Be sure that you are completely familiar with the safe operation of this equipment. This
equipment may be connected to other machines that have rotating parts or parts that are
controlled by this equipment. Improper use can cause serious or fatal injury. Always
disconnect all electrical loads before starting the generator.
Installation and repair procedures require specialized skills with electrical generating equipment
and liquid cooled engine systems. Any person that installs or repairs this generator must have
these specialized skills to ensure that this generating unit is safe to operate. Contact Baldor
service department for repairs or any questions you may have about the safe installation and
operation of this system.
The precaution statements are general guidelines for the safe use and operation of this
generator. It is not practical to list all unsafe conditions. Therefore, if you use a procedure that is
not recommended in this manual you must determine if it is safe for the operator and all
personnel in the proximity to the generator and connected loads. If there is any question of the
safety of a procedure please contact Baldor before starting the generator.
This equipment contains high voltages. Electrical shock can cause serious or fatal injury. Only
qualified personnel should attempt the start−up procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts that are
driven by this equipment. Improper use can cause serious or fatal injury. Only qualified
personnel should attempt the start−up procedure or troubleshoot this equipment.
−System documentation must be available to anyone that operates this equipment at all
times.
−Keep non-qualified personnel at a safe distance from this equipment.
−Only qualified personnel familiar with the safe installation, operation and maintenance
of this device should attempt start-up or operating procedures.
−Always stop engine before making or removing any connections.
−Always stop engine and allow it to cool before refueling.
Responsibility
Read This Manual Thoroughly
When your generator is delivered, it becomes the responsibility of the owner/operator of the
generator set to prevent unsafe conditions and operation of the equipment. Some
responsibilities include (but are not limited to) the following:
1.It is the responsibility of the owner/operator of this generator to ensure that this
equipment is correctly and safely installed.
2.It is the responsibility of the owner/operator of this generator to ensure that this
equipment, when installed fully complies with all federal, state and local codes.
3.It is the responsibility of the owner/operator of this generator to ensure that any person
operating this equipment has been properly trained.
4.It is the responsibility of the owner/operator of this generator to ensure that any person
operating this equipment has access to all manuals and information required for the
safe use and operation of this equipment.
5.It is the responsibility of the owner/operator of this generator to ensure that it is properly
maintained and safety inspected at regular scheduled intervals.
6.It is the responsibility of the owner/operator of this generator to ensure that any person
who has not been trained on the safe use of this equipment does not have access to
this equipment.
If you do not understand any concept, any procedure, any safety warning statement, any safety
caution statement or any portion of this manual, contact Baldor or your nearest authorized Baldor
representative. We are happy to make sure you understand the information in this manual so
that you can safely enjoy the full use of this generator.
Product Safety Information 1-1MN2411
Symbols
This symbol is shown throughout the manual to indicate a connection to ground reference point.
Indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
Indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
Precaution Statements Used In This Manual
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in injury or
Caution:Indicates a potentially hazardous situation which, if not avoided, could result in damage to
Note:Additional information that is not critical to the installation or operation.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS − This manual contains important instructions for the generator that should
be followed during installation, operation and maintenance of the generator.
For ease of reading, the Warning statements are divided into four categories: Operation, Burn, Installation,
and Maintenance.
Operation
WARNING: Gasoline and diesel fuel are flammable and can cause fire, explosions, injury or death. For
WARNING: Do not overfill the fuel tank. Only fill the tank to within
WARNING: Clean up fuel spills by wiping completely dry before starting engine. Gasoline and diesel fuel
WARNING: Make sure the fuel cap is completely and securely closed after refueling to prevent spillage.
WARNING: Never operate this generator in a manner other than as described in this manual. Operation
WARNING: Be sure that you are completely familiar with the safe operation of this equipment. This
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never
WARNING: Hot exhaust gasses must never be directed toward anything that may catch fire or explode.
WARNING: This generator must not be used on or near any forest covered, brush covered, or grass
WARNING: Never move a generator set that is running. Hazards are caused by moving a generator set
There are three classifications of precautionary statements used in this manual. The most critical
is a WARNING statement, then the Caution statement and the least critical is the Note
statement. The usage of each statement is as follows:
death.
property.
storage or refueling handle fuel with care and only in clean, approved, properly marked safety
fuel containers.
1
/2, of the top of the tank to allow
space for fuel expansion. Overfilling of tank may cause fuel to spill out onto engine and
cause fire or explosion.
are flammable and can cause fire, explosions, injury or death.
Gasoline and diesel fuel are flammable and can cause fire, explosions, injury or death.
in any manner not described in this manual should be considered unsafe and should not be
attempted. Never start the engine unless you have first verified that the installation and
operation of the generator are as described in this manual.
equipment may be connected to other machines that have rotating parts or parts that are
controlled by this equipment. Improper use can cause serious or fatal injury.
breath exhaust fumes produced by a running engine. Only run the engine outdoors where
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or
incoherence. If you or anyone else experiences these symptoms, get out into fresh air
immediately. Stop the engine and do not restart the engine until it has been inspected and if
necessary repaired or reinstalled in a well ventilated area.
covered land unless the engine’s exhaust system is equipped with a spark arrestor. The
spark arrestor must be maintained in effective working order by the operator.
that is running.
Continued on next page.
1-2 Product Safety InformationMN2411
Operation Warning Statements
WARNING: Some parts of this generator rotate during operation. Rotating parts can present extreme
danger if clothing or body extremities are caught by the rotating part and can cause serious
or fatal injury. Never touch a part of the generator until the engine has been stopped and all
rotating parts are completely stopped. Also, disconnect the spark plug wires and battery
connection to prevent accidental engine rotation during servicing.
WARNING: Be sure that you understand how to stop the engine quickly in case of an emergency situation.
Become familiar with the controls and safety systems provided with this generator set.
WARNING: Always wear safety glasses with side shields and hearing protection when working near the
generator.
WARNING: Improper operation may cause violent motion of connected equipment. Be certain that
unexpected movement will not cause injury to personnel or damage to equipment.
WARNING: Never operate the generator set indoors or in a poorly ventilated area such as a tunnel or
cave. Exhaust fumes are extremely dangerous to all personnel that are in or in contact with
that area.
WARNING: Never permit anyone to operate the generator without proper instructions. Be sure to keep a copy
of this manual with the generator so that all users can be properly informed of its safe operation.
WARNING: Never allow children or pets to be in the area where the generator is running. The generator
and the equipment being powered by the generator may cause injury or death.
WARNING: Never operate the generator unless all guards, covers, shields and other safety items are
properly installed.
WARNING: Do not put hands, feet, tools clothing or other objects near rotating parts such as drive shaft,
pulley, belt etc. Rotating parts cause extremely dangerous situations because they can catch
loose clothing or extremities and cause serious or fatal injury.
WARNING: When operating this generator remain alert at all times. Never operate machinery when
physically or mentally fatigued, or while under the influence of alcohol, drugs or medication.
WARNING: Never operate the engine when the air cleaner is removed. An engine backfire can cause
serious burns.
WARNING: High voltage is present whenever engine is running. Electrical shock can cause serious or
fatal injury. Never operate electrical equipment while standing in water, on wet ground or with
wet hands, feet or shoes or while barefoot.
WARNING: High voltage is present whenever the engine is running. Electrical shock can cause serious
or fatal injury.
WARNING: Do not smoke near generator during operation or while refueling. Gasoline and diesel fuel are
flammable and can cause fire, explosions, injury or death.
WARNING: Stop engine and allow engine to cool before refueling. Gasoline and diesel fuel are flammable
and can cause fire, explosions, injury or death.
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area
where gasoline fumes could reach an ignition source and cause an explosion. Fumes may
reach an open flame, electrical spark or pilot light as on a furnace, water heater, clothes dryer,
etc. Gasoline and diesel fuel are flammable and can cause fire, explosions, injury or death.
WARNING: Allow generator to cool before transporting it or storing it. Always drain fuel from tank after
generator has cooled.
WARNING: When transporting the generator (especially over rough roads) always drain the fuel tank to
prevent leakage or spillage of fuel. Gasoline and diesel fuel are flammable and can cause fire,
explosions, injury or death.
WARNING: Operate the generator only on a level surface. If the generator is tilted during operation, fuel
spillage may result. Gasoline and diesel fuel are flammable and can cause fire, explosions,
injury or death.
WARNING: Keep generator at least three feet away from buildings and other structures.
WARNING: Keep generator away from flammable or hazardous materials (trash, rags, lubricants,
explosives, paints etc.) and grass or leaf build up.
WARNING: Keep a fire extinguisher near the generator while generator is in use. An extinguisher rated
“ABC” by the National Fire Protection Association is appropriate.
Continued on next page.
Continued
Product Safety Information 1-3MN2411
Warning Statements
Burn
WARNING: Parts of this generator are extremely hot during and after operation. To prevent severe burns,
do not touch any part of the generator until you have first determined if the part is hot. Wear
protective clothing and after use allow sufficient time for parts to cool before touching any
part of the generator.
WARNING: Do not touch the hot exhaust parts or the high voltage spark plug or coil terminals of the
engine. Although spark plug voltages are not normally lethal, a sudden involuntary jerk of the
hand or body part caused by contact with high voltage or a hot surface can result in injury to
yourself or others.
Installation
WARNING: Installation and repair procedures requires specialized skills with electrical generating
equipment and small engine systems. Any person that installs or performs repairs must have
these specialized skills to ensure that the generator set is safe to operate. Contact Baldor for
installation or repairs.
WARNING: Be sure all wiring complies with the National Electrical Code (NEC) and all regional and local
codes or CE Compliance. Improper wiring may cause a hazardous condition and exposure to
electrical hazards can cause serious injury or death.
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power
before you ensure that grounds are connected. Electrical shock can cause serious or fatal
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be
connected to an approved earth ground. Local codes may also require proper grounding of
generator systems.
WARNING: Place protective covers over all rotating parts such as drive shaft, pulley, belt etc. Rotating
parts cause extremely dangerous situations because they can catch loose clothing or
extremities and cause serious or fatal injury.
WARNING: Unauthorized modification of a generator set may make the unit unsafe for operation or may
impair the operation of the unit. Never start a generator set that has been modified or
tampered with. Be sure that all covers and guards are properly installed and that the unit is
safe before starting the engine. If you are unsure, contact Baldor before starting the engine.
WARNING: When moving the generator, use reasonable caution. Be careful where you place fingers and
toes to prevent injury “Pinch Points”. Never try to lift a generator without a hoist or lift means
because they are heavy and bodily injury may result.
WARNING: When transporting a generator secure the unit to prevent movement during transport.
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician
has installed an approved transfer switch. The National Electrical Code (NEC) requires that
connection of a generator to any electrical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.
WARNING: Circuit overload protection must be provided in accordance with the National Electrical Code
and local regulations.
WARNING: Check Ground Fault Circuit Interrupt (GFCI) receptacles monthly by using the “Test” and
“Reset” buttons.
Continued
Continued on next page.
1-4 Product Safety InformationMN2411
Warning Statements
Maintenance
WARNING: Before cleaning, inspecting, repairing, refueling or performing any maintenance to the
generator set, always be sure the engine has stopped and that all rotating parts have also
stopped. After stopping, certain components are still extremely hot so be careful not to get
burned.
WARNING: Before servicing the generator set, be sure to disconnect the spark plug wires to prevent
accidental engine rotation or starting.
WARNING: Inspect all wiring frequently and replace any damaged, broken or frayed wiring or wires with
damaged insulation immediately. Electrical shock can cause serious or fatal injury.
WARNING: Disconnect all electrical wires and load devices from generator power outlets before servicing
the generator. Electrical shock can cause serious or fatal injury. Always treat electrical
circuits as if they are energized.
WARNING: Check fuel tank, fuel line, and connections monthly for fuel leaks. Gasoline is flammable and
can cause fire, explosions, injury or death. If a leak is found, replace only with approved pipe
or components.
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area
where gasoline fumes could reach an ignition source and cause an explosion.
Caution Statements
Caution:The brass connecting tab on some 120VAC duplex receptacles have been removed. Each
receptacle is powered by a separate generator winding. When replacing a receptacle, inspect
the brass tab that normally links both receptacles. If it is removed, be sure to remove the
brass tab from the replacement receptacle before it is installed. Failure to remove the tab will
cause a direct short to the generator windings and cause possible generator damage.
Caution:Avoid installing the generator set beside heat generating equipment, or directly below water
or steam pipes or in the vicinity of corrosive substances or vapors, metal particles and dust.
Heat can cause engine problems to develop and unwanted substances can cause rust or
generator failure over time.
Caution:Do not apply high voltage to windings (start the generator) in a moisture−saturated condition.
Moisture can cause insulation breakdown, making it necessary to return the generator to the
factory for repair, and consequent expense and loss of time.
Caution:Use only original equipment or authorized replacement parts. Using the correct parts will
assure continued safe operation as designed.
Caution:Do not suspend the generator from the top handle during operation.
Caution:Do not tamper with or change the engine speed. Engine speed is factory set to produce the
correct voltage and output frequency.
Caution:Never operate the engine without a muffler and spark arrestor. The engine is designed to
have the correct exhaust components installed. Operating without these components can
present a fire hazard, cause excessive exhaust gases and cause damage to engine.
Caution:Operate the generator only on a level surface. Operation of the generator on an incline or
slope may degrade engine lubrication and result in engine failure.
Caution:Always fill fuel tank with clean fresh fuel before use. Never leave fuel in tank for long storage
periods. Old fuel becomes stale and can damage the fuel system causing the engine not to
start. Always drain the fuel tank after use before storage.
Caution:For electric start models, do not place the key switch in the start position when engine is
running. This causes the starting motor to engage and may damage the starter and engine.
Continued
Product Safety Information 1-5MN2411
1-6 Product Safety InformationMN2411
Section 2
General Information
Thank you for purchasing your Baldor Generator Set. This manual contains information you need to safely and efficiently
install and operate your generator set. During the preparation of this manual every effort was made to ensure the
accuracy of its contents. This manual describes only very basic engine information. A separate owner’s manual for the
engine is supplied with this unit for your use. Please refer to the engine manual for information relative to engine
operation, maintenance, recommendations and additional safety warnings.
Copyright Baldor E 2004. All rights reserved.
This manual is copyrighted and all rights are reserved. This document may not, in whole or in part, be copied or
reproduced in any form without the prior written consent of Baldor Electric Company, Inc.
Baldor Generators have earned the reputation of being high quality and dependable. We take pride in this fact and
continue to keep our quality standards high on our list of priorities. We are also constantly researching new technological
ideas to determine if they could be used to make our generator sets even better.
Baldor makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied
warranties of fitness for any particular purpose. The information in this document is subject to change without notice.
Baldor assumes no responsibility for any errors that may appear in this document.
Limited Warranty
Baldor Generators will replace or repair free of charge any part or parts of the generator of their manufacture that are
defective in workmanship and materials for a period of time as set forth in the Warranty Period chart below. All Baldor
products requiring warranty service shall be transported or shipped freight pre--paid, at the risk of the party requiring
warranty service, to a Baldor Generator repair facility, or to Baldor Generators’ Customer Service Department. Written
notification of the alleged defect in addition to a description of the manner in which the Baldor generator is used, and the
name, address and telephone number of the party requiring warranty service must be included. Baldor is not responsible
for removal and shipment of the Baldor product to the service center or for the reinstallation of the Baldor product upon its
return to the party requiring warranty service. Problems with Baldor products can be due to improper maintenance, faulty
installation, non--Baldor additions or modifications, or other problems not due to defects in Baldor workmanship or
materials. If a Baldor Generator repair facility determines that the problem with a Baldor product is not due to defects in
Baldor workmanship or materials, then the party requesting warranty service will be responsible for the cost of any
necessary repairs. EXCEPT FOR THE EXPRESSED WARRANTY SET FORTH ABOVE, BALDOR GENERATORS
DISCLAIMS ALL OTHER EXPRESSED AND IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY. NO OTHER WARRANTY, EXPRESSED OR
IMPLIED, WHETHER OR NOT SIMILAR IN NATURE TO ANY OTHER WARRANTY PROVIDED HEREIN, SHALL
EXIST WITH RESPECT TO THE GOODS SOLD UNDER THE PROVISIONS OF THESE TERMS AND CONDITIONS.
ALL OTHER SUCH WARRANTIES ARE HEREBY EXPRESSLY WAIVED BY THE BUYER. UNDER NO
CIRCUMSTANCES SHALL BALDOR GENERATORS BE LIABLE OR RESPONSIBLE IN ANY MANNER WHATSOEVER
FOR ANY INCIDENTAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, OR ANTICIPATED PROFITS RESULTING
FROM THE DEFECT, REMOVAL, REINSTALLATION, SHIPMENT OR OTHERWISE. This is the sole warranty of Baldor
Generators and no other affirmations or promises made by Baldor Generators shall be deemed to create an expressed or
implied warranty. Baldor Generators has not authorized anyone to make any representations or warranties other than the
warranty contained herein.
Warranty Period
Generator SeriesLabor*Parts
Portable Products (Premier, Powerchief,
*For products covered under labor coverage, travel expenses will be allowed up to 7 hours straight labor or 300 miles,
whichever occurs first and only applies to permanently wired and mounted products (AE, DLC, GLC, IDLC).
No warranty registration card is necessary to obtain warranty on Baldor Generators.
You must save the purchase receipt. Proof of purchase, date, serial number and model number will be required for all
portable and Towable products to qualify for any warranty consideration.
For all other products, a start--up inspection form/warranty registration must be completed in its entirety and submitted to
Baldor Generators within 30 days of start--up to qualify for any warranty consideration.
DG Series, K Series)
Towable Products (TS)1 Year or 3,000 Hours
POW’R LITE Light Towers1 Year or 3,000 Hours
3600 RPM Standby Systems
(Some AE Models)
1800 RPM Standby Systems
(Some AE Models, DLC, GLC)
Industrial Standby Systems1 Year or 1,000 Hours
Industrial Prime Power Systems1 Year or 1,000 Hours
International1 Year or 1,000 Hours
Whichever comes first
Whichever comes first
1 Year or 1,000 Hours
Whichever comes first
1 Year or 3,000 Hours
Whichever comes first
Whichever comes first
Whichever comes first
Whichever comes first
1 Year3 Years
3 Years or 3,000 Hours
Whichever comes first
3 Years or 3,000 Hours Whichever comes first
Excluded from any warranty coverage regardless of
time period: Light Fixture, Lamps and Ballasts
3 Years or 1,000 Hours
Whichever comes first
3 Years or 3,000 Hours
Whichever comes first
2 Years or 1,000 Hours
Whichever comes first
1 Year or 1,000 Hours
Whichever comes first
1 Year or 1,000 Hours
Whichever comes first
General Information 2-1MN2411
2-2 General InformationMN2411
Section 3
Receiving & Installation
Receiving & Inspection When you receive your generator, there are several things you should do immediately.
1.Observe the condition of the shipping container and report any damage immediately to
the commercial carrier that delivered your system.
2.Verify that the part number of the system you received is the same as the part number
listed on your purchase order.
3.If the system is to be stored for several weeks before use, be sure that it is stored in a
location that conforms to published storage temperature and humidity specifications.
Lifting the Generator
The generator weighs about 55 lbs dry. Use proper lift equipment and methods to avoid injury.
Figure 3-1 PC17RI Portable Generator
PC1100RPC1700RI
PILOT
LAMP
STOP
~ AC OUTPUT
RUN
CHOKE
DC12V − 8.3A
BATTERY CHARGE ONLY
−
+
ONOFF
OVER
PILOT
LAMP
STOP
+−
LOAD
~ AC OUTPUT
RUN
CHOKE
AUTO
POWER
SAVE
DC12V − 8.3A
BATTERY CHARGE ONLY
−
ONOFF
ONOFF
+
+−
ENGINE SWITCH
ENGINE SWITCH
StorageIf you will not be using the generator set for a significant amount of time (3 months or longer) you
should store the generator to prevent any problems that could arise from sitting idle. Please fully
read the storage guidelines in Section 5 of this manual.
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area
where gasoline fumes could reach an ignition source and cause an explosion.
Receiving & Installation 3-1MN2411
Physical Location
Your generator is portable to go where the work is. To be safe, several factors must be considered:
1.Keep extension cords as short as possible.
2.For effective cooling and maintenance, the generator should be mounted on a flat, smooth,
non-flammable level surface. A concrete pad is ideal and provides a secure installation.
3.The location for the generator must be dry. Never operate a generator in an area that
has standing water or puddles.
4.Prevent obstructions (buildup of leaves, grass, sand, snow, etc.). It is important that
the unit be operated in a reasonably clean environment.
5All engines give off considerable heat when running. The engine in your generator set
uses air to keep it cool so it is important that the ambient temperature is cool. Where
natural ventilation is inadequate a fan to boost circulation should be used.
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never
breath exhaust fumes produced by a running engine. Only run the engine outdoors where
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or
incoherence. If you or anyone else experiences these symptoms, get out into fresh air
immediately. Stop the engine and do not restart the engine until it has been inspected and if
necessary repaired or reinstalled in a well ventilated area.
6.Exhaust gases from internal combustion engines are extremely poisonous. Never
operate an engine indoors.
7.All electrical equipment should be protected from excessive moisture. Failure to do so
will result in deterioration of the insulation and may result in short circuits and a
possible electrocution hazard.
Installation
Electrical Connections All load connections are made at the front panel using electrical cords with the proper
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician
The generator is completely assembled, tested and adjusted at the factory before it is shipped to
you. External connections required at the time of installation are:
1.Electrical Connections.
2.Frame Ground Connection.
mating plug for the receptacle being used. More than one receptacle can be used as long as the
total load does not exceed the continuous rating of the generator.
has installed an approved transfer switch. The National Electrical Code (NEC) requires that
connection of a generator to any electrical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.
Use correct size insulated wire to connect the generator to the load. The gauge of the wire will
depend on the distance to the load, the permissible voltage drop at the load, and the current
required by the load. If you are not sure of the gauge wire needed for your application, consult a
competent electrician. Using wire that is too small can result in fire hazard. Also, be sure the
wire has the appropriate ratings for insulation and environment conditions. Use only U.L.
approved extension cords rated for outdoor use.
3-2 Receiving & InstallationMN2411
Frame Ground Connection
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power
before you ensure that grounds are connected. Electrical shock can cause serious or fatal
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be
connected to an approved earth ground. Local codes may also require proper grounding of
generator systems.
The NEC requires that the frame and exposed metal surfaces be at local ground reference
potential to avoid electrical shock hazard. A local ground reference may require a driven earth
ground conductor at the generator installation site. Make the ground connection as shown in
Figure 3-2. Use the appropriate size wire (normally 6 AWG) as required by NEC and local
codes. The local reference ground is normally a copper clad earth ground rod driven into the
earth at least 8 feet.
Figure 3-2 Frame Ground Connection
Engine OilThe generator is shipped dry. This means no oil is in the engine crankcase and no fuel is in the
fuel tank. Refer to section 5 of this manual for lubricant and fuel requirements and obtain the
correct type and quantity of engine motor oil and fuel.
1.Refer to section 5 of this manual and add the required amount of engine oil.
2.Refer to section 5 of this manual and add the appropriate amount of fuel.
After installation, the post installation checks must be performed prior to starting the engine.
After these checks have been performed and the system operation is verified to be good, refer to
Section 5 Maintenance for periodic checks that must be performed at scheduled intervals to
ensure continued operation with minimal problems.
Receiving & Installation 3-3MN2411
Use of Electric Motor Loads
Electric motors require much more current (amperes) to start them than to keep them running.
Some motors, particularly split−phase motors are very difficult to start and require 5 to 7 times
more current to start them. Repulsion−induction type motors are the easiest to start and normally
only require 2 to 3 times as much current to start them.
Most fractional horsepower motors take about the same amount of current to start them and
keep them running. This is true whether they are the repulsion−induction type motor, capacitor
type motor, or the split−phase type motor.
Other factors that influence the amount of current needed to start a motor are:
1.The type of load connected to the motor. If the electric motor is connected to a hard
2.The brand or design of the electric motor. The expected starting current for a
3.The condition of the electric motor. A clean motor with free turning bearings will
starting load such as an air compressor it will require more starting current. If the same
electric motor is connected to a light load such as a heater or power saw it will require
less starting current.
particular size motor will vary depending on the brand of the electric motor as well as
the type of electric motor (Split Phase, capacitor, Repulsion−induction type, etc.)
require less starting currents than a similar type motor that is dirty and the bearings are
not as free turning as they used to be.
3-4 Receiving & InstallationMN2411
Section 4
Operation
Operator Control Panel
The Operator Control Panel is shown in Figure 4-1.
Figure 4-1 Operator Control Panel
PILOT
LAMP
STOP
OVER
LOAD
~ AC OUTPUT
RUN
CHOKE
AUTO
POWER
SAVE
AC
DC12V − 8.3A
BATTERY CHARGE ONLY
−
+
ONOFF
ONOFF
AC Circuit Breaker
+−
DC Circuit Breaker
ENGINE SWITCH
Pilot LampLamp (Green) is ON when generator is running properly.
Overload Lamp *Lamp (Red) is ON when generator is running and an overload condition exists.
If Overload Lamp is ON, Stop the generator and Start the generator again to resume
operation.
Oil Level LampLamp is on when engine oil level is less than a predetermined level. When the lamp
turns ON, the engine will stop automatically. If Oil Lamp is ON, replenish the engine oil
level and restart the engine.
Auto Power Save *
(switch)
OFF. Generator runs at full speed and produces full power. Use OFF for DC power.
ON. Generator idles during no load condition and automatically resumes full
speed when a load demand is present.
* Available only on PC1700RI.
Operation 4-1MN2411
Operator Control Panel
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician
has installed an approved transfer switch. The National Electrical Code (NEC) requires that
connection of a generator to any electrical circuit normally powered by means of an electric
utility must be connected by means of approved transfer switch equipment so as to isolate
the electrical circuit from the utility distribution system when the generator is operating.
Failure to isolate the electrical circuits by such means may result in injury or death to utility
power workers due to backfeed of electrical energy onto the utility lines.
~ AC Output Two AC receptacles are provided to allow easy connection of electrical loads. Both
AC Circuit Breaker Protects the generators output windings from overload (only available on PC1100R).
DC Circuit BreakerProvide overcurrent protection for the DC Output terminals. When tripped, the plunger
DC Output The DC output can be used to charge automotive type batteries. However several
The following precautions are to be followed when working on batteries:
WARNING: A battery presents a risk of electrical shock hazard and high short circuit current. The
following precautions are to be followed when working on batteries:
WARNING: The battery electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is
electrically conductive and corrosive. The following precautions are to be followed when
working on batteries:
WARNING: A battery presents a risk of fire because they generate hydrogen gas. Hydrogen gas is
extremely explosive. Never jump start a battery, smoke in the area around the battery or
cause any spark to occur in the area around the battery.
Continued
receptacles may be used at the same time provided the total electrical load does not
exceed the generators rated output. GFCI (Ground Fault Circuit Interrupter) provides
ground fault protection.
Note: The nominal voltage produced by the generator at each receptacle is 120VAC.
will extend from the body of the breaker. Simply push the plunger in to reset the
breaker.
safety precaution must be followed:
SWhen charging a large capacity battery or a totally discharged battery, excessive
current may trip the DC breaker. If this happens, use a battery charger to charge the
battery. The battery charger can be plugged into the generators AC output.
SAn explosive hydrogen gas is given off by the battery (through the batteries vent holes)
when it is charged. Do not allow a spark or open flame to be present during battery
charging. Always turn off the generator before disconnecting the battery leads from the
DC Output terminals to avoid a spark.
SThe battery contains electrolyte solution which is caustic and can cause severe burns
and blindness. If electrolyte contacts skin or eyes, immediately flush the area with
water and seek medical attention quickly.
1.Wear full eye protection (safety glasses or goggles) and protective clothing.
2.Where electrolyte contacts the skin, flush the area immediately with water and wash it
off using soap and water.
3.Where electrolyte contacts the eyes, immediately flush the eye thoroughly with water
and seek medical attention quickly.
4.Spilled electrolyte is to be washed down with an acid neutralizing agent. A common
practice is to use a solution of one pound (500 grams) bicarbonate of soda to one
gallon (four liters) of water. the bicarbonate solution is to be added until evidence of
reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the
area dried.
Automotive type batteries can be charged using this output (12VDC @ 8.3 Amperes).
Red terminal post is positive (+).
Black terminal post is negative (−).
Note: The DC and AC outlets of the generator can be used at the same time as long as the total
power consumed does not exceed the output rating.
4-2 OperationMN2411
Operator Control Panel
DC Circuit BreakerProvide overcurrent protection for the DC Output terminals. When tripped, the plunger
Engine SwitchStopIn this position, the engine is stopped and fuel supply line is closed.
Pre−Start Checks
Start−Up Procedure
WARNING: Never move a generator set that is running. Hazards are caused by moving a generator set
that is running.
Stopping Procedure
WARNING: Parts of this generator are extremely hot during and after operation. To prevent severe burns,
do not touch any part of the generator until you have first determined if the part is hot. Wear
protective clothing and after use allow sufficient time for parts to cool before touching any
part of the generator.
Continued
will extend from the body of the breaker. Simply push the plunger in to reset the
breaker.
Note: If the breaker continues to trip, disconnect all loads and reset the breaker. If the breaker
trips with all loads disconnected, turn off the generator and discontinue use until the
generator is repaired.
Run Allows the engine to start and run during normal operation.
ChokeAllows cold weather starting, place the Engine Switch in the Run position after
engine is started.
Before the engine is started, several things must first be checked.
1.Place the generator set in an open, dry, well ventilated and reasonably level location.
2.If grounding is required for your application, check to make sure your unit is grounded
properly (see Section 3).
3.Check the engine’s oil level, see Section 5.
4.Check the fuel level, see Section 5.
5.Disconnect or “turn off” all external loads.
6.Make sure DC circuit breaker is set (pushed in).
7.Tighten any bolts or nuts that may have loosened due to vibration.
8.Be sure all extension cords are in good condition before starting the generator.
Use only U.L. listed extension cords.
1.Move the Engine Switch to the “Choke” position. If the engine is warm or if the ambient
air temperature is high; try starting the engine switch in the Run position.
2.Check the fuel system for fuel leaks and repair them prior to starting the engine.
3.Pull lightly on the recoil grip until you feel significant resistance, then pull sharply. Allow
the recoil to gently rewind into the recoil housing. Do not allow the recoil rope to “snap
back” into the recoil housing.
Note: If the engine does not start after turning the engine over a few times, smell for fuel near
the air cleaner. If there is a significant gasoline smell coming from the air cleaner, turn the
engine switch to the Run position and attempt to start the engine.
Note: If engine does not start using normal starting methods, check the oil level. The oil level
sensor will prevent engine operation if oil level is low.
4.When the engine starts, turn the engine switch to the Run position.
5.Turn the Auto Power Save switch to On so engine can idle (if equipped).
6.Ensure that the Pilot Lamp is on and the Overload Lamp is off. Otherwise stop engine
immediately and correct the problem.
7.Allow engine to run for 20 or 30 seconds with no load. (Warm up).
8.Power is now present at the receptacles.
Connect or “Turn On” the loads you wish to operate.
9.Turn the Auto Power Save switch to Off or On as desired.
1.Disconnect or “Turn Off” all loads connected to the generator set.
2.Turn the Auto Power Save switch to On so engine can idle (if equipped).
3.Allow the generator to run at idle for 3 minutes with no load. (Cool down).
4.Move the engine switch to the Stop position.
Operation 4-3MN2411
4-4 OperationMN2411
Section 5
Troubleshooting and Maintenance
WARNING: Before cleaning, inspecting, repairing, refueling or performing any maintenance to the generator
set, always be sure the engine has stopped and that all rotating parts have also stopped. After
stopping, certain components are still extremely hot so be careful not to get burned.
WARNING: Before servicing the generator set, be sure to disconnect the spark plug wires to prevent
accidental engine rotation or starting.
Maintenance
General Checks1.Inspect the fuel system for leaks. Replace defective components immediately.
WARNING: Do not smoke near generator during operation or while refueling. Gasoline and diesel fuel are
WARNING: Stop engine and allow engine to cool before refueling. Gasoline and diesel fuel are flammable
Check Fuel Level (Right side cover)
Red" marking
The following are general maintenance recommendations. The engine must be stopped and all
electrical load devices removed from the generator plugs or terminals before any maintenance is
performed. The Maintenance Schedule is given in Table 5-1.
2.Inspect and replace any fuel line that shows signs of deterioration.
3.Inspect all fuel clamps to ensure they are tight and no leaks exist.
4.Make sure the fuel cap fits snugly on the fuel tank and that the fuel tank does not leak.
5.Inspect the condition of AC and DC terminals for damage and replace if damaged.
6.Test all GFCI (Ground Fault Circuit Interrupter) receptacles daily by pressing the test
button on the receptacle during operation. Ensure that the GFCI trips and and no
voltage is present at the receptacle. Replace any GFCI receptacle that fails the test.
7.Inspect the external wire cables (extension cords) and connectors used with the
generator set for cuts, frayed insulation, or loose connections. Repair or replace any
problems prior to using the unit.
8.Inspect bolts and nuts for tightness. Vibration can cause nuts or bolts to loosen.
9.Inspect the recoil starting rope for any damage and replace it if necessary.
flammable and can cause fire, explosions, injury or death. Keep open flames away from unit.
and can cause fire, explosions, injury or death.
1.Remove fuel filler cap.
2.Fuel level should be at or below the Red" marking at inlet portion of filler neck.
3.If fuel level is low, add unleaded automotive gasoline to just below the Red" marking.
Fuel tank capacity is 0.9 gallons (3.5 liters)
4.Install the fuel filler cap. Wipe up any fuel spill.
Check Oil Level (SE or higher grade) SAE 10W−30 or SAE 10W−40
1.Remove oil filler cap and check the oil for contaminants (moisture or excessive dirt).
2.Change the oil if contaminated.
Upper Level
Lower Level
Change Engine Oil (SE or higher grade) SAE 10W−30 or SAE 10W−40
Check Air Cleaner (Left side cover)
3.Clean the dip stick and fully insert it into oil and remove to check the oil level. Do not screw the filler cap in
when checking the oil level.
4.If oil is below lower level on dip stick, add oil to bring oil to the upper level. Check for oil leaks.
5.Install and tighten the oil filler cap.
1.If the engine is cold, start the engine and let it run for 1 minute. This will warm the oil to make it easier to
drain. If engine is hot, allow it to cool. Hot engine oil can cause severe burns. Always wear protective
clothing and eye protection when working on engine.
2.Drain oil by removing the drain plug and catch the used oil in a pan or tray. Remove the oil filler cap to let
oil flow out quicker. The generator is shown raised using lumber so the pan can slide under.
3.When oil is drained, install and tighten the drain plug.
4.Fill the crankcase with clean oil until the oil level reaches the upper level on the filler cap.
(Approximately 6 ounces or 0.35 liters).
5.Check for oil leaks.
1.Unhook the air filter cover and remove the elements.
2.Clean the paper element by gently tapping the element to remove dirt and contaminants. Blow off dust
and remaining dirt from the element. Replace the element if torn or extremely dirty. Replace every 200
hours or once each year.
3.Wash the urethane element with fresh water. Squeeze (do not twist) the water out and let air dry.
4.Install the elements and hook the cover.
Troubleshooting and Maintenance 5-1MN2411
Clean/Adjust Spark Plug (Right side cover)
1.Remove the plug wire and spark plug.
2..If the spark plug is contaminated, remove the carbon buildup with a plug cleaner or wire brush.
3.Adjust the electrode gap to 0.025 in. (0.6mm).
0.024 − 0.028 in.
(0.6 − 0.7 mm)
4.Install the spark plug and plug wire.
Clean Spark Arrester
1.Remove the flange bolts from the muffler cover and remove the muffler cover.
2.Remove the screw that secures the spark arrester and remove the spark arrestor from the muffler.
3.Clean and remove carbon deposits from spark arrester with a wire brush. Be careful not to damage the
fine mesh screen material. Replace spark arrester if damaged (breaks or holes).
4.Install spark arrester in muffler and secure with screw.
5.Install muffler cover and secure with flange bolts.
CleaningKeeping the generator clean is an important part of good operation. If dirt buildup is not
removed, the generator will run hotter than normal and it’s life is reduced. The following are
general guidelines for cleaning.
1.Clean the generator set and remove any and all dust, dirt, or other foreign material.
2.Inspect and clean the cooling air intake and exhaust louvers of the generator end.
Make sure they are clean. Remove dirt or any buildup that may restrict the cooling air
flow.
3.Clean the generator set and its components with a damp cloth or sponge.
Never use a water hose or pressure washer as this may damage electrical
components.
4.Inspect and replace any control panel components that are broken or not working
properly (receptacles, circuit breakers, switches, etc.)
5.Inspect and clean all governor and carburetor linkages so they operate properly.
Table 5-1 Periodic Maintenance Schedule
Maintenance Item8 Hours or
Daily
Check condition of AC Receptacles and GFCI operation
Check condition of Extension Cords
Check condition of DC terminals
Check condition of Engine Switch
Clean generator and check tightness of bolts and nuts.
Check engine oil level and replenish (to upper level) if
necessary.
Change engine oil (see Note 1)
Clean Spark Plug and set plug air gap
Replace Spark Plug
Clean Air Filter element
Replace Air Filter element
Replace Fuel Filter
Replace Spark Arrestor
Remove carbon from Cylinder Head (see Note 2)
Check and adjust Valve Clearance (see Note 2)
Clean and adjust carburetor (see Note 2)
Clean and replace Carbon Brushes
Replace Fuel Lines (annually)
Check condition of Rotor
Check condition of Stator
Replace Engine Mounts
50 Hours or
Weekly
100 Hours200 Hours or
Monthly
500 Hours1000 Hours
Note 1: Initial oil change should be performed after 20 hours of operation and every 100 hours
thereafter. Dispose of used oil properly at recycling center.
Note 2: Please consult with Baldor Service for the correct procedures to follow for these items.
5-2 Troubleshooting and MaintenanceMN2411
Voltage Variations
This generator set must be run at its proper speed to obtain the correct electrical power at its
output. All engines have a tendency to slow down when a load is applied to it. The engine
governor is designed to hold the operating speed as nearly constant as possible. When the
electrical load is increased, the engine is more heavily loaded and engine speed drops slightly.
This slight decrease in engine speed results in a slight decrease in generator voltage and
frequency output. This voltage and frequency variation has no appreciable effect in the operation
of motors, lights, and most appliances and tools. However, timing devices and clocks will not
keep perfect time when used on this generator.
Reduced voltage to the load can also be caused by using the wrong extension cord. Small
diameter wire will have a voltage drop across the cord when current flows through the wire. This
voltage drop can be very significant over long cord lengths. Always use the proper wire size
(gauge wire size) for the extension cord to minimize the voltage drop at rated current draw.
Problems and Solutions
Some of the more common problems are listed in Table 5-1. This information is intended to be a
check or verification that simple causes can be located and fixed. It is not an exhaustive “how to”
for all types of problems.
Table 5-1 Troubleshooting Guide
ProblemPossible CauseRemedy
Engine will not start
Engine will not crank (electric start)Dead battery.Remove battery and trickle charge or replace with new battery.
Engine starts but will not run smoothlyFuel or ignition problemHave engine serviced.
Engine overheatsExcessive load
No output voltageCiruit Breaker tripped or defective.
Output voltage variesIrregular speed (fixed speed mode)
Low output voltageLow engine speed
High output voltageExcessive speed (fixed speed mode)Check engine for malfunction
Electrical shock when frame is touchedStatic charge.
No fuel.
Restricted air flow.
No spark.
Low oil level.
Debris or dirt buildup on engine
Loss of residual magnetism in exciter
field poles.
Open in stator windings
Defective exciter circuit.
Fluctuating speed (fixed speed mode)
Loose terminal or load connections
Defective bearing (uneven air gap)
Excessive load
High resistance connections −
connections will be warm or hot
Shorted field
Low power factor
Grounded armature or field coil.
Check that fuel valves are ON. Check fuel level in fuel tank.
Check/replace air filter.
Check/replace spark plug(s). Verify engine switch is in Run".
Oil sensor will prevent engine starting if oil level is low.
Never Jump Start.
Remove one or more electrical loads.
Remove debris. Clean engine surfaces to allow cooling.
Reset circuit breaker or replace if required.
Flash field.
Check for continuity in windings. Return to factory for repair if open.
Check/replace diode and capacitor and flash the field.
Check engine for malfunction or load for fluctuation
Stabilize load. The addition of a lamp load (resistance load) may
compensate partially for load changes caused by intermittent motor
operation. Do not overload.
Verify all connections are proper and check tighness torque of
terminals.
Replace worn bearing
Check that the Auto Idle switch is in OFF position.
Check engine for malfunction or system for overload. Reduce load.
Verify all connections are proper and check tighness torque of
terminals.
Test field coils for possible short by checking resistance with an
ohmmeter or resistancebridge. Return rotor assembly to factory
forrepair if alternator field coils are shorted.
Reduce inductive (motor) load. Some AC motors use about the
same current regardless of load. Do not use motors of greater
horsepower rating than is necessary to move the mechanical load.
Ground generator frame at local reference ground (see Section 3).
Return to factory for repair
Troubleshooting and Maintenance 5-3MN2411
ServiceService for your generator can be obtained from Baldor Generators. Please have the following
information available prior to contacting the factory:
The model number and serial number of the generator set.
A complete and accurate description of the problem.
PartsParts for your generator can be obtained from Baldor Generators. Please have the following
information available prior to contacting the factory:
The model number and serial number of the generator set.
A complete and accurate description of the part (part number if known).
Engine Oil
(SE or higher grade) SAE 10W−30 or SAE 10W−40
Use class SE (API classification) or better grade oil. SAE 10W−30 or SAE 10W−40 is
recommended for general use. For single viscosity oil use at a specific temperature, refer to the
following chart.
5W
10W
Single Grade
20W
30W
40W
14
10W 30
10W 40
0
32
10
50
206830
86
40 °C
104 °F
Storage
Multigrade
Ambient
Temperature
−204−10
If you will not be using the generator set for a significant amount of time (3 months or longer) you
should store the generator to prevent any problems that could arise from sitting idle. Please
follow this procedure prior to storing the unit. This will help to ensure that the generator will start
and provide good service when it is removed from storage.
1.Remove fuel filler cap.
2.Use a siphon pump to remove all fuel from fuel tank.
3.Install fuel filler cap.
4.Start the generator set and allow it to run out of fuel.
5.Place the Engine Switch in “Stop” position. This closes the fuel valve.
6.Drain the used oil from the engine’s crankcase and refill it with clean oil.
7.Remove the spark plug and pour 1 oz. of clean engine oil into the cylinder. Put a rag
over the spark plug port and turn the engine over approximately 5 times to distribute
the oil in the cylinder.
8.Install the spark plug but do not connect the plug wire. This will help prevent accidental
or unauthorized starting.
9.Provide maintenance to the engine and generator set as described in this section.
10. Inspect bolts and nuts for tightness. Vibration can cause nuts or bolts to loosen.
11. Inspect the recoil starting rope for any damage and replace it if necessary.
12. Cover any bare metal spots with paint or another type of rust preventative.
WARNING: Never store an engine with fuel in its tank indoors or in an enclosed, poorly ventilated area
where gasoline fumes could reach an ignition source and cause an explosion.
5-4 Troubleshooting and MaintenanceMN2411
UNITED STATES
ARIZONA
PHOENIX
4211 S 43RD PLACE
PHOENIX, AZ 85040
PHONE: 602−470−0407
FAX: 602−470−0464
CALIFORNIA
LOS ANGELES
6480 FLOTILLA
COMMERCE, CA 90040
PHONE: 323−724−6771
FAX: 323−721−5859
HAYWARD
21056 FORBES STREET
HAYWARD, CA 94545
PHONE: 510−785−9900
FAX: 510−785−9910
COLORADO
DENVER
2520 W BARBERRY PLACE
DENVER, CO 80204
PHONE: 303−623−0127
FAX: 303−595−3772