OverviewIf you are an experienced user of Baldor controls, you are probably already familiar with
the keypad programming and keypad operation methods. If so, this quick start guide has
been prepared for you. This procedure will help get your system up and running in the
keypad mode quickly and will allow motor and control operation to be verified. This
procedure assumes that the Control, Motor and Dynamic Brake hardware are correctly
installed (see Section 3 for procedures) and that you have an understanding of the
keypad programming & operation procedures. It is not necessary to wire the terminal
strip to operate in the Keypad mode (Section 3 describes terminal strip wiring
procedures). The quick start procedure is as follows:
1.Read the Safety Notice and Precautions in section 2 of this manual.
2.Mount the control. Refer to Section 3, “Physical Location” procedure.
3.Connect AC power. Refer to Section 3 “AC Line Connections”.
4.Connect the motor. Refer to Section 3, “Motor Connections”.
5.Install Dynamic brake hardware, if required. Refer to Section 3,
“Optional Dynamic Brake Hardware”.
6.Plug in the keypad. Refer to Section 3, “Keypad Installation” procedure.
Quick Start ChecklistCheck of electrical items.
1.Verify AC line voltage at source matches control rating.
2.Inspect all power connections for accuracy, workmanship and tightness as well
as compliance to codes.
3.Verify control and motor are grounded to each other and the control is
connected to earth ground.
4.Check all signal wiring for accuracy.
5.Be certain all brake coils, contactors and relay coils have noise suppression.
This should be an R-C filter for AC coils and reverse polarity diodes for DC
coils. MOV type transient suppression is not adequate.
Check of Motors and Couplings
1.Verify freedom of motion of motor shaft.
2.Verify that the motor coupling is tight without backlash.
3.Verify the holding brakes if any, are properly adjusted to fully release and set to
the desired torque value.
Quick Start Guide 1-1MN715
Section 1General Information
Quick Start Procedure The following procedure will help get your system up and running in the keypad mode
quickly, and will allow you to prove the motor and control operation. This procedure
assumes that the Control, Motor and Dynamic Brake hardware are correctly installed (see
Section 3 for procedures) and that you have an understanding of the keypad
programming & operation procedures.
Initial Conditions
Be sure the Control (Physical Installation & AC Line Connections), Motor and Dynamic
Brake hardware are wired according to the procedures in Section 3 of this manual.
Become familiar with the keypad programming and keypad operation of the control as
described in Section 4 of this manual.
WARNING: Make sure that unexpected operation of the motor shaft during start
up will not cause injury to personnel or damage to equipment.
1.Verify that any enable inputs to J4-8 are open.
2.Turn power on. Be sure no faults are displayed on the keypad display.
3.Set the Level 1 Input block, Operating Mode to “Keypad”.
4.Be sure the Level 2 Protection block, Local Enable INP parameter is OFF and
the Level 2 Protection block, External Trip parameter is OFF.
5.Set the Level 2 Output Limits block, “Operating Zone” parameter as desired
(STD CONST TQ, STD VAR TQ, QUIET CONST TQ or QUIET VAR TQ).
Note: JP1 is in position 2–3 as shipped from the factory (<120Hz operation).
For operation with MAX Output FREQ >120Hz, change the position of
JP1 to pins 1–2. Refer to Section 3 for jumper location.
8.If the desired peak current limit setting is different than is automatically set by
the Operating Zone, set the Level 2 Output Limits block, “PK Current Limit”
parameter as desired.
9.Enter the following motor data in the Level 2 Motor Data block parameters:
Motor Voltage (input)
Motor Rated Amps (FLA)
Motor Rated Speed (base speed)
Motor Rated Frequency
Motor Mag Amps (no load current)
10. If External Dynamic Brake hardware is used, set the Level 2 Brake Adjust
block, “Resistor Ohms” and “Resistor Watts” parameters.
11. Set the Level 1 V/HZ Boost block, “V/HZ Profile” parameter for the correct V/Hz
ratio for your application.
12. If the load is a high initial starting torque type, the torque boost and Accel time
may need to be increased. Set the Level 1 V/HZ Boost block, “Torque Boost”
and the Level 1 Accel/Decel Rate block, “ACCEL TIME #1” as required.
13. Select and program additional parameters to suit your application.
The control is now ready for use in keypad mode or the terminal strip may be wired and
the programming changed for another operating mode.
1-2 Quick Start GuideMN715
Section 2
General Information
OverviewThe Baldor Series 15H control is a PWM inverter motor control. The control converts AC
line power to fixed DC power. The DC power is then pulse width modulated into
synthesized three-phase AC line voltage for the motor. In this way, the control converts
the fixed input frequency to variable output frequency to cause the motor to have variable
speed operation.
The rated horsepower of the control is based on a NEMA design B four pole motor and
60Hz operation at nominal rated input voltage. If any other type of motor is used, or input
voltage other than 230, 460 or 575 VAC is applied to the input terminals, the control
should be sized to the motor using the rated current of the motor.
The Baldor Series 15H control may be used in many different applications. It may be
programmed by the user to operate in four different operating zones; standard constant
torque, standard variable torque, quiet constant torque or quiet variable torque. It can
also be configured to function in a number of operating modes for custom operation.
It is the responsibility of the user to determine the optimum operating zone and operating
mode for the application. These choices are programmed using the keypad as explained
in the programming section of this manual.
CE ComplianceA custom unit may be required, contact Baldor. Compliance to Directive 89/336/EEC is
the responsibility of the system integrator. A control, motor and all system components
must have proper shielding grounding and filtering as described in MN1383. Please refer
to MN1383 for installation techniques for CE compliance.
General Information 2-1MN715
Limited Warranty
For a period of two (2) years from the date of original purchase, BALDOR will
repair or replace without charge controls and accessories which our
examination proves to be defective in material or workmanship. This
warranty is valid if the unit has not been tampered with by unauthorized
persons, misused, abused, or improperly installed and has been used in
accordance with the instructions and/or ratings supplied. This warranty is in
lieu of any other warranty or guarantee expressed or implied. BALDOR
shall not be held responsible for any expense (including installation and
removal), inconvenience, or consequential damage, including injury to any
person or property caused by items of our manufacture or sale. (Some
states do not allow exclusion or limitation of incidental or consequential
damages, so the above exclusion may not apply.) In any event, BALDOR’s
total liability, under all circumstances, shall not exceed the full purchase
price of the control. Claims for purchase price refunds, repairs, or
replacements must be referred to BALDOR with all pertinent data as to the
defect, the date purchased, the task performed by the control, and the
problem encountered. No liability is assumed for expendable items such as
fuses.
Goods may be returned only with written notification including a BALDOR
Return Authorization Number and any return shipments must be prepaid.
2-2 General InformationMN715
Safety Notice:This equipment contains voltages that may be as great as 1000 volts! Electrical shock
can cause serious or fatal injury. Only qualified personnel should attempt the start–up
procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts
that are driven by this equipment. Improper use can cause serious or fatal injury. Only
qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
PRECAUTIONS:
WARNING: Do not touch any circuit board, power device or electrical
connection before you first ensure that power has been
disconnected and there is no high voltage present from this
equipment or other equipment to which it is connected. Electrical
shock can cause serious or fatal injury. Only qualified personnel
should attempt the start–up procedure or troubleshoot this
equipment.
WARNING: Be sure that you are completely familiar with the safe operation of
this equipment. This equipment may be connected to other
machines that have rotating parts or parts that are controlled by
this equipment. Improper use can cause serious or fatal injury.
Only qualified personnel should attempt the start–up procedure or
troubleshoot this equipment.
WARNING: Do not use motor overload relays with an automatic reset feature.
These are dangerous since the process may injure someone if a
sudden or unexpected automatic restart occurs. If manual reset
relays are not available, disable the automatic restart feature using
external control wiring.
WARNING: This unit has an automatic restart feature that will start the motor
whenever input power is applied and a RUN (FWD or REV)
command is issued and maintained. If an automatic restart of the
motor could cause injury to personnel, the automatic restart feature
should be disabled by changing the “Restart Auto/Man” parameter
to MANUAL.
WARNING: Be sure the system is properly grounded before applying power.
Do not apply AC power before you ensure that grounds are
connected. Electrical shock can cause serious or fatal injury.
WARNING: Do not remove cover for at least five (5) minutes after AC power is
disconnected to allow capacitors to discharge. Electrical shock can
cause serious or fatal injury.
WARNING: Improper operation of control may cause violent motion of the
motor shaft and driven equipment. Be certain that unexpected
motor shaft movement will not cause injury to personnel or damage
to equipment. Peak torque of several times the rated motor torque
can occur during control failure.
WARNING: Motor circuit may have high voltage present whenever AC power is
applied, even when motor is not rotating. Electrical shock can
cause serious or fatal injury.
Continued on next page.
General Information 2-3MN715
Section 1General Information
WARNING: Dynamic brake resistors may generate enough heat to ignite
combustible materials. Keep all combustible materials and
flammable vapors away from brake resistors.
Caution:Suitable for use on a circuit capable of delivering not more than the
RMS symmetrical short circuit amperes listed here at rated voltage.
HorsepowerRMS Symmetrical Amperes
1–505,000
51–20010,000
201–40018,000
401–60030,000
601–90042,000
Caution:Do not supply any power on the External Trip (motor thermostat)
leads at J4-16 or J4-17 as the control may be damaged. Use a dry
contact type that requires no external power to operate.
Caution:Disconnect motor leads (T1, T2 and T3) from control before you
perform a “Megger” test on the motor. Failure to disconnect motor
from the control will result in extensive damage to the control. The
control is tested at the factory for high voltage / leakage resistance
as part of Underwriter Laboratory requirements.
Caution:Do not connect AC power to the Motor terminals T1, T2 and T3.
Connecting AC power to these terminals may result in damage to
the control.
Caution:Baldor recommends not using “Grounded Leg Delta” transformer
power leads that may create ground loops and provide unstable
power to the motor controller. Instead, we recommend using a four
wire Wye.
Caution:If the DB hardware mounting is in any position other than vertical,
the DB hardware must be derated by 35% of its rated capacity.
2-4 General InformationMN715
Section 3
Receiving & Installation
Receiving & InspectionWhen you receive your control, there are several things you should do immediately.
1.Observe the condition of the shipping container and report any damage
immediately to the commercial carrier that delivered your control.
2.Verify that the control you received is the same as listed on your purchase
order.
3.If the control is to be stored for several weeks before use, be sure that it is
stored in a location that conforms to published storage specifications. (Refer to
Section 6 of this manual).
Physical InstallationThe mounting location of the control is important. It should be installed in an area that is
protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic
particles, and vibration.
Several other factors should be carefully evaluated when selecting a location for
installation:
1.For effective cooling and maintenance, the control should be mounted on a
smooth, non-flammable vertical surface. Table 3-1 lists the Watts Loss ratings
for enclosure sizing.
2.At least two inches clearance must be provided on all sides for airflow.
3.Front access must be provided to allow the control cover to be opened or
removed for service and to allow viewing of the Keypad Display.
4.Altitude derating. Up to 3300 feet (1000 meters), no derating required. Above
3300 feet, derate peak output current by 2% for each 1000 feet above 3300
feet.
5.Temperature derating. Up to 40°C, no derating required. Above 40°C, derate
peak output current by 2% per °C above 40°C.
Maximum ambient is 55°C.
Control InstallationThe control must be securely fastened to the mounting surface at the mounting holes.
Shock Mounting
If the control will be subjected to levels of shock greater than 1G or vibration greater than
0.5G at 10 to 60Hz, the control should be shock mounted.
Through the Wall Mounting
Control sizes B2, C2 and D2 are designed for panel or through the wall installation. Refer
to Section 6 of this manual for drawings and dimensions of the through the wall mounting
kits.
Keypad Installation
Procedure:
1.Refer to the Remote Keypad Installation procedure and mount the keypad.
2.Connect the keypad cable to the keypad connector of the main control board.
3-2 Receiving & InstallationMN715
Section 1General Information
Optional Remote Keypad Installation The keypad may be remotely mounted using optional Baldor keypad
extension cable. Keypad assembly (white - DC00005A-01; gray - DC00005A-02) comes
complete with the screws and gasket required to mount it to an enclosure. When the
keypad is properly mounted to a NEMA Type 4X enclosure, it retains the Type 4X rating.
Tools Required:
•Center punch, tap handle, screwdrivers (Phillips and straight) and crescent
wrench.
•8-32 tap and #29 drill bit (for tapped mounting holes) or #19 drill (for clearance
mounting holes).
1
•1-
•RTV sealant.
•(4) 8-32 nuts and lock washers.
•Extended 8-32 screws (socket fillister) are required if the mounting surface is
•Remote keypad mounting template. A tear out copy is provided at the end of
Mounting Instruction: For tapped mounting holes
1.Locate a flat 4″ wide x 5.5″ minimum high mounting surface. Material should
2.Place the template on the mounting surface or mark the holes as shown.
3.Accurately center punch the 4 mounting holes (marked A) and the large
4.Drill four #29 mounting holes (A). Thread each hole using an 8-32 tap.
5.Locate the 1-1/4″ knockout center (B) and punch using the manufacturers
6.Debur knockout and mounting holes making sure the panel stays clean and flat.
7.Apply RTV to the 4 holes marked (A).
8.Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers.
9.From the inside of the panel, apply RTV over each of the four mounting screws
Mounting Instructions: For clearance mounting holes
1.Locate a flat 4″ wide x 5.5″ minimum high mounting surface. Material should
2.Place the template on the mounting surface or mark the holes as shown on the
3.Accurately center punch the 4 mounting holes (marked A) and the large
4.Drill four #19 clearance holes (A).
5.Locate the 1-1/4″ knockout center (B) and punch using the manufacturers
6.Debur knockout and mounting holes making sure the panel stays clean and flat.
7.Apply RTV to the 4 holes marked (A).
8.Assemble the keypad to the panel. Use 8–32 screws, nuts and lock washers.
9.From the inside of the panel, apply RTV over each of the four mounting screws
/4″ standard knockout punch (1-11/16″ nominal diameter).
thicker than 12 gauge and is not tapped (clearance mounting holes).
this manual for your convenience. (Photo copy or tear out.)
be sufficient thickness (14 gauge minimum).
knockout (marked B).
instructions.
and nuts. Cover a 3/4″ area around each screw while making sure to completely
encapsulate the nut and washer.
be sufficient thickness (14 gauge minimum).
template.
knockout (marked B).
instructions.
and nuts. Cover a 3/4″ area around each screw while making sure to completely
encapsulate the nut and washer.
Receiving & Installation 3-3MN715
Section 1General Information
Electrical InstallationTo make electrical connections, use UL listed closed loop connectors that are of
appropriate size for wire gauge being used. Connectors are to be installed using crimp
tool specified by the manufacturer of the connector. Only Class 1 wiring should be used.
Baldor Series H controls feature UL approved adjustable motor overload protection
suitable for motors rated at no less than 50% of the output rating of the control. Other
governing agencies such as NEC may require separate over-current protection. The
installer of this equipment is responsible for complying with the National Electric Code
and any applicable local codes which govern such practices as wiring protection,
grounding, disconnects and other current protection.
System GroundingBaldor Controls are designed to be powered from standard three phase lines that are
electrically symmetrical with respect to ground. System grounding is an important step in
the overall installation to prevent problems. The recommended grounding method is
shown in Figure 3-1.
Figure 3-1 Recommended System Grounding
LOCAL
PROG
JOG
DISP
FWD
SHIFT
ENTER
REV
RESET
STOP
Safety
Ground
Note: A line reactor is recommended
and must be ordered separately.
AC Main Supply
L1
L2
L3
Earth
Four Wire
“Wye”
Driven Earth
Ground Rod
(Plant Ground)
Route all 4 wires L1, L2, L3 and Earth
(Ground) together in conduit or cable.
Route all 4 wires T1, T2, T3 and Motor
Ground together in conduit or cable.
Connect all wires (including motor ground)
inside the motor terminal box.
Line
Reactor
Series H
L1
L2 L3T1 T2 T3
Note: A load reactor is recommended
and must be ordered separately.
Load
Reactor
Ground per NEC and
Local codes.
3-4 Receiving & InstallationMN715
Section 1General Information
System Grounding Continued
Ungrounded Distribution System
With an ungrounded power distribution system it is possible to have a continuous current
path to ground through the MOV devices. To avoid equipment damage, an isolation
transformer with a grounded secondary is recommended. This provides three phase AC
power that is symmetrical with respect to ground.
Input Power Conditioning
Baldor controls are designed for direct connection to standard three phase lines that are
electrically symmetrical with respect to ground. Certain power line conditions must be
avoided. An AC line reactor or an isolation transformer may be required for some power
conditions.
If the feeder or branch circuit that provides power to the control has
permanently connected power factor correction capacitors, an input AC line
reactor or an isolation transformer must be connected between the power factor
correction capacitors and the control.
If the feeder or branch circuit that provides power to the control has power
factor correction capacitors that are switched on line and off line, the capacitors
must not be switched while the control is connected to the AC power line. If the
capacitors are switched on line while the control is still connected to the AC
power line, additional protection is required. TVSS (Transient Voltage Surge
Suppressor) of the proper rating must be installed between the AC line reactor
or an isolation transformer and the AC input to the control.
Line ImpedanceThe Baldor control requires a minimum line impedance. If the impedance of the incoming
power does not meet the requirement for the control, a 3 phase line reactor can be used
to provide the needed impedance in most cases. Line reactors are optional and are
available from Baldor.
Control SizeA, B, C, D, EB2, C2, D2, F, G, G2, G+, H
Line Impedance Required3%1%
The input impedance of the power lines can be determined as follows:
Measure the line to line voltage at no load and at full rated load.
Use these measured values to calculate impedance as follows:
%Impedance +
(Volts
No Load Speed
(Volts
* Volts
No Load Speed
Full Load Speed
)
)
100
Line ReactorsThree phase line reactors are available from Baldor. The line reactor to order is based on
the full load current of the motor (FLA). If providing your own line reactor, use the
following formula to calculate the minimum inductance required.
(V
0.03)
L +
L*L
(I 3Ǹ 377)
Where:LMinimum inductance in Henries.
V
L-L
0.03Desired percentage of input impedance.
IInput current rating of control.
377Constant used with 60Hz power.
Input volts measured line to line.
Use 314 if input power is 50Hz.
Load ReactorsLine reactors may be used at the control output to the motor. When used this way, they
are called Load Reactors. Load reactors serve several functions that include:
Protect the control from a short circuit at the motor.
Limit the rate of rise of motor surge currents.
Slowing the rate of change of power the control delivers to the motor.
Load reactors should be installed as close to the control as possible. Selection should be
based on the motor nameplate FLA value.
Receiving & Installation 3-5MN715
AC Main Circuit
Power DisconnectA power disconnect should be installed between the input power service and the control
for a fail safe method to disconnect power. The control will remain in a powered-up
condition until all input power is removed from the control and the internal bus voltage is
depleted.
Protective DevicesRecommended fuse sizes are based on the following:
115% of maximum continuous current for time delay.
150% of maximum continuous current for Fast or Very Fast action.
Note: These general size recommendations do not consider harmonic currents or
ambient temperatures greater than 40°C.
Be sure a suitable input power protection device is installed. Use the recommended
circuit breaker or fuses listed in tables 3-2 through 3-4 (Wire Size and Protection
Devices). Input and output wire size is based on the use of copper conductor wire rated
at 75 °C. The table is specified for NEMA B motors.
Circuit Breaker:1 phase, thermal magnetic.
Equal to GE type THQ or TEB for 230VAC
3 phase, thermal magnetic.
Equal to GE type THQ or TEB for 230VAC or
Equal to GE type TED for 460VAC and 575VAC.
Fast Action Fuses:230VAC, Buss KTN
460VAC, Buss KTS to 600A (KTU for 601 to 1200A)
575VAC, Buss KTS TO 600A (KTU for 601 to 1200A)
Very Fast Action:230VAC, Buss JJN
460VAC, Buss JJS
575VAC, Buss JJS
Time Delay Fuses:230VAC, Buss FRN
460VAC, Buss FRS to 600A (KLU for 601 to 1200A)
575VAC, Buss FRS to 600A (KLU for 601 to 1200A)
1–2Relay1 Normally Open (N.O.) contact.
2–3Relay1 Normally Closed (N.C.) contact.
JP4
1–2Relay2 Normally Open (N.O.) contact.
2–3Relay2 Normally Closed (N.C.) contact.
Receiving & Installation 3-9MN715
AC Line Connections
Reduced Input Voltage Derating All power ratings stated in Section 6 are for the stated nominal AC input
voltages (230, 460 or 575VAC). The power rating of the control must be reduced when
operating at a reduced input voltage. The amount of reduction is the ratio of the voltage
change.
Examples:
A 10hp, 230VAC control operating at 208VAC has a reduced power rating of 9.04hp.
10HP
208VAC
230VAC
+ 9.04hp
Likewise, a 10hp, 460VAC control operating at 380VAC has a reduced power rating of
8.26hp.
10HP
380VAC
460VAC
+ 8.26hp
To obtain the full output rating of 10hp in either case requires a 15hp Control.
380-400VAC Operation Be sure all power to the control is disconnected before proceeding.
Size A, B, B2, C2 and D2 controls may be used directly with a 380-400VAC power
source, control modification is not necessary.
Size C, D, E, F and G controls all require modification for operation on the reduced line
voltage.
Tap change procedure (size C, D, E and F controls)
1.Be sure drive operation is terminated and secured.
2.Remove all power sources from the control. If power has been applied, wait at
least 5 minutes for bus capacitors to discharge.
3.Remove or open the front cover and locate the control transformer (Figure 3-3).
4.Remove the wire from terminal 5.
5.Place the wire that was removed from terminal 5 onto terminal 4.
6.Install or close the front cover.
Figure 3-3 Control Transformer Identification
3-10 Receiving & InstallationMN715
Section 1General Information
Figure 3-4 Configuring the Control Transformer Terminal Block for 380 - 400VAC (Size G)
Control Transformer Tap Change Procedure (size G controls).
1.Be sure drive operation is terminated and control is disabled.
2.Remove all power sources from the control. If power has been applied, wait at
least 5 minutes for bus capacitors to discharge.
3.Remove or open the front cover and locate the control transformer (Figure 3-4).
4.Remove the wires from the two right side terminals.
5.Place the wires on the center terminals as shown.
6.Install or close the front cover.
3 Phase Installation
Note 1
Note 3
Note 4
Note 3
* Circuit
Breaker
A1B1C1
*Optional
Line
Reactor
A2B2C2
460VAC380 - 400VAC
The AC power connections are shown in Figure 3-5.
L1L2L3
L1L2L3
Baldor
Series 15H
Control
Figure 3-5 3 Phase AC Power Connections
Earth
Note 2
Alternate *
Fuse
Connection
L1L2L3
A1B1C1
* Optional components not provided with control.
Notes:
1.See “Protective Devices” described previously in this section.
2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3.Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.See Line/Load Reactors described previously in this section.
Note 1
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-11MN715
Table 3-6 and 3-7 list the wire size for the input AC power wires. Motor leads should be
sized from the 3 phase tables.
Table 3-6 Single Phase Rating Wire Size and Protection Devices - 230 VAC Controls*
*Note:All wire sizes are based on 75°C copper wire. Higher temperature smaller gauge wire may be used per NEC
and local codes. Recommended fuses/breakers are based on 40°C ambient, maximum continuous control
output current and no harmonic current.
3-12 Receiving & InstallationMN715
Section 1General Information
Single Phase Input Power Considerations Single phase operation of G and H size controls is not possible.
Single phase AC input power can be used to power the control instead of three phase for
control sizes A, B, B2, C, C2, D, D2, E and F. The specifications and control sizes are
listed in Section 6 of this manual. If single phase power is to be used, the rated
Horsepower of the control may have to be reduced (derated). In addition, power wiring
and jumper changes are required. Single phase 3 wire connections are standard in the
USA. However, single phase 2 wire connection is used in most of the world. Both
connections types are shown.
Single phase rating wire size and protection devices are listed in Tables 3-6 and 3-7.
Single Phase Control Derating: Single phase power derating requires that the continuous and peak current ratings
of the control be reduced by the following percentages:
1.1-2 hp 230 and 460VAC controls:
No derating required.
2.3-25 hp (Size B, B2 and C2) 230 and 460VAC controls:
Derate hp by 40% of the nameplate rating.
3.15 hp (Size C, D2) and Larger 230 and 460VAC controls:
Derate hp by 50% of the nameplate rating.
Size A, B and B2 Single Phase Power Installation (See Figure 3-6).
Jumper Configuration
Size A, B and B2 controls, no jumper changes required.
Figure 3-6 Size A, B & B2 Single Phase 230/460VAC Power Connections
Note 1
Note 3
Note 4
* Circuit
Breaker
*Optional
Line
Reactor
L1L2
A1B1
A2B2
Earth
Note 2
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 Neutral
* Circuit
Breaker
A1
*Line
Reactor
A2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
L1L2
A1B1
Note 3
L1L2L3
Baldor
Series 15H
Control
Notes:
1.See “Protective Devices” described previously in this section.
2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3.Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-13MN715
Size C2 Single Phase Power Installation
Jumper Configuration
Locate the Interface board, and place JP7 on pins 2 & 3 for single phase operation.
Figure 3-7 Jumper Configuration
Control Board
Bend plastic insulator upward
to access the Interface Board.
L1L2
Note 1
Note 3
Note 4
Note 3
* Circuit
Breaker
*Optional
Line
Reactor
A1B1
A2B2
L1L2L3
JP7
Interface Board
JP7
Pins 1 & 2 = Three Phase
Pins 2 & 3 = Single Phase
Figure 3-8 Size C2 Single Phase 230/460VAC Power Connections
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
Baldor
Series 15H
Control
Earth
Note 2
L1 Neutral
* Circuit
Breaker
A1
*Line
Reactor
A2
Notes:
1.See “Protective Devices” described previously in this section.
2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3.Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.See Line/Load Reactors described previously in this section.
* Fuse
Connection
Note 1
* Optional components
not provided with control.
L1L2
A1B1
See Recommended Tightening Torques in Section 6.
3-14 Receiving & InstallationMN715
Section 1General Information
Size C and D Single Phase Power Installation
Jumper Configuration
Place JP2 on pins 1 & 2 for control single phase operation.
Place JP3 in position B for single phase operation of cooling fan.
Figure 3-9 Jumper Configuration
Note 1
Note 3
Note 4
Note 3
JP2
Pins 1 & 2 = Single Phase
Pins 2 & 3 = Three Phase
Figure 3-10 Size C & D Single Phase 230/460VAC Power Connections
L1L2
* Circuit
Breaker
B1C1
*Optional
Line
Reactor
B2C2
L1L2L3
Baldor
Series 15H
Control
JP3
Position A = Three Phase
Position B = Single Phase
JP2
1
JP3
A
B
Earth
Note 2
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 Neutral
* Circuit
Breaker
A1
*Line
Reactor
A2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
L1L2
A1B1
Notes:
1.See “Protective Devices” described previously in this section.
2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3.Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-15MN715
Size D2 Single Phase Power Installation
Jumper Configuration
Locate the Interface board, and place J100 on pins 2 & 3 for single phase operation.
Figure 3-11 Jumper Configuration
Note 1
Note 3
Note 4
Note 3
* Circuit
Breaker
*Optional
Line
Reactor
J100
Pins 1 & 2 = Three Phase
Pins 2 & 3 = Single Phase
1
2
3
J100
Figure 3-12 Size D2 Single Phase 230/460VAC Power Connections
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1L2
A1B1
A2B2
L1L2L3
Baldor
Series 15H
Control
Earth
Note 2
L1 Neutral
* Circuit
Breaker
A1
*Line
Reactor
A2
Notes:
1.See “Protective Devices” described previously in this section.
2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3.Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.See Line/Load Reactors described previously in this section.
L1L2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
A1B1
See Recommended Tightening Torques in Section 6.
3-16 Receiving & InstallationMN715
Size E Single Phase Power Installation
Place JP1 on the High Voltage Circuit Board across pins 1 and 2.
Figure 3-13 Jumper Configuration
Note 1
Note 3
Note 4
Note 3
* Circuit
Breaker
*Optional
Line
Reactor
JP1
Pins 1 & 2 = Single Phase
Pins 2 & 3 = Three Phase
1
JP1
Figure 3-14 Size E Single Phase 230/460VAC Power Connections
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1L2
A1B1
A2B2
L1L2L3
Baldor
Series 15H
Control
Earth
L1 Neutral
* Circuit
Breaker
A1
*Line
Reactor
A2
Notes:
1.See “Protective Devices” described previously in this section.
2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3.Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.See Line/Load Reactors described previously in this section.
L1L2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
A1B1
See Recommended Tightening Torques in Section 6.
Receiving & Installation 3-17MN715
Size F Single Phase Power Installation
Place JP2 on the High Voltage Circuit Board across pins 1 and 2.
Figure 3-16 Size F Single Phase 230/460VAC Power Connections
Note 1
Note 3
Note 4
* Circuit
Breaker
*Optional
Line
Reactor
L1L2
B1C1
B2C2
Earth
Figure 3-15 Jumper Configuration
JP2
1
JP2
Pins 1 & 2 = Single Phase
Pins 2 & 3 = Three Phase
Single phase 2 wire ConnectionsSingle phase 3 wire Connections
L1 Neutral
Note 2
* Circuit
Breaker
A1
*Line
Reactor
A2
L1L2
* Fuse
Connection
Note 1
* Optional components
not provided with control.
A1B1
Note 3
L1L2L3
Baldor
Series 15H
Control
Notes:
1.See “Protective Devices” described previously in this section.
2.Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3.Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4.See Line/Load Reactors described previously in this section.
See Recommended Tightening Torques in Section 6.
3-18 Receiving & InstallationMN715
Section 1General Information
Motor Brake Connections For motors with spring set brakes, connect the brake power leads and the motor power
leads separately. Because the inverter has variable voltage output to the motor, the
inverter may not supply enough power at low frequencies for proper brake operation. If
using a motor with an internally connected brake, the brake power leads must be
connected to a separate power source for proper brake operation.
Motor ConnectionsMotor connections are shown in Figure 3-17.
Figure 3-17 Motor Connections
Notes:
1.Metal conduit should be used. Connect conduits so the use of Load
Baldor
Series 15H
Control
T1T2T3
Note 1
A1B1C1
Reactor or RC Device does not interrupt EMI/RFI shielding.
2.See Line/Load Reactors described previously in this section.
3.Use same gauge wire for Earth ground as for L1, L2 and L3.
Note 2
Note 1
*Optional
Load
Reactor
A2B2C2
T2 T3
T1
G
* Optional components not provided with control.
Note 3
See Recommended Tightening Torques in Section 6.
* AC Motor
M-ContactorIf required by local codes or for safety reasons, an M-Contactor (motor circuit contactor)
may be installed. However, incorrect installation or failure of the M-contactor or wiring
may damage the control. If an M-Contactor is installed, the control must be disabled for
at least 20msec before the M-Contactor is opened or the control may be damaged.
M-Contactor connections are shown in Figure 3-18.
Figure 3-18 M-Contactor Diagram
T1T2T3
MMM
M=Contacts of optional M-Contactor
T2 T3
T1
* Motor
To Power Source
(Rated Coil Voltage)
J4
*
M Enable
G
7
Note: Close “Enable”
8
after “M” contact closure.
9
* M-Contactor
See Recommended Tightening Torques in Section 6.
* Optional
RC Device
Electrocube
RG1781-3
Receiving & Installation 3-19MN715
Loading...
+ 93 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.