Baldor ID15J202-ER, ID15J101-ER, ID15J1F33-ER, ID15J1F75-ER, ID15J201F5-ER Installation And Operating Manual

...
Series 15J
Inverter Control
7/04 MN715J
Installation and Operating Manual
Table of Contents
MN715J Table of Contents i
Quick Start 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Start Checklist 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power-up Procedure 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CE Compliance 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Limited Warranty 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Notice 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Receiving and Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Receiving & Inspection 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Remote Keypad Installation 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Installation 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Grounding 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Impedance 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Reactors 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load Reactors 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Current Requirements 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cover Removal 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Identification 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Line Connections 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reduced Input Voltage Derating 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Disconnect 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protective Devices 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Three Phase Wire Size and Protection Devices 3-8. . . . . . . . . . . . . . . . . . .
3 Phase Installation 3-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115VAC 1 Phase Wire Size and Protection Devices 3-10. . . . . . . . . . . . . . . .
230VAC Single Phase Derating for Three Phase Controls 3-11. . . . . . . . . .
Motor Brake Connections 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Dynamic Brake Hardware 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inputs and Outputs 3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Inputs 3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Output 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay Outputs 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External Trip Input 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii Table of Contents MN715J
Selection of Operating Mode 3-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keypad Connection 3-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard Run 3 Wire Connection 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Speed Connection 3-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Pump 2 Wire Connection 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Pump 3 Wire Connection 3-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Process Control Connection 3-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Speed Analog 2 Wire Connection 3-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Speed Analog 3 Wire Connection 3-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EPOT 2 Wire Connection 3-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EPOT 3 Wire Connection 3-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pre-Operation Checklist 3-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power-up Procedure 3-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming and Operation 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation Examples 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating the Control from the Keypad 4-3. . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the Keypad JOG Command 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . .
Speed Adjustment using Local Speed Reference 4-4. . . . . . . . . . . . . . . . . .
Speed Adjustment using Arrow Keys 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Mode 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting Display Contrast 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Screens 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Log Access 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic Information Access 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Mode 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Blocks Access for Programming 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Parameter Values 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reset Parameters to Factory Settings 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Definitions 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Block Definitions 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
No Keypad Display - Display Contrast Adjustment 5-1. . . . . . . . . . . . . . . . . . . . . .
Wrong Language Selection 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic Information Access 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Access the Fault Log 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Clear the Fault Log 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Noise Considerations 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay and Contactor Coils 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wires between Controls and Motors 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Drive Situations 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Motor Considerations 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Signal Wires 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MN715J Table of Contents iii
Specifications and Product Data 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications: 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Conditions: 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keypad Display: 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Specifications: 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Inputs: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Output: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital Inputs: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Digital Outputs: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Indications: 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ratings 6-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Tightening Torque Specifications 6-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Dimensions 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A
Dynamic Brake Hardware A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B
Parameter Values B-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix C
Remote Keypad Mounting Template C-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv Table of Contents MN715J
Section 1 Quick Start
MN715J Quick Start 1-1
Overview
If you are an experienced user of Baldor controls, you are probably already familiar with the keypad programming and keypad operation methods. If so, this quick start guide has been prepared for you. This procedure will help get your system up and running in the keypad mode quickly and will allow motor and control operation to be verified. It assumes that the Control and Motor are correctly installed (see Section 3 for procedures) and that you have an understanding of the keypad programming & operation. It is not necessary to wire the terminal strip to operate in the Keypad mode (Section 3 describes how to wire the terminal strip). The quick start procedure is as follows:
1. Read the Safety Notice and Precautions in section 2 of this manual.
2. Mount the control. Refer to Section 3, “Physical Installation” procedure.
3. Connect AC power. Refer to Section 3, “AC Line Connections”.
4. Connect the motor. Refer to Section 3, “AC Line Connections”.
Quick Start Checklist Check of electrical items.
1. Verify that the AC line voltage at the source matches the control rating.
2. Inspect all power connections for accuracy, workmanship and tightness as well as compliance to codes.
3. Verify that the control and motor are grounded to each other and the control is connected to earth ground.
4. Check all signal wiring for accuracy.
5. Be certain all brake coils, contactors and relay coils have noise suppression. This should be an R-C filter for AC coils and reverse polarity diodes for DC coils. MOV type transient suppression is not adequate.
Check of Motors and Couplings
1. Verify freedom of motion of motor shaft.
2. Verify that all motor couplings are tight without backlash.
3. If holding brakes are used, verify they are properly adjusted to fully release and set to the desired torque value.
1-2 Quick Start MN715J
WARNING: Make sure that unexpected operation of the motor shaft during start
up will not cause injury to personnel or damage to equipment.
Power-up Procedure
1. Turn power on. Be sure no faults are displayed on the keypad display.
2. Set the Level 1 Input block, Operating Mode to “Keypad”.
3. Set the Level 2 Output Limits block, “MIN Output FREQ” parameter.
4. Set the Level 2 Output Limits block, “MAX Output FREQ” parameter.
5. If the desired peak current limit setting is not correct, set the Level 2 Output Limits block, “PK Current Limit” parameter as desired.
6. Enter the following motor data in the Level 2 Motor Data block parameters: Motor Rated Amps (FLA) Motor Rated Speed (base speed) Motor Rated Frequency (Nameplate)
7. If External Dynamic Brake hardware is used, set the Level 2 Brake Adjust block parameters as desired.
8. Set the Level 1 V/HZ Boost block, “V/HZ Profile” parameter for the correct V/Hz ratio for your application.
9. If the load is a high initial starting torque type, the torque boost and accel time may need to be increased. Set the Level 1 V/HZ Boost block, “Torque Boost” and the Level 1 Accel/Decel Rate block, “Accel Time #1” as required.
10. Select and program additional parameters to suit your application.
The control is now ready for use in keypad mode. The terminal strip wiring may be changed and different parameter values used for another operating mode.
Section 2 General Information
MN715J General Information 2-1
CE Compliance
A custom unit may be required, contact Baldor. Compliance to Directive 89/336/EEC is the responsibility of the system integrator. A control, motor and all system components must have proper shielding grounding and filtering as described in MN1383. Please refer to MN1383 for installation techniques for CE compliance.
Overview
The Baldor Series 15J control is a PWM inverter motor control. The control operates by converting AC line power into fixed DC power. The DC power is then pulse width modulated into synthesized three-phase AC line voltage for the motor. In this way, the control converts the fixed input frequency to variable output frequency to cause the motor to have variable speed operation.
The rated horsepower of the control is based on a NEMA design B four pole motor and 60Hz operation at nominal rated input voltage. If any other type of motor is used, or input voltage other than 230 or 460 VAC is applied to the input terminals, the control should be sized to the motor using the rated output current of the control.
The Baldor Series 15J control may be used in many different applications. It can be programmed to operate in a number of operating modes, PWM rates and output current levels for custom operation.
It is the responsibility of the user to determine the optimum operating mode for the application. These choices are programmed using the keypad as explained in the programming section of this manual.
Limited Warranty
For a period of two (2) years from the date of original purchase, BALDOR will repair or replace without charge controls and accessories which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized persons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied. This warranty is in lieu of any other warranty or guarantee expressed or implied. BALDOR shall not be held responsible for any expense (including installation and removal), inconvenience, or consequential damage, including injury to any person or property caused by items of our manufacture or sale. (Some states do not allow exclusion or limitation of incidental or consequential damages, so the above exclusion may not apply.) In any event, BALDOR’s total liability, under all circumstances, shall not exceed the full purchase price of the control. Claims for purchase price refunds, repairs, or replacements must be referred to BALDOR with all pertinent data as to the defect, the date purchased, the task performed by the control, and the problem encountered. No liability is assumed for expendable items such as fuses.
Goods may be returned only with written notification including a BALDOR Return Authorization Number and any return shipments must be prepaid.
2-2 General Information MN715J
Safety Notice:
This equipment contains voltages that may be as great as 1000 volts! Electrical shock can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts that are driven by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
PRECAUTIONS:
WARNING: Do not touch any circuit board, power device or electrical
connection before you first ensure that power has been disconnected and there is no high voltage present from this equipment or other equipment to which it is connected. Electrical shock can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
WARNING: Be sure that you are completely familiar with the safe operation of
this equipment. This equipment may be connected to other machines that have rotating parts or parts that are controlled by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start–up procedure or troubleshoot this equipment.
WARNING: Do not use motor overload relays with an automatic reset feature.
These are dangerous since the process may injure someone if a sudden or unexpected automatic restart occurs. If manual reset relays are not available, disable the automatic restart feature using external control wiring.
WARNING: This unit has an automatic restart feature that will start the motor
whenever input power is applied and a RUN (FWD or REV) command is issued and maintained. If an automatic restart of the motor could cause injury to personnel, the automatic restart feature should be disabled by changing the “Restart Auto/Man” parameter to MANUAL.
WARNING: Be sure the system is properly grounded before applying power. Do
not apply AC power before you ensure that grounds are connected. Electrical shock can cause serious or fatal injury.
WARNING: Do not remove cover for at least five (5) minutes after AC power is
disconnected to allow capacitors to discharge. Electrical shock can cause serious or fatal injury.
WARNING: Improper operation of control may cause violent motion of the
motor shaft and driven equipment. Be certain that unexpected motor shaft movement will not cause injury to personnel or damage to equipment. Peak torque of several times the rated motor torque can occur during control failure.
Continued on next page.
MN715J General Information 2-3
WARNING: Motor circuit may have high voltage present whenever AC power is
applied, even when motor is not rotating. Electrical shock can cause serious or fatal injury.
WARNING: Dynamic brake resistors may generate enough heat to ignite
combustible materials. Keep all combustible materials and flammable vapors away from brake resistors.
Caution: Suitable for use on a circuit capable of delivering not more than
5,000 RMS symmetrical amperes, at rated voltage.
Caution: Do not supply any power on the External Trip (motor thermostat)
leads at J4-17 or J4-18 as the control may be damaged. Use a dry contact type that requires no external power to operate.
Caution: Disconnect motor leads (T1, T2 and T3) from control before you
perform a “Megger” test on the motor. Failure to disconnect motor from the control will result in extensive damage to the control. The control is tested at the factory for high voltage / leakage resistance as part of Underwriters Laboratories Inc. requirements.
Caution: Do not connect AC power to the motor terminals T1, T2 and T3.
Connecting AC power to these terminals may result in damage to the control.
Caution: Baldor recommends not using “Grounded Leg Delta” transformer
power leads that may create ground loops. Instead, we recommend using a four wire Wye.
2-4 General Information MN715J
Section 3 Receiving and Installation
MN715J Receiving and Installation 3-1
Receiving & Inspection
The Series 15J Inverter Control is thoroughly tested at the factory and carefully packaged for shipment. When you receive your control, there are several things you should do immediately:
1. Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control.
2. Verify that the control you received is the same as listed on your purchase order.
3. If the control is to be stored for several weeks before use, be sure that it is stored in a location that conforms to published storage specifications. (Refer to Section 6 of this manual).
Physical Installation
The mounting location of the 15J is important. It should be installed in an area that is protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration. Exposure to these elements can reduce the operating life and degrade performance of the control.
Several other factors should be carefully evaluated when selecting a location for installation:
1. For effective cooling and maintenance, the control should be mounted on a smooth, non-flammable vertical surface. Table 3-1 lists the Watts Loss ratings for enclosure sizing.
2. At least two inches clearance must be provided on all sides for airflow.
3. Front access must be provided to allow the control cover to be opened or removed for service and to allow viewing of the Keypad Display.
4. Altitude derating. Up to 3300 feet (1000 meters), no derating required. Above 3300 feet, derate output current by 2% for each 1000 feet above 3300 feet.
5. Temperature derating. Up to 40°C, no derating required. Above 40°C, derate output current by 2% per °C above 40°C. Maximum ambient is 55°C.
Table 3-1 Series 15J Watts Loss Ratings
115VAC 230VAC 460VAC
2.5kHz PWM
7.5kHz PWM
2.5kHz PWM
7.5kHz PWM
2.5kHz PWM
7.5kHz PWM
17 Watts/
Amp
20 Watts/
Amp
17 Watts/
Amp
20 Watts/
Amp
19 Watts/
Amp
28 Watts/
Amp
Control Installation
The control must be securely fastened to the mounting surface. Use the four (4) mounting holes to fasten the control to the mounting surface or enclosure.
Shock Mounting
If the control will be subjected to levels of shock greater than 1G or vibration greater than 0.5G at 10 to 60Hz, the control should be shock mounted. Excessive vibration within the control could cause internal connections to loosen and cause component failure or electrical shock hazard.
3-2 Receiving and Installation MN715J
Optional Remote Keypad Installation
Note: Requires phone jack connector on the control board. Some models may not
have a phone jack installed. If the phone jack is not installed and you wish to connect a remote keypad, contact Baldor.
A separate keypad may be remotely mounted using an optional Baldor keypad extension cable (in addition to the keypad within the control). Keypad assembly (CBLSM015KP - 5 ft, CBLSM046KP - 15 ft or CBLSM091KP - 30 ft) comes complete with the extension cable and gasket required to mount it to an enclosure. When the keypad is properly mounted to a NEMA Type 4X indoor enclosure, it retains the Type 4X indoor rating.
Tools Required:
Center punch, tap handle, screwdrivers (Phillips and straight) and crescent wrench.
8-32 tap and #29 drill bit (for tapped mounting holes) or #19 drill (for clearance mounting holes).
1-
1
/4″ standard knockout punch (1-11/16″ nominal diameter).
RTV sealant.
(4) 8-32 nuts and lock washers.
Extended 8-32 screws (socket fillister) are required if the mounting
surface is thicker than 12 gauge and is not tapped (clearance mounting holes).
Remote keypad mounting template. A tear out copy is provided at the end of this manual for your convenience. (Photo copy or tear out.)
Mounting Instruction: For tapped mounting holes
1. Locate a flat 4 wide x 5.5 minimum height mounting surface. Material should have sufficient thickness (14 gauge minimum).
2. Place the template on the mounting surface or mark the holes as shown.
3. Accurately center punch the 4 mounting holes (marked A) and the large knockout (marked B).
4. Drill four #29 mounting holes (A). Thread each hole using an 8-32 tap.
5. Locate the 1-
1
/4″ knockout center (B) and punch using the manufacturers
instructions.
6. Debur knockout and mounting holes making sure the panel stays clean and flat.
7. Apply RTV to the 4 holes marked (A).
8. Assemble the keypad to the panel. Use 8-32 screws, nuts and lock washers.
9. From the inside of the panel, apply RTV over each of the four mounting screws and nuts. Cover a
3
/4″ area around each screw while making
sure to completely encapsulate the nut and washer.
MN715J Receiving and Installation 3-3
Mounting Instructions: For clearance mounting holes
1. Locate a flat 4 wide x 5.5 minimum high mounting surface. Material should have sufficient thickness (14 gauge minimum).
2. Place the template on the mounting surface or mark the holes as shown on the template.
3. Accurately center punch the 4 mounting holes (marked A) and the large knockout (marked B).
4. Drill four #19 clearance holes (A).
5. Locate the 1-
1
/4″ knockout center (B) and punch using the manufacturers
instructions.
6. Debur knockout and mounting holes making sure the panel stays clean and flat.
7. Apply RTV to the 4 holes marked (A).
8. Assemble the keypad to the panel. Use 8-32 screws, nuts and lock washers.
9. From the inside of the panel, apply RTV over each of the four mounting screws and nuts. Cover a
3
/4″ area around each screw while making
sure to completely encapsulate the nut and washer.
Electrical Installation
Interconnection wiring is required between the motor control, AC power source, motor, host control and any operator interface stations. Use listed closed loop connectors that are of appropriate size for the wire gauge being used. Connectors are to be installed using crimp tool specified by the manufacturer of the connector. Only Class 1 wiring should be used.
System Grounding
Baldor Controls are designed to be powered from standard three phase lines that are electrically symmetrical with respect to ground. System grounding is an important step in the overall installation to prevent problems. The recommended grounding method is shown in Figure 3-1.
Ungrounded Distribution System
With an ungrounded power distribution system it is possible to have a continuous current path to ground through the MOV devices. To avoid equipment damage, an isolation transformer with a grounded secondary is recommended. This provides three phase AC power that is symmetrical with respect to ground.
Input Power Conditioning
Baldor controls are designed for direct connection to standard three phase lines that are electrically symmetrical with respect to ground. Certain power line conditions must be avoided. An AC line reactor or an isolation transformer may be required for some power conditions.
S If the feeder or branch circuit that provides power to the control has
permanently connected power factor correction capacitors, an input AC line reactor or an isolation transformer should be connected between the power factor correction capacitors and the control.
3-4 Receiving and Installation MN715J
S If the feeder or branch circuit that provides power to the control has
power factor correction capacitors that are switched on line and off line, the capacitors must not be switched while the control is connected to the AC power line. If the capacitors are switched on line while the control is still connected to the AC power line, additional protection is required. TVSS (Transient Voltage Surge Suppressor) of the proper rating should be installed between the AC line reactor or an isolation transformer and the AC input to the control.
Line Impedance
The Baldor Series 15J control requires a minimum line impedance of 1%. The input impedance of the power lines can be determined as follows:
Measure the line to line voltage at no load and at full rated load. Use these measured values to calculate impedance as follows:
%Impedance +
(Volts
NoLoad
* Volts
FullLoad
)
(Volts
NoLoad
)
100
Line Reactors
3 phase line reactors are available from Baldor. The size of the line reactor to use is based on the maximum continuous load. If providing your own line reactor, use the following formula to calculate the minimum inductance required. Table 3-3 lists the input current required for this calculation.
L +
(V
L*L
0.01)
(I 3Ǹ 377)
Where: L Minimum inductance in henrys.
V
L-L
Input volts measured line to line.
0.01 Desired percentage of input impedance (1% shown). I Input current rating of control. 377 Constant used with 60Hz power.
Use 314 with 50Hz power.
Table 3-2 Recommended Line Reactors
230VAC, 60Hz, 3% Impendance 460VAC, 60Hz, 3% Impendance
Catalog No. HP Amps Inductance
(mH)
Catalog No. HP Amps Inductacne
(mH)
LRAC00401 1 4 3 LRAC00202 1 2 12 LRAC00801 1.5 8 1.15 LRAC00202 1.5 2 12 LRAC00801 2 8 1.15 LRAC00402 2 4 6.5 LRAC01201 3 12 1.25 LRAC00402 3 4 6.5 LRAC01801 5 18 0.8 LRAC00802 5 8 3.0
LRAC3501 7.5 25 0.5 LRAC01202 7.5 12 2.5
LRAC01802 10 18 1.5
Load Reactors
Line reactors may be used at the control output to the motor. When used this way, they are called Load Reactors. Load Reactors serve several functions.
S Protect the control from a short circuit at the motor. S Limit the rate of rise of motor surge currents. S Slow the rate of change of power the control delivers to the motor.
Load reactors should be installed as close to the control as possible.
MN715J Receiving and Installation 3-5
Figure 3-1 Recommended System Grounding
L1
AC Main Supply
Safety
Ground
Driven earth ground
rod (plant ground)
Four Wire
“Wye”
L1
L2
L3
Earth
L2L3 T1 T3
Line
Reactor
Load
Reactor
Route all 4 wires L1, L2, L3 and Earth
(ground) together in conduit or cable.
Route all 4 wires T1, T2, T3 and motor ground
together in conduit or shielded cable.
Connect all wires (including
motor ground) inside the
motor terminal box.
Ground per NEC and Local codes.
Note: A line reactor is recommended
and must be ordered separately.
Note: A load reactor is
recommended and must
be ordered separately.
Baldor Control
T2
Note: Use shielded cable for control
signal wires. Route control
signal wires in conduit. These
wires must be kept separate
from power and motor wires.
3-6 Receiving and Installation MN715J
Input Current Requirements
Table 3-3 Input Current Requirements for Stock Products
115VAC - 1f 230VAC - 3f 460VAC - 3f
Catalog
Numbers
Input
Amps
Catalog
Numbers
Input
Amps
Catalog
Numbers
Input
Amps
ID15J1F33-ER 3.5 ID15J201-ER 5.0 ID15J401-ER 2.5 ID15J1F50-ER 5.0 ID15J201F5-ER 7.0 ID15J401F5-ER 3.5 ID15J1F75-ER 7.5 ID15J202-ER 8.0 ID15J402-ER 4.0 ID15J101-ER 10.0 ID15J203-ER 11.0 ID15J403-ER 5.5
ID15J205-ER 15.0 ID15J405-ER 9.0
ID15J407-ER 10.0 ID15J410V-ER 13.0
Cover Removal
The cover is made of plastic and could be damaged during removal if handled roughly. Refer to Figure 3-2. Insert a screwdriver or small blade tool and pry cover outward as shown to release the side. When both sides are released, remove the cover.
Figure 3-2 Cover Removal
Use small screwdriver or suitable tool to pry cover slightly outward to release cover from catch.
Use small screwdriver or suitable tool to pry cover slightly outward to release cover from catch.
MN715J Receiving and Installation 3-7
Terminal Identification
The terminals for signal, AC power and motor connections are shown in Figure 3-3. Separate ground connections are provided for power and motor grounds.
Figure 3-3 Terminal Identification
J4 Control Terminal Strip
J5 Power Terminal Strip
Power GND
Motor GND
L1 L2 L3 T1 T2 T3R2
R1/ B+
120
Shown with cover removed.
Note: J5 is accessible with the cover on.
Keypad may be plugged in or removed while control is ON. If remote keypad is plugged into J5, the main keypad is automatically disabled.
J5 Connector for Optional Remote Keypad
AC Line Connections
Be sure all power to the control is disconnected before proceeding. If power has been applied to the control, wait at least 5 minutes after power disconnect for residual voltage across the bus capacitors to discharge.
Reduced Input Voltage Derating
All power ratings stated in Section 6 are for the nominal AC input voltages (115, 230, or 460). The power rating of the control must be reduced when operating at a reduced input voltage. The amount of reduction is the ratio of the voltage change.
Examples:
A 5hp, 230VAC control operating at 208VAC has a reduced power rating of
4.52hp.
5HP
208VAC 230VAC
+ 4.52hp
Likewise, a 5hp, 460VAC control operating at 380VAC has a reduced power rating of 4.13hp.
5HP
380VAC 460VAC
+ 4.13hp
Power Disconnect
A power disconnect should be installed between the input power service and the control for a fail-safe method to disconnect power. The control will remain in a powered-up condition until all input power is removed from the control and the internal bus voltage is discharged.
3-8 Receiving and Installation MN715J
Protective Devices
Recommended fuse sizes are based on the following: 115% of maximum continuous current for time delay. 150% of maximum continuous current for Fast or Very Fast action.
Note: These general size recommendations do not consider harmonic currents or
ambient temperatures greater than 40°C. Be sure a suitable input power protection device is installed. Use the
recommended fuses listed in Tables 3-4 and 3-5. Input and output wire size is based on the use of copper conductor wire rated at 75°C. The table is specified for NEMA B motors.
Fast Action Fuses: 230VAC, Buss KTN
460VAC, Buss KTS
Very Fast Action: 230VAC, Buss JJN
460VAC, Buss JJS
Time Delay Fuses: 230VAC, Buss FRN
460VAC, Buss FRS
Three Phase Wire Size and Protection Devices
Table 3-4 Three Phase Wire Size and Protection Devices 230VAC Controls
Control Power
I
nput Fuse
Wire G
auge
Control Power
Output Rating
Fast Acting Time Delay AWG mm
2
1 6 5 14 2.08
1.5 8 7 14 2.08 2 12 9 14 2.08 3 15 12 14 2.08 5 25 20 12 3.31
Table 3-5 Three Phase Wire Size and Protection Devices 460VAC Controls
Control Power
I
nput Fuse
Wire G
auge
Control Power
Output Rating
Fast Acting Time Delay AWG mm
2
1 3 2.5 14 2.08
1.5 4 3.5 14 2.08 2 5 4.5 14 2.08 3 8 6.3 14 2.08 5 12 10 14 2.08
7.5 17.5 15 14 2.08
10 20 17.5 12 3.31
Note: All wire sizes are based on 75°C copper wire, 1% line impedance. Higher
temperature, smaller gauge wire may be used per NEC and local codes. Recommended fuses are based on 40°C ambient, maximum continuous control output current and no harmonic current.
MN715J Receiving and Installation 3-9
3 Phase Installation
The AC power and motor connections are shown in Figure 3-4. The 15J control has electronic I
2
t motor overload protection. If motor overloads are desired, they should be sized according to the manufacturers specifications and installed between the motor and the T1, T2 and T3 terminals of the control. Refer to Figure 3-3 for terminal locations.
Figure 3-4 3 Phase AC Power and Motor Connections
L1 L2 L3
L1 L2 L3
Earth
* AC Motor
Note 2
Note 3
Baldor Series 15J Control
*Optional
Line Reactor
Note 1
Note 3
Note 3
A1 B1 C1
A2 B2 C2
T1 T2 T3
Note 4
T1
T2 T3
G
Notes:
1. See Protection Devices described in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a reactor or RC device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
* Optional components not
provided with 15J Control.
*Optional Fusing
3-10 Receiving and Installation MN715J
115VAC 1 Phase Wire Size and Protection Devices
Table 3-6 Wire Size and Protection Devices - 1 phase
I
nput Fuse
Wire G
auge
C
ontro
l O
utput
Rating HP
Fast Acting
Amps
Time Delay
Amps
AWG mm
2
0.33 10 10 14 2.08
0.5 10 10 14 2.08
0.75 15 10 14 2.08
1.0 20 15 14 2.08
Note: All wire sizes are based on 75°C copper wire, 1% line impedance. Higher
temperature, smaller gauge wire may be used per NEC and local codes. Recommended fuses are based on 40°C ambient, maximum continuous control output current and no harmonic current.
Figure 3-5 Single Phase AC Power and Motor Connections
L1 N
Earth
* AC Motor is not provided with control.
Baldor Series 15J Control
Metal conduit should be used to shield output wires (from T1, T2, T3 of control to T1, T2, T3 of motor).
T1 T2 T3
T1
T2 T3
G
Shield wires inside
a metal conduit.
Motor wire should be sized using the 3 phase information in Table 3Ć4.
* Optional components not
provided with 15J Control.
L1 L2 L3
*Optional Fusing
MN715J Receiving and Installation 3-11
230VAC Single Phase Derating for Three Phase Controls
Single phase AC input power can be used to power a three phase control. However, the continuous and peak current ratings of the control must be reduced by 35% (derated).
I
nput Fuse
Wire G
auge
C
ontro
l O
utput
Rating HP
Fast Acting
Amps
Time Delay
Amps
AWG mm
2
0.75 10 9 14 2.08 1 12 10 14 2.08
1.5 15 15 14 2.08 2 20 17.5 14 2.08 3 25 25 12 3.31
Note: All wire sizes are based on 75°C copper wire, 1% line impedance. Higher
temperature, smaller gauge wire may be used per NEC and local codes. Recommended fuses are based on 40°C ambient, maximum continuous control output current and no harmonic current.
Figure 3-6 Single Phase 230VAC Power and Motor Connections
L1 L2
L1 L2 L3
Earth
* AC Motor is not provided with control.
Baldor Series 15J Control
Metal conduit should be used to shield output wires (from T1, T2, T3 of control to T1, T2, T3 of motor).
T1 T2 T3
T1
T2 T3
G
Shield wires inside
a metal conduit.
Motor wire should be sized using the 3 phase information in Table 3Ć4.
* Optional components not
provided with 15J Control.
*Optional Fusing
3-12 Receiving and Installation MN715J
Motor Brake Connections
For motors with spring set brakes, connect the brake power leads and the motor power leads separately. Because the inverter has variable voltage output to the motor, the inverter may not supply enough power at low frequencies for proper brake operation. If using a motor with an internally connected brake, the brake power leads must be connected to a separate power source for proper brake operation.
Optional Dynamic Brake Hardware
Dynamic Brake (DB) Hardware must be installed on a flat, non-flammable, vertical surface for effective cooling and operation. See Figure 3-7 for terminal identification.
See Appendix A of this manual for additional information.
Note: Although not shown, metal conduit should be used to shield all power wires
and motor leads.
Figure 3-7 Wiring for RGA Assembly
See recommended Terminal Tightening Torques in Section 6.
* Optional Customer Supplied Fuse Protection Ć Subject to Local Codes
50/60 Hz 3 Phase Power
Motor GND
R1/B+
T3 T2
T1
L3 L2
L1
Power GND
GND
T1
T2
T3
* Optional Dynamic Brake Resistor
J5 Power Terminal Strip
DB Terminals
R1 R2
R2
* Motor
Optional hardware. Must be ordered separately.
MN715J Receiving and Installation 3-13
Inputs and Outputs (Refer to Figure 3-8). Analog Inputs
Two analog inputs are available: analog input #1 (J4-5 and J4-4) and analog input #2 (J4-7 and J4-8) as shown. Either analog input #1 or #2 may be grounded provided the common mode range is not exceeded. Either analog input may be selected in the Level 1 INPUT block, ANA CMD Select parameter value. Analog input #1 is selected if parameter value “Potentiometer” is selected. Analog input #2 is selected if parameter value “0-10Volts, 0-5 Volts, 4-20mA or 0-20mA” is selected.
Figure 3-8 Analog Inputs and Outputs
8 9
10
Analog Input 2Ć Analog Output 1Ć
J4
N.O.
Relay Common
N.C.
Analog Ground Analog Input 1 Pot Reference
Analog Input 2+
Analog Output 1+
1 2 3
4 5 6
7
5k
Command Pot
Programmable Relay Outputs
0Ć5VDC, 0Ć10VDC, 4Ć20mA or 0Ć20mA
0Ć5VDC, 0Ć10VDC, 4Ć20mA or 0Ć20mA
See recommended Terminal Tightening Torques in Section 6.
Analog Input #1
The single ended analog input #1 can be used when the controller is set to Standard Run, 7 Speed, Fan Pump 2 Wire, Fan Pump 3 Wire, Process Control, 3 SPD ANA 2Wire, 3 SPD ANA 3Wire, EPOT 2Wire or EPOT 3Wire (not Keypad).
The single ended analog input #1 can be used as a Speed command (Level 1 Input block, ANA CMD Select=Potentiometer).
Note: A potentiometer value of 5kW to 10kW, 0.5 watt may be used.
1. Connect the wires from the 5KW pot at the J4 terminal strip. One end of the pot is connected to J4-4 (analog ground) and the other end is connected to J4-6 (reference voltage).
2. Connect the wiper of the pot to J4-5. The voltage across terminals J4-4 and J4-5 is the speed command input.
Analog Input #2
Analog input #2 accepts a differential command 0-5VDC, 0-10VDC, 4-20 mA or 0-20 mA. The (Differential) command mode is defined in the Level 1 Input block ANA CMD Select parameter.
Note: Analog Input #2 can be used with Standard Run, 7 Speed, Fan Pump 2 Wire,
Fan Pump 3 Wire, Process Control, 3 SPD ANA 2Wire or 3 SPD ANA 3Wire, EPOT 2Wire or EPOT 3Wire (not Keypad).
1. Connect the Analog Input + wire to J4-7 and the - wire to J4-8.
2. If using a 0-20 mA or 4-20 mA command signal, “Level 1 Input block, ANA CMD Select” parameter should be set to 0-20 mA or 4-20 mA.
3-14 Receiving and Installation MN715J
Analog Output
One programmable analog output is provided at J4-10 and J4-9. The output is scaled 0 - 5 VDC, 0 - 10 VDC, 4-20mA or 0-20mA. The output function is programmed in the Level 1 Output block, Analog Out parameter value. The scaling of the output is programmed in the Level 1 Output block, Analog Scale.
Relay Outputs
One normally open (N.O.) and one normally closed (N.C.) relay contact is available at terminals J4-1, J4-2 and J4-3. J4-2 is relay common. The output is programmable in the Level 1 Output block, Relay Output parameter.
1. Connect the N.O. contact to another circuit by attaching the wires to J4-1 and J4-2.
2. Connect the N.C. contact to another circuit by attaching the wires to J4-3 and J4-2.
External Trip Input
Terminal J4-17 is available for connection to a normally closed thermostat or overload relay in some operating modes as shown in Figure 3-9. The thermostat or overload relay should be a dry contact type with no power available from the contact. If the motor thermostat or overload relay activates, the control will automatically shut down and give an external trip fault.
The optional relay (CR1) shown provides the isolation required. The N.O. contact is closed when power is applied to the relay and the motor is cold. Connect the external trip input wires to J4-17 and J4-18. Do not place these wires in the same conduit as the motor power leads.
To activate the external trip input, the external trip parameter in the Level 2 Protection Block must be set to “ON”.
Figure 3-9 External Trip Input Connection
T1 T2 T3
T1
T2
T3
G
* Motor
17 18
J4
Do not run these wires in same conduit as motor leads or AC power wiring.
Customer supplied source voltage
Motor Thermostat Leads
CR1
*
*
Optional hardware. Must be ordered separately.
See recommended terminal tightening torque in section 6.
Note: Add appropriately rated protective device
for AC relay (snubber) or DC relay (diode).
External or remote motor overload protection may be required by National Electrical Code or equivalent
MN715J Receiving and Installation 3-15
Selection of Operating Mode (and Connection Diagram)
Several operating modes are available that define the basic motor control setup and the operation of the input and output terminals. These operating modes are selected by programming the Operating Mode parameter in the Level 1 Input programming Block. Available operating modes include:
Keypad
Standard Run, 3 Wire
7 Speed
Fan Pump 2 Wire
Fan Pump 3 Wire
Process Control
3 Speed Analog 2 Wire
3 Speed Analog 3 Wire
Electronic Potentiometer 2 Wire
Electronic Potentiometer 3 Wire
Each mode requires connections to the J4 terminal strip (except that all J4 connections are optional in the keypad mode).
Note: J4-19 and J4-20 are not to be used. These terminals are reserved for
manufacturing use only.
3-16 Receiving and Installation MN715J
Keypad Connection
The Keypad operating mode allows the control to be operated from the keypad. In this mode, no control connection wiring is required. However, the Stop, Accel/Decel select and External Trip inputs may optionally be used. All other digital inputs are inactive. The analog output and relay outputs remain active at all times.
For operation in Keypad mode, set the Level 1 Input block, Operating Mode parameter to Keypad.
To use the Stop input, J4-13 must be connected and the Level 1 Keypad Setup block, LOC. Hot Start parameter must be set to ON. The Stop line is normally closed. When opened, the motor will COAST or REGEN to a stop depending upon the setting of Level 1 Keypad Setup block Keypad Stop Key parameter value. Closing the input will immediately start the motor if a run command was given before the stop line was opened.
The Accel/Decel select input is used to select ACC / DEC / S-CURVE group 1 or group 2. This connection is made at J4-14.
The External Trip input is used to cause a fault condition during a motor over-temperature condition. The External Trip input (J4-17) must be connected and the External Trip parameter in the Level 2 Protection block must be set to ON. When J4-17 is opened, the motor will coast to a stop and an External Trip fault will be displayed on the keypad display.
Figure 3-10 Keypad Connection Diagram
11
12
13
14 15 16 17 18
Accel/Decel Select
External Trip
J4
Input Common
Refer to Figure 3Ć9.
See recommended terminal tightening torques in Section 6.
Stop
Keypad Only Connection
J4-13 If J4-13 is connected, you must set Level 1 Keypad Setup block, LOC. Hot Start
parameter to “ON” to activate the opto input. CLOSED allows normal control operation. OPEN disables the control and the motor will coast or brake to a stop. The motor will restart when J4-13 closes after open.
J4-14 OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J4-17 If J4-17 is connected, you must set Level 2 Protection block, External Trip to
“ON” to activate the opto input. OPEN causes an external trip fault. The control will disable and the motor coasts to a stop. An external trip fault is displayed (also logged in the fault log). CLOSED allows normal operation.
Loading...
+ 62 hidden pages