.
Refer to Figure NO TAG for 4-20mA.
Refer to Analog Outputs. Refer to Opto Isolated Inputs. Refer to Opto Isolated Outputs. Refer to Encoder installation. Refer to Buf
fered Encoder Output.
J1
ANALOG GND
0-10VDC or 5kW Command Pot
±5VDC, ±10VDC or 4-20mA
to
Note 5
J1-8 OPEN disables the control and motor coasts to a stop.
CLOSED allows current to flow in the motor.
J1-9 CLOSED starts motor operation in the Forward direction.
OPEN initiates Stop command.
J1-10 CLOSED starts motor operation in the Reverse direction.
OPEN initiates Stop command.
J1-11 OPEN selects setting of “Command Select” parameter. Closed selects Analog Input #1.
Note: If Command Select (Level 1 Input block) is set to Potentiometer, then Analog Input
#1 is always selected regardless of this switch position.
J1-12 Run Command. OPEN selects STOP/START and Reset commands from Keypad.
CLOSED selects STOP/START and Reset commands from terminal strip.
J1-13 Speed Command. OPEN selects speed commanded from Keypad.
CLOSED selects terminal strip speed source (selected in the Level 1 Input block, Command Select parameter).
Note: When changing from Keypad to Terminal Strip (J1-12 or J1-13) the motor speed and
direction will remain the same after the change.
J1-14 OPEN selects preset speed #1 regardless of the Speed Command input J1-13.
(FIRESTAT).
J1-15 OPEN selects preset speed #2 regardless of the Speed Command input J1-13.
(FREEZESTAT).
Note: If J1-14 and J1-15 are both Open, Preset Speed #1 is selected.
J1-16 OPEN causes an external trip to be received by control. The control will disable and
display external trip when programmed “ON”. When this occurs, the drive is disabled and an external trip fault is displayed on the keypad display (also logged into the fault log). If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
ANALOG INPUT 1
POT REFERENCE ANALOG INPUT +2 ANALOG INPUT –2
ANALOG OUT 1 ANALOG OUT 2
ENABLE
FORWARD RUN
REVERSE RUN
ANALOG INPUT SELECT
RUN COMMAND
SPEED COMMAND
PRESET SPEED #1
PRESET SPEED #2
EXTERNAL TRIP
O INPUT COMMON
OPT
OPT
O OUT COMMON
OPTO OUT #1 OPTO OUT #2 OPTO OUT #3 OPTO OUT #4
1
23
A
2
24
A
3
25
B
4
26
B
5
27
INDEX
6
28
INDEX
7
29
+5VDC
8
30
9 10 11 12 13 14 15
16 17 18
19 20 21 22
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
COMMON
31
A A
32
B
33
B
34
INDEX
35
INDEX
36
Not Used
37 38
COMMON
39
+24VDC
40
OPTO IN POWER
41
OPTO OUT #1 RETURN
42
OPTO OUT #2 RETURN
43
OPTO OUT #3 RETURN
44
OPTO OUT #4 RETURN
Encoder Input Note 6
Buffered Encoder Output Note 7
MN718
Receiving
& Installation 3-39
Section
1
General Information
Fan Pump 3 Wire Control Mode
Figure 3-24 Fan Pump, 3 Wire Control Connection Diagram
Note 1
Notes 1 and 2
Note 3
Programmable 0–5v Output (Factory Preset: Speed) Programmable 0–5v Output (Factory Preset: Current)
Note 4
Notes:
1. Refer
2.
to Analog Inputs.
Refer to Figure NO TAG for 4-20mA.
3.
Refer to Analog Outputs.
4.
Refer to Opto Isolated Inputs.
5.
Refer to Opto Isolated Outputs.
6.
Refer to Encoder installation.
7.
Refer to Buf
fered Encoder Output.
±5VDC, ±10VDC or 4-20mA.
Both CLOSED=
J1
ANALOG GND
0-10VDC or 5kW Command Pot
Fault Reset
Refer
to Figure NO T AG.
Note 5
J1-8 OPEN disables the control and motor coasts to a stop.
CLOSED allows current to flow in the motor. J1-9 MOMENTARY CLOSED starts motor operation in the Forward direction. J1-10 MOMENTARY CLOSED starts motor operation in the Reverse direction. J1-11 When OPEN motor Decels to stop. J1-12 Run Command. OPEN selects STOP/START and Reset commands from Keypad.
CLOSED selects STOP/START and Reset commands from terminal strip. J1-13 Speed Command. OPEN selects speed commanded from Keypad.
CLOSED selects terminal strip speed source (selected in the Level 1 Input block,
Command Select parameter).
Note: When changing from Keypad to Terminal Strip (J1-12 or J1-13) the motor speed and
direction will remain the same after the change.
J1-14 OPEN selects preset speed #1 regardless of the Speed Command input J1-13.
(FIRESTAT) J1-15 OPEN selects preset speed #2 regardless of the Speed Command input J1-13.
(FREEZESTAT)
Note: If J1-14 and J1-15 are both Open, Preset Speed #1 is selected.
J1-16 OPEN causes an external trip to be received by control. The control will disable and
display external trip when programmed “ON”. When this occurs, the drive is disabled
and an external trip fault is displayed on the keypad display (also logged into the fault
log). If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
ANALOG INPUT 1
POT REFERENCE ANALOG INPUT +2 ANALOG INPUT –2
ANALOG OUT 1 ANALOG OUT 2
FORWARD RUN
REVERSE RUN
RUN COMMAND
SPEED COMMAND PRESET SPEED #1 PRESET SPEED #2
EXTERNAL TRIP
O INPUT COMMON
OPT
OPT
O OUT COMMON
OPTO OUT #1 OPTO OUT #2 OPTO OUT #3 OPTO OUT #4
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
ENABLE
STOP
1 2 3 4 5 6 7
8
9 10 11 12 13 14 15 16 17 18
19 20 21 22
23 24 25 26 27 28 29
30
31 32 33 34 35 36 37 38 39 40
41 42 43 44
A A B B INDEX INDEX +5VDC
COMMON A A B B INDEX INDEX Not Used
COMMON +24VDC OPTO IN POWER
OPTO OUT #1 RETURN OPTO OUT #2 RETURN OPTO OUT #3 RETURN OPTO OUT #4 RETURN
Encoder Input Note 6
Buffered Encoder Output Note 7
3-40 Receiving & Installation
MN718
Section 1 General Information
Bipolar Speed and Torque Mode Connections
In
addition to individual motor bipolar speed or torque control, this mode of operation allows the user to store up to four (4) different complete sets of operating parameters. This is important if you wish to store and use dif commands, jog speeds or to store tuning parameter values for dif 3-13 shows switch settings required to access each parameter table. The following procedure allows you to program up to four complete sets of parameter values and to use these multiple parameter sets. When programming each parameter set, use the ENTER key to accept and automatically save parameter values.
Note:
Except for the Level 1 Operating Mode parameter, the control can be programmed in the REMOTE mode with the drive enabled and switches closed. The control must be disabled to change the operating mode parameter.
1.
Set the Level 1 INPUT block, Operating Mode parameter value to BIPOLAR in each of the parameter sets.
2.
Set switches J1-13 and J1-14 to Parameter T sure switches J1-9 and J1-10 are OPEN, J1-8 is CLOSED. Enter all parameter values, and autotune as instructed in Section 3 of this manual. This creates and saves the first parameter set which is numbered T
3.
Set switches J1-13 and J1-14 to Parameter Table #1. Be sure switches J1-9 and J1-10 are OPEN, J1-8 is CLOSED. Enter all parameter values, and autotune as instructed in Section 3 of this manual. This creates and saves the second parameter set which is numbered T
4.
Set switches J1-13 and J1-14 to Parameter Table #2. Be sure switches J1-9 and J1-10 are OPEN, J1-8 is CLOSED. Enter all parameter values, and autotune as instructed in Section 3 of this manual. This creates and saves the third parameter set which is numbered T
5.
Set switches J1-13 and J1-14 to Parameter Table #3. Be sure switches J1-9 and J1-10 are OPEN, J1-8 is CLOSED. Enter all parameter values, and autotune as instructed in Section 3 of this manual. This creates and saves the final parameter set which is numbered T
6.
Remember that to change the value of a parameter in one of the parameter tables, you must first select the table using the switches. Y value in a table until you have first selected that table.
Table 3-13 Bipolar Mode Table Select Truth Table
ferent acceleration rates, speed
ferent motors etc. T
able #0 (both switches open). Be
able#0.
able#1.
able#2.
able#3.
ou cannot change a
able
MN718
Function J1-13 J1-14
Parameter Table #0 Open Open Parameter Table #1 Closed Open Parameter Table #2 Open Closed Parameter Table #3 Closed Closed
Note: All
Note:
parameters except operating mode can be changed and saved for each
table. Preset speed does not apply to table select.
Receiving
& Installation 3-41
Section 1 General Information
Figure 3-25 Bipolar Speed or Torque Connection Diagram
Note 1
Note 4
Note 2
Notes
1.
2.
3.
4.
5.
6.
Programmable 0–5V Output (Factory Preset: Speed) Programmable 0–5V Output (Factory Preset: Current)
(for Figure 3-25):
Refer to Analog Inputs. Refer to Analog Outputs. Refer to Opto Isolated Outputs. Refer to Figure NO TAG for 4-20mA. Refer to Encoder installation. Refer to Buf
fered Encoder Output.
* See Table 3-13.
±5VDC, ±10VDC or 4-20mA
Refer to Figure NO
5kW Command Pot
TAG.
Note 3
ANALOG GND
ANALOG INPUT 1
POT REFERENCE ANALOG INPUT +2 ANALOG INPUT –2
ANALOG OUT 1 ANALOG OUT 2
FORWARD ENABLE
REVERSE ENABLE
CLOSED=ORIENT
SPEED/TORQUE
* TABLE SELECT * TABLE SELECT
FAULT RESET
EXTERNAL TRIP
OPT
O INPUT COMMON
OPT
O OUT COMMON
OPTO OUT #1 OPTO OUT #2 OPTO OUT #3 OPTO OUT #4
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
ENABLE
10 11 12 13 14 15
16 17 18
19 20 21 22
J1
1
23
A
2
24
A
3
25
B
4
26
B
5
27
INDEX
6
28
INDEX
7
29
+5VDC
8
30
COMMON
9
A
31
A
32
B
33
B
34
INDEX
35
INDEX
36
Not Used
37 38
COMMON
39
+24VDC
40
OPTO IN POWER
41
OPTO OUT #1 RETURN
42
OPTO OUT #2 RETURN
43
OPTO OUT #3 RETURN
44
OPTO OUT #4 RETURN
Encoder Input Note 5
Buffered Encoder Output Note 6
J1-8 OPEN disables the control & motor coasts to a stop.
CLOSED allows current to flow in the motor and produce torque.
J1-9 CLOSED to enable operation in the Forward direction.
OPEN TO DISABLE Forward operation (drive will brake to a stop if a Forward command is still present).
J1-10 CLOSED to enable operation in the Reverse direction.
OPEN to disable Reverse operation (drive will brake to a stop if a Reverse command is
still present). J1-11 Causes the motor shaft to orient to a marker or external switch. J1-12 CLOSED puts the control in torque mode.
OPEN puts the control in velocity mode. J1-13 & Select from four parameter tables as defined
J1-14 in Table 3-13. J1-15 Momentary CLOSED to reset fault condition.
OPEN to run, J1-16 OPEN causes an external trip to be received by control. The control will disable and
J1-39 & Jumper as shown to power the Opto Inputs from the internal +24VDC supply. 40
display external trip when programmed “ON”. When this occurs, the motor stop
command is issued, drive operation is terminated and an external trip fault is displayed
on the keypad display (also logged into the fault log).
If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
3-42
Receiving & Installation
MN718
Section 1 General Information
Process Mode Connections
The process control mode provides an auxiliary closed loop general purpose PID set point control that is shown in Figure 3-26. The process control loop may be configured in either of two ways.
1.
Using two (2) inputs; a set point and a process feedback input. The error signal (between the setpoint and the feedback signals) adjusts the speed or torque of the motor to eliminate error
2.
Using three (3) inputs; a setpoint, process feedback and feedforward inputs. Instead of waiting for an error signal to develop between the setpoint and the process feedback signals, the feedforward signal adjusts the speed or torque of the motor to reduce the amount of error that will develop between the feedback and setpoint inputs.
The objective of either method is to force the process feedback to be as close to the setpoint as possible and eliminate process error Mode Input Signal Compatibility for the Setpoint Source, Process Feedback and Feedforward signals. Be sure to use this information to select the signal types and expansion boards for your application.
Two Input Configuration
For 2 input operation, several parameters must be set as follows:
1.
Level 2 Process Control block, “Process Feedback” parameter must be set to the type of feedback signal used. The process feedback signal can be any Analog input available at the J1 terminal strip or expansion board. Selections are shown in Figure 3-26.
2.
Level 2 Process Control block, “Setpoint Source” parameter must be set to the type of set point being used.
A.
A fixed value setpoint is a keypad programmed parameter value. T program a fixed setpoint, do the following: i.
Set the Level 2 Process Control block, “Setpoint Source” parameter to Setpoint CMD.
ii.
Set the Level 2 Process Control block, “Setpoint CMD” parameter to a value between –100% to +100% of the process feedback input.
B.
If a variable value setpoint is used, the Setpoint Source must be set to any available terminal strip or expansion board input not being used for the process feedback input. Selections are shown in Figure 3-26.
3.
Level 1 Input block “Command Select” parameter must be set to “None”.
Three Input Configuration
For 3 input operation, several parameters must be set as follows:
1.
Level 2 Process Control block “Process Feedback” parameter must be set to the type of feedback signal used. The process feedback signal can be any Analog input available at the J1 terminal strip or expansion board. Selections are shown in Figure 3-26.
2.
Level 2 Process Control block “Setpoint Source” parameter must be set to the type of set point being used.
A.
If a fixed value setpoint is used, set the Level 2 Process Control block, Setpoint Source parameter to “Setpoint CMD”. Set the Level 2 Process Control block “Setpoint Command” parameter to a value between –100% to +100% of the process feedback.
B.
If a variable value setpoint is used, set the Level 2 Process Control block, Setpoint Source parameter to any Analog1, Analog2 or expansion board input not being used for the process feedback input. Selections are shown in Figure 3-26.
.
. T
able 3-14 shows a matrix of Process
o
MN718
Receiving
& Installation 3-1
Section 1 General Information
Figure 3-26 Simplified Process Control Block Diagram
SETPOINT SOURCE
Available sources are: Set Point Command Potentiometer
± 10 Volts ± 5 Volts
4-20 mA 5 Volt EXB 10 Volt EXB 4-20mA EXB 3-15 PSI EXB Tachometer EXB None
3.
Level 1 Input block “Command Select” parameter must be set to the feedforward signal type. This signal may be any Analog1, Analog2 or expansion board input not being used for the process feedback or setpoint source inputs. Selections are shown in Figure 3-26.
Note:
An input can only be used one time for Process Feedback, OR Setpoint Source, OR Feedforward.
Baldor Series “H” Control
PROCESS FEEDBACK
Available sources are: Potentiometer
± 10 Volts ± 5 Volts
4-20 mA 5 Volt EXB 10 Volt EXB 4-20mA EXB 3-15 PSI EXB Tachometer EXB None
PROCESS FEEDFORWARD
COMMAND SELECT Available sources are: Potentiometer
± 10 Volts ± 5 Volts
4-20 mA 10 V w/Torq FF EXB Pulse Follower 5 Volt EXB 10 Volt EXB 4-20mA EXB 3-15 PSI EXB Tachometer EXB Serial None
Auxiliary PID Control
Motor Control
ACC/DEC S–Curve Profiler
Differentiator
EXB Pulse Follower Only
s
+
Proportional
Closed When Process
Mode is Enabled (J1–13)
+
Proportional
+
+
s
Differentiator
Gp
Differential
Gd s
Gp
Integral
Gi
s
Set Point adjustment limit w/ integral clamp to max limit value
Existing Baldor Control System
Differential
Gd s
+
+
+
+
+
Integral
Gi
s
+
Amp
Motor
Enc.
3-2
Receiving & Installation
MN718
Section 1
Setpoint
General Information
Table 3-14 Process Mode Input Signal Compatibility
or
Feedforward
J1-1 & 2 J1-4 & 5 5V EXB 10V EXB 4-20mA EXB 3-15 PSI EXB DC Tach EXB EXB PULSE FOL Serial

Requires
Requires expansion board EXB004A01 (4 Output Relays/3-15 PSI Pneumatic Interface EXB). Requires expansion board EXB006A01 (DC T Requires expansion board EXB005A01 (Master Pulse Reference/Isolated Pulse Follower EXB). Used for Feedforward only Requires expansion board EXB001A01 (RS232 Serial Communication EXB). or
Requires expansion board EXB002A01 (RS422/RS485 High Speed Serial Communication EXB). Conflicting inputs. Do not use same input signal multiple times. Conflicting level 1 or 2 expansion boards. Do not use!
Feedback
J1-1 & 2 J1-4 & 5
5V EXB 10V EXB

expansion board EXB007A01 (High Resolution Analog I/O EXB).
achometer Interface EXB).
. Must not be used for Setpoint Source or Feedback.
4-20mA
EXB
3-15 PSI
EXB
DC
Tach EXB
Specific Process Mode Outputs
Process Mode Only
, Analog Monitoring Outputs
Name Description
Process FDBK Process Feedback scaled input. Useful for observing or tuning the
process control loop.
Setpoint CMD Setpoint Command scaled input. Useful for observing or tuning the
process control loop.
Speed Command Commanded Motor Speed. Useful for observing or tuning the output of
the control loop.
Process
Mode Only
, Opto Isolated Outputs
Name Description
Process Error CLOSED when the Process Feedback is within the specified tolerance
band. OPEN when the Process Feedback is greater than the specified tolerance band. The width of the tolerance band is adjusted by the Level 2 Process Control block Process ERR TOL parameter value.
MN718
Receiving
& Installation 3-3
Section 1 General Information
Note 4
Note 2
Notes:
1.
2.
3.
4.
5.
6.
Programmable 0–5V Output (Factory Preset: Speed) Programmable 0–5V Output (Factory Preset: Current)
Refer to Analog Inputs. Refer to Analog Outputs. Refer to Opto Isolated Outputs. Refer to Figure 3-30 for 4-20mA. Refer to Encoder installation. Refer to Buf
fered Encoder Output.
Refer
Figure 3-27 Process Mode Connection Diagram
ANALOG GND
Note 1
±5VDC, ±10VDC or 4-20mA
5kW Command Pot
to Figure 3-32.
Note 3
ANALOG INPUT 1
POT REFERENCE ANALOG INPUT +2 ANALOG INPUT –2
ANALOG OUT 1 ANALOG OUT 2
Enable
Forward
Reverse
Table Select
Speed/Torque
Process Mode Enable
Jog
Fault Reset
External Trip
Opto Input Common
Opto Out Common
OPTO OUT #1 OPTO OUT #2 OPTO OUT #3 OPTO OUT #4
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
19 20 21 22
J1
23
A
24
A
25
B
26
B INDEX
27
INDEX
28
+5VDC
29
30
COMMON A
31
A
32
B
33
B
34
INDEX
35
INDEX
36
Not Used
37 38
COMMON
39
+24VDC
40
OPTO IN POWER
41
OPTO OUT #1 RETURN
42
OPTO OUT #2 RETURN
43
OPTO OUT #3 RETURN
44
OPTO OUT #4 RETURN
Encoder Input Note 5
Buffered Encoder Output Note 6
J1-8 OPEN disables the control & motor coasts to a stop. Closed allows current to flow in the
motor and produce torque.
J1-9 CLOSED operates the motor in the Forward direction (with J1-10 open).
OPEN motor decels to stop (depending on Keypad Stop mode parameter setting).
J1-10 CLOSED operates motor in the Reverse direction (with J1-9 open).
OPEN motor decels to stop depending on Keypad Stop mode parameter setting. J1-11 OPEN = TABLE 0, CLOSED = TABLE 1 J1-12 CLOSED, the control is in torque mode.
OPEN, the control is in velocity mode. J1-13 CLOSED to enable the Process Mode. J1-14 CLOSED places control in JOG mode. The control will only JOG in the forward
direction. J1-15 CLOSED to reset a fault condition.
OPEN to run. J1-16 OPEN causes an external trip to be received by control. The control will disable and
J1-39 & Jumper as shown to power the Opto Inputs from the internal +24VDC supply. 40
display external trip when programmed “ON”. When this occurs, the motor stop
command is issued, drive operation is terminated and an external trip fault is displayed
on the keypad display (also logged into the fault log).
If J1-16 is connected, you must set Level 2 Protection block, External Trip to “ON”.
3-4
Receiving & Installation
MN718
Section 1 General Information
Analog Inputs and Outputs
Analog Inputs T
wo analog inputs are available: analog input #1 (J1-1 and J1-2) and analog input #2 (J1-4 and J1-5) as shown in Figure 3-28. Either analog input #1 or #2 may be grounded provided the common mode range is not exceeded. Either analog input may be selected in the Level 1 INPUT block, Command Select parameter value. Analog input #1 is selected if parameter value “Potentiometer” is selected. Analog input #2 is selected if parameter value “+/–10V
olts, +/–5 V
olts or 4-20mA” is selected. Figure 3-29 shows the
equivalent circuits of the Analog Inputs.
Figure 3-28 Analog Inputs and Outputs
Analog Input #1
Command Pot
or
0-10VDC
±5VDC, ±10VDC or 4-20 mA Input
Programmable 0-5VDC (Factory Preset: Speed)
Programmable 0-5VDC (Factory Preset: Current)
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
5KW
Analog Ground Analog Input 1 Pot Reference Analog Input +2 Analog Input -2
Analog Output 1
Analog Output 2
The single ended analog input #1 is used when the controller is set to Standard 3 Wire, Fan Pump 2 or 3 Wire, Process, or Bipolar Control (not Keypad or 15 Speed 2 Wire modes). When using a potentiometer as the speed command, process feedback or setpoint source, the Level 1 Input block COMMAND SELECT parameter must be set to “POTENTIOMETER”.
1.
Connect the wires from the 5KW pot as shown in Figure 3-28. One end of the pot is connected to J1-1 (analog ground) and the other end is connected to J1-3 (reference voltage).
2.
Connect the wiper of the pot to J1-2. The voltage across terminals J1-1 and J1-2 is the speed command input.
3.
A 0-10VDC speed command signal may be connected across J1-1 and J1-2 instead of a 5KW pot.
MN718
Receiving
& Installation 3-5
Section 1 General Information
Analog Input #2
Analog input #2 accepts a dif operating mode is defined in the of the Level 1 Input block OPERA parameter.
Note:
Analog Input #2 is used with Standard Run 3-Wire, Fan Pump 2 or 3 Wire or Bipolar Control modes and not used for the Keypad or 15 Speed 2 Wire or the Serial operating modes.
1.
Connect the Analog Input +2 wire to J1-4 and the –2 wire to J1-5.
2.
If using a 4-20 mA command signal, jumper JP1 located on the main control board must be on pins 2 & 3. For all other modes, JP1 must be on pins 1 & 2. Refer to Figure NO TAG for jumper position information.
Note:
Analog Input #2 can be connected for single ended operation by grounding either of the inputs, provided the common mode voltage range is not exceeded. The common mode voltage can be measured with a voltmeter Apply the maximum command voltage to analog input 2 (J1A-4, 5). Measure the AC and DC voltage across J1A-1 to J1A-4. Add the AC and DC readings together and DC readings together
If either of these measurement totals exceeds a total of ±15 volts, then the common mode voltage range has been exceeded. If the common mode voltage range has been exceeded, the solution is either to change the command voltage source or isolate the command voltage with a commercially available signal isolator
. Measure the AC and DC voltage from J1A-1 to J1A-5. Add the AC
ferential command ±5VDC, ±10VDC or 4-20 mA. The
.
.
TING MODE
.
3-6
Receiving & Installation
MN718
Section 1 General Information
Figure 3-29 Analog Inputs Equivalent Circuits
J1
-15VDC
30KW
1
20KW
2
– +
5.1V Zener
.033 mF
5KW
T
o Microprocessor
3 4
5
JP2
JP1 4-20mA
500W
X N/C
Notes:
123
1.96KW +15VDC
10KW 10KW
+ –
10KW
+ –
Figure 3-30
T
o Microprocessor
10KW
All OP Amps are TL082 or TL084
Analog
Ground is separated from Chassis Ground. Electrically are separated by an RC network.
they
JP1
Jumper Jumper
JP1
JP2
MN718
123
Table 3-15 Control Board Jumper
Position
1–2 V 2–3 1–2 2–3
oltage Speed Command Signal. (Factory Setting) 4-20mA input at Analog #2 Factory Setting Not used.
Description of Jumper Position Setting
Refer
to T
able 3-15
for jumper placement information.
Receiving
& Installation 3-7
Section 1 General Information
Analog Outputs T
From Microprocessor
.033 mf
wo programmable analog outputs are provided on J1-6 and J1-7. See Figure 3-31. These outputs are scaled 0 - 5 VDC (1mA maximum output current) and can be used to provide real-time status of various control conditions. The output conditions are defined in
Table NO TAG
of Section 4 of this manual.
The return for these outputs is J1-1 analog ground. Each output is programmed in the Level 1 Output block.
1.
Connect the Output #1 wires to J1-6 and J1-1.
2.
Connect the Output #2 wires to J1-7 and J1-1.
Figure 3-31 Analog Outputs Equivalent Circuits
J1
1
10KW
+ –
10KW
50W
6
Notes:
From Microprocessor
10KW
.033 mf
+ –
10KW
50W
+ –
7
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
All OP Amps are TL082 or TL084
Analog
Ground is separated from Chassis Ground. Electrically are separated by an RC network.
they
3-8
Receiving & Installation
MN718
Section 1 General Information
External Trip Input Terminal
relay in all operating modes as shown in Figure 3-32. The thermostat or overload relay should be a dry contact type with no power available from the contact. If the motor thermostat or overload relay activates the control will automatically shut down and give an External T and the N.O. contact is closed when power is applied to the relay and the motor is cold.
Connect the External T same conduit as the motor power leads.
T
o activate the External T
Block must be set to “ON”.
Figure 3-32 Motor Temperature Relay
T1 T2 T3
External or remote motor overload protection may be required by National Electrical Code or equivalent
MMM
T3
T2
T1
* Motor
Opto-Isolated Inputs The
equivalent circuit for the nine Opto inputs is shown in Figure 3-33. The function of each input depends on the operating mode selected. Refer to the operating mode connection diagrams shown previously in this section.
Figure 3-33 Opto-Input Equivalent Circuit (Using Internal Supply)
J1
J1-16 is available for connection to a normally closed thermostat or overload
rip fault. The optional relay (CR1) shown provides the isolation required
rip Input wires to J1-16 and J1-17. Do not place these wires in the
rip input, the External T
Customer Provided
Source Voltage
rip parameter in the Level 2 Protection
Note: Add appropriately rated
protective device for AC relay (snubber) or DC relay (diode).
J1
*
G
Motor Thermostat Leads
CR1
Do not run these wires in same conduit as motor leads or AC power wiring.
Optional hardware. Must be ordered separately.
*
16 17
External Trip
Opto Input Common
+24VDC @ 200mA
(supply terminal 39).
Jumper terminals 39 to 40
(Factory Installed)
MN718
Opto Input 1 Opto Input 2 Opto Input 3 Opto Input 4 Opto Input 5 Opto Input 6 Opto Input 7 Opto Input 8 Opto Input 9
10
11 12 13 14 15 16 17
39 40
8 9
6.8K 6.8K 6.8K 6.8K 6.8K 6.8K 6.8K 6.8K
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
Receiving
6.8K
& Installation 3-9
Section
1
General Information
Figure 3-34 Opto-Input Equivalent Circuit (Using External Supply)
J1
J1
* User VCC (–)
Opto Inputs Closing to Ground Opto Inputs Closing to +VCC
Opto Input 1 Opto Input 2
Opto Input 3
Opto Input 4
Opto Input 5 Opto Input 6 Opto Input 7 Opto Input 8 Opto Input 9
* User VCC (+)
8 9
10
11 12 13 14 15 16 17
39 40
* User VCC = 10 - 30VDC
External Power Source
Opto Input 1 Opto Input 2 Opto Input 3 Opto Input 4 Opto Input 5 Opto Input 6 Opto Input 7 Opto Input 8 Opto Input 9
* User VCC (+)
* User VCC (–)
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
8
9 10 11 12 13 14 15 16
17
39 40
3-10 Receiving & Installation
MN718
Section 1 General Information
Opto-Isolated Outputs Four
See Figure 3-35. Each output may be programmed to represent one output condition. The output conditions are defined in
The Opto-isolated outputs may be configured for sinking or sourcing 60 mA each. However common when active is 1.0 VDC (TTL compatible). The Opto-isolated outputs may be connected in dif Opto-isolated outputs is shown in Figure 3-36.
If the opto outputs are used to directly drive a relay (IN4002) minimum should be connected across the relay coil. See Electrical Noise Considerations in Section 5 of this manual.
Each Opto Output is programmed in the Output programming block.
Figure 3-35 Opto-isolated Output Configurations
24COM
Optional
Customer
Supplied
Relays
17 18
19
programmable Opto-isolated outputs are available at terminals J1-19 through J1-22.
Table NO TAG
of Section 4 of this manual.
, all must be configured the same. The maximum voltage from opto output to
ferent ways as shown in Figure 3-35. The equivalent circuit for the
, a flyback diode rated at 1A, 100 V
1.
Connect OPT
2.
Connect OPT
3.
Connect OPT
4.
Connect OPT
39 40
41
+24VDC
O OUT #1 wires to J1-19 and J1-41. O OUT #2 wires to J1-20 and J1-42. O OUT #3 wires to J1-21 and J1-43. O OUT #4 wires to J1-22 and J1-44.
24COM
17 18
19
39 40
41
+24VDC
Optional
Customer
Supplied
Relays
Using Internal Supply
(Sinking the Relay Current)
Optional Customer Supplied
10VDC to 30VDC Source
+
Optional
Customer
Supplied
Relays
Using External Supply
(Sinking the Relay Current)
24COM
20 21 22
17 18
19 20
21 22
42 43 44
39 40
41 42
43 44
+24VDC
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
20 21 22
(Sourcing the Relay Current)
Optional Customer Supplied
10VDC to 30VDC Source
+
24COM
17 18
19 20
21 22
(Sourcing the Relay Current)
42 43 44
Using Internal Supply
+24VDC
39 40
41 42
43 44
Using External Supply
Customer
Optional Supplied
Relays
Receiving
& Installation 3-1
1MN718
Section 1 General Information
PC865
50mA max
PC865
50mA max
Figure 3-36 Opto-Output Equivalent Circuit
J1
18
Opto Output 1
19
Opto Output 2
20
Opto Output 3
21
Opto Output 4
22
PC865
50mA max
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
PC865
50mA max
Opto Out 1 Return
41
Opto Out 2 Return
42
Opto Out 3 Return
43
Opto Out 4 Return
44
10
– 30VDC
Opto Outputs
3-12
Receiving & Installation
MN718
Section 1 General Information
Pre-Operation Checklist Check
CAUTION: After completing the installation but before you apply power
W
Check of Motors and Couplings
of Electrical Items
, be
sure to check the following items.
1. V
erify AC line voltage at source matches control rating.
2.
Inspect all power connections for accuracy compliance to codes.
3. V
erify control and motor are grounded to each other and the control is
connected to earth ground.
4.
Check all signal wiring for accuracy
5.
Be certain all brake coils, contactors and relay coils have noise suppression. This should be an R-C filter for AC coils and reverse polarity diodes for DC coils. MOV type transient suppression is not adequate.
ARNING: Make sure that unexpected operation of the motor shaft during start
up will not cause injury to personnel or damage to equipment.
1. V
erify freedom of motion for all motor shafts and that all motor couplings are
tight without backlash.
2. V
erify the holding brakes if any, are properly adjusted to fully release and set to
the desired torque value.
.
, workmanship and tightness and
MN718
Receiving
& Installation 3-13
Section 1 General Information
Power-Up Procedure This procedure will help get your system up and running in the keypad mode quickly. This
will allow you to prove the motor and control operation. This procedure assumes that the Control, Motor and Dynamic Brake hardware are correctly installed (see Section 3 for procedures) and that you have an understanding of the keypad programming & operation procedures.
Initial Conditions
Be sure the Control, Motor and Dynamic Brake hardware are wired according to the procedures described previously in this manual. Become familiar with the keypad programming
1. Verify
2. T
3.
4.
5.
6.
7.
8.
It is not necessary to wire the terminal strip to operate
and keypad operation
that any enable inputs to J1-8 are open.
urn power on. Be sure there are no faults. Set the Level 1 Input block, Operating Mode to “KEYP Be sure the Level 2 Protection block, Local Enable INP parameter is OFF and
the Level 2 Protection block, External T Set the Level 2 Output Limits block, “OPERA
(STD CONST TQ, STD V Enter the following motor data in the Level 2 Motor Data block parameters:
Motor V Motor Rated Amps (FLA) Motor Rated Speed (base speed) Motor Rated Frequency Motor Mag Amps (no load current) Encoder Counts
Go to Level 2 Motor Data block, press ENTER, at CALC PRESETS select YES (using the  key) and let the control calculate preset values for the parameters that are necessary for control operation.
Disconnect the motor from the load (including coupling or inertia wheels). If the load cannot be disconnected, refer to Section 6 and manually tune the control. After manual tuning, perform steps 10, 1
oltage (input)
of the control as described in Section 4 of this manual.
rip parameter is OFF
TING ZONE” parameter as desired
AR TQ, QUIET CONST TQ or QUIET V
1, 15, 16 and 17.
the motor in Keypad mode.
AD”.
.
AR TQ).
W
ARNING: The motor shaft will rotate during this procedure. Be certain that
unexpected motor shaft movement will not cause injury to personnel or damage to equipment.
9.
Go to Level 2 Autotune block, and do the following tests:
CMD OFFSET TRIM CUR LOOP COMP STAT
OR R1 FLUX CUR SETTING ENCODER TESTS SLIP FREQ TEST
10.
Set the Level 2 Output Limits block, “MIN OUTPUT SPEED” parameter
11.
Set the Level 2 Output Limits block, “MAX OUTPUT SPEED” parameter
12.
Remove all power from the control.
13.
Couple the motor to its load.
14. T
urn power on. Be sure no errors are displayed.
15.
Go to Level 2 Autotune block and perform the SPD CNTRLR CALC test.
16.
Run the drive from the keypad using one of the following: the arrow keys for direct speed control, a keypad entered speed or the JOG mode.
17.
Select and program additional parameters to suit your application.
The
control is now ready for use the in keypad mode. If a dif
refer
to Section 3 Control Connections and Section 4 Programming and Operation.
ferent operating
mode is desired,
.
.
3-14
Receiving & Installation
MN718
Section 4 Programming and Operation
Overview
The keypad is used to program the control parameters, operate the motor and monitor the status and outputs of the control by accessing the display options, diagnostic menus and the fault log.
JOG - (Green) lights when Jog is active. FWD - (Green) lights when FWD direction is commanded. REV - (Green) lights when REV direction is commanded. STOP - (Red) lights when motor STOP is commanded.
Indicator Lights
JOG - Press JOG to select the
preprogrammed jog speed. After the jog key has been pressed, use the FWD or REV keys to run the motor in the direction that is needed. The JOG key is only active in the local mode.
FWD - Press FWD to initiate forward
rotation of the motor. This key is only active in the Keypad or local mode.
REV - Press REV to initiate reverse
rotation of the motor. This key is active only in the Keypad or local mode.
STOP - Press STOP one time to initiate
a stop sequence. Depending on the setup of the control, the motor will either ramp or coast to a stop. This key is operational in all modes of operation unless it has been disabled by the Keypad Stop parameter in the Keypad (programming) Setup Block. Press STOP twice to disable control (coast to stop).
Note: If the control is operating in
remote mode and the stop key is pressed the control will change to the local mode when the stop command is initiated. To resume operation in the remote mode, press the LOCAL key.
LOCAL - Press LOCAL to change
between the local (keypad) and remote operation. When the control is in the local mode all other external commands to the J1 terminal strip will be ignored with the exception of the external trip input.
Figure 4-1 Keypad
DISP - Press DISP to return to display
mode from programming mode. Provides operational status and advances to the next display menu item including the diagnostic screens.
SHIFT - Press SHIFT in the program
mode to control cursor movement. Pressing the SHIFT key once moves the blinking cursor one character position to the right. While in program mode, a parameter value may be reset to the factory preset value by pressing the SHIFT key until the arrow symbols at the far left of the keypad display are flashing, then press an arrow key. In the display mode the SHIFT key is used to adjust the keypad contrast.
RESET - Press RESET to clear all fault
messages (in local mode). Can also be used to return to the top of the block programming menu without saving any parameter value changes.
Keypad Display -
information during Local or Remote operation. It also displays information during parameter setup and fault or Diagnostic Information.
Displays status
PROG - Press PROG to enter the
program mode. While in the program mode the PROG key is used to edit a parameter setting.
Y - (UP Arrow).
Press Y to change the value of the parameter being displayed. Pressing Y increments the value to the next greater value. Also, when the fault log or parameter list is displayed, the Y key will scroll upward through the list. In the local mode pressing the Y key will increase motor speed to the next greater value.
ENTER - Press ENTER to save
parameter value changes and move back to the previous level in the programming menu. In the display mode the ENTER key is used to directly set the local speed reference. It is also used to select other operations when prompted by the keypad display.
B - (Down Arrow)
Press B to change the value of the parameter being displayed. Pressing B decrements the value to the next lesser value. Also, when the fault log or parameter list is displayed, the B key will scroll downward through the list. In the local mode pressing the B key will decrease motor speed to the next lower value.
MN718
Programming
& Operation 4-1
Section 1 General Information
Display Mode The
control is in the DISPLA
Y MODE at all times except when parameter values are changed (Programming mode). The Keypad Display shows the status of the control as in the following example.
Motor Status
Control Operation
The
DISPLA
Y MODE is used to view DIAGNOSTIC INFO and the F
description of how to do these tasks are described on the following pages.
Adjusting Display Contrast
When AC power is applied to the control the keypad should display the status of the control. If there is no visible display, use the following procedure to adjust the contrast of the display
.
(Contrast may be adjusted in display mode when motor is stopped or running)
Action Description Display Comments
Apply Power No visible display
Press DISP Key Places control in display mode
Press SHIFT SHIFT Allows display contrast
Press Y or B Key
adjustment Adjusts display intensity
Output Condition Value and Units
AUL
T LOG. The
Press ENTER Saves level of contrast and exits
to display mode
Typical display
4-2
Programming & Operation
MN718
Section 1 General Information
Display Mode
Continued
Display Mode Screens
Action Description Display Comments
Apply Power Logo display for 5 seconds.
Display mode showing motor speed.
Press DISP key Display mode custom unit output
rate (only if Level 2 Custom Units block parameters are set).
Press DISP key Display Frequency First Display Mode Screen.
Press DISP key DIsplay Current
Press DISP key DIsplay Voltage
Press DISP key Combined DIsplay
Press DISP key Screen to enter Fault Log
No faults present. Local keypad mode. If in remote/serial mode, press local for this display.
Press DISP key Screen to enter Diagnostic Menu
Press DISP key Exit Display mode and return to
Motor Speed display
MN718
Programming
& Operation 4-3
Section 1 General Information
Display Mode
Continued
Display Screens & Diagnostic Information Access
Action Description Display Comments
Apply Power Logo display for 5 seconds.
Display mode showing motor speed.
Press DISP key 6 times Scroll to Diagnostic Information
Press ENTER key Access diagnostic information. First Diagnostic Information
Press DISP key Display mode showing control
Press DISP key Display mode showing bus
Press DISP key Display mode showing %
Press DISP key Display mode showing opto
screen
temperature.
voltage.
overload current remaining.
inputs & outputs states.
XXXV
No faults present. Local keypad mode. If in remote/serial mode, press local for this display.
Diagnostic Access screen.
screen.
Opto Inputs states (Left); Opto Outputs states (Right).
Press DISP key Display mode showing actual
drive running time.
Press DISP key Display mode showing operating
zone, voltage and control type.
Press DISP key Display mode showing continuous
amps; PK amps rating; amps/volt scale of feedback, power base ID.
Press DISP key Display mode showing which
Group1 or 2 expansion boards are installed.
Press DISP key Display mode showing motor
shaft revolutions from the REV home set point.
Press DISP key Display mode showing parameter
table selected.
Press DISP key Display mode showing firmware
version and revision installed in the control.
Press DISP key Displays exit choice. Press ENTER to exit diagnostic
HR.MIN.SEC format.
Typical display.
ID is displayed as a hexadecimal value.
information.
4-4
Programming & Operation
MN718
Section 1 General Information
Display Mode
Fault Log Access When
Continued
a fault condition occurs, motor operation stops and a fault code is displayed on the
Keypad display
. The control keeps a log of up to the last 31 faults. If more than 31 faults have occurred the oldest fault will be deleted from the fault log to make room for the newest fault. To access the fault log perform the following procedure:
Action Description Display Comments
Apply Power Logo display for 5 seconds.
Display mode showing motor speed.
Press DISP key 5 times Scroll to the Fault Log screen Fault Log access screen.
Press ENTER key Display first fault type and time
Press key
Press ENTER key Return to display mode. Display mode stop key LED is on.
fault occurred. Scroll through fault messages.
Display mode.
Most recent fault displayed.
If no messages, the fault log exit choice is displayed.
MN718
Programming
& Operation 4-5
Section 1 General Information
Program Mode The
Program Mode is used to:
1.
Enter motor data.
2.
Autotune the motor
3.
Customize the drive (Control and Motor) parameters to your application.
From the Display Mode press the PROG key to access the Program Mode.
Note:
When a parameter is selected, alternately pressing the Disp and Prog keys will toggle between the Display Mode and the selected parameter parameter is selected for programming, the keypad display gives you the following information:
Parameter Parameter Status
Parameter
Status
left corner of the keypad display value may be viewed but not changed while the motor is operating. If the parameter is displayed with an “L:”, the value is locked and the security access code must be entered before its’ value can be changed.
Parameter Blocks Access for Programming
Use
the following procedure to access parameter blocks to program the control.
Action Description Display Comments
Apply Power Keypad Display shows this
opening message.
.
. When a
Value and Units
. All programmable parameters are displayed with a “P:” in the lower
. If a parameter is displayed with a “V
Logo display for 5 seconds.
:”, the parameter
If no faults and programmed for LOCAL operation.
If no faults and programmed for REMOTE operation.
Press PROG key Press ENTER to access Preset
Press Y or B key
Press Y or B key
Press ENTER key First Level 2 block display.
Press Y or B key
Press ENTER key Return to display mode.
Scroll to the ACCEL/DECEL block.
Scroll to the Level 2 Block.
Scroll to Programming Exit menu.
Display mode.
If fault is displayed, refer to the Troubleshooting section of this manual.
Speed parameters. Press ENTER to access Accel
and Decel rate parameters. Press ENTER to access Level 2
Blocks.
Press ENTER to return to Display mode.
4-6
Programming & Operation
MN718
Section 1 General Information
Program Mode
Continued
Changing Parameter Values when Security Code Not Used
Use
the following procedure to program or change a parameter already programmed into
the control when a security code is not being used. The example shown changes the operating mode from Keypad to Bipolar
Action Description Display Comments
Apply Power Keypad Display shows this
Press PROG key Access programming mode.
Press Y or B key
Press ENTER key Access Input Block. Keypad mode shown is the
Press ENTER key Access Operating Mode
Press Y key
opening message. If no faults and programmed for
LOCAL operation.
Scroll to Level 1 Input Block.
parameter. Scroll to change selection.
Logo display for 5 seconds.
Display mode. Stop LED on.
Press ENTER to access INPUT block parameter.
factory setting. Keypad mode shown is the
factory setting. At flashing cursor, select desired
mode, BIPOLAR in this case.
.
Press ENTER Save selection to memory. Press ENTER to save selection.
Press Y key
Press ENTER key Return to Input Block.
Press DISP key Return to Display Mode. Typical display mode.
Scroll to menu exit.
MN718
Programming
& Operation 4-7
Section 1 General Information
Program Mode
Continued
Reset Parameters to Factory Settings
Sometimes this procedure to do so. Be sure to change the Level 2 Motor Data block “Motor Rated Amps” to the correct value after this procedure (restored factory setting is 999).
Action Description Display Comments
Apply Power Keypad Display shows this
Press PROG key Enter program mode.
Press Y or B key
Press ENTER key Select Level 2 Blocks.
opening message. If no faults and programmed for
LOCAL operation.
Scroll to Level 2 Blocks.
it is necessary to restore the parameter values to the factory settings. Follow
Note:
All specific application parameters already programmed will be lost when resetting the control to factory settings.
Note:
After factory settings are restored, the drive must be auto tuned.
Logo display for 5 seconds.
Display mode. Stop LED on.
Press Y or B key
Press ENTER key Select Miscellaneous block.
Press Y key
Press ENTER key Access Factory Settings
Press Y key
Press ENTER key Restores factory settings. “Loading Presets” is first message
Press Y key
Press Y or B key
Press ENTER key Return to display mode. Display mode. Stop LED on.
Scroll to the Miscellaneous block.
Scroll to Factory Settings parameter.
parameter. Scroll to YES, to choose original
factory settings.
Scroll to menu exit.
Scroll to Programming exit.
V represents blinking cursor.
“Operation Done” is next “No” is displayed last.
Exit Level 2 blocks.
Exit Programming mode and return to Display mode.
4-8
Programming & Operation
MN718
Section 1 General Information
Program Mode
Continued
Initialize New Firmware
After
new firmware is installed, the control must be initialized to the new firmware version
and memory locations. Use the following procedure to Initialize the firmware.
Action Description Display Comments
Apply Power Keypad Display shows this
Press PROG key Enter program mode.
Press Y or B key
Press ENTER key Select Level 2 Blocks.
Press Y or B key
Press ENTER key Select Miscellaneous block.
opening message. If no faults and programmed for
LOCAL operation.
Scroll to Level 2 Blocks.
Scroll to the Miscellaneous block.
Logo display for 5 seconds.
Display mode. Stop LED on.
Press Y key
Press ENTER key Access Factory Settings
Press Y key
Press ENTER key Restores factory settings. “Loading Presets” is first message
Press Y key
Press ENTER key Return to display mode. Display mode. Stop LED on.
Press DISP key several times
Press ENTER key Access diagnostic information. Displays commanded speed,
Press DISP key Display mode showing firmware
Press DISP key Displays exit choice. Press ENTER to exit diagnostic
Scroll to Factory Settings parameter.
parameter. Scroll to YES, to choose original
factory settings.
Scroll to menu exit.
Scroll to diagnostic information screen.
version and revision installed in the control.
V represents blinking cursor.
“Operation Done” is next “No” is displayed last.
If you wish to verify the firmware version, enter diagnostic info.
direction of rotation, Local/ Remote and motor speed.
Verify new firmware version.
information.
MN718
Programming
& Operation 4-9
Section 1 General Information
Parameter Definitions To
make programming easier
the
PROG key to enter the programming
, parameters have been arranged as shown in T
mode and the “Preset Speeds” programming block will be displayed. Use the Up (Y) and Down (B) arrows to scroll through the parameter blocks.
Tables Values preset
Press ENTER to access parameters within a programing block.
4-2 and 4-3 provide an explanation of each parameter
. A complete Parameter Block
list is located at the end of this manual. This list defines the programmable range
value for each parameter and has space to record your settings for future reference.
Table 4-1 List of Parameters
LEVEL 1 BLOCKS
Preset Speeds Input Output Limits Brake Adjust
Preset Speed #1 Operating Mode Operating Zone Resistor Ohms Preset Speed #2 Command Select Min Output Speed Resistor Watts Preset Speed #3 ANA CMD Inverse Max Output Speed DC Brake Current Preset Speed #4 ANA CMD Offset PK Current Limit Preset Speed #5 ANA 2 Deadband PWM Frequency Process Control Preset Speed #6 ANA1 CUR Limit Current Rate Limit Process Feedback Preset Speed #7 Process Inverse Preset Speed #8 Output Custom Units Setpoint Source Preset Speed #9 Opto Output #1 Decimal Places Setpoint Command Preset Speed #10 Opto Output #2 Value at Speed Set PT ADJ Limit Preset Speed #11 Opto Output #3 Units of Measure Process ERR TOL Preset Speed #12 Opto Output #4 Process PROP Gain Preset Speed #13 Zero SPD Set PT Protection Process INT Gain Preset Speed #14 At Speed Band Overload Process DIFF Gain Preset Speed #15 Set Speed External Trip Follow I:O Ratio
Analog Out #1 Local Enable INP Follow I:O Out Accel / Decel Rate Analog Out #2 Following Error Master Encoder Accel Time #1 Analog #1 Scale Torque Proving Decel Time #1 Analog #2 Scale Communications S-Curve #1 Position Band Miscellaneous Protocol Accel Time #2 Restart Auto/Man Baud Rate Decel Time #2 Vector Control Restart Fault/Hr Drive Address S-Curve #2 Ctrl Base Speed Restart Delay
Feedback Filter Factory Settings Auto-Tuning Jog Settings Feedback Align Homing Speed CALC Presets Jog Speed Current PROP Gain Homing Offset Jog Accel Time Current INT Gain CUR Loop Comp Jog Decel Time Speed PROP Gain Security Control Stator R1 Jog S-Curve Time Speed INT Gain Security State Flux CUR Setting
Speed DIFF Gain Access Timeout Feedback Test Keypad Setup Position Gain Access Code Slip Freq Test Keypad Stop Key Slip Frequency SPD CNTRLR CALC Keypad Stop Mode Stator R1 Motor Data Keypad Run Fwd Stator X1 Motor Voltage Keypad Run Rev Motor Rated Amps Keypad Jog Fwd Motor Rated SPD Keypad Jog Rev Motor Rated Freq
Motor Mag Amps Encoder Counts Resolver Speeds CALC Presets
LEVEL 2 BLOCKS
CMD Of
fset Trim
able 4-1. Press
and
4-10
Programming & Operation
MN718
Section 1
Out ut Limits block.
S-C
2
S-C
direction (FWD or REV)
For Standard Run mode, close the JOG in ut (J1 12) at the
g
Jog Accel Time
Jog Accel Time changes the Accel Time to a new reset value for jog mode
General Information
Table 4-2 Level 1 Parameter Block Definitions
Block Title Parameter Description
PRESET SPEEDS
ACCEL/DECEL RATE
JOG SETTINGS Jog Speed Jog Speed is the programmed speed used during for jog. Jog can be initiated from the
Preset Speeds #1 – #15
Allows selection of 15 predefined motor operating speeds.
Each speed may be selected using external switches connected to J1-11, J1-12, J1-13 and J1-14 when Operating Mode is set to 15 Speed. For motor operation, a motor direction command must be given along with a preset speed command.
Accel Time #1,2 Accel time is the number of seconds required for the motor to increase at a linear rate
from 0 RPM to the RPM specified in the “Max Output Speed” parameter in the Level 2 Output Limits block.
Decel Time #1,2
Decel time is the number of seconds required for the motor to decrease at a linear rate
from the speed specified in the “Max Output Speed” parameter to 0 RPM.
urve #1,
urve is a percentage of the total Accel and Decel time and provides smooth starts
p
p and stops. Half of programmed S-Curve % applies to Accel and half to Decel ramps. 0% represents no “S” and 100% represents full “S” with no linear segment.
Note: Accel #1, Decel #1 and S-Curve #1 are associated together. Likewise,
Accel #2, Decel #2 and S-Curve #2 are associated together. These associations can be used to control any Preset Speed or External Speed command.
Note: If drive faults occur during rapid Accel or Decel, selecting an S-curve may
eliminate the faults.
keypad or terminal strip. At the Keypad, press the JOG key then press and hold the direction (FWD or REV). For Standard Run mode, close the JOG input (J1-12) at the
.
terminal strip then close and maintain the direction input (J1-9 or J1-10).
Jog Accel Time Jog Decel Time Jog S-Curve
0%
Curve
20
%
Output Speed
0
Accel Time
Accel S-Curves
40%
Curve
Process Control mode operation is different. If the terminal strip Process Mode Enable input (J1-13) is closed, pressing the Keypad JOG key (or closing J1-14) will cause the drive to move in the direction of the error (without pressing FWD or REV).
Jo
Accel Time changes the Accel Time to a new preset value for jog mode. Jog Decel Time changes the Decel Time to a new preset value for jog mode. Jog S-Curve changes the S-Curve to a new preset value for jog mode.
Figure 4-2 40% S-Curve Example
40%
Curve
20
%
20
%
Output Speed
0
Decel S-Curves
0%
Curve
Decel Time
20
%
.
Programming
& Operation 4-1
1MN718
Section 1
gqy
General Information
Table 4-2 Level 1 Parameter Block Definitions
Block Title Parameter Description
KEYPAD SETUP Keypad Stop Key
Keypad Stop Mode
Keypad Run FWD Keypad Run REV Keypad Jog FWD Keypad Jog REV
INPUT Operating Mode
Command Select
ANA CMD Inverse “OFF” will cause a low input voltage (e.g. 0VDC) to be a low motor speed command and
ANA CMD Offset Provides an offset to the Analog Input to minimize signal drift. For example, if the
ANA 2 Deadband Allows a defined range of voltage to be a deadband. A command signal within this
ANA 1 CUR Limit Allows the 5V input at J1-2 (referenced to J1-1) to be used for reduction of the
Stop Key - Allows keypad “STOP” key to initiate motor stop during remote or serial
Stop Mode - Selects if the Stop command causes the motor to “COAST” to a stop or
Run FWD - ON makes the keypad “FWD” key active in Local mode. Run REV - ON makes the keypad “REV” key active in Local mode. Jog FWD - ON makes the keypad “FWD” key active in Local Jog mode. Jog REV - ON makes the keypad “REV” key active in Local Jog mode.
Eight “Operating Modes” are available. Choices are: Keypad, Standard Run, 15SPD,
Fan Pump 2 Wire, Fan Pump 3 Wire, Serial, Bipolar, and Process. External connections to the control are made at the J1 terminal strip (wiring diagrams are shown in Section 3 “Control Circuit Connections”).
Selects the external speed reference to be used. The easiest method of speed control is
to select POTENTIOMETER and connect a 5KW pot to J1-1, J1-2, and J1-3. ±5 or ±10VDC input command can be applied to J1-4 and J1-5.
If
long distance is required between the external speed control and the control, the 4-20mA
selections without attenuation of the command signal.
10
VOL
T W/T tional 5V torque feedforward input at J1-1, 2 and 3 to set a predetermined amount of torque inside the rate loop with high gain settings.
EXB PULSE FOL - selects optional Master Pulse Reference/Isolated Pulse Follower ex-
pansion board if installed.
5VOLT EXB - selects optional High Resolution I/O expansion board if installed. 10VOLT EXB - selects optional High Resolution I/O expansion board if installed. 3-15 PSI EXB selects optional 3-15 PSI expansion board if installed. Tachometer EXB- selects optional DC Tachometer expansion board if installed. Serial -selects optional Serial Communications expansion board if installed.
Note: When using the 4-20mA input, the JP1 jumper on the main control board
a maximum input voltage (e.g. 10VDC) to be a maximum motor speed command.
“ON”
will cause a low input voltage (e.g. 0VDC) to be a maximum
and a maximum input voltage (e.g. 10VDC) to be a low motor speed command.
minimum speed signal is 1VDC (instead of 0VDC) the ANA CMD Offset can be set to
-10% so the minimum voltage input is seen by control as 0VDC.
range will not affect the control output. The deadband value is the voltage above and below the zero command signal level.
programmed current limit parameter for torque trimming during operation.
- Continued
operation (if Stop key is set to Remote ON). If active, pressing “STOP” automatically selects Local mode and initiates the stop command.
“REGEN” to a stop. In COAST, the motor is turned off and allowed to coast to a stop. In REGEN, the voltage and frequency to the motor is re­duced at a rate set by “Decel Time”.
at J1-4 and J1-5 should be considered. Current loop allows long cable lengths
ORQ FF - when a dif
must be moved to pins 2 and 3.
ferential command is present at J1-4 and
motor speed command
5, allows addi
-
4-12
Programming & Operation
MN718
Section 1 General Information
Table 4-2 Level 1 Parameter Block Definitions
Block Title Parameter Description
OUTPUT OPTO OUTPUT
#1 – #4
Zero SPD Set PT Sets
At Speed Band The At Speed Band serves two Opto Output Conditions and the Level 2 Protection block
Set Speed Sets the speed that the AT Set Speed opto output becomes active (turns on). When the
Four optically isolated digital outputs that have two operating states, logical High or Low.
Each output may be configured to any of the following conditions:
Condition Description
Ready - Active when power is applied and no faults are present. Zero Speed - Active when output frequency to motor is below the value of the
At Speed - Active when output speed is within the speed range defined by
At Set Speed - Active when output speed is at or above the Level 1 Output
Overload - A normally closed contact that is active (opens) during an
Keypad Control - Active when control is in Local keypad control. Fault - Active when a fault condition is present. Following ERR - Active when the motor speed is outside the user specified
Motor Direction - Active High when REV direction command received. Active Low
Drive On - Active when control is “Ready” (has reached excitation level and
CMD Direction - Active at all times. Logical output state indicates Forward or
AT Position - Active during a positioning command when control is within the
Over Temp Warn - Active when control heat sink is within 3°C of Int Overtemp. Process Error - Active when process feedback signal is outside the range
Drive Run - Active
the speed at which the Zero Speed opto output becomes active (turns on).
speed
is less than
ful when a motor brake is to interlock operation with a motor.
Following Error:
Sets the speed range in RPM at which the At Speed opto output turns on and remains
active within the range.
Sets the Following Error Tolerance Band for the Level 1 OUTPUT, Opto Output condition
Following ERR. The opto output is active if the motor speed is outside this band.
Sets the no fault operating speed range of the drive. This value is used by the Level 2
Protection block, Following Error parameter (if it is set to ON). If the drive speed falls out of this band, the Level 2 Protection block, Following Error parameter will shut down the drive (if it is set to ON).
speed is greater than the Level 1 Output SET SPEED parameter, the Opto Output becomes active. This is useful when another machine must not start or stop until the motor exceeds a predetermined speed.
- Continued
Level 1 Output “Zero SPD Set Pt” parameter.
the Level 1 Output “At Speed Band” parameter.
“Set Speed” parameter.
Overload fault caused by a time out when output current is greater than Rated Current.
tolerance band defined by the At Speed Band parameter.
when FWD direction command received.
capable of producing torque).
Reverse direction.
position band parameter tolerance.
specified by the Level 2 Process Control block, AT Setpoint Band parameter. Turns off when process feedback error is eliminated.
when drive is Ready
received with FWD/REV direction issued.
the ZERO SPD SET PT
, Enabled, Speed or Torque command
, the Opto Output becomes active. This is use
When the
-
MN718
Programming
& Operation 4-13
Section 1 General Information
Table 4-2 Level 1 Parameter Block Definitions
Block Title Parameter Description
OUTPUT (Continued)
Analog Output #1 and #2
Analog Scale #1 Scale factor for the Analog Output voltage. Useful to set the zero value or full scale
Position Band Sets the acceptable range in digital counts (pulses) at which the AT Position Opto
Two Analog 0-5VDC linear outputs may be configured to represent any of 19 conditions
Condition Description
ABS Speed - Represents the absolute motor speed where 0VDC = 0 RPM and
ABS Torque - Represents the absolute value of torque where
Speed Command - Represents the absolute value of commanded speed where
PWM Voltage - Represents the amplitude of PWM voltage where
Flux Current - Represents the actual portion of total current used for excitation.
CMD Flux CUR - Represents the calculated value for flux current.
Load Current - Represents the actual portion of total current used to produce torque
CMD Load Current - Represents the calculated value of load current.
Motor Current - Amplitude of continuous current including motor excitation current.
Load Component - Amplitude of load current not including the motor excitation
Quad Voltage - Load controller output. Used to diagnose control problems. Direct Voltage - Flux controller output. Used to diagnose control problems. AC Voltage - A scaled AC waveform that represents the AC line to line motor
Bus Voltage - Bus voltage scaled to 0-5VDC. 5V = 1000VDC. Torque - Bipolar torque output. 2.5V centered, 5V = Max Positive Torque,
Power - Bipolar power output. 2.5V = Zero Power, 0V = negative rated peak
Velocity - Represents motor speed scaled to 0V = negative max RPM,
Overload - (Accumulated current) PH 2 Current - Sampled AC phase 2 motor current. 2.5V = zero amps,
PH 1 Current - Sampled AC phase 1 motor current. 2.5V = zero amps,
Process Feedback - Represents the selected Process Feedback signal.
Position - Position within a single revolution. +5V = 1 complete revolution.
Setpoint Command - Represents the selected Setpoint Command signal.
range for external meters.
becomes active (turns on).
- Continued
as follows:
+5VDC = MAX RPM.
+5VDC = Torque at CURRENT LIMIT.
+5VDC = MAX RPM.
+5VDC = MAX AC Voltage.
5VDC= MAX flux current.
5VDC= MAX commanded flux current.
(CW and CCW torque). 5V = Max. CW torque, 0V = Max. CCW torque.
5V = Max. commanded load current.
5VDC = Rated Current.
current. 5VDC = Rated Current.
terminal voltage. 0V = Neg Peak PWM voltage. 2.5V centered. 5V = Pos Peak PWM voltage. At rated motor voltage, a full 0 to 5V sinusoidal waveform should be present. This waveform should be at or greater than the motor base frequency. (At half the motor base frequency, a 1.25V to 3.75 sine wave is present.)
0V = Max negative torque.
power, +5V = Positive rated peak power.
+2.5V = Zero Speed, +5V = positive max RPM.
2
x (time), Overload occurs at +5V.
0V = negative rated peak amps, +5V = positive rated peak amps.
0V = negative rated peak amps, +5V = positive rated peak amps.
2.5V centered, 5V = 100%, 0V = –100%.
The counter will reset to 0 every revolution.
2.5V centered, 5V = 100%, 0V = –100%.
4-14
Programming & Operation
MN718
Section 1 General Information
Table 4-2 Level 1 Parameter Block Definitions
Block Title Parameter Description
VECTOR CONTROL CTRL BASE Speed
Feedback Filter
Feedback Align Current PROP
Gain Current INT Gain Speed PROP Gain Speed INT Gain Speed DIFF Gain Position Gain Slip Frequency
Stator R1 Stator resistance in ohms. If set too high, the motor will tend to stall at zero speed when
Stator X1 Stator leakage reactance, in ohms at 60Hz. This parameter has most impact when
LEVEL 2 BLOCK ENTERS LEVEL 2 MENU
Sets the speed in RPM at which the saturation voltage of the control is reached. Above this RPM value the control will output constant voltage and variable frequency.
A larger value provides a more filtered signal but at the cost of reduced bandwidth.
Sets the encoder’s electrical direction of rotation to match that of the motor. Sets the current loop proportional gain.
Sets the current loop integral gain. Sets the speed (velocity) loop proportional gain. Sets the speed (velocity) loop integral gain. Sets the speed (velocity) loop differential gain. Sets the position loop proportional gain. Sets the rated slip frequency of the motor.
reversing or accelerating from low speed. Reducing this value will eliminate the problem. When too low, speed regulation may suffer.
reversing motor rotation at full current limit. If set too low, the true decel time will tend to increase.
- Continued
MN718
Programming
& Operation 4-15
Section 1 General Information
Table 4-3 Level 2 Parameter Block Definitions
Block Title Parameter Description
OUTPUT LIMITS Operating Zone Sets the PWM operating zone to Standard 2.5KHz or Quiet 8.0KHz output carrier
MIN Output Speed Sets the minimum motor speed in RPM. During operation, the motor speed will not be
MAX Output Speed Sets the maximum motor speed in RPM. PK Current Limit The maximum output peak current to the motor. V
PWM Frequency The frequency that the output transistors are switched. PWM frequency is also referred
Current Rate Limit Limits the rate of torque change in response to a torque command.
CUSTOM UNITS Decimal Places
Value At Speed
Units of Measure
PROTECTION Overload Sets the protection mode to Fault (trip off during overload condition) or to Foldback
External Trip OFF - External Trip is Disabled.
Local Enable INP OFF - Ignores J1-8 switched input when in the “LOCAL” mode.
Following Error This parameter determines if the control is to monitor the amount of following error that
Torque Proving When this parameter is set to ON the control looks for balanced output current in all
frequency. Two operating modes are also selectable: Constant Torque and Variable Torque. Constant Torque allows 170 - 200% for 3 seconds overload or 150% for 60 seconds overload. Variable Torque allows 115% peak overload for 60 seconds.
allowed to go below this value except for motor starts from 0 RPM or during dynamic braking to a stop.
alues above 100% of the rated current
are available depending upon the operating zone selected.
to as “Carrier” frequency. PWM should be as low as possible to minimize stress on the output transistors and motor windings. It is recommended that the PWM frequency be set to approximately 15 times the maximum output frequency of the control. Ratios less than 15 will result in non-Sinusoidal current waveforms. See Figure 4-3.
The number of decimal places of the Output Rate display on the Keypad display. This
value will be automatically reduced for large values. The output rate display is only available if the Value At Speed parameter value is non zero.
Sets the desired output rate per RPM of motor speed. Two numbers are displayed on
the keypad display (separated by a slash “/”). The first number (left most) is the value you want the keypad to display at a specific motor speed. The second number (right most) is the motor RPM corresponding to the units in the first number. A decimal may be inserted into the numbers by placing the flashing cursor over the up/down arrow.
Allows user specified units of measure to be displayed on the Output Rate display. Use
the shift and arrow keys to scroll to the first and successive characters. If the character you want is not displayed, move the flashing cursor over the special up/down character arrow on the left side of the display. Use the up/down arrows and the shift key to scroll through all 9 character sets. Use the ENTER key to save your selection.
(automatically reduce the output current below the continuous output level) during an overload. Foldback is the choice if continuous operation is desired. Fault will require the control be “Reset” after an overload.
Note: The “Foldback” selection may not be available on some early versions of
the firmware.
ON - External Trip is enabled. If a normally closed contact at J1-16 is opened, an External Trip fault will occur and cause the drive to shut down.
ON - Requires J1-8 Enable input to be closed to enable the control when in the “LOCAL” mode.
occurs in an application. Following Error is the programmable tolerance for the AT Speed Opto output as defined by the Level 1 Output block, AT Speed Band parameter. Operation outside the speed range will cause a fault and the drive will shut down.
three phases to the motor. If output current is unbalanced, the control will trip off generating a torque proving fault. In a hoist application, for example, this is useful to ensure that motor torque exists before the fail safe brake is released. “Drive On” output, if programmed, will occur if torque proving fails.
4-16
Programming & Operation
MN718
Section 1 General Information
Figure 4-3 Maximum Output Frequency vs PWM Frequency
1000
It
is recommended that the PWM frequency parameter be set
to approximately16 times the maximum output frequency of
900
the control. The greater the ratio, the more sinusoidal the output current waveform will be.
800
700
600
500
400
OUTPUT FREQUENCY
300
200
100
HZ
50
1.00KHz 8.00KHz 16.00KHz
Note:
The output current rating of the control must be derated for high PWM frequency operation as follows: Standard Constant T
orque and Standard V
ariable T
orque: Linearly derate to 10% between 2.5 and 5.0KHz (10% derating at 5.0KHz). Quiet Constant T
orque and Quiet V
ariable T
orque: Linearly derate to
30% between 8.0 and 16KHz (30% derating at 16KHz).
PWM FREQUENCY
Caution: If an automatic restart of the motor control could cause injury to
personnel, the automatic restart feature should be disabled by changing the Level 2 Miscellaneous block, Restart Auto/Man parameter to manual.
Table 4-3 Level 2 Parameter Block Definitions
Block Title Parameter Description
MISCELLANEOUS Restart Auto/Man Manual - If a fault or power loss occurs, the control must be manually reset to resume
operation. Automatic - If a fault or power loss occurs, the control will automatically reset to resume operation.
Restart Fault/Hr The maximum number of automatic restart attempts before requiring a manual restart.
After one hour without reaching the maximum number of faults or if power is turned off and on again, the fault count is rest to zero.
Restart Delay The amount of time allowed after a fault condition for an automatic restart to occur.
Useful to allow sufficient time to clear a fault before restart is attempted.
Factory Settings Restores factory settings for all parameter values. Select YES and press “ENTER” key
to restore factory parameter values. The keypad Display will show “Operation Done” then return to “NO” when completed.
Note: When factory settings are reset, the Motor Rated Amps value is reset to
999.9 amps. This Level 2 Motor Data block parameter value must be changed to the correct value (located on the motor rating plate) before attempting to start the drive.
Continued
MN718
Programming
& Operation 4-17
Section 1 General Information
Table 4-3 Level 2 Parameter Block Definitions
Block Title Parameter Description
MISCELLANEOUS continued
SECURITY CONTROL
MOTOR DATA Motor Voltage The rated voltage of the motor (listed on the motor nameplate).
Homing Speed In Bipolar and Serial modes, this parameter sets the speed that the motor shaft will
rotate to a “Home” position when the orient input switch is closed (J1-11).
Homing Offset In Bipolar and Serial modes, this parameter sets the number of digital encoder counts
past home at which the motor stop command is issued. Quadrature encoder pulses are 4 times the number of encoder lines per revolution. The recommended minimum number is 100 encoder counts to allow for deceleration distance to allow the motor to stop smoothly.
Note: Homing direction is always forward.
Security State Off - No security Access Code required to change parameter values.
Local - Requires security Access Code to be entered before changes can be made using the Keypad. Serial - Requires security Access Code to be entered before changes can be made using the Serial Link. Total - Requires security Access Code to be entered before changes can be made using the Keypad or serial link.
Note: If security is set to Local, Serial or Total you can press PROG and scroll
through the parameter values that are programmed but you are not allowed to change them unless you enter the correct access code.
Access Timeout The time in seconds the security access remains enabled after leaving the programming
mode. If you exit and go back into the program Mode within this time limit, the security Access Code does not have to be re-entered. This timer starts when leaving the Program Mode (by pressing DISP).
Access Code A 4 digit number code. Only persons that know the code can change secured Level 1
and Level 2 parameter values.
Note: Please record your access code and store it in a safe place. If you cannot
gain entry into parameter values to change a protected parameter, please contact Baldor. Be prepared to give the 5 digit code shown on the lower right side of the Keypad Display at the Security Control Access Code parameter prompt.
Motor Rated Amps The rated current of the motor (listed on the motor nameplate). If the motor current
exceeds this value for a period of time, an Overload fault will occur.
Motor Rated SPD The rated speed of the motor (listed on the motor nameplate). If Motor Rated SPD =
1750 RPM and Motor Rated Freq = 60 Hz, the Keypad Display will show 1750 RPM
at 60 Hz and 875 RPM at 30Hz. Motor Rated Freq The rated frequency of the motor (listed on the motor nameplate). Motor Mag Amps The motor magnetizing current value (listed on the motor nameplate). Also called no
load current. Measure using a clamp on amp meter at the AC power line while the
motor is running at line frequency with no load connected to the motor shaft. Encoder Counts The number of encoder feedback counts (lines per revolution). Resolver Speed The speed of the resolver, if a resolver is used for feedback. CALC Presets This procedure loads preset values into memory that are required to perform Auto Tune.
Always run CALC Presets as the first step of Auto Tune.
Continued
4-18
Programming & Operation
MN718
Section 1 General Information
Table 4-3 Level 2 Parameter Block Definitions
Block Title Parameter Description
BRAKE ADJUST Resistor Ohms The dynamic braking resistor value in ohms. Refer to dynamic braking manual or call
Resistor Watts The dynamic braking resistor watts rating. Refer to dynamic braking manual or call
DC Brake Current The amount of DC injection brake current. 0% = Flux current,
PROCESS CONTROL
COMMUNICATIONS Protocol Sets the type of communication the control is to use, RS-232 or RS-485 ASCII (text)
Process Feedback Process Inverse
Setpoint Source
Setpoint Command
Set PT ADJ Limit
Process ERR TOL
Process PROP
Gain
Process INT Gain Process DIFF Gain Follow I:O Ratio
Follow I:O Out
Master Encoder
Baud Rate Sets the speed at which communication is to occur. Drive Address Sets the address of the control for communication.
Baldor for additional information.
Baldor for additional information.
100% = Motor rated current.
Sets the type of signal used for the process feedback signal. Causes the process feedback signal to be inverted. Used with reverse acting processes
that use a unipolar signal such as 4-20mA. If “ON”, 20mA will decrease motor speed and 4mA will increase motor speed.
Sets the source input signal type to which the process feedback will be compared.
If “Setpoint CMD” is selected, the fixed value of the set point is entered Command parameter value.
Sets the value of the setpoint the control will try to maintain by adjusting motor speed.
This is only used when the Setpoint Source is a fixed value “Setpoint CMD” under Setpoint Source.
Sets the maximum speed correction value to be applied to the motor (in response to the
maximum feedback setpoint error). For example, if the max motor speed is 1750 RPM, the setpoint feedback error is 100% and the setpoint adjustment limit is 10%, the maximum speed the motor will run in response to the setpoint feedback error is ±175 RPM. If at the process setpoint, the motor speed is 1500 RPM, the maximum speed adj limits is then 1325 to 1675 RPM.
Sets the width of the comparison band (% of setpoint) with which the process input is
compared. The result is that if the process input is within the comparison band the corresponding Opto Output will become active.
Sets the PID loop proportional gain. This determines how much adjustment to motor
speed (within the Set PT ADJ Limit) is made to move the analog input to the setpoint.
Sets the PID loop Integral gain. This determines how quickly the motor speed is
adjusted to correct long term error.
Sets the PID loop differential gain. This determines how much adjustment to motor
speed (within the Set PT ADJ Limit) is made for transient error.
Sets the ratio of the Master to the Follower in Master/Follower configurations. Requires
the Master Pulse Reference/ Isolated Pulse Follower expansion board. For example, the master encoder you want to follow is a 1024 count encoder. The follower motor you wish to control also has a 1024 count encoder on it. If you wish the follower to run twice the speed of the master, a 1:2 ratio is entered. Fractional ratios such as
0.5:1 are entered as 1:2. Master:Follower ratio limits are (1-65,535) : (1-20). Note: The Master Encoder parameter must be defined if a value is entered in the
Follow I:O Ratio parameter.
Note: When using Serial Communications to operate the control, this value is the
MASTER portion of the ratio. The FOLLOWER portion of the ratio is set in the Follow I:O Out parameter.
This parameter is used only when Serial Communications is used to operate the control.
A Master Pulse Reference/ Isolated Pulse Follower expansion board is required. This parameter represents the FOLLOWER portion of the ratio. The MASTER portion of the ratio is set in the Follow I:O Ratio parameter.
Only used if an optional Master Pulse Reference/Isolated Pulse Follower expansion
board is installed. Defines the number of pulses per revolution of the master encoder. Only used for follower drives.
protocol.
Continued
in the Setpoint
MN718
Programming
& Operation 4-19
Section 1 General Information
Table 4-3 Level 2 Parameter Block Definitions
Block Title Parameter Description
AUTO TUNING
CALC Presets CMD Of
CUR Loop COMP Stator R1 Flux CUR Setting Feedback Tests
Slip FREQ Test SPD CNTRLR
LEVEL 1 BLOCK ENTERS LEVEL 1 MENU
fset Trim
CALC
The Auto Tune procedure is used to automatically measure and calculate certain
parameter values. Dynamic Brake Hardware is required to perform “Slip Freq Test” and “Spd Cntrlr Calc” autotuning test. Occasionally, the Auto Tune procedure cannot be run due to various circumstances such as the load cannot be uncoupled from the
The control can be manually tuned by entering the parameter values based on
motor. calculations you have made. Refer to “Manually Tuning the Control” in the Troubleshooting section of this manual.
This procedure loads preset values into memory that are required to perform Auto Tune.
Always run CALC Presets as the first step of Auto Tune. This procedure trims out voltage offsets for the differential analog input at J1-4 and J1-5. Measures current response to pulses of one half the rated motor current. Measures motor stator resistance. Sets motor magnetizing current by running motor at near rated speed. Checks the values for Encoder Lines per revolution and encoder alignment parameters
while the motor is running at near full rated speed. Test will automatically switch
encoder phasing to match motor rotational direction. Calculates motor Slip Frequency during repeated motor accelerations. Should be performed with the load coupled to the motor shaft. Sets the motor current to
acceleration ratio, Speed INT gain and Speed PROP gain values. If done under no
load, the Integral gain will be too large for high inertia loads if the PK Current Limit is
set too low. If the control is too responsive when the drive is loaded, adjust the PK
Current Limit parameter to a greater value and repeat this test.
Continued
4-20
Programming & Operation
MN718
Section 5 Troubleshooting
The Baldor Series 18H Control requires very little maintenance and should provide years of trouble free operation when installed and applied correctly inspection should be considered to ensure tight wiring connections and to avoid the build up of any dust, dirt, or foreign debris which can reduce heat dissipation.
Before attempting to service this equipment, all input power must be removed from the control to avoid the possibility of electrical shock. The servicing of this equipment should be handled by a qualified electrical service technician experienced in the area of high power electronics.
It is important to familiarize yourself with the following information before attempting any troubleshooting or service of the control. Most troubleshooting can be performed using only a digital voltmeter having an input impedance exceeding 1 meg Ohm. In some cases, an oscilloscope with 5 MHZ minimum bandwidth may be useful. Before consulting the factory recommendations given in this manual.
No Keypad Display - Display Contrast Adjustment
If there is no visible display display.
Action Description Display Comments
Apply Power No visible display.
, check that all power and control wiring is correct and installed per the
. Occasional visual
, use the following procedure to adjust the contrast of the
Press DISP key Ensures control in Display mode. Display mode.
Press SHIFT key 2 times Allows display contrast
Press Y or B key
Press ENTER key Saves display contrast
adjustment. Adjusts display contrast
(intensity).
adjustment level and exits to display mode.
MN718
Troubleshooting
5-1
Table 5-1 Fault Messages
FAULT
Current Sens FL
MESSAGE
T
DC Bus High DC Bus Low Encoder Loss
External T
rip Following Error GND FLT INT Over-Temp T Invalid Base ID Inverter Base ID Line Regen FL Logic Supply FL
T
T
Lost User Data
Low INIT Bus V Memory Error New Base ID No Faults No EXB Installed Over Current FLT Overload - 1 min Overload - 3 sec Over speed
m
P Reset PWR Base FL Regen R PWR FL
T
T Resolver Loss T
orque Prove FL
User Fault T
T
ext
DESCRIPTION
Defective phase current sensor or open circuit detected between control board and current sensor.
Bus over voltage condition occurred. Bus under voltage condition occurred. Encoder coupling slipping or broken; noise on encoder lines, encoder power supply loss or
defective encoder
. An external over temperature condition occurred or open circuit on J1-16. Excessive following error detected between command and feedback signals. Low impedance path detected between an output phase and ground.
emperature of control heatsink exceeded safe level. Control does not recognize power base ID. Control board installed on power base without current feedback. Only applies to Series 21H and 22H Line Regen controls. Logic power supply not working properly
.
Battery backed RAM parameters have been lost or corrupted. When fault cleared (Reset), the control will reset to factory preset values.
Insuf
ficient bus voltage on startup.
EEPROM error occurred. Contact Baldor
. Control board was changed since last operation. Fault log is empty
. Programmed operating mode requires an expansion board. Instantaneous over current condition detected by bus current sensor
. Output current exceeded 1 minute rating. Output current exceeded 3 second rating. Motor RPM exceeded 1
10% of programmed MAX Motor Speed. Power cycled before the residual Bus voltage reached 0VDC. Desaturation of power device occurred or bus current threshold exceeded. Regen power exceeded DB resistor rating. Resolver feedback problem is indicated (if resolver used). Unbalanced current between all 3 motor phases. Custom software operating fault occurred.
5-2 Troubleshooting MN718
Section 1 General Information
How to Access the Fault Log
When a fault condition occurs, motor operation stops and a fault code is displayed on
the Keypad display
. The control keeps a log of up to the last 31 faults. If more than 31 faults have occurred the oldest fault will be deleted from the fault log to make room for the newest fault. T
o access the fault log use the following procedure:
Action Description Display Comments
Apply Power Logo display for 5 seconds.
Display mode showing output frequency
Press DISP key 5 times Use DISP key to scroll to the
Press ENTER key Display first fault type and time
Press Y key
Press ENTER key Return to display mode. Display mode stop key LED is on.
How to Clear the Fault Log
Fault Log entry point.
fault occurred. Scroll through fault messages.
Use the following procedure to clear the fault log.
Display mode.
Typical display.
If no messages, the fault log exit choice is displayed.
Action Description Display Comments
Apply Power Logo display for 5 seconds.
Display mode showing output frequency.
Press DISP key Press DISP to scroll to the Fault
Press ENTER key Displays most recent message.
Press SHIFT key
Press RESET key
Press SHIFT key
Press ENTER key Fault log is cleared. No faults in fault log.
Press Y or B key
Press ENTER key Return to display mode.
Log entry point.
Scroll Fault Log Exit.
Display mode.
MN718
Troubleshooting
5-3
Section 1 General Information
How to Access Diagnostic Information
Action Description Display Comments
Apply Power Logo display for 5 seconds.
Display mode showing motor speed.
Press DISP key 6 times Scroll to Diagnostic Information
screen
Press ENTER key Access diagnostic information. First Diagnostic Information
Press DISP key Display showing control
temperature.
Press DISP key Display showing bus voltage.
No faults present. Local keypad mode. If in remote/serial mode, press local for this display.
Diagnostic Access screen.
screen.
XXXV
Press DISP key Display showing % overload
Press DISP key Display showing opto inputs &
Press DISP key Display showing actual drive
Press DISP key Display showing operating zone,
Press DISP key Display showing continuous
Press DISP key Display showing which Group1 or
current remaining.
outputs states.
running time.
voltage and control type.
amps; PK amps rating; amps/volt scale of feedback, power base ID.
2 expansion boards are installed.
Opto Inputs states (Left); Opto Outputs states (Right).
HR.MIN.SEC format.
ID is displayed as a hexadecimal value.
Press DISP key Display showing motor shaft
Press DISP key Display mode showing parameter
Press DISP key Display showing software version
Press DISP key Displays exit choice. Press ENTER to exit diagnostic
revolutions from the REV home set point.
table selected.
and revision installed in the control.
information.
5-4 Troubleshooting MN718
Section 1 General Information
Table 5-2 Troubleshooting
INDICATION POSSIBLE CAUSE CORRECTIVE ACTION
No Display Lack of input voltage. Check input power for proper voltage.
Loose connections. Check input power termination.
Adjust display contrast. See Adjust Display Contrast in Sec. 4.
Auto Tune Encoder Test failed
Current Sense FLT Open circuit between control board
DC Bus High Excessive dynamic braking power. Increase the DECEL time.
DC Bus Low Input voltage too low. Disconnect dynamic brake hardware and repeat operation.
Encoder Loss Encoder power supply failure. Check 5VDC at J1-29 and J1-30.
Encoder miswired. Correct wiring problems. Encoder coupling slipping, broken
or misaligned. Excessive noise on encoder lines. Check the position counter in the Diagnostic Information for
and current sensor. Defective current sensor. Replace current sensor.
Dynamic brake wiring problem. Check dynamic brake hardware wiring. Input voltage too high. Verify proper AC line voltage.
Encoder coupling slipping, broken or misaligned
Excessive noise on encoder lines. Check the position counter in the Diagnostic Information for
Verify fuses are good (or breaker is not tripped).
Verify connection of operator keypad.
Correct encoder to motor coupling.
jittering which will confirm an encoder problem. Use recommended encoder cable. Check encoder connections including shields. Separate encoder leads from power wiring. Cross encoder wires and power leads at 90°. Electrically isolate encoder from motor. Install optional Isolated Encoder Feedback expansion board.
Check connections between control board and current sensor.
Check dynamic brake watt and resistance parameter values. Add optional dynamic braking hardware.
Use step down isolation transformer if needed. Use line reactor to minimize spikes.
Verify proper AC line voltage. Use step up isolation transformer if needed. Check power line disturbances (sags caused by start up of
other equipment). Monitor power line fluctuations with date and time imprint
to isolate power problem.
Also check at encoder end pins D and F. Correct or replace encoder to motor coupling.
jittering which will confirm an encoder problem. Check encoder connections. Separate encoder leads from power wiring. Cross encoder wires and power leads at 90°. Electrically isolate encoder from motor. Install optional Isolated Encoder Feedback expansion board.
MN718
Troubleshooting
5-5
Section 1 General Information
Table 5-2 Troubleshooting
INDICATION POSSIBLE CAUSE CORRECTIVE ACTION
External Trip Motor ventilation insufficient. Clean motor air intake and exhaust.
Motor draws excessive current. Check motor for overloading.
No thermostat connected. Connect thermostat.
Poor thermostat connections. Check thermostat connections. External trip parameter incorrect. Verify connection of external trip circuit at J1-16.
Following ERR Speed proportional gain set too low. Following error tolerance band set too narrow.
Current limit set too low. Increase Current Limit parameter value. ACCEL/DECEL time too short. Increase ACCEL/DECEL parameter time Excessive load. Verify proper sizing of control and motor.
GND FLT Improper wiring.
Wiring shorted in conduit. Motor winding shorted.
INT Over-Temp Motor Overloaded. Correct motor loading.
Ambient temperature too high. Relocate control to cooler operating area.
Invalid Base ID Control does not recognize HP and
Inverter Base ID Power base with no output phase
Logic Supply FLT Power supply malfunctioned. Replace logic power supply. Lost User Data Battery backed memory failure. Parameter data was erased. Disconnect power to control and
Low INIT Bus V Improper AC line voltage. Disconnect Dynamic Brake hardware and retry test.
Memory Error EEPROM memory fault occurred. Press “RESET” key on keypad. If fault remains, call Baldor. mP Reset
Voltage configuration.
current sensors being used.
Power was cycled before Bus voltage reached 0VDC.
Check external blower for operation. Verify motor’s internal fan is coupled securely.
Verify proper sizing of control and motor.
Verify connection of all external trip circuits used with thermostat. Disable thermostat input at J1-16 (External Trip Input).
Set external trip at J1-16.
Increase Speed PROP Gain parameter value.
Disconnect wiring between control and motor. Retry test. If GND FLT is cleared, reconnect motor leads and retry the test. Rewire as necessary. Repair motor. If GND FLT remains, contact Baldor.
Verify proper sizing of control and motor.
Add cooling fans or air conditioner to control cabinet. Press “RESET” key on keypad. If fault remains, call Baldor.
Replace power base with one that has output leg current
feedback. Contact Baldor.
apply power (cycle power). Enter all parameters. Cycle power. If problem persists, contact Baldor.
Check input AC voltage level.
Press “RESET” key on keypad.
Disconnect power and allow at least 5 minutes for Bus capacitors to discharge before applying power. If fault remains, call Baldor.
Continued
parameter to “OFF” if no connection made
5-6 Troubleshooting MN718
Section 1 General Information
Table 5-2 Troubleshooting
INDICATION POSSIBLE CAUSE CORRECTIVE ACTION
Motor has wrong response to Speed Command
Motor Shaft Oscillates back and forth
Motor Shaft rotates at low speed regardless of commanded speed
Motor Shaft rotates in wrong direction
Motor Will Not Start
Motor Will Not Reach Maximum Speed
Motor Will Not Stop Rotation
Analog input common mode voltage may be excessive.
Incorrect encoder alignment direction.
Incorrect encoder alignment direction.
Incorrect encoder wiring. Reverse the A and A or B and B encoder wires at the J1 input to control
Not enough starting torque. Increase Current Limit setting. Motor overloaded. Check for proper motor loading.
Control not in local mode of operation.
Motor may be commanded to run below minimum frequency setting.
Incorrect Command Select parameter.
Incorrect speed command. Verify control is receiving proper command signal at J1. Max Output Speed set too low. Adjust MAX Output Speed parameter value. Motor overloaded. Check for mechanical overload. If unloaded motor shaft does not rotate
Improper speed command. Verify control is set to proper operating mode to receive speed command.
Speed potentiometer failure. Replace potentiometer. MIN Output Speed parameter set
too high. Improper speed command. Verify control is receiving proper command signal at input terminals.
Speed potentiometer failure. Replace potentiometer.
Connect control input source common to control common to minimize common mode voltage. Maximum common mode voltage at terminals J1-4 and J1-5 is ±15VDC referenced to chassis common.
Change the Feedback Align parameter in the Level 1 Vector Control block. If it is Reverse, change it to Forward. If it is Forward, change it to Reverse.
Check encoder connections. Change the Feedback Align parameter in the Level 1 Vector Control block. If it is Reverse, change it to Forward. If it is Forward, change it to Reverse.
and change encoder direction in the Feedback Align parameter in the Level 1 Vector Control block.
Check couplings for binding. Verify proper sizing of control and motor.
Place control in local mode.
Increase speed command or lower minimum frequency setting.
Change Command Select parameter to match wiring at J1.
freely, check motor bearings.
Verify control is receiving proper command signal at input terminals. Check velocity loop gains.
Adjust MIN Output Speed parameter value.
Verify control is set to receive speed command.
Continued
MN718
Troubleshooting
5-7
Section 1 General Information
Table 5-2 Troubleshooting
INDICATION POSSIBLE CAUSE CORRECTIVE ACTION
New Base ID Software parameters are not
No EXB Installed Incorrect operating mode
Over Current FLT Current Limit parameter set lower
Overload - 3 Sec FLT
Overload - 1 Min FLT
Over Speed Motor exceeded 110% of MAX
initialized on newly installed control board.
programmed. Need expansion board. Install the correct expansion board for selected operating mode.
than drive rating. ACCEL/DECEL time too short. Increase ACCEL/DEC parameters in the Level 1
Encoder coupling slipping, broken or misaligned.
Encoder bearing failure. Replace and align encoder. Excessive noise on encoder lines. Check the position counter in the Diagnostic Information for
Electrical noise from external DC coils.
Electrical noise from external AC coils.
Excessive load. Reduce the motor load.
Peak output current exceeded 3 second rating.
Encoder coupling slipping, broken or misaligned.
Encoder bearing failure. Replace and align encoder. Peak output current exceeded 1
minute rating.
Encoder coupling slipping, broken or misaligned.
Encoder bearing failure. Replace and align encoder.
Speed parameter value.
Press “RESET” key on keypad to clear the fault condition. Cycle power (turn power OFF then ON). Reset parameter values to factory settings. Access diagnostics and compare power base ID number to list in Table 5-3 to ensure a match. Re-enter the Parameter Block Values you recorded in the User Settings at the end of this manual. Autotune the control.
Change Operating Mode in the Level 1 Input block to one that does not require the expansion board.
Increase PK Current Limit parameter in the Level 2 Output Limits block, not to exceed drive rating.
ACCEL/DECEL Rate block. Correct or replace encoder to motor coupling.
jittering which will confirm an encoder problem. Check encoder connections. Separate encoder leads from power wiring. Cross encoder wires and power leads at 90°. Electrically isolate encoder from motor. Install optional Isolated Encoder Feedback expansion board.
Install reverse biased diodes across all external DC relay coils as shown in the Opto Output circuit examples of this manual. See Electrical Noise Considerations in Section 5 of this manual.
Install RC snubbers on all external AC coils. See Electrical Noise Considerations in Section 5 of this manual.
Verify proper sizing of control and motor. Check PK Current Limit parameter in the Level 2
Output Limits block. Change Overload parameter In the Level 2 Protection block
from Trip to Foldback. Check motor for overloading. Increase ACCEL time. Reduce motor load. Verify proper sizing of control and motor.
Correct or replace encoder to motor coupling.
Check PK Current Limit parameter in the Level 2
Output Limits block. Change Overload parameter In the Level 2 Protection block
from Trip to Foldback. Check motor for overloading. Increase ACCEL/DECEL times. Reduce motor load. Verify proper sizing of control and motor.
Correct or replace encoder to motor coupling.
Check Max Output Speed in the Level 2 Output Limits block. Increase Speed PROP Gain in the Level 1 Vector Control block.
Continued
5-8 Troubleshooting MN718
Section 1 General Information
Table 5-2 Troubleshooting
INDICATION POSSIBLE CAUSE CORRECTIVE ACTION
Power Module Power supply failure. Press “RESET” key on keypad. If fault remains, call Baldor. PWR Base FLT Improper ground
Excessive current usage.
Encoder coupling slipping, broken or misaligned.
Encoder bearing failure. Replace and align encoder. Excessive noise on encoder lines. Check encoder connections.
Electrical noise from external DC coils.
Electrical noise from external AC coils.
Excessive load. Correct motor load.
Excessive power in dynamic brake circuit.
Regen R PWR FLT
Resolver Loss Resolver defect. Check resolver to motor coupling (align or replace if needed).
Torque Prove FLT Unbalanced current in 3 motor
Unknown Fault Fault occurred but cleared before its
User Fault Text Fault detected by custom software. Refer to custom software fault list.
Incorrect dynamic brake parameter. Check Resistor Ohms and Resistor Watts parameters in the Level 2 Brake
Regen power exceeded dynamic brake resistor rating.
Input voltage too high. Verify proper AC line voltage.
phases.
source could be identified.
Be sure control has separate ground wire to earth ground. Panel grounding or conduit connections is not sufficient. Disconnect motor leads from control and retry test. If fault remains, call Baldor.
Correct or replace encoder to motor coupling.
Separate encoder leads from power wiring. Cross encoder wires and power leads at 90°. Electrically isolate encoder from motor. Install optional Isolated Encoder Feedback expansion board.
Install reverse biased diodes across all external DC relay coils as shown in the Opto Output circuit examples of this manual. See Electrical Noise Considerations in Section 7 of this manual.
Install RC snubbers on all external AC coils. See Electrical Noise Considerations in Section 7 of this manual.
Verify proper sizing of control and motor. Verify proper Ohm and Watt parameters of DC Injection Braking.
Increase decel time. Add optional dynamic braking hardware.
Adjust block. Add optional dynamic braking hardware.
Use step down transformer if needed. Use line reactor to minimize spikes.
Verify correct wiring. Refer to the Resolver to Digital
expansion board manual.
Electrically isolate resolver from motor. Check continuity from control to motor windings and verify motor
connections. Check AC line for high frequency noise.
Check input switch connections and switching noise.
Continued
MN718
Troubleshooting
5-9
Section 1
230VAC
460VAC
VAC
Catal
Catal
Catal
General Information
Table 5-3 Power Base ID - Series 18H
Power Base ID
FIF10 / FIF40 FIF20 / FIF24
og
Bus
No.
201–E 002 802 023 823 401–E 202 A02 23B A3B 501–E 602 E02 61A E1A 201–W 002 802 023 823 401–W 202 A02 23B A3B 501–W 602 E02 61A E1A 202–E 003 803 024 824 402–E 203 A03 23C A3C 502–E 603 E03 61B EIB 202–W 003 803 024 824 402–W 203 A03 23C A3C 502–W 603 E03 61B EIB 203–E 004 804 025 825 403–E 204 A04 23D A3D 503–E 604 E04 61C E1C 203–W 004 804 025 825 403–W 204 A04 23D A3D 503–W 604 E04 61C E1C 205–E 005 805 026 826 405–E 205 A05 241 A41 505–E 605 E05 61D E1D 205–W 005 805 02A 82A 405–W 205 A05 241 A41 505–W 605 E05 61D E1D 207–E 006 806 027 827 407–E 206 A06 23E A3E 507–E 606 E06 61E E1E 207–W 006 806 027 827 407–W 206 A06 23E A3E 507–W 606 E06 61E E1E 207L–E 001 801 407L–E 201 A01 510–E 607 E07 61F E1F 210–E 007 807 028 828 410–E 207 A07 207 A07 510–W 607 E07 61F E1F 210–W 028 828 410–W 207 A07 515–E 608 E08 620 E20 210L–E 02B 82B 410L–E 23F A3F 515–W 608 E08 620 E20 215–E 01A 81A 01A 81A 415–E 22C A2C 242 A42 510L 215–W 01A 81A 415–W 242 A42 515L 210L–ER 00C 80C 410L–ER 208 A08 520 611 E11 215V 008 808 415V 20E A0E 520L 60B EOB 215L 00A 80D 415L 20F A0F 525 612 E12 220 011 811 420 211 A11 525L 60C E0C 220L 00E 80E 420L 220 A20 530 613 E13 225 01D 81D 425 212 A12 530L 60D E0D 225V 009 809 425V 20B A0B 540 614 E14 225L 00F 80F 425L 221 A21 540L 60E E0E 230 013 813 430 213 A13 550 615 E15 230V 016 816 430V 20C A0C 550L 60F E0F 230L 017 817 430L 222 A22 560 616 E16 240 014 814 440 214 A14 575 617 E17 240L 018 818 440L 223 A23 5100 618 E18 250 015 815 450 215 A15 5150 E1A 250V 00A 80A 450L 21C A1C 5150V 619 E19 250L 01C 81C 460 216 A16 5200 E2A 275 829 460V 20A A0A 5250 E3A
Cur
Phase
Cur
Bus
Cur
Phase
Cur
Note: The
og
No.
460L 224 A24 5300 EA4
475 217 A17 5350 EA5 475L 21D A1D 5400 EA6 4100 218 A18
4100L A2F 4125L A30
4150 A9A
4150V 219 A19
4200 A9B 4250 AA5 4300 AAE 4350 AA6 4400 AA7 4450 AA9
Power Base ID number of a control is displayed in a Diagnostic
Information screen as a hexadecimal value.
Power Base ID
FIF10 / FIF40 FIF20 / FIF24
Bus
Cur
Phase
Cur
Bus
Cur
Phase
Cur
575
No.
Power Base ID
FIF10 / FIF40 FIF20 / FIF24
og
Bus
Phase
Cur
Cur
Bus
Cur
Phase
Cur
5-10 Troubleshooting MN718
Section 1 General Information
Electrical Noise Considerations
electronic interference signals (commonly called “Electrical Noise”). At the lowest level, noise can cause intermittent operating errors or faults. From a circuit standpoint, 5 or 10 millivolts of noise may cause detrimental operation. For example, analog speed and torque inputs are often scaled at 5 to 10 VDC maximum with a typical resolution of one part in 1,000. Thus noise of only 5 mV represents a substantial error
At the extreme level, significant noise can cause damage to the drive. Therefore, it is advisable to prevent noise generation and to follow wiring practices that prevent noise generated by other devices from reaching sensitive circuits. In a control, such circuits include inputs for speed, torque, control logic, and speed and position feedback, plus outputs to some indicators and computers.
Causes and Cures
Unwanted electrical noise can be produced by many sources. Depending upon the source, various methods can be used to reduce the ef coupling to sensitive circuits. All methods are less costly when designed into a system initially than if added after installation.
Figure 5-1 shows an oscilloscope trace of noise induced (as the coil circuit is opened) in a 1–ft. wire located next to a lead for a Size 2 contactor coil. Scope input impedance is 10KW often enough noise to ruin the output of a productive machine.
All electronic devices including the Series 18H Control are vulnerable to significant
.
fects of this noise and to reduce the
for all scope traces. Maximum peak voltage is over 40V
. Unless well filtered this is
Figure 5-1 Electrical Noise Display
Relay and Contactor Coils
Among the most common sources of noise are the ever–present coils of contactors and relays. When these highly inductive coil circuits are opened, transient conditions often generate spikes of several hundred volts in the control circuit. These spikes can induce several volts of noise in an adjacent wire that runs parallel to a control–circuit wire.
T
o suppress noise in these AC coils, add an R–C snubber across each relay and
contactor coil. A snubber consisting of a 33KW resistor in series with a 0.47mF capacitor usually works well. The snubber reduces the rate of rise and peak voltage in the coil when current flow is interrupted. This eliminates arcing and reduces the noise voltage induced in adjacent wires. In our example, the noise was reduced from over 40 Vpeak to about 16 Vpeak as shown in Figure 5-2.
Figure 5-2 R-C Snubber Circuit
Troubleshooting
5-1
1MN718
Section 1 General Information
Electrical Noise Considerations
Continued
Combining an R-C snubber and twisted-pair shielded cable keeps the voltage in a circuit to less than 2 V for a fraction of a millisecond. The waveform shown in Figure 5-3 in addition to the snubber across the coil, the adjacent wire is grounded in a twisted–pair shielded cable. Note that the vertical scale is 1 V/div
., rather than the 20 V/div
. in figures
,
5-1 and 5-2. This shows that snubbers and twisted-pair shielded wire should be used for sensitive circuits located adjacent to coil wires.
Figure 5-3 R-C Snubber Circuit & twisted-pair
A
reverse biased diode across a DC coil achieves the same result as adding an R–C
snubber across an AC coil, Figure 5-4.
Figure 5-4 AC & DC Coil Noise Suppression
RC snubber
+
AC Coil
0.47 mF 33 W
DC Coil
Diode
5-12 Troubleshooting MN718
Section 1 General Information
Electrical Noise Considerations
W
ires between Controls and Motors
Continued
Output leads from a typical 460 V by power semiconductors switching 650V in less than a microsecond, 1,000 to 10,000 times a second. These noise signals can couple into sensitive drive circuits as shown in Figure 5-5. For this waveform, a transient induced in 1 ft. of wire adjacent to motor lead
of a 10 hp, 460 V
AC drive. Scope is set at 5 V/div
AC drive controller contain rapid voltage rises created
. and 2
msec/div.
Figure 5-5 10HP, 460VAC Drive
If
the shielded pair cable is used, the coupling is reduced by nearly 90%, Figure 5-6.
Figure 5-6 10HP, 460VAC Drive, Shielded
The
motor leads of DC motors contain similar voltage transients. The switching rate is about 360 times a second. These noise transients can produce about 2V of noise induced in a wire adjacent to the motor lead. A 30HP
5-7. Scope is set at 1 V/div
. and 5
msec/div.
, 500VDC Drive, as shown in Figure
Figure 5-7 30HP, 500VDC Drive
Again,
Replacing a single wire with a shielded pair cable reduces the induced noise to
less than 0.3 V
, Figure 5-8.
Figure 5-8 30HP, 500VDC Drive, Shielded
MN718
Troubleshooting
5-13
Loading...