Baldor FPX A02T, FPX A02S, FPX A015S, FP4 A02TB, FP4 A07TB Installation & Operating Manual

...
SERVO DRIVE
Servo Control
Installation & Operating Manual
Flex+Drive
2/03 MN1276
Table of Contents
General Information 1-1.............................................................
CE Compliance 1-1..............................................................
Limited Warranty 1-1.............................................................
Product Notice 1-2...............................................................
Safety Notice 1-2................................................................
Product Overview 2-1...............................................................
Receiving and Installation 3-1.......................................................
Receiving & Inspection 3-1.......................................................
Location Considerations 3-1......................................................
Mechanical Installation 3-1........................................................
Electrical Installation 3-2..........................................................
System Grounding 3-2.......................................................
Power Disconnect 3-4.......................................................
Protection Devices 3-4.......................................................
X1 Power Connections 3-5...................................................
X1 Motor Connections 3-10....................................................
M-Contactor 3-10............................................................
Motor Thermostat 3-11........................................................
X1 Dynamic Brake Resistor 3-11...............................................
X1 +24VDC Logic Supply 3-12.................................................
X3 Control Inputs & Digital I/O Connections 3-12.................................
Factory Installed Settings 3-15.................................................
Move to Buffer 1 Position 3-15.................................................
X6 RS232 / 485 Connections 3-17..............................................
X7 Simulated Encoder Output 3-20.............................................
X8 Resolver Feedback 3-21...................................................
X9 Encoder w/Hall Tracks 3-22.................................................
Switch Setting and Start-Up 4-1......................................................
Switch AS1 Settings 4-1..........................................................
Start-Up Procedure 4-3...........................................................
Power Off Checks 4-3.......................................................
Power On Checks 4-3.......................................................
Table of Contents iMN1276
Operation 5-1.......................................................................
Installing Software on your PC 5-1.................................................
Minimum system requirements 5-1............................................
Installation 5-1..............................................................
Host Ccommunications Setup 5-1..................................................
UsingTheSetupWizard 5-3......................................................
Set up Software 5-5..............................................................
Motor 5-6..................................................................
Control 5-6.................................................................
Operating Mode 5-7.........................................................
Current Parameter 5-8.......................................................
Velocity Parameter 5-8.......................................................
Positioning 5-9..................................................................
Software Triggered 5-9.......................................................
Hardware Triggered 5-9......................................................
Initialize Buffers 5-9.........................................................
Home 5-10......................................................................
Limit Switches 5-10...............................................................
Drift 5-11....................................................................
Autotune 5-11...............................................................
Main Menu Choice Descriptions 5-12................................................
File 5-12....................................................................
Edit 5-12....................................................................
Setup 5-12..................................................................
Tuning 5-13.................................................................
Watch 5-13..................................................................
Functions 5-13...............................................................
Motion 5-13.................................................................
Terminal 5-13................................................................
Windows 5-13...............................................................
PLC Program 5-14................................................................
Troubleshooting 6-1................................................................
ii Table of Contents MN1276
Specifications & Product Data 7-1....................................................
Identification 7-1.................................................................
Specifications 7-2...............................................................
24VDC Logic Power Input 7-4.................................................
Velocity Control 7-4..........................................................
Resolver Feedback 7-4......................................................
Simulated Encoder Output 7-4................................................
Encoder Input 7-5...........................................................
Serial Interface 7-5..........................................................
Optional Interface 7-5........................................................
Regeneration 7-5...........................................................
Dimensions 7-6.................................................................
CE Guidelines 8-1...................................................................
CE Declaration of Conformity 8-1..................................................
EMC -- Conformity and CE -- Marking 8-1...........................................
EMC Installation Instructions 8-3.................................................
Accessories and Options 9-1........................................................
Cables 9-1......................................................................
Connectors 9-1..................................................................
EMC AC Mains Filter 9-2.........................................................
Regeneration Resistor 9-4........................................................
CAN Bus 9-5....................................................................
Getting Started with CAN_OPEN 9-7...............................................
Identifiers and object list 9-10......................................................
Appendix A
Manual Tuning A-1..................................................................
Motor A-2.......................................................................
Control A-2.....................................................................
Operating Mode A-3.............................................................
Current Parameter A-4...........................................................
Velocity Parameter A-4...........................................................
Drift A-5........................................................................
Manual Tuning A-5...............................................................
Plotting of Move A-9.............................................................
Pulse Follower Applications A-10...................................................
Appendix B
Command Set B-1...................................................................
MN1276
Table of Contents iii
iv Table of Contents
MN1276
Section 1 General Information
Copyright Baldor ! 1999. All rights reserved. This manual is copyrighted and all rights are reserved. This document may not, in
whole or in part, be copied or reproduced in any form without the prior written consent of Baldor.
Baldor makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of fitness for any particular purpose. The information in this document is subject to change without notice. Baldor assumes no responsibility for any errors that may appear in this document.
Microsoft and MS--DOS are registered trademarks, and Windows is a trademark of Microsoft Corporation.
UL and cUL are registered trademarks of Underwriters Laboratories.
CE Compliance
A custom unit may be required, contact Baldor. Compliance to Directive 89/336/EEC is the responsibility of the system integrator. A control, motor and all system components must have proper shielding, grounding, and filtering as described in MN1383. Please refer to MN1383 for installation techniques for CE compliance. For additional information, refer to Sections 3 and 8 of this manual.
Limited Warranty
For a period of two (2) years from the date of original purchase, BALDOR will repair or replace without charge controls and accessories which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized persons, misused, abused, or improperly installed and hasbeenusedinaccordancewiththeinstructionsand/orratingssupplied. Thiswarranty is in lieu of any other warranty or guarantee expressed or implied. BALDOR shall not be held responsible for any expense (including installation and removal), inconvenience, or consequential damage, including injury to any person or property caused by items of our manufacture or sale. (Some states do not allow exclusion or limitation of incidental or consequentialdamages,sotheabove exclusionmaynotapply.) Inany event,BALDOR’s total liability, under all circumstances, shall not exceed the full purchase price of the control. Claims for purchase price refunds, repairs, or replacements must be referred to BALDOR with all pertinent data as to the defect, the date purchased, the task performed bythecontrol, andtheproblemencountered. Noliabilityisassumedforexpendableitems such as fuses.
Goods may be returned only with written notification including a BALDOR Return Authorization Number and any return shipments must be prepaid.
General Information 1-1MN1276
Product Notice Intended use:
These drives are intended for use in stationary ground based applications in industrial power installations according to the standards EN60204 and VDE0160. They are designed for machine applications that require variable speed controlled three phase brushless AC motors.
These drives are not intended for use in applications such as:
-- Home appliances
-- Medical instrumentation
-- Mobile vehicles
-- Sh i p s
-- Airplanes
Unless otherwise specified, this drive is intended for installation in a suitable enclosure. The enclosure must protect the control from exposure to excessive or corrosive moisture, dust and dirt or abnormal ambient temperatures. The exact operating specifications are found in Section 7 of this manual.
The installation, connection and control of drives is a skilled operation, disassembly or repair must not be attempted.
In the event that a control fails to operate correctly, contact the place of purchase for return instructions.
Safety Notice: This equipment contains high voltages. Electrical shock can cause serious or fatal
injury. Only qualified personnel should attempt the start--up procedure or troubleshoot this equipment.
This equipment may be connected to other machines that have rotating parts or parts that are driven by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt the start--up procedure or troubleshoot this equipment.
-- System documentation must be available at all times.
-- Keep non-qualified personnel at a safe distance from this equipment.
-- Only qualified personnel familiar with the safe installation, operation and maintenance of this device should attempt start-up or operating procedures.
-- Always remove power before making or removing any connections to this control.
PRECAUTIONS: Classifications of cautionary statements.
WARNING: Indicates a potentially hazardous situation which, if not avoided,
could result in injury or death.
Caution: Indicates a potentially hazardous situation which, if not avoided,
could result in damage to property.
1-2 General Information MN1276
PRECAUTIONS:
WARNING: Do not touch any circuit board, power device or electrical
connection before you first ensure that power has been disconnected and there is no high voltage present from this equipment or other equipment to which it is connected. Electrical shock can cause serious or fatal injury.
WARNING: Be sure that you are completely familiar with the safe operation
of this equipment. This equipment may be connected to other machines that have rotating parts or parts that are controlled by this equipment. Improper use can cause serious or fatal injury.
WARNING: Be sure all wiring complies with the National Electrical Code and
all regional and local codes or CE Compliance. Improper wiring may cause a hazardous condition.
WARNING: Be sure the system is properly grounded before applying power.
Do not apply AC power before you ensure that grounds are connected. Electrical shock can cause serious or fatal injury.
WARNING: Do not remove cover for at least five (5) minutes after AC power
is disconnected to allow capacitors to discharge. Electrical shock can cause serious or fatal injury.
WARNING: Improper operation of control may cause violent motion of the
motor shaft and driven equipment. Be certain that unexpected motor shaft movement will not cause injury to personnel or damage to equipment. Peak torque of several times the rated motor torque can occur during control failure.
WARNING: Motor circuit may have high voltage present whenever AC power
is applied, even when motor is not rotating. Electrical shock can cause serious or fatal injury.
WARNING: If a motor is driven mechanically, it may generate hazardous
voltages that are conducted to its power input terminals. The enclosure must be grounded to prevent a possible shock hazard.
WARNING: When operating a motor with no load coupled to its shaft,
remove the shaft key to prevent injury if it were to fly out when the shaft rotates.
WARNING: The motor shaft will rotate during the autotune procedure. Be
certain that unexpected motor shaft movement will not cause injury to personnel or damage to equipment.
WARNING: A DB Resistor may generate enough heat to ignite combustible
materials. To avoid fire hazard, keep all combustible materials and flammable vapors away from brake resistors.
WARNING: The user must provide an external hard-wired emergency stop
circuit to disable the control in the event of an emergency.
Caution: To prevent equipment damage, be certain that the input power has
correctly sized protective devices installed as well as a power disconnect.
Continued on next page.
MN1276
General Information 1-3
Caution: Suitable for use on a circuit capable of delivering not more than the RMS
symmetrical short circuit amperes listed here at rated voltage. Horsepower
RMS Symmetrical Amperes
1--50 5,000
Caution: Avoid locating control immediately above or beside heat generating
equipment, or directly below water or steam pipes.
Caution: Avoid locating control in the vicinity of corrosive substances or vapors,
metal particles and dust.
Caution: For UL installations, do not connect any resolver cable shields to the
motor frame. At a minimum, resolver signal integrity will be compromised and damage to the control may result. For CE installations, refer to CE guidelines stated in Sections 3 and 8 of this manual.
Caution: Do not connect AC power to the control terminals U, V and W. Connecting
AC power to these terminals may result in damage to the control.
Caution: Baldor recommends not using “Grounded Leg Delta” transformer power
leads that may create ground loops and degrade system performance. Instead, we recommend using a four wire Wye.
Caution: Logic signals are interruptible signals; these signals are removed when
power is removed from the drive.
Caution: Controls are intended to be connected to a permanent main power source,
not a portable power source. Suitable fusing and circuit protection devices are required.
Caution: The safe integration of the drive into a machine system is the
responsibility of the machine designer. Be sure to comply with the local safety requirements at the place where the machine is to be used. In Europe this is the Machinery Directive, the ElectroMagnetic Compatibility DirectiveandtheLowVoltageDirective.IntheUnitedStatesthisisthe National Electrical code and local codes.
Caution: Controls must be installed inside an electrical cabinet that provides
environmental control and protection. Installation information for the drive is provided in this manual. Motors and controlling devices that connect to the drive should have specifications compatible to the drive.
Caution: Violent jamming (stopping) of the motor shaft during operation may
damage the motor and control.
Caution: Do not tin (solder) exposed wires. Solder contracts over time and may
cause loose connections.
Caution: Electrical components can be damaged by static electricity. Use ESD
(electro-static discharge) procedures when handling this control.
Caution: Ensure that resolver or encoder wires are properly connected. Incorrect
installation may result in improper rotation or incorrect commutation.
Caution: The holes in the top and bottom of the enclosure are for cable clamps. Be
sure to use an M4 bolt 12mm in length. Longer bolts may short circuit the electrical components inside the control.
1-4 General Information
MN1276
Section 2 Product Overview
Overview The Flex+Drive product is designed to serve the needs of machine designers and
manufacturers. Baldor products have both UL and CE approvals. The Flex+Drive is a “flexible” versatile compact control for brushless servo motors. This digital servo control can be tailored to suit many applications. It can accept 0--10VDC input, standard "10VDC input, current loop input, electronic handwheel input or 15 preset point to point moves.
Some flexible options are CAN bus interface (for resolver feedback only), internal or external regen, or with customer provided 24VDC to maintain logic power.
The Flex+Drive can be integrated with Baldors’ motion controllers or to any industry standard motion controller.
Motors Baldor servo controls are compatible with many motors from Baldor and other
manufacturers. Motor parameters are provided with the PC software making the setup easy. Baldor compatible motors include:
S BSM--A--Series motors S BSM--B--Series motors S BSM--F--Series motors S BSM--N--Series motors
Refer to the Speed/Torque curves in the BR1202 catalog or contact your local Baldor distributor or sales representative for assistance with motor sizing and compatibility. Custom motors or motors not manufactured by Baldor may be used. Please contact your local Baldor distributor or sales representative for assistance.
Command Source
In the analog mode (current or velocity), the control requires a variable 0-10VDC or "10VDC external analog signal. Suitable sources can be a PLC or motion controller.
Positioning Mode
In the positioning mode, up to 15 preset repeatable positions (moves) may be defined in software. These moves may either be incremental, absolute or mixed. A specific “preset” position is selected using the switch inputs (machine inputs 1--4) and a “trigger” input activates the move. A home position could also be set if desired.
Serial Communications Interface
A serial port allows external communication. This means that the Flex+Drive can interface to a PC (for configuration and control) or to other user--supplied equipment such as:
S Host computers S PLC’s S PC’s S Motion controllers
The serial communication interface supports:
S RS232 and the four wire RS--485 communication standards S Baud rate: 9600
Product Overview 2-1MN1276
Control Inputs Opto isolated inputs are single ended, user selectable and active high or low:
Enable Machine Input 1 Quit Machine Input 2 Fault Reset Machine Input 3 Home Flag Machine Input 4 Trigger
Control Outputs
One normally closed relay contact provides a dedicated “Drive Ready” output. Two opto isolated outputs are single ended, active low and are current sinking.
Either output can be assigned to one of the following:
In Position Machine Input 1 CW Warning Machine Input 2 CCW Warning Machine Input 3 Following Error Flag Machine Input 4 Following Error Warning Drive Over Temperature
2
t Warning
I
Simulated Encoder Output
Resolver Feedback
The resolver feedback signal is converted to PPR (pulses per revolution) by a Resolver to Digital Converter. A position controller uses position feedback
The resolution of the simulated encoder output is software controlled with the following available resolutions:
512 PPR, 1024 PPR, 2048 PPR or 4096 PPR
Note: For speeds above 6000 RPM, resolution is limited to 1024PPR maximum.
Encoder Feedback
When encoder feedback is used, the encoder input signal is buffered and provided at the simulated encoder output.
2-2 Product Overview MN1276
Section 3 Receiving and Installation
Receiving & Inspection Baldor Controls are thoroughly tested at the factory and carefully
packaged for shipment. When you receive your control, there are several things you should do immediately.
1. Observe the condition of the shipping container and report any damage immediately to the commercial carrier that delivered your control.
2. Remove the control from the shipping container and remove all packing materials. The container and packing materials may be retained for future shipment.
3. Verify that the part number of the control you received is the same as the part number listed on your purchase order.
4. Inspect the control for external physical damage that may have been sustained during shipment and report any damage immediately to the commercial carrier that delivered your control.
5. If the control is to be stored for several weeks before use, be sure that it is stored in a location that conforms to published storage humidity and temperature specifications stated in this manual.
Location Considerations The location of the control is important. Installation should be in an area
that is protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic particles, and vibration. Exposure to these can reduce the operating life and degrade performance of the control.
Several other factors should be carefully evaluated when selecting a location for installation:
1. For effective cooling and maintenance, the control should be mounted on a smooth, non-flammable vertical surface.
2. At least 0.6 inches (15mm) top and bottom clearance must be provided for air flow. At least 0.4 inches (10mm) clearance is required between controls (each side).
3. Altitude derating. Up to 3300 feet (1000 meters) no derating required. Derate the continuous and peak output current by 1.1% for each 330 feet (100 meters) above 3300 feet.
4. Temperature derating.From0#Cto40#C ambient no derating required. Above 40#C, derate the continuous and peak output current by
2.5% per #C above 40#C. Maximum ambient is 50#C.
5. The control must be installed where the pollution degree according to IEC664 shall not exceed 2.
Mechanical Installation
Mount the control to the mounting surface. The control must be securely fastened to the mounting surface by the control mounting holes. The location of the mounting holes is shown in Section 7 of this manual.
Receiving & Installation 3-1MN1276
Electrical InstallationAll interconnection wires between the control, AC power source, motor, host
control and any operator interface stations should be in metal conduits. Use listed closed loop connectors that are of appropriate size for wire gauge being used. Connectors are to be installed using crimp tool specified by the manufacturer of the connector. Only class 1 wiring should be used.
System Grounding Baldor controls are designed to be powered from standard single and three
phase lines that are electrically symmetrical with respect to ground. System grounding is an important step in the overall installation to prevent problems. The recommended grounding method is shown in Figure 3-1 and 3-3 for UL compliant systems (Figure 3-2 and 3-4 for CE compliant systems).
Figure 3-1 Recommended System Grounding (3 phase) for UL
L1
AC Main Supply
Safety
Ground
Driven Earth Ground Rod
(Plant Ground)
Note: Use shielded cable for control signal wires. Route
control signal wires in conduit. These wires must be kept separate from power and motor wires.
L2
L3 Earth
Four Wire
“Wye”
Route all power wires L1, L2, L3 and Earth (Ground) together in conduit or cable.
Figure 3-2 Recommended System Grounding (3 phase) for CE
AC Main Supply
Four Wire
“Wye”
Safety
Ground
PE
L1
L2
L3
Route all power wires L1, L2, L3 and Earth (Ground) together in conduit or cable.
Control
VL1 L2 L3 U WPE
Ground per NEC and Local codes.
Control
VL1 L2 L3 U WPE
Note: Wiring shown for clarity of grounding method only. Not representative of actual terminal block location.
Note: Wiring shown for clarity of grounding method only. Not representative of actual terminal block location.
Motor
GND
All shields
Note: Use shielded cable for control signal wires. Route
control signal wires in conduit. These wires must be kept separate from power and motor wires.
Enclosure Backplane (see Section 8)
3-2 Receiving & Installation MN1276
AC Main Supply
Figure 3-3 Recommended System Grounding (1 phase) for UL
L
Control
N
VLN U W
Note: Wiring shown for clarity of grounding method only. Not representative of actual terminal block location.
Safety
Ground
Driven Earth Ground Rod
(Plant Ground)
Note: Use shielded cable for control signal wires. Route
control signal wires in conduit. These wires must be kept separate from power and motor wires.
Earth
Route all 3 wires L, N, and Earth (Ground) together in conduit or cable.
Figure 3-4 Recommended System Grounding (1 phase) for CE
AC Main Supply
Four Wire
“Wye”
Safety
Ground
PE
L1
L2
L3
Neutral
Route all power wires together in conduit or cable.
Ground per NEC and Local codes.
Control
VLN U W
Note: Wiring shown for clarity of grounding method only. Not representative of actual terminal block location.
Motor
GND
All shields
Note: Use shielded cable for control signal wires. Route
control signal wires in conduit. These wires must be kept separate from power and motor wires.
MN1276
Enclosure Backplane (see Section 8)
Receiving & Installation 3-3
System Grounding
Continued
Ungrounded Distribution System
With an ungrounded power distribution system it is possible to have a continuous current path to ground through the MOV devices. To avoid equipment damage, an isolation transformer with a grounded secondary is recommended. This provides three phase AC power that is symmetrical with respect to ground.
Input Power Conditioning
Baldor controls are designed for direct connection to standard single and three phase lines that are electrically symmetrical with respect to ground. Certain power line conditions must be avoided. An AC line reactor or an isolation transformer may be required for some power conditions.
$ If the feeder or branch circuit that provides power to the control has
permanently connected power factor correction capacitors, an input AC line reactor or an isolation transformer must be connected between the power factor correction capacitors and the control.
$ If the feeder or branch circuit that provides power to the control has
power factor correction capacitors that are switched on line and off line, the capacitors must not be switched while the control is connected to the AC power line. If the capacitors are switched on line while the control is still connected to the AC power line, additional protection is required. TVSS (Transient Voltage Surge Suppressor) of the proper rating must be installed between the AC line reactor or an isolation transformer and the AC input to the control.
Power Disconnect A power disconnect should be installed between the input power service
and the control for a fail--safe method to disconnect power. The control will remain in a powered-up condition until all input power is removed from the control and the internal bus voltage is depleted.
Protection Devices The control must have a suitable input power protection device installed.
Input and output wire size is based on the use of copper conductor wire r ated at 75 #C. Table 3-1 and 3-2 describes the wire size to be used for power connections and the ratings of the protection devices. Use the recommended circuit breaker or fuse types as follows:
Circuit Breaker: 1 phase, thermal magnetic.
Equal to GE type THQ or TEB for 115 or 230 VAC 3 phase, thermal magnetic.
Equal to GE type THQ or TEB for 230 VAC or GE type TED for 460 VAC.
Time Delay Fuses: Buss FRN on 230 VAC or
Buss FRS on 460 VAC or equivalent.
Recommended fuse sizes are based on the following:
UL 508C suggests a fuse size of four times the continuous output current of the control. Dual element, time delay fuses should be used to avoid nuisance trips due to inrush current when power is first applied.
For European installations, you may want to consider the following fast acting fuse: Gould Shawmut Cat. No. ATMR15 for up to 15 amperes.
3-4 Receiving & Installation
MN1276
Table 3-1 Wire Size and Protection Devices (for units with Power Supply)
g
Input
W
ireG
NominalInpu
t
CatalogNumb
W
ireG
g
Continuou
s
Catalog Number Incoming Power
Input Fuse
Time
Delay (A)
AWG
(USA)
FP1A02SR-XXXX FP2A02SR-XXXX FP1A02TR-XXXX FP2A02TR-XXXX FP4A02TB-XXXX FP1A05SR-XXXX FP1A05SR-XXXX FP1A05TR-XXXX FP2A05TR-XXXX FP4A05TB-XXXX FP1A07TR-XXXX FP2A07TR-XXXX FP4A07TR-XXXX FP1A10SR-XXXX FP2A10SR-XXXX FP1A15SR-XXXX
FP2A15SR-XXXX FP4A15TR-XXXX FP4A20TR-XXXX FP4A27TR-XXXX
Nominal Input
Voltage
115V (1Ô) 230V (3Ô) 115V (1Ô) 230V (1Ô)
400/460V (3Ô)
115V (1Ô) 230V (3Ô) 115V (1Ô) 230V (1Ô)
400/460V (3Ô)
115V (1Ô) 230V (1Ô)
400/460V (3Ô)
115V (1Ô) 230V (3Ô) 115V (1Ô)
230V (3Ô) 400/460V (3Ô) 400/460V (3Ô) 400/460V (3Ô)
Continuous
Output
(RMS)
Amps
2.0A 7.5 8 14 2.5
2.5A 7 4.5 14 2.5
2.0A 7.5 8 14 2.5
2.5A 5 4.5 14 2.5
2.5A 7 4 14 2.5 5A 7.5 8 14 2.5 5A 7 8 14 2.5 5A 7.5 8 14 2.5 5A 7.5 7 14 2.5 5A 7 7.5 14 2.5
7.5A 10 10 14 2.5
7.5A 10 10 14 2.5
7.5A 15 12 14 2.5
10A 12.5 15 14 2.5 10A 15 15 14 2.5 15A 20 20 12 2.5
15A 20 25 12 2.5 15A 20 20 12 2.5 20A 30 35 10 5.26
27.5A 40 45 10 5.26
Input
Breaker
(A)
auge
mm
(Europe)
2
Table 3-2 Wire Size (for units without Power Supply)
er
Bus
Voltage
FP1A02PO-xxxx 160VDC 2.0A 14 2.5 FP2A02PO-xxxx 300VDC 2.5A 14 2.5 FP1A05PO-xxxx 160VDC 5.0A 14 2.5 FP2A05PO-xxxx 300VDC 5.0A 14 2.5 FP1A10PO-xxxx 160VDC 10.0A 12 2.5 FP2A10PO-xxxx 300VDC 10.0A 12 2.5 FP1A15PO-xxxx 160VDC 15.0A 10 2.5 FP2A15PO-xxxx 300VDC 15.0A 10 2.5
Continuous
Output
Amps
AWG
(USA)
Note: All wire sizes are based on 75#C copper wire. Higher temperature smaller gauge wire may
be used per NEC and local codes. Recommended fuses/breakers are based on 25 # C ambient, maximum continuous control output current and no harmonic current.
X1 Power Connections
Power connections are shown in Figures 3-5 through 3-8.
MN1276
auge
mm
(Europe)
2
Receiving & Installation 3-5
Figure 3-5 Single Phase AC Power Connections (FP1AxxT & FP2AxxT only)
L1 L2
L1 L2
Note 1
Note 2
* Circuit Breaker
Earth
Note 3 & 4
Alternate *
Fuse
Connection
Note 1
LN
Baldor
Control
For CE Compliance, refer to Section 8 of this manual.
Figure 3-6 Single Phase AC Power Connections (FP1AxxS only)
L1 L2
Earth
Note 1
Note 2
For CE Compliance, refer to Section 8 of this manual.
* Circuit Breaker
L1 L2 L3
Baldor
Control
Note 3 & 4
PE
* Components not provided with Control.
Notes:
1. See “Protection Devices” described in this section.
2. Metal conduit or shielded cable should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
3. Use same gauge wire for Earth ground as is used for L and N. (VDE (Germany) requires 10mm Compliance, connect tothe backplane of the enclosure.
4. Reference EMC wiring in Section 8.
2
minimum). For CE
L1 L2
Alternate *
Fuse
Note 1
Connection
* Components not provided with Control.
Notes:
1. See “Protection Devices” described in this section.
2. Metal conduit or shielded cable should be used. Connect conduits so the use of a Reactor or RC Device does not interrupt EMI/RFI shielding.
3. Use same gauge wire for Earth ground as is used for L and N. (VDE (Germany) requires 10mm Compliance, connect tothe backplane of the enclosure.
4. Reference EMC wiring in Section 8.
2
minimum). For CE
Note: These Flex+Drive versions are not designed for use with 400/460VAC
connections.
3-6 Receiving & Installation
MN1276
Figure 3-7 3 Phase Power Connections (FP2AxxS & FP4AxxT only)
L1 L2 L3
Earth
Note 1
Note 2
For CE Compliance, refer to Section 8 of this manual.
* Circuit Breaker
L1 L2 L3
PE
Baldor
Control
A shared supply configuration is shown in Figure 3-8. The first drive must have an internal power supply such as an Option “S” control.
L1 L2 L3
Note 3 & 4
Notes:
1. See Protection Device description in this section.
2. Metal conduit or shielded cable should be used. Connect conduitsso theuse ofa Reactoror RC Devicedoes notinterrupt EMI/RFI shielding.
3. Use the same gauge wire for Earth as used for L1, L2, L3 connections.
3. Use same gauge wire for Earth ground as is used for L and N. (VDE (Germany) requires 10mm compliance, connect “PE” to the backplane of the enclosure.
4. Reference EMC wiring in Section 8.
Alternate *
Fuse
Connection
A1 B1 C1
Note 1
* Components not provided with Control.
2
minimum). For CE
Figure 3-8 Shared Supply Power Connections
VCC+
VCC-
R1
R2
Baldor
Option S
Control
To
Regen
Resistor
VCC+
VCC-
VCC+
VCC-
Baldor
Option P
Control
VCC+
VCC-
VCC+
Baldor
Option P
Control
VCC-
MN1276
Receiving & Installation 3-7
Figure 3-9 Connector Locations (Single Phase Controls)
X1 - Power Connector
Earth
LACLine N Neutral U Motor lead “U” V Motor lead “V” W Motor lead “W” R1 Dynamic Brake R2 Dynamic Brake +24V Customer 0V Provided
Terminal tightening torque is
0.5 lb-in (0.6Nm)
X3 - Control Signals & Digital I/O
1CMD+ 2CMD­3AGND 4 Fault Relay+ 5 Fault Relay-­6CIV 7 CREF 8CGND 9 Enable 10 MaI3 11 MaI4 12 Quit 13 Fault Reset 14 Home Flag 15 Trigger 16 MaI1 17 MaI2 18 MaO1 19 MaO2 20 DrOK
Input Power
Motor
Dynamic Brake (Regen Resistor)
FPxAxxxx-xxx3 only ¡
NC
L
N U
V
W R1 R2
+24V
0V
DB On
X1
AS1
Off/On
Ready
Monitor
1 2 3
4 5
6 7 8
The holes in the top and bottom of the enclosure are for cable clamps. Be sure to use an M4 bolt 12mm in length. Longer bolts may short circuit the electrical components inside the control.
X9 - Encoder Feedback Option
(only --Exxx versions)
1 CHA+ 9 HALL3+ 2 CHB+ 10 HALL2+ 3 CHC+ 11 +5VDC 4 HALL1+ 12 N.C. 5 HALL1-- 13 DGND 6 CHA-- 14 HALL3--
Encoder In X9RS232 / 485 X6Encoder Out X7Resolver In X8
7 CHB-- 15 HALL2-­8 CHC--
X6 - RS232 / 485
RS232
1 Reserved 1 TX-
Data 2 TX+
2R
x
3T
Data 3 RX+
x
4DTR 4RX­5 DGND 5 DGND 6DSR 6RTS­7RTS 7RTS+ 8CTS 8CTS+ 9+5V 9CTS-
X7 - Simulated Encoder Output
1 CHA 6 CHA-­2 CHB 7 CHB-­3 CHC 8 CHC-­4 Reserved 9 Reserved 5DGND
X8 - Resolver Input
1REF 6REF-­2COS 7COS-­3SIN 8SIN-­4 Reserved 9 Reserved 5AGND
RS485
Important:
¡
FPxAxxxx-xxx3 only. A separate 24VDC supply to the “Logic Power” input is required for operation. An FPxAxxxx-xxx3 control will not operate without 24VDC on this input.
3-8 Receiving & Installation
X3
Note: Reserved means no
connection is required and no connection should be made to this terminal. It is reserved for future use.
MN1276
Figure 3-10 Connector Locations (Three Phase Controls)
X1 - Power Connector
PE Earth L1 Phase 1 Input L2 Phase 2 Input L3 Phase 3 Input U Motor lead “U” V Motor lead “V” W Motor lead “W” R1 Dynamic Brake R2 Dynamic Brake +24V Customer 0V Provided
Terminal tightening torque is
0.5 lb-in (0.6Nm)
X3 - Control Signals & Digital I/O
1CMD+ 2CMD­3AGND 4 Fault Relay+ 5 Fault Relay-­6CIV 7 CREF 8CGND 9 Enable 10 MaI3 11 MaI4 12 Quit 13 Fault Reset 14 Home Flag 15 Trigger 16 MaI1 17 MaI2 18 MaO1 19 MaO2 20 DrOK
Input Power
Motor
Dynamic Brake (Regen Resistor)
FPxAxxxx-xxx3 only ¡
The holes in the top and bottom of the enclosure are for cable clamps. Be sure to use an M4 bolt 12mm in length. Longer bolts may short circuit the electrical components inside the control.
X9 - Encoder Feedback Option
(only --Exxx versions)
1 CHA+ 9 HALL3+ 2 CHB+ 10 HALL2+ 3 CHC+ 11 +5VDC 4 HALL1+ 12 N.C. 5 HALL1-- 13 DGND 6 CHA-- 14 HALL3-­7 CHB-- 15 HALL2-­8 CHC--
X6 - RS232 / 485
RS232
1 Reserved 1 TX-
Data 2 TX+
2R
x
Data 3 RX+
3T
x
4DTR 4RX­5 DGND 5 DGND 6DSR 6RTS­7RTS 7RTS+ 8 CTS 8 CTS+ 9 +5V 9 CTS-
X7 - Simulated Encoder Output
1 CHA 6 CHA-­2 CHB 7 CHB-­3 CHC 8 CHC-­4 Reserved 9 Reserved 5DGND
X8 - Resolver Input
1 REF 6 REF-­2 COS 7 COS-­3SIN 8SIN-­4 Reserved 9 Reserved 5AGND
RS485
¡ Important:
FPxAxxxx-xxx3 only. A separate 24VDC supply to the “Logic Power” input is required for operation. An FPxAxxxx-xxx3 control will not operate without 24VDC on this input.
MN1276
Note: Reserved means no connection is required
and no connection should be made to this terminal. It is reserved for future use.
Receiving & Installation 3-9
X1 Motor Connections Motor connections are shown in Figure 3-11 and Figure 3-12.
It is important to connect the motor leads U, V and W correctly at the X1 connector of the control. Incorrect wiring can cause erratic operation including moves at peak force until the overcurrent limit trips. This will result in a display of “7” and a “6” on the monitor. If erratic movement of the motor occurs, turn off power immediately and check the connections of the motor, resolver or hall sensors and encoder.
Figure 3-11 Motor Connections for UL
Notes:
Baldor
Control
UVW
Note 1
1. Metal conduit or shielded cable should be used. Connect conduits so the use of Load Reactor* or RC Device* does not interrupt EMI/RFI shielding.
2. Use same gauge wire for Earth ground as is used for L and N. (VDE (Germany) requires 10mm
3. Reference EMC wiring in Section 8.
4. Motor and resolver are phase sensitive. Connect only as instructed.
2
minimum, 6AWG).
Note 1
* AC Servo Motor
* AC Servo Motor
Note: For CE compliant installations, connect unused leads within the motor cable
VW
U
G
Note 2
* Optional components not provided with control.
Figure 3-12 Motor Connections for CE
Notes:
Baldor
Control
UVW
VW
U
Note 2
G
to “PE” on both ends of the cable.
1. Metal conduit or shielded cable should be used. Connect
2. Use same gauge wire for Earth ground as is used for L and N.
3. Reference EMC wiring in Section 8.
4. Motor and encoder are phase sensitive. Connect only as
For three phase controls, this is labeled “PE”.
conduits so the use of Load Reactor* or RC Device* does not interrupt EMI/RFI shielding.
(VDE (Germany) requires 10mm compliance, connect motor ground to the backplane of the enclosure.
instructed.
Enclosure Backplane (see Section 8)
2
minimum, 6AWG). For CE
* Optional components not provided with control.
M-Contactor If required by local codes or for safety reasons, an M-Contactor (motor circuit
contactor) may be installed. However, incorrect installation or failure of the M-contactor or wiring may damage the control. If an M-Contactor is installed, the control must be disabled for at least 20msec before the M-Contactor is opened or the control may be damaged. M-Contactor connections are shown in Figure 3-13.
3-10 Receiving & Installation
MN1276
Figure 3-13 Optional M-Contactor Connections
UVW
To Power Source
(Rated Coil Voltage)
Note 1 Note 2
For three phase controls, this is labeled “PE”.
M Enable
* Optional components not provided with control.
*
X3
9
*
MMM
VW
U
G
* Motor
M=Contacts of optional M-Contactor
Notes:
1. Use same gauge wire for Earth ground as is used for L and N. (VDE (Germany) requires 10mm
2. For UL installations, connect motor ground to of the control as shown. For CE installations, connect motor ground to the enclosure backplane (see Figure 3-12).
* M-Contactor
Note: Close “Enable” after “M” contact closure.
* RC Device
Electrocube
RG1781-3
2
minimum, 6AWG).
Motor Thermostat A relay contact can be used to isolate the motor thermostat leads for use
with other devices, shown in Figure 3-14. The thermostat or overload relay should be a dry contact type with no power available from the contact. The optional relay (CR1) shown provides the isolation required and the N.O. contact is open when power is applied to the relay and the motor is cold. If the motor thermostat is tripped, CR1 is de-energized and the N.O. contact closes.
Connect the External Trip Input wires (N.O. relay contact) to a PLC or other device. Note that a machine input may be used and the PLC software of the Flex+Drive can define the thermal protection. Do not place these wires in the same conduit as the motor power leads.
Figure 3-14 Motor Temperature Relay
Customer Provided
Source Voltage
Note: Add appropriately rated protective
device for AC relay (snubber) or DC relay (diode).
W
V
U
Note:
1. For UL installations, connect motor ground to of the control as shown. For CE installations, connect motor ground to the enclosure backplane (see Figure 3-12).
* Motor
Note 1
G
Motor Thermostat Leads
X1 Dynamic Brake Resistor An external DB (dynamic brake or regen resistor) resistor may be
required to dissipate excess power from the DC bus during motor deceleration operations. Some controls have an internal resistor. For selection of the DB resistor, refer to the specifications located in Section 7 and the regeneration resistor specifications in Section 9 of this manual. DB hardware is connected at R1 and R2 terminals of the X1 connector, Figure 3-9 and 3-10.
MN1276
*
CR1
Do not run these wires in same conduit as motor leads or AC power wiring.
Optional, customer supplied.
*
External Trip
Receiving & Installation 3-11
X1 +24VDC Logic Supply For FPxAxxxx-xxx3 only. A separate 24VDC supply to the “Logic
X
A
Power” input is required for operation. An external 24 VDC power source must be used. If bus power is lost, the logic circuits are still active if the 24VDC is present. This is important to maintain position reference, for example. If the control was not ordered with this option, do not connect any voltage to these pins.
X3 Control Inputs & Digital I/O Connections Control Inputs X3 pins 1 and 2 allows connection of an external analog command input. This
input can accept a 0-10VDC or "10VDC signal and can be wired as a single ended or differential input, shown in Figure 3-15.
Figure 3-15 Control Input Wiring
Single Ended Connection Differential Connection
X3
X3
CMD+
Signal
Source
1
CMD-
2
AGND
3
Signal
Source
X3 Digital Inputs - Opto Isolated Inputs (uses CREF, X3-7)
Active High (Sourcing) - If pin X3-7 is grounded, an input is active when it is
at +24VDC (+12VDC to +30VDC).
Active Low (Sinking) - If pin X3-7 is at +24VDC (+12VDC to +30VDC), an
input is active when it is grounded.
Logic input connections are made at terminal strip X3. Input connections can be wired as active High or active Low as shown in Figure 3-16. X3 pin 7 is the Control Reference point (CREF) for the Opto Isolated Input signals.
Note: An internal 24VDC power supply connection is not available from the control
to power the Opto Input circuits. A customer provided external power source must be used as indicated in Figure 3-16.
Figure 3-16 Active HIGH /LOW Relationship
Active Low (Sink)
+24VDC GND
+24VDC
B
GND
A
Source
Active High (Source)
GND +24VDC
20mA 20mA
9-17
7
Typical
Control
Input
A B
B
A
Note:
GND
+24VDC
Sink
ll Opto inputs are referenced to
CREF, X3-7.
9-17
7
Typical
Control
Input
A
B
CMD+
1
CMD-
2
AGND
3
3
CREF
7
CGND
8
ENABLE
9
MAI3
10
MAI4
11
QUIT
12
FAULT RESET
13
HOME FLAG
14
TRIGGER
15 16
MAI1 MAI2
17
3-12 Receiving & Installation
MN1276
X3 Digital Inputs Continued
Table 3-3 Opto Input Signal Conditions
Pin
Number
X3-9 Enable Drive enabled. Drive disabled. X3-10 MaI3 Machine Input 3 = Logical 1 Machine Input 3 = Logical 0 X3-11 MaI4 Machine Input 4 = Logical 1 Machine Input 4 = Logical 0 X3-12 Quit Stop positioning mode operation Positioning mode is operating X3-13 Fault Reset Fault Reset is active (reset control). Fault Reset is not active. X3-14 Home Flag Home flag = closing (rising) edge Home flag = opening (falling) edge X3-15 Trigger Trigger = closing (rising) edge Trigger = opening (trailing) edge X3-16 MaI1 Machine Input 1 = Logical 1 Machine Input 1 = Logical 0 X3-17 MaI2 Machine Input 2 = Logical 1 Machine Input 2 = Logical 0
Signal
Name
Switch = Closed (active) Switch = Open (not active)
Signal Name Opto Input Signal Definition
Enable CLOSED allows normal operation.
OPEN disables the control and motor coasts to a stop.
Quit CLOSED cancels any move in progress and the motor will decelerate (at
parameter MOT.ACC) to rest. This input is edge triggered. OPEN allows position mode operation.
Fault Reset CLOSED allows the control to be cleared or “Reset” for any of the following four
fault conditions (provided that the cause of the fault has been removed):
$ Overvoltage $ Electronic Fusing $ Undervoltage $ Resolver Fault
OPEN allows normal operation.
Home Flag Edge triggered input that is used to sense the “Home Position”. Trigger Rising edge triggered input that initiates a “point-to-point move”. The move is
defined by the machine inputs MaI1-4.
MaI1,2,3,& 4 Four machine inputs are provided. These may be used with the internal PLC
software program. The internal PLC software can cause an event to occur based on the presence of these inputs.
However, more often these inputs are used to define up to 15 preset positions or point to point moves. The 16th move is always home. With this method, it is not possible to use hardware limits (CW and CCW). Therefore, software limits must be used. Software limits are only active after a homing routine has completed.
Note: Hardware limit switches may be wired in series with the “Enable” input
X3--9. Then if a limit is reached, the control will be disabled.
MN1276
Receiving & Installation 3-13
X3 Digital Inputs Continued
Figure 3-17 Positioning Mode Timing Diagram
MaI1-4
SeeTable3-4.
Trajectory
Motion Ready =
Motion in Process
Table 3-4 Process Duration for Resolver and Encoder Feedback
Trigger
T3
T2
T1
T4
T5 T6
Time Resolver Encoder
T1 %1ms &2ms T2 T3 &28ms &14ms T4 &28ms &14ms T5 %10ms %14ms T6 %10ms %14ms T7 %10ms %14ms T8 &28ms &100ms T9
T10
&1.2ms
&1.2ms &1.2ms
&1ms
&2ms &2ms
Time
Time
T7
Time
Time
Figure 3-18 Homing Process Timing Diagram
Trigger
Home Flag
SeeTable3-4.
3-14 Receiving & Installation
T2
T8 T9
T4
T10
Time
Time
Recognition Time (T10)
MN1276
Factory Installed Settings Absolute moves
A
Buffe
r
Positi
Speed
Acceleratio
n
15 predefined absolute moves have been programmed at the factory. These moves are defined in Table 3-5.
Table 3-5 Machine Inputs and Position Move Definitions
Buffer
(Move Number)
0(Home) OFF OFF OFF OFF 0 100 40
1 OFF OFF ON OFF 100000 2000 300 2 OFF OFF OFF ON 200000 2000 300 3 OFF OFF ON ON 300000 2000 300 4 OFF ON OFF OFF 400000 2000 300 5 OFF ON ON OFF 500000 2000 300 6 OFF ON OFF ON 600000 2000 300 7 OFF ON ON ON 700000 2000 300 8 ON OFF OFF OFF 800000 2000 300 9 ON OFF ON OFF 900000 2000 300
10 ON OFF OFF ON 1000000 2000 300
11 ON OFF ON ON 1100000 2000 300 12 ON ON OFF OFF 1200000 2000 300 13 ON ON ON OFF 1300000 2000 300 14 ON ON OFF ON 1400000 2000 300 15 ON ON ON ON 1500000 2000 300
MAI4 MAI3 MAI1 MAI2
Note: The machine Inputs of Table 3-5 are “OFF” when the switch is open.
Machine Inputs
on
Speed
(RPM)
Therefore, when MAI1 -- 4 are open, move number 0 (Home) is selected.
Move to Buffer 1 Position (Absolute move to position 100000).
Note:Tostopa movebeforeithascompleted,disablethedrive (Enableinput= Open)
orResetthe drive (Reset input = closed then open) or Quit (Quit input=closed then open).
1. Open MAI1 -- 4 inputs (position 0 select).
2. Enable the drive.
3. Close MAI1 input.
4. Close the Trigger input. Motor immediately moves to position 100000.
5. Open the Trigger input.
cceleration
(RPM / ms)
This completes an absolute move to buffer 1 position. Use switches MAI1 -- 4 to select other move numbers and use the Trigger switch to begin each move.
Note: If the motor is already at buffer 1 position, commanding another absolute
move to the same position will not cause the motor shaft to rotate. Therefore, command a move to a different absolute position before commanding another move to buffer 1 position.
MN1276
Receiving & Installation 3-15
X3 Digital Outputs - Opto Isolated Outputs
The control outputs are located on the X3 connector. A customer provided, external power supply must be used if digital outputs are to be used. The opto outputs provide status information and are not required for operation, Table 3-6.
Figure 3-19 Fault Relay Connections
Relay
Contact is closed when power is on and no faults are present.
Control
4
5
Customer Provided Interface Circuit
Customer provided external power source: and Non-Inductive Load
110VAC @ 0.3A maximum or 24VDC @ 0.8A maximum
Figure 3-20 Opto Output Connections
+
Typical
35mA
Maximum
CIV
18, 19, 20
CGND
Control
6
8
Customer Provided Interface Circuit
(+12VDC to +30VDC)
Output Signal
OR
Relay
Table 3-6 Opto Output Signal Conditions
Pin
Number
X3-4 Fault + Drive OK - no faults detected Fault is detected
X3-5 Fault - Drive OK - no faults detected Fault is detected X3-18 MAO1 Machine Output 1 = Logical 1 Machine Output 1 = Logical 0 X3-19 MAO2 Machine Output 2 = Logical 1 Machine Output 2 = Logical 0 X3-20 DrOK Drive OK - no faults detected Fault is detected
Signal
Name
Switch = Closed (active) Switch = Open (not active)
Fault Relay A normally closed relay contact that opens if a fault occurs. The contact is rated:
24VDC @ 0.8A maximum or 110VAC @ 0.3A maximum.
MaO1 & 2 Two machine outputs are provided. Either output can be set to one of the
following conditions: CW Warning, CCW Warning, In Position, Error Flag, Following Error Warning, MAI1-2, Drive Overtemperature or I Each output is rated 30VDC @ 35mA maximum.
DrOK This output is active when the control is ready for operation.
This output is rated 30VDC @ 35mA maximum.
3-16 Receiving & Installation
2
T Warning.
MN1276
X6 RS232 / 485 Connections
RS232
A null modem cable (also called a modem eliminator cable) must be used to connect the control and the computer COM port. This will ensure that the transmit and receive lines are properly connected. Either a 9 pin or a 25 pin connector can be used at the computer, Figure 3-21. Maximum recommended length for RS232 cable is 3 ft. (1 meter).
Figure 3-21 9 & 25 Pin RS-232 Cable Connections for UL Installations
9 Pin Connector
RXD TXD
GND
Signal
25 Pin Connector
Signal
Computer
COM
Port
(DTE)
Control
(DCE)
X6
RXD
TXD
GND
Chassis
Pin 2RXD 3TXD 5GND
Pin 2RXD 3TXD 7GND
Null Modem Cable Connections
Figure 3-22 9 & 25 Pin RS-232 Cable Connections for CE Installations
Null Modem Cable Connections
X6
Control
(DCE)
Note: For CE installations, connect the overall shield at each end of the cable to PE. The voltage potential between the PE points at each end of the cable must be Zero Volts.
MN1276
RXD
TXD
GND
PE PE
RXD TXD
GND
Computer
COM
Port
(DTE)
Receiving & Installation 3-17
RS485
Standard RS485 connections are shown in Figure 3-24. Maximum cable length is 3280 ft (1000M).
Figure 3-23 9 Pin RS-485 Cable Connections For UL Installations
9 Pin Connector
Pin 1TX­2TX+ 3RX+ 4RX­5DGND
Signal
Control
(DCE)
X6
RX+ RX-­TX+
TX­DGND
Chassis
TX+ TX-­RX+
RX­DGND
Computer
COM
Port
(DTE)
Figure 3-24 9 Pin RS-485 Cable Connections For CE Installations
9 Pin Connector
Pin 1TX­2TX+ 3RX+ 4RX­5DGND
Signal
Note: For CE installations, connect the overall shield at each end of the cable to PE. The voltage potential between the PE points at each end of the cable must be Zero Volts.
RS485 Multi-Drop Connections What does termination or a termination resistor do?
Termination resistance is used to match the impedance of the load to the impedance of the transmission line (cable) being used. Unmatched impedance causes the transmitted signal to not be fully absorbed by the load. This causes a portion of the signal to be reflected back into the transmission line (noise). If the Source impedance, Transmission Line impedance, and Load impedance are all equal, these reflections (noise) are eliminated.
Termination does increase load current and sometimes changes the bias requirements and increases the complexity of the system.
What is a termination resistor?
A resistor is added in parallel with the receiver input to match the impedance of the cable being used. Typically, the resistor value that is used is 100 ohm or 120 ohm. Resistors with 90 ohms or less should never be used.
Where are these resistors placed?
Terminators or Termination resistors are placed in parallel with the receiver at both ends of a transmission line. This means that you should never have more than two terminators in the system (unless repeaters are being used).
How many resistors should my system have?
Terminators or Termination resistors are placed in parallel with the receiver at both ends of a transmission line. This means that you should never have more than two terminators in the system (unless repeaters are being used).
Control
(DCE)
X6
RX+ RX-­TX+
TX­DGND
Chassis
PE PE
TX+ TX-­RX+
RX­DGND
Computer
COM
Port
(DTE)
3-18 Receiving & Installation
MN1276
Figure 3-25 RS485 4 Wire Multi-Drop for UL Installations
Host
P
=TwistedPair
Computer
RX+ RX-­TX+ TX-
DGND
GND
*
T
R
*
T
R
P
P
Use twisted pair shielded cable with an overall shield.
* Terminating resistor TRis 120 W typical value.
Only the PC and last control are terminated.
Figure 3-26 RS485 4 Wire Multi-Drop for CE Installations
Host
Computer
P
=TwistedPair
RX+ RX-­TX+ TX-
DGND
GND
Use twisted pair shielded cable with an overall shield.
* Terminating resistor TRis 120 W typical value.
Only the PC and last control are terminated.
Note: For CE installations, connect the overall shield at each end of the cable to PE. The voltage potential between the PE points at each end of the cable must be Zero Volts.
*
T
R
*
T
R
P
P
PE
Shields
PE
PE
Shields
PE
X6
TX+ TX-­RX+ RX-
DGND
GND
X6
T
R
*
TX+ TX--
T
R
*
RX+ RX-
DGND
GND
X6
TX+ TX-­RX+ RX-
DGND
GND
X6
T
R
*
TX+ TX--
T
R
*
RX+ RX-
DGND
GND
See Section 4 of this manual for the description of switch “AS1-1 to AS1-4” for address settings for multi-drop applications.
MN1276
Receiving & Installation 3-19
Loading...
+ 80 hidden pages