The basic steps for connection and setup are provided in this section. Detailed descriptions of each step and
parameter settings are provided later in this manual. Be sure to comply with all applicable codes when installing
this control. The Series 29 DC control is a one way control. That is, it is non–regen and cannot reverse
direction. It operates in the forward direction only. All references to reverse operation or regen operation apply
to the Series 30 DC Control only.
Minimum Connection Requirements Refer to Section 4 for cover removal procedure.
Power and Motor Connections
Figure 1-1 shows the minimum connections required at the power connector.
Figure 1-1 Power Connections
3 Phase
Power
L1
L2
L3
GND
Thermistor
For Size 1 & 2 controls, be sure the
logic power jumper is in the correct
position. Refer to Figure 4-9.
To 1 Phase 115VAC Control Power
(except units with internal
control transformer,
100hp and less)
or jumper TH1 to TH2 if
motor thermistor is not connected.
Armature
Reference and Jumpersfor Keypad Operation
For keypad operation, the speed reference connections are not required. Speed is set at the keypad. Figure
1-2 shows the minimum connections required A, B and C signal connectors for Keypad operation.
Figure 1-2 Reference and Jumper Connections
If Optional Speed Feedback Board is used, refer
to Speed Feedback at the end of this section.
Signal Connections
Minimum jumper connections:
A1 to A2 – 500 ohm jumper for 20mA input
A6 to B3 – Analog Input 5 = +10VDC
B8 to C9 – PROG Stop = +24VDC
B9 to C9 – Coast Stop = +24VDC
C4 to C9 – Enable = +24VDC
C1 to C2 – No External Trip
Parameter Settings (for Keypad Operation)
The factory settings should be sufficient to operate the control using the “Local” mode with the keypad. Only a
few changes to the motor data parameters must be made. Before any parameters can be changed, set
System::Configure I/O::Configure Enable to enable. All LEDs will blink during configuration.
Note: To separate the various menu level designation, a double colon is used (System::Configure I/O).
500 ohm
Jumper for
0-20mA
Field
AB
0V 1
AnIn 1 2
500
Motor Starter on Size 1 & 2 controls.
AnIn 2 3
AnIn 3 4
AnIn 4 5
AnIn 5 6
AnOut 1 7
AnOut 2 8
0V 1
Not Used 2
Arm I Fbk 9
+10V Ref 3
DigOut 1 5
DigOut 2 6
DigOut 3 7
-10V Ref 4
Prog Stop 8
Coast Stop 9
Motor Blower connections when using optional
C
0V 1
Start 3
DigIn E 4
DigIn R 5
Ext Trip 2
+24V 9
DigIn 1 6
DigIn 2 7
DigIn 3 8
Quick Start 1-1MN792
Reference and Jumpersfor Remote Operation
For remote operation, the speed reference and other connections are made at the terminal strip connector. Not
all of these connections are shown in Figure 1-3.
Figure 1-3 Reference and Jumper Connections
Speed Reference connections:
A1 – one end of Pot
B3– one end of Pot
A4– wiper of Pot
C1 to C2 – No External Trip
Minimum jumper connections:
A1 to A2 – 500 ohm jumper for 20mA input
A6 to B3 – Analog Input 5 = +10VDC
C4 to C9 – Enable = +24VDC
C1 to C2 – No External Trip
Jumper if contacts are not used:
B8 to C9 – PROG Stop = +24VDC
B9 to C9 – Coast Stop = +24VDC
The Health relay (24VDC coil) may be installed between B6 and C1
to provide fault indication to an external device or circuit.
Signal
Connections
AB
500 ohm
Jumper for
0-20mA
Optional Speed
Feedback Board
0V 1
AnIn 1 2
AnIn 2 3
AnIn 3 4
AnIn 4 5
AnIn 5 6
AnOut 1 7
AnOut 2 8
500
0V 1
DigOut 1 5
Arm I Fbk 9
Not Used 2
DigOut 2 6
-10V Ref 4
+10V Ref 3
C
0V 1
Start 3
DigIn E 4
DigIn R 5
DigOut 3 7
Prog Stop 8
Coast Stop 9
Ext Trip 2
+24V 9
DigIn 1 6
DigIn 3 8
DigIn 2 7
DH
Jog
Start
Health Relay
PROG Stop
Coast Stop
Speed Feedback The factory setting for speed feedback is Armature Voltage which does not require an optional feedback
board. If an optional board must be used, refer to its manual to install and set the board configuration.
Serial LinkA PC COM port may be connected to the control at the System Port (P3). At Menu Level : Serial Links, all of
the parameters can be set for your application.
1-2 Quick StartMN792
and scroll the menu choices, and “M” goes to next level menu and “E” comes back up one menu level.
ActionDescriptionDisplayComments
Apply PowerKeypad Display shows this opening
Press “PROG” key
Press “M” key
Press “M” keyAccess the menus.
Press
Press “M” keyAccess the Configure Drive Menu
Press “M” keyAccess Configure Enable.
Press key
Press “E” keyReturn to the Configure Drive Menu
Press
message.
Scroll to “Configure Drive” menu.
Change Disabled to Enabled.
Set the motor volts.
FORWARD
REF: 0.00%
BALDOR DC DRIVE
DC 4Q 15A
DC 4Q 15A
MENU LEVEL
MENU LEVEL
DIAGNOSTICS
MENU LEVEL
CONFIGURE DRIVE
CONFIGURE DRIVE
CONFIGURE ENABLE
CONFIGURE ENABLE
DISABLED
CONFIGURE ENABLE
ENABLED
CONFIGURE DRIVE
CONFIGURE ENABLE
NOM MOTOR VOLTS
Local control display.
This message may be different for
each control size.
Press M twice to go down 2 menu
levels
Configure enable is disabled and
no parameter value can be
changed.
Configure enable must be enabled
to allow a change to any parameter
value. All LED’s on keypad are
blinking to show it is enabled.
Use up and down arrows to set the
motor voltage.
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Set the armature current.
Set the field current (skip if field is
in voltage mode.
Set the field control mode (voltage
or current).
Field Volts Ratio=
(field volts/AC supply)*100
Set the current limit
(normally 100%).
Leave autotune off.
Select Armature Volts, Analog
TACH or Encoder.
Set the pulses per REV of the
encoder.
Set the encoder max speed (100%
speed).
Change the polarity of the encoder
signal if needed.
The Speed Loop Integral Gain.
ARMATURE CURRENT
FIELD CURRENT
FLD. CTRL MODE
FLD. VOLTS RATIO
MAIN CURR. LIMIT
AUTOTUNE
SPEED FBK SELECT
ENCODER LINES
ENCODER RPM
ENCODER SIGN
SPD INT TIME
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Autotune after calibration is
complete.
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Use up and down arrows to set.
Press “E” when done.
Press
The Speed Loop Proportional Gain.
SPEED PROP GAIN
Use up and down arrows to set.
Press “E” when done.
Quick Start 1-3MN792
Configure the drive parameters and block diagram connections.
ActionDescriptionDisplayComments
Press “M” key
Press “M” keyAccess the menus.
Press or
Scroll to “Configure Drive” menu.
Setup Parameters
At Menu Level : Setup Parameters, several sub menus set values for your application:
Ramps, AUX I/O, Op Station, Jog/Slack, Raise/Lower, Special Blocks, Field Control, Current Profile, Inverse
Time, Stop Rates, Calibration, Inhibit Alarms, Current Loop, Speed Loop, Standstill and Setpoint Sum 1.
Password
At Menu Level : Password, a password can be set to prevent unauthorized access to the setup and other
parameters.
Configure I/O
At Menu Level : System : Configure I/O, make the connections using the Tags to configure the block diagram to
your application.
Autotune
At Menu Level : Configure Drive, set Autotune to On, press “E” to exit configure menu. At the keypad, press L/R
for local mode. Press Run, the drive will autotune. When the drive stops and no error messages are displayed,
autotune was successful. Repeat the Save Parameters procedure to ensure the new values are saved.
When completed, change the Configure Enable parameter from Enabled to Disabled.
DC 4Q 15A
MENU LEVEL
MENU LEVEL
DIAGNOSTICS
MENU LEVEL
SETUP PARAMETERS
Press “E” when done.
ActionDescriptionDisplayComments
Press or
Press “M” keyAccess the Configure Drive Menu
Press “M” keyAccess Configure Enable.
Press key
Press “E” key 2 timesReturn to the Menu Level.
Scroll to “Configure Drive” menu.
Change Disabled to Enabled.
MENU LEVEL
CONFIGURE DRIVE
CONFIGURE DRIVE
CONFIGURE ENABLE
CONFIGURE ENABLE
ENABLED
CONFIGURE ENABLE
DISABLED
Press M twice to go down 2 menu
levels
Configure enable is disabled and
no parameter value can be
changed.
Configure enable must be enabled
to allow a change to any parameter
value. All LED’s on keypad are
blinking to show it is enabled.
MENU LEVEL
CONFIGURE DRIVE
Save Parameters
At Menu Level : Save Parameters, save the settings you have programmed into the control. This will be the
parameters that are restored for use after power up. If you do not save the parameters, the factory settings (or
the last saved) will be used after a power up.
ActionDescriptionDisplayComments
Start at Menu
Level 1
Press
Scroll to “PARAMETER SAVE” menu.
Press “M” key
Press Press to save parameters.
Press “E” keyExit one level
MENU LEVEL
DIAGNOSTICS
MENU LEVEL
PARAMETER SAVE
PARAMETER SAVE
UP TO ACTION
PARAMETER SAVE
REQUESTED
MENU LEVEL
PARAMETER SAVE
Parameters are saved. Except the
“Local Setpoint”.
Press “E” several times to return to
the top level.
1-4 Quick StartMN792
Section 2
General Information
Copyright Baldor 2002. All rights reserved.
This manual is copyrighted and all rights are reserved. This document may not, in whole or in part, be copied or
reproduced in any form without the prior written consent of Baldor.
Baldor makes no representations or warranties with respect to the contents hereof and specifically disclaims any
implied warranties of fitness for any particular purpose. The information in this document is subject to change
without notice. Baldor assumes no responsibility for any errors that may appear in this document.
Microsoft and MS–DOS are registered trademarks, and Windows is a trademark of Microsoft Corporation. UL
and cUL are registered trademarks of Underwriters Laboratories.
OverviewThe Series 29 DC control is a one way control. That is, it is non–regen and cannot reverse direction. It
CE Compliance A custom unit may be required, contact Baldor. Compliance to Directive 89/336/EEC is the responsibility of the
Enclosure Sizes Five enclosure sizes are available:
operates in the forward direction only. All references to reverse operation or regen operation apply to the Series
30 DC Control only. The Baldor Digital DC control is a three phase, full wave, DC motor armature and field
control. The SCR bridge converts three phase AC power to controlled DC to operate the DC motor armature.
The AC input is also used for the reference transformer input to operate power supplies and synchronize to the
AC input line. This control is of the NEMA Type C designation.
The control may also be used with permanent magnet field motors and DC spindle drive motors. In addition,
standard feedback from armature may be used. An optional Encoder, Tachometer or resolver feedback is
available with optional expansion boards. The control can be configured to operate in a number of modes
depending upon the application requirements and user preference.
It is the responsibility of the user to determine the correct operating mode to use for the application. These
choices are made using the keypad as explained in this manual.
system integrator. A control, motor and all system components must have proper shielding, grounding, and
filtering as described in MN1383. Please refer to MN1383 for installation techniques for CE compliance. For
additional information, refer to Section 4 and Appendix A of this manual.
Size 115A to 35A
Size 240A to 165A
Size 3180A to 270A
Size 4380A to 830A
Size 5850A and larger
Limited Warranty
For a period of one (1) year from the date of original purchase, BALDOR will repair or replace
without charge controls and accessories which our examination proves to be defective in
material or workmanship. This warranty is valid if the unit has not been tampered with by
unauthorized persons, misused, abused, or improperly installed and has been used in
accordance with the instructions and/or ratings supplied. This warranty is in lieu of any other
warranty or guarantee expressed or implied. BALDOR shall not be held responsible for any
expense (including installation and removal), inconvenience, or consequential damage,
including injury to any person or property caused by items of our manufacture or sale. (Some
states do not allow exclusion or limitation of incidental or consequential damages, so the above
exclusion may not apply.) In any event, BALDOR’s total liability, under all circumstances, shall
not exceed the full purchase price of the control. Claims for purchase price refunds, repairs, or
replacements must be referred to BALDOR with all pertinent data as to the defect, the date
purchased, the task performed by the control, and the problem encountered. No liability is
assumed for expendable items such as fuses.
Goods may be returned only with written notification including a BALDOR Return Authorization
Number and any return shipments must be prepaid.
General Information 2-1MN792
Product NoticeIntended use:
These drives are intended for use in stationary ground based applications in industrial power installations
according to the standards EN60204 and VDE0160. They are designed for machine applications that require
variable speed controlled three phase brushless AC motors.
These drives are not intended for use in applications such as:
Unless otherwise specified, this drive is intended for installation in a suitable enclosure. The enclosure must
protect the control from exposure to excessive or corrosive moisture, dust and dirt or abnormal ambient
temperatures.
In the event that a control fails to operate correctly, contact Baldor for return instructions.
Safety Notice:This equipment contains high voltages. Electrical shock can cause serious or fatal injury. Only qualified
personnel should attempt the start–up procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts that are driven by this
equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start–up
procedure or troubleshoot this equipment.
–System documentation must be available at all times.
–Keep non-qualified personnel at a safe distance from this equipment.
–Only qualified personnel familiar with the safe installation, operation and maintenance of this device
should attempt start-up or operating procedures.
–Always remove power before making or removing any connections to this control.
PRECAUTIONS: Classifications of cautionary statements.
WARNING:Indicates a potentially hazardous situation which, if not avoided, could result in
injury or death.
Caution:Indicates a potentially hazardous situation which, if not avoided, could result in
damage to property.
Continued on next page.
2-2 General InformationMN792
PRECAUTIONS:
WARNING:Do not touch any circuit board, power device or electrical connection before you
WARNING:Be sure that you are completely familiar with the safe operation of this equipment.
WARNING:Be sure all wiring complies with the National Electrical Code and all regional and
WARNING:Be sure the system is properly grounded before applying power. Do not apply AC
WARNING:Do not remove cover for at least five (5) minutes after AC power is disconnected
WARNING:Improper operation may cause violent motion of the motor and driven equipment.
WARNING:Motor circuit may have high voltage present whenever AC power is applied, even
WARNING:If a motor is driven mechanically, it may generate hazardous voltages that are
WARNING:The user must provide an external hard-wired emergency stop circuit to disable
first ensure that power has been disconnected and there is no high voltage
present from this equipment or other equipment to which it is connected.
Electrical shock can cause serious or fatal injury.
This equipment may be connected to other machines that have rotating parts or
parts that are controlled by this equipment. Improper use can cause serious or
fatal injury.
local codes or CE Compliance. Improper wiring may cause a hazardous
condition.
power before you ensure that grounds are connected. Electrical shock can cause
serious or fatal injury.
to allow capacitors to discharge. Electrical shock can cause serious or fatal
injury.
Be certain that unexpected movement will not cause injury to personnel or
damage to equipment.
when motor is not moving. Electrical shock can cause serious or fatal injury.
conducted to its power input terminals. The enclosure must be grounded to
prevent a possible shock hazard.
the control in the event of an emergency.
Continued on next page.
General Information 2-3MN792
Caution:To prevent equipment damage, be certain that the input power has correctly sized protective
devices installed as well as a power disconnect.
Caution:Avoid locating the control immediately above or beside heat generating equipment, or
directly below water or steam pipes.
Caution:Avoid locating the control in the vicinity of corrosive substances or vapors, metal particles
and dust.
Caution:Suitable for use on a circuit capable of delivering not more than the RMS symmetrical short
circuit amperes listed here at rated voltage.
HorsepowerRMS Symmetrical Amperes
Caution:Baldor recommends not using “Grounded Leg Delta” transformer power leads that may
create ground loops and degrade system performance. Instead, we recommend using a
four wire Wye.
Caution:Logic signals are interruptible signals; these signals are removed when power is removed
from the drive.
Caution:The safe integration of the drive into a machine system is the responsibility of the machine
designer. Be sure to comply with the local safety requirements at the place where the
machine is to be used. In Europe this is the Machinery Directive, the ElectroMagnetic
Compatibility Directive and the Low Voltage Directive. In the United States this is the
National Electrical code and local codes.
Caution:Controls must be installed inside an electrical cabinet that provides environmental control
and protection. Installation information for the drive is provided in this manual. Motors and
controlling devices that connect to the driver should have specifications compatible to the
drive.
Caution:Do not tin (solder) exposed wires. Solder contracts over time and may cause loose
connections.
Caution:Electrical components can be damaged by static electricity. Use ESD (electro-static
discharge) procedures when handling this control.
Caution:This control is not designed for regenerative use with stabilized shunt or compound wound
motors. If stabilized shunt or compound wound are to be used, the series field must be
isolated and not connected. Contact the motor manufacturer for motor derating
specifications under these conditions.
2-4 General InformationMN792
Section 3
Getting Started
Control Overview
Control Loops
In very simple terms, control of the DC motor is maintained by Control Loops. An inner Current Loop and an
outer Speed Loop are used. These control loops are shown in the Block Diagram of Appendix C. From the
keypad, you can select the control loops to be used by the Control to provide either:
Normally a current or speed feedback signal is applied to the appropriate loop to control the process. While
current feedback sensors are built–in, speed feedback is normally provided directly from the armature sensing
circuit (default), or by “Tachogenerator” or encoder connection to an option board.
•Current Control
•Speed Control (factory setting)
Figure 3-1 Speed Control
speed increase due to fieldweakening
Armatureremains constant
Voltage 200V
Field Current 5.7A
field current reduced
base
speed
During speed control the speed of the motor can be increased by adjusting the motor field. Weakening the field
current allows an increase in motor speed beyond that normally achieved for the motor rated armature voltage.
Control and Communications
Some of the internal blocks of this control must be connected for your application. This means that you must
understand the application and how the software blocks should be connected to implement your design. The
block diagram in Appendix C shows the factory set connections. These diagrams assist in understanding this
concept and will be described next.
The Keypad (Operator Station) provides access to parameters, diagnostic messages, trip settings and full
application programming. The heart of the control is a microprocessor that provides advanced features such as:
•Complex control algorithms not achievable by simple analog techniques.
•Software configured control circuitry that uses standard software blocks.
•Serial link communications with other drives or a PC for advanced process systems.
armature voltage
Speed
To customize drive performance for optimum use, you may need to configure, or reroute software connections to
and from the drive’s inputs and outputs and to and from the drive’s software blocks. You can configure the drive
and change software block parameter values either using the keypad or with a personal computer (PC) running
the software package Workbench D (see MN794).
Getting Started 3-1MN792
Local and Remote Modes
Determine what operating mode is best for your application. Four modes are possible, see Figure 3-2.
Figure 3-2 Local and Remote Modes
Local:
Keypad Setting
(Factory Setting)
Remote:
Terminal Strip Setting
Preset
Analog & Digital
Inputs and Outputs
Remote:
Serial Setting
Remote:
COMMS Setting
For local operation, use the keypad to change parameters or control operation.
Process control and other applications may require the control to be used in remote mode with
analog and digital input/output signals performing all control operations. The control is
configured in this mode from the factory.
Remote Serial mode is used to initially setup and configure the parameters of the control.
For applications that are controlled by a PC that is running suitable software. Workbench D is
recommended.
For Baldor RS485/Modbus, Profibus DP and DeviceNet.
Two forms of control are in operation at all times: Start/Stop Control and Speed Control. These are operate by
local or remote control.
Local
The keypad is used to set motor speed and other parameters. The Start, Stop and Jog keys then control motor
rotation.
Remote
A speed reference signal (pot) and the various analog and digital inputs and outputs are used for speed control
and rotation of the motor shaft.
3-2 Getting StartedMN792
Source / Destination Tags
The control is very flexible because of the programming capability. The software block diagram of the control is
shown in Appendix C. Each logic block has inputs and outputs. These I/O points are called “Tags” because
they have a tag number associated with it and shown in brackets “[tag]” . Some tags are read only values and
some are read/write. Besides setting the value of each parameter, its source or destination connections can be
programmed. This means you can connect inputs and outputs of logic blocks as you desire to implement your
application.
Destination Tag example
Consider Digital Input 1. The external connection (input) is made at the C connector pin 6. The block diagram of
this input is shown in Figure 3-3. Tag [102] is the destination tag for the output signal. The destination is
presently set to 90. This connects the output of Digital Input 1 to the Bipolar Clamps [90] input of the Current
Loop Logic Block. The value of [102] Digital output is determined by the switch position, either the value of [103]
or [104] will be applied to the output as the input changes from false to true.
Digital Input 1 – DIGIN 1 (C6)
Tag ParameterSetting
[102] Destination Tag90
[104] Value for False0.00%
Digital
[103] Value for True0.01%
Input 1
C6
Source Tag example
Consider Digital Output 1. The external connection (output) is made at the B connector pin 5. The block
diagram of this input is shown in Figure 3-4. Tag [97] is the source tag for the input signal. The source is
presently set to 77. This means that Digital output 1 receives its input signal from [77] At Zero Speed parameter
from the Standstill Logic Block. To connect Digital Output 1 to the At Zero Setpoint parameter, simply change
[97] Source Tag value from 77 to 78.
Standstill
[11] Standstill Logic
[12] Zero Threshold
At Zero Setpoint [78][306] Source Tag
At Zero Speed [77]
At Standstill [79]
Figure 3-3 Digital Inputs
Current Loop
[102]
[71]
Diagnostic
connection
[90] Bipolar ClampsDigital IN 1
[48] NEG I ClampAnalog IN 4
Figure 3-4 Digital Outputs
Digital Output 1 – DIOUT 1 (B5)
Tag Parameter
[359] InvertedFalse
[195] Threshold (>)
[97] Source Tag77
[43] ModulusTrue
Setting
0.00%
ABS
[88] NEG I Clamp
-1
[87] POS I Clamp
B5
Digital
Output 1
From these examples, it is easy to see that several things are required to program the control.
1.First, you must understand the application and know how to implement it in the control parameters.
2.Second, layout all of the connections for your application using the block diagrams in Appendix C.
3.Third, program the connections and parameter preset values. To do this you will need to refer to the
Parameter Values in Appendix B. This will tell you where in the keypad menu system you can locate
each parameter value or [tag].
For example, find [97] in Appendix B, (see Figure 3-5). To locate [97] using the keypad, begin at the System
menu, select Configure I/O menu, then select Digital Outputs menu, finally select Digital Output 1 (B5)
parameter. Change the value of that parameter to the desired value.
Note: Tag number “[97]” is not shown at the keypad for the Digital Output 1 (B5) parameter value. To display
the [TAG] number of the parameter, display the parameter value then press the “M” key to show the
parameters tag number. Appendix B and C are the key to programming your application.
Programming Block A very important step to installing this control is to determine the configuration that will best implement your
application. Each input and output of each block has an assigned tag number. Tags are connected in software
much like jumper wires are used in hardware. The control is shipped with a factory set software connection.
This may be changed at any time. The method of changing these connections (source or destination tags) is
described later in the programming Section 6 of this manual.
Note: It is important to correctly set the software to implement your application in the most efficient way. Some
parameters are Tags (connections) and others are programmed values. Be careful when programming
to be sure the correct input or output is being set.
Example(View Analog Input 1 parameter settings)
As an example, a portion of the block diagram is shown in Figure 3-6. The output of Analog Input 1 [246] is
connected to [100] “Input 1” of Setpoint Sum 1 block. Each input and output shown on these diagrams is
programmable.
The parameter values for Analog Input 1 can be changed at the keypad. Figure 3-7 shows a partial map of the
menu levels. The Analog Input 1 parameters are at Level 4 under the Level 3 Analog Inputs. The keypad
operation is shown in Table 3-1. Figure 3-7 can be used to visualize the menu structure that is being navigated
in Table 3-1.
Figure 3-7
1234
Diagnostics
Menu Levels
Configure Enable
System
Software
Configure I/O
Analog InputsANIN1 (A2)
Calibration
MAX Value
MIN Value
Destination Tag
Table 3-1 Set Analog Input 1 for 4–20mA
ActionDescriptionDisplayComments
Apply PowerKeypad Display shows this opening
message.
Press “PROG” key
Press MAccess the menus.
Press Scroll to System menu. Press
several times.
Press MAccess the System menus.
Press
Scroll to Configure I/O menu.
Press MAccess Configure I/O menu.
FORWARD
REF: 0.00%
BALDOR DC DRIVE
DC 4Q 35A
MENU LEVEL
DIAGNOSTICS
MENU LEVEL
SYSTEM
SYSTEM
SOFTWARE
SYSTEM
CONFIGURE I/O
CONFIGURE I/O
CONFIGURE ENABLE
This message may be different for
each control.
This is menu level 1. Refer to Figure
3-7 for a description of the menu
levels.
This is menu level 1, System
parameters.
This is menu level 2.
3-4 Getting StartedMN792
Table 3-1 Set Analog Input 1 for 4–20mA Continued
Action
DescriptionDisplayComments
Press MAccess Configure I/O menu.
Press
Change Configure Enable to Enabled.
Press EAccess Configure I/O menu.
Press
Scroll to analog inputs menu.
Press MAccess analog inputs 1 menu.
Press MAccess Calibration menu.
Press MView or change the Calibration value.
Press E
Press
Scroll to next menu.
Press MView or change the MAX Value menu.
Press E
Press
Scroll to next menu.
Press MView or change the MIN Value menu.
Press E
Press
Scroll to next menu.
Press MView or change the Destination tag
Value menu.
Press EPress “E” several times to return to
the Configure Enable menu.
Press MAccess Configure I/O menu.
Press MAccess Configure I/O menu.
Press
Change Configure Enable to Disabled.
Press E
CONFIGURE ENABLE
DISABLE
CONFIGURE ENABLE
ENABLED
CONFIGURE I/O
CONFIGURE ENABLE
CONFIGURE I/O
ANALOG INPUTS
ANALOG INPUTS
ANIN1 (A2)
ANIN1 (A2)
CALIBRATION
CALIBRATION
1.0000
ANIN1 (A2)
CALIBRATION
ANIN1 (A2)
MAX VALUE
MAX VALUE
100.00%
ANIN1 (A2)
MAX VALUE
ANIN1 (A2)
MIN VALUE
MIN VALUE
–100.00%
ANIN1 (A2)
MIN VALUE
ANIN1 (A2)
DESTINATION TAG
DESTINATION TAG
100
ANIN1 (A2)
DESTINATION TAG
CONFIGURE I/O
CONFIGURE ENABLE
CONFIGURE ENABLE
ENABLED
CONFIGURE ENABLE
DISABLED
CONFIGURE I/O
CONFIGURE ENABLE
This is menu level 3. Before any
parameter values can be changed,
Configure Enable must be “Enabled”
(it is normally disabled”).
Note that the LED’s on Keypad are
flashing until changed back to Disable.
Move back one menu level using the
E key.
This is menu level 4.
Use the and keys to change the
value. Press E when finished.
Use the and keys to change the
value. Press E when finished.
Use the and keys to change the
value. Press E when finished.
Use the and keys to change the
value. Press E when finished.
This is menu level 2.
This is menu level 3. Before the
control can be used again, Configure
Enable must be “Disabled”.
Note when is pressed, the keypad
will briefly display “calibrating”
followed by Disabled and all Keypad
LED’s stop blinking.
Press the “E” key several times to move back through the menu items or press “PROG” to return to control operation.
Note: When changing a numeric value, pressing the “M” key will change the cursor position one digit to the left.
Getting Started 3-5MN792
3-6 Getting StartedMN792
Section 4
Receiving and Installation
Receiving & Inspection
Baldor Controls are thoroughly tested at the factory and carefully packaged for shipment. When you receive
your control, there are several things you should do immediately.
1.Observe the condition of the shipping container and report any damage immediately to the
commercial carrier that delivered your control.
2.Remove the control from the shipping container and remove all packing materials. The container and
packing materials may be retained for future shipment.
3.Verify that the part number of the control you received is the same as the part number listed on your
purchase order.
4.Inspect the control for external physical damage that may have been sustained during shipment and
report any damage immediately to the commercial carrier that delivered your control.
5.If the control is to be stored before use, be sure that it is stored in a location that conforms to
published storage humidity and temperature specifications stated in this manual.
Location Considerations The location of the control is important. Installation should be in an area that is protected from direct
sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration. Exposure to these can
reduce the operating life and degrade performance of the control.
Several other factors should be carefully evaluated when selecting a location for installation:
1.For effective cooling and maintenance, the control should be mounted vertically on a smooth
non-flammable surface.
2.At least 1.0 inches (25mm) top and bottom clearance must be provided for air flow. At least 0.4
inches (10mm) clearance is required between controls (each side).
3.Operating Altitude derating. Up to 1640 feet (500 meters) no derating required. Derate the
continuous and peak output current by 1% for each 660 feet (200 meters) above 1640 feet.
Maximum operating altitude 16,500 feet (5,000 meters).
4.Operating Temperature derating. 0°C to 45°C (Sizes 1, 2); 0°C to 40°C (Sizes 3,4,5) ambient.
Above rated temperature, derate the continuous and peak output current by 2% per °C above rating.
Maximum ambient is 55°C.
Cover Removal To connect power and signal wires, the cover must be removed. This procedure describes how to access all
terminal connections inside the control.
1.Loosen the two cover screws shown in Figure 4-8, then lift and remove the cover as shown.
Figure 4-1 Top Cover Removal
Lift and
remove cover
Cover
Screws
(2)
2.Locate the two 1/4 turn screws shown in Figure 4-2. Rotate each screw 1/4 turn CCW. This releases
the control from the base.
Figure 4-2 Signal Connections
Feedback Expansion
Board location
1/4 Turn Screw1/4 Turn Screw (1/4 turn to release,
Power Connections (Control and base must
be opened to view, see Figure 4-9)
Power Ground
Motor Ground
Communications Expansion
Board location
Signal Connections
press screw into hole to close).
See Recommended Tightening Torques in Section 9.
4-2 Receiving & InstallationMN792
Cover Removal Continued
3.The control and base are hinged and are opened as shown in Figure 4-3.
Figure 4-3 Hinged Assembly
Rubber
Grommet
The knock–out panel is part of the base
assembly to allow connections to be made.
Use the correct size rubber grommet,
conduit coupling or 360 degree coupling.
Metal
Coupling
360 Degree Coupling
360 Degree
Coupling
Mechanical Installation
Mount the control to the mounting surface. The control must be securely fastened to the mounting surface by
the control mounting holes. The location of the mounting holes is shown in Section 9 of this manual.
External Vent Kit (Size 4 & 5 controls only)
Raise the control to
expose the base
Knock–out
panel
Hinge
Control
Base
Upper Housing
Foam gasket stretches over duct prior to
attaching upper housing.
Duct slides down between duct clip and mounting
panel and fits within the sides of the control housing.
Fit duct clip under fasteners at top of drive.
Be sure it is tight against the mounting panel.
Receiving & Installation 4-3MN792
Optional Remote Keypad Installation (Enclosure rating of IP54 when correctly mounted). The keypad may be
remotely mounted using optional Baldor keypad extension cable.
Tools Required:
•Center punch, file and screwdrivers (Phillips and straight) and crescent wrench.
•#19 drill and drill motor .
Figure 4-4 Remote Keypad Installation
5
1
Mounting Instruction:
2
3
4
Keypad ACBD01A01
Bezel ACBD02A01
1.Locate a flat mounting surface. Place the template on the mounting surface (step 1).
2.Accurately center punch the mounting holes.
3.Drill holes for the two mounting screws.
4.Use the drill to remove metal for the 27 x 29 mm rectangular hole (step 2).
5.Debur the rectangular hole making sure the panel stays clean and flat.
6.Remove the protective film from the keypad gasket (step 3).
7.Assemble the keypad to the panel. Use two screws provided (step 4).
8.Connect the 10 ft. cable at the keypad and P3 of the control (step 5).
Figure 4-5 Template
CBLD030KP
4.09 (104)
1.90 (48.25)
3.78 (96.5)
3.40
(86.5)
5.22
(132.5)
1.57
1.06 (27)
(40)
1.97
(50)
1.14
0.16 (4.0) Dia.
(29)
Bottom
4 Places
4-4 Receiving & InstallationMN792
Electrical InstallationAll interconnection wires between the control, AC power source, motor, host control and any operator
interface stations should be in metal conduits. Use listed closed loop connectors that are of appropriate size for
wire gauge being used. Connectors are to be installed using crimp tool specified by the manufacturer of the
connector. Only class 1 wiring should be used.
System Grounding Baldor controls are designed to be powered from standard single and three phase lines that are electrically
symmetrical with respect to ground. System grounding is an important step in the overall installation. The
recommended grounding method is shown in Figure 4-6.
Figure 4-6 Recommended System Grounding (3 phase) for UL
Note: Wiring shown for clarity of grounding method only. Not representative of actual terminal block location.
AC
Supply
(Mains)
Earth
Driven Earth Ground
(Facility Ground)
L1
Disconnect
L2
and Fuses
L3
Four Wire “Wye”
Route all power wires L1, L2, L3 and Earth
(Ground) together in conduit or cable.
L1
L2
L3
Control
TH1
TH2
A+
A–
F+
F–
Motor
See Recommended Tightening Torques in Section 9.
+
+
Armature
Field
Thermistor
GND
Ungrounded Distribution System
With an ungrounded power distribution system it is possible to have a continuous current path to ground through
the MOV devices. To avoid equipment damage, an isolation transformer with a grounded secondary is
recommended. This provides three phase AC power that is symmetrical with respect to ground.
Input Power Conditioning
Baldor controls are designed for direct connection to standard single and three phase lines that are electrically
symmetrical with respect to ground. Certain power line conditions must be avoided. An AC line reactor or an
isolation transformer may be required for some power conditions.
•If the feeder or branch circuit that provides power to the control has permanently connected power
factor correction capacitors, an input AC line reactor or an isolation transformer must be connected
between the power factor correction capacitors and the control.
•If the feeder or branch circuit that provides power to the control has power factor correction
capacitors that are switched on line and off line, the capacitors must not be switched while the control
is connected to the AC power line. If the capacitors are switched on line while the control is still
connected to the AC power line, additional protection is required. TVSS (Transient Voltage Surge
Suppressor) of the proper rating must be installed between the AC line reactor or an isolation
transformer and the AC input to the control.
Line Impedance The control requires a 5% maximum line impedance (voltage drop across the reactor is 5% when the control
draws rated input current). If the impedance of the incoming power does not meet the requirement for the
control, a 3 phase line reactor can be used to provide the needed impedance in most cases. Line reactors are
optional and are available from Baldor.
The input impedance of the power lines can be determined as follows:
Measure the line to line voltage at no load and at full rated load.
Use these measured values to calculate impedance as follows:
%Impedance +
(Volts
No Load Speed
(Volts
* Volts
No Load Speed
Full Load Speed
)
)
100
Power Disconnect A power disconnect should be installed between each input power source and the control for a fail–safe
method to disconnect power. The control will remain in a powered-up condition until all input power is removed
from the control and the internal voltage is depleted.
Protection Devices The control must have a suitable input power protection device installed. Input and output wire size is
based on the use of copper conductor wire rated at 75 °C. Table 4-3 describes the wire size to be used for
power connections and Table 4-4 describes the ratings of the protection devices.
Recommended fuse sizes are based on the following:
UL 508C suggests a fuse size of four times the continuous output current of the control.
Dual element, time delay fuses should be used to avoid nuisance trips due to inrush current when
power is first applied.
Receiving & Installation 4-5MN792
Electrical Installation Continued
Isolation Transformer Sizing
Use the information in Table 4-2 to select the KVA rating of the transformer based on the HP rating of the
control. The secondary voltage will be the input voltage to the control and the impedance should be 2% or less.
One exception to Table 4-2 is when the DC armature voltage is less than the AC input voltage. If this is the
case, use the following formula:
KVA + 0.00163 VAC
Secondary
IDC
Secondary
Table 4-2 Isolation Transformer KVA Selection
HP57.5101520253040506075100125150200250300
KVA7.511142027344051637593118145175220275330
Single Phase Power Since the control rectifies all three input power phases, operation from a single phase power source is
L1, L2, L3Main AC input power. A 3–phase AC contactor should be connected in the main AC power supply connections.
A+, A–The motor armature is connected to busbar terminals A+ and A–. If a DC contactor is used the contactor poles
F+, F–Connect the motor field (–) to terminal F– and field (+) to terminal F+. If the motor has no field connections, is a
FL1, FL2An external field supply may be used for Size 2–5 controls. Connect this supply to terminals FL1 and FL2. The
3, 4Size 3–5, the AC Contactor coil can be connected between TB3–3 (line) and TB3–4 (neutral) and its purpose is to
L, NSingle phase AC power for logic circuits. The auxiliary supply must be connected directly to the incoming supply,
TH1, TH2Connection for motor thermal protection. Thermistors must have a combined working resistance of 750 ohms or
(AC Contactor is internal for Size 1 and 2 controls. For other sizes, use terminals 3 and 4).
should be interposed between the control terminals and the motor terminals.
permanent magnet motor, or if the field is derived externally, you must disable the Field Enable [170] parameter.
voltage is determined by the desired field voltage. The supply must be protected externally with suitable fuses.
Always derive the supply from the Red and Yellow phases of the main power supply, with the Red phase
connected to terminal FL1 and the Yellow phase connected to FL2.
provide AC power disconnection. Maximum coil inrush current must not exceed 3A.
(disconnect only). (Logic Supply is internal for Size 1 and 2 controls).
less, increasing to at least 4k ohms at over–temperature. The alarm is latched and the contol must be restarted.
Receiving & Installation 4-7MN792
Electrical Installation Continued
Power Connections Single phase operation of this control is not possible.
Power connections are shown in Figure 4-8. (The location of these terminals is shown in Figure 4-9).
Figure 4-8 3 Phase Power Connections
Note 1
Note 2
Start
Contactor
Fuse
Connection
RE
3
4
L1L2L3
L1L2L3
Earth
Note 3 & 4
Note 6
Notes:
1.See Protection Device description in this section.
2.Metal conduit or shielded cable should be used. Connect conduits so
the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
3.Use the same gauge wire for Earth as used for L1, L2, L3 connections.
4.Use same gauge wire for Earth ground as is used for L and N,
or L1, L2 L3. (VDE (Germany) requires 10mm
6AWG).
5.Reference EMC wiring in Appendix A for CE compliance.
6.AC Contactor is internal for size 1 and 2 controls. Size 3–5, the
contactor can be connected between TB3–3 (line) and TB3–4
(neutral) and its purpose is to provide AC power disconnection.
Maximum inrush current must not exceed 3A.
This figure shows optional components not furnished with control.
See Recommended Tightening Torques in Section 9.
Size 1 control
Logic
Transformer
Conn1
Conn2
Conn3
Conn4
Conn5
Move the jumper to the
correct voltage of the
480
L1,L2,L3 supply input.
400
Note: When the internal logic
230
208
transformer is installed, FS7
on the main board is
removed. FS1 on the logic
supply board is used.
FS1
Setting
480
400
230
208
Voltage Range
460–500
380–415
220–240
208
Size 2 control
208
230
400
480
Logic
Transformer
Power
Connections
AC Main Supply
Motor GroundEarth from
Move the jumper to the
correct voltage of the
L1,L2,L3 supply input.
(480V position shown.)
See Recommended Tightening Torques in Section 9.
Logic PowerFor size 1 and 2 controls, the logic transformer is internal. The location is shown in Figure 4-9. Because the
logic transformer is powered from the L1,L2,L3 input AC power, the jumper must be placed in the location that
corresponds to the AC line voltage.
For size 3, 4 and 5 controls the single phase logic power must be supplied by an external source. Normally
115VAC is applied at TB3 terminals L and N, see Figure 4-7 for the location. (Your control may have been
ordered with 230VAC logic power. In that case, 230VAC is applied at TB3 terminals L and N.)
4-8 Receiving & InstallationMN792
Electrical Installation Continued
Motor Connections Motor connections are shown in Figure 4-10. (The location of these terminals is shown in Figure 4-9).
Note: If your motor requires more than 85% of the line voltage as its DC input voltage, a step up transformer is
required. This is added between the incoming line terminals and the L1 and L2 terminals of the field
supply module. This connection is phase sensitive with main input L1 and L2.
Figure 4-10 Motor Connections
Notes:
1. Shield wires inside a metal conduit.
2. Metal conduit should be used to shield output
wires (between control and motor). Connect
conduits for continuous EMI/RFI shielding.
See Recommended Tightening Torques in Section 9.
Control
TH1
TH2
A+
A–
F+
F–
Motor
+
+
Armature
Field
Thermistor
GND
Note: The control may be connected to a permanent magnet field DC motor. In this case, the field supply is not
connected and the “Field Enable” [170] parameter must be set to “Disable”.
Shunt Wound
Typical shunt wound motor field connection 120/240V or
150/300V. Consult manufacturers specific motor data for details.
See Recommended Tightening Torques in Section 9.
External AC Field (Not available for size 1 controls)
The internal motor field is more widely used, it provides up to 90% of rated AC main voltage to the field
windings. However if an external field supply is required (an application that requires more field voltage than
90% of AC main), terminals FL1 and FL2 can be used. The magnitude of this voltage is determined by the
desired field voltage. The external supply must be protected with suitable fuses and disconnect. Always derive
the supply from the Red and Yellow phases of the main power supply, with the Red phase connected to FL1
and the Yellow phase to FL2 (see jumpers in the External Field Connections diagrams).
Figure 4-11 External Field Connections
L1L2L3
Note 3 & 4
Earth
FL1FL2
External
Field Supply
Note 1
Note 2
Start
Contactor
Note 6
Fuse
Connection
RE
3
4
TB3
Baldor Control
L1L2L3
TB1
F1F2
F1F4F2F3
F3F4
120V or 150V
Notes:
1.See Protection Device description in this section.
2.Metal conduit or shielded cable should be used. Connect conduits so
the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
3.Use the same gauge wire for Earth as used for L1, L2, L3 connections.
4.Use same gauge wire for Earth ground as is used for L and N.
(VDE (Germany) requires 10mm
2
minimum, 6AWG).
5.Reference EMC wiring in Appendix A for CE compliance.
6.AC Contactor is internal for size 1 and 2 controls. Size 3–5, the
contactor can be connected between TB3–3 (line) and TB3–4
(neutral) and its purpose is to provide AC power disconnection.
Maximum inrush current must not exceed 3A.
This figure shows optional components not furnished with control.
See Recommended Tightening Torques in Section 9.
240V or 300V
Receiving & Installation 4-9MN792
Electrical Installation Continued
External Field Terminal and Jumper Locations – Size 2
The position of the jumper selects the board to use either an internal or external motor field.
Figure 4-12 External Field Sensor Plug Jumper Settings
PLG1 to Power BoardPLG2 to Power BoardPLG3 to Power Board
External Field Selector Plug
FL1 FL2 F+F–M1M2M3
Field Bridge
FL1 FL2
Jumper selecting external field supplyJumper selecting internal field supply
L1 L2
FL1 FL2
External Field Terminal and Jumper Locations – Size 3
Relocating the Red and Yellow phase wires (as shown in Figure 4-13) allows terminals D1 and D2 on the Power
Board to be used as the external field AC supply connections. External fuse must not exceed 10A.
Figure 4-13 External Field Connections
Yellow
D1
F8
Red
F19
F16
Motor Vent Fan Circuit Breaker
Field Bridge
Power Board
D2
F18
L N 3 4 TH1 TH2
Terminal Board
L1 L2
Connection
No Connection
See Recommended Tightening Torques in Section 9.
D3
D4
F8 & F16 = Internal Field Supply.
F18 & F19 = External Field Supply.
Red = FL1
Yellow = FL2
Procedure:
1.Remove the control board (2 screws secure it) to allow access to the power board.
2.Remove the red phase lead from connector “F16” on the left–hand side of the board.
3.Connect the red phase lead to connector “F19” located below D1.
4.Remove the yellow phase lead to connector “F8” on the left–hand side of the board.
5.Connect the yellow phase lead to connector “F18” located below D2.
6.Connect L1 to D1, and L2 to D2. When using an external AC input it is important to have the correct
phase relationship on the terminals. The supply must be derived from L1 (Red) and L2 (Yellow)
phases directly or indirectly through a single phase transformer. L1 must be connected to D1, and L2
connected to D2.
4-10 Receiving & InstallationMN792
Loading...
+ 148 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.