Part Detail
Revision: U Status: INA/A Change #: Proprietary: No Type: AC Elec. Spec: 06WGW390 CD Diagram: CD0005 Mfg Plant: Mech. Spec: 06J001 Layout: 06LYJ001 Poles: 04 Created Date: Base: RG Eff. Date: 01-21-2010 Leads: 9#16
Specs
Catalog Number: M7144T Frame: 184T Frame Material: Iron Output @ Frequency: 5.000 HP @ 60 HZ
3.000 HP @ 50 HZ
Synchronous Speed @ Frequency: 1500 RPM @ 50 HZ
1800 RPM @ 60 HZ
Voltage @ Frequency: 460.0 V @ 60 HZ
380.0 V @ 50 HZ
190.0 V @ 50 HZ
230.0 V @ 60 HZ XP Division: Not Applicable Agency Approvals: UL
CSA Auxillary Box: No Auxillary Box Auxillary Box Lead Termination: None Base Indicator: Rigid
Front Shaft Indicator: None Heater Indicator: No Heater Insulation Class: B Inverter Code: Not Inverter KVA Code: K Lifting Lugs: Standard Lifting Lugs Locked Bearing Indicator: No Locked Bearing Motor Lead Quantity/Wire Size: 9 @ 16 AWG Motor Lead Exit: Ko Box Motor Lead Termination: Flying Leads Motor Type: 0638M Mounting Arrangement: F1 Power Factor: 80 Product Family: General Purpose Pulley End Bearing Type: Ball Pulley Face Code: Standard Pulley Shaft Indicator: Standard
Bearing Grease Type: Polyrex EM (-20F +300F)
Rodent Screen: None
Product Information Packet: M7144T - 5HP,1800RPM,3PH,60HZ,L184T,TEFC,FOOT,
Blower: None Current @ Voltage: 10.600 A @ 190.0 V
13.400 A @ 230.0 V
14.200 A @ 208.0 V
5.300 A @ 380.0 V
6.700 A @ 460.0 V Design Code: B Drip Cover: No Drip Cover Duty Rating: CONT Electrically Isolated Bearing: Not Electrically Isolated Feedback Device: NO FEEDBACK Front Face Code: Standard
Shaft Extension Location: Pulley End Shaft Ground Indicator: No Shaft Grounding Shaft Rotation: Reversible Shaft Slinger Indicator: No Slinger Speed Code: Single Speed Motor Standards: NEMA Starting Method: Direct on line Thermal Device - Bearing: None Thermal Device - Winding: Normally Closed Thermostat Vibration Sensor Indicator: No Vibration Sensor Winding Thermal 1: None Winding Thermal 2: None XP Temp Code: T3C
Product Information Packet: M7144T - 5HP,1800RPM,3PH,60HZ,L184T,TEFC,FOOT,
AC Induction Motor Performance Data
Record # 20669 - Typical performance - not guaranteed values
Winding: 06WGW390-R009 Type: 0638M Enclosure: XPFC
Nameplate Data
460 V, 60 Hz:
High Voltage Connection Rated Output (HP) 5//3 Full Load Torque 15 LB-FT Volts 230/460//190/380 Start Configuration direct on line Full Load Amps 13.4/6.7//10.6/5.3 Breakdown Torque 52.5 LB-FT R.P.M. 1750//1460 Pull-up Torque 29 LB-FT Hz 60//50 Phase 3 Locked-rotor Torque 36.4 LB-FT NEMA Design Code B KVA Code K Starting Current 51.2 A Service Factor (S.F.) 1 No-load Current 3.2 A NEMA Nom. Eff. 87.5 Power Factor 80 LinelineRes.@25ºC 2.49Ω Rating - Duty 40C AMB-CONT Temp. Rise @ Rated Load 54°C
Locked-rotor Power Factor 41
Rotor inertia 0.356 LB-FT2
Load Characteristics 460 V, 60 Hz, 5 HP
% of Rated Load 25 50 75 100 125 150 S.F. Power Factor 42 63 74 80 83 84 82 Efficiency 81.1 87.3 88.4 87.9 86.8 85.2 87.2 Speed 1791 1779 1767 1753 1739 1722 1745 Line amperes 3.5 4.3 5.4 6.7 8.1 9.7 7.5
Product Information Packet: M7144T - 5HP,1800RPM,3PH,60HZ,L184T,TEFC,FOOT,
Performance Graph at 460V, 60Hz, 5.0HP Typical performance - Not guaranteed values
Product Information Packet: M7144T - 5HP,1800RPM,3PH,60HZ,L184T,TEFC,FOOT,
AC Induction Motor Performance Data
Record # 20670 - Typical performance - not guaranteed values
Winding: 06WGW390-R009 Type: 0638M Enclosure: XPFC
Nameplate Data
380 V, 50 Hz:
High Voltage Connection Rated Output (HP) 5//3 Full Load Torque 10.8 LB-FT Volts 230/460//190/380 Start Configuration direct on line Full Load Amps 13.4/6.7//10.6/5.3 Breakdown Torque 49.5 LB-FT R.P.M. 1750//1460 Pull-up Torque 30 LB-FT Hz 60//50 Phase 3 Locked-rotor Torque 37.7 LB-FT NEMA Design Code B KVA Code K Starting Current 49.1 A Service Factor (S.F.) 1 No-load Current 3.1 A NEMA Nom. Eff. 87.5 Power Factor 80 LinelineRes.@25ºC 2.49Ω Rating - Duty 40C AMB-CONT Temp. Rise @ Rated Load 56°C
Locked-rotor Power Factor 46
Rotor inertia 0.356 LB-FT2
Load Characteristics 380 V, 50 Hz, 3 HP
% of Rated Load 25 50 75 100 125 150 Power Factor 35 56 69 77 82 85 Efficiency 77.6 85.5 88.1 88.9 88.9 87.9 Speed 1492 1486 1475 1464 1448 1432 Line amperes 3.4 4.1 5 5.3 6.4 7.6
Product Information Packet: M7144T - 5HP,1800RPM,3PH,60HZ,L184T,TEFC,FOOT,
Performance Graph at 380V, 50Hz, 3.0HP Typical performance - Not guaranteed values
Product Information Packet: M7144T - 5HP,1800RPM,3PH,60HZ,L184T,TEFC,FOOT,