Balboa Water Group Spa Therapy Sequencer 52200-98 User Manual

Installation Suggestions
P/N 52200-98
Suggestions For Installing The
Balboa Therapy Sequencer
Introduction
The Balboa Therapy Sequencer consists of a controller that opens and closes valves that supply water to four groups of jets. When these jets are strategically located in a spa, they provide a sequencing massage therapy that enhances the spa experience and provides added value to a spa. The top side control panel for the system allows the user to start or stop the sequence, choose from 9 sequencing programs, select 1 of 3 sequencing speeds, and pause at any point in the current program.
The valves in the system are intended to be hydraulically powered by a dedicated 2 hp or larger pump. This pump should not be used for other operational functions such as heating or filtering. The maximum number of .312 diameter orifice jets (full size jets) that should be connected to each 1” sequencing valve is five. If .250 diameter orifice jets are being used, (euro jets) up to eight jets per sequencing valve may be connected. See Figure 1 for a basic overview of the Balboa Therapy Sequencer control system.
The Balboa Therapy Sequencer is designed to receive electrical power from a Balboa Spa Controller that is configured to energize a dedicated output for the Therapy Sequencer when the appropriate pump(s) have been energized.
Suggestion 1. Select the proper jets.
Use a jet that has an individual air connection that accepts 3/8” I.D. tubing. The air inlet for the jet should use check valves to prevent water from backing into the air plumbing. Some jet manufacturers provide jets that are available with this feature built into the jet and some provide individual inline check valves that are installed at the air inlet port when the air tubing is installed. Regardless of which jet is selected, the check valve will prevent water from entering the air system and will enable the jet to aspirate immediately when water is supplied to the jet from the sequencing valves. Jets that do not aspirate quickly will not produce effective hydrotherapy as they are being sequenced on and off, especially during the shorter “on” times of the faster sequences. The “on” time will be used up waiting for the jet to aspirate.
In addition to using check valves in the air lines to the jets, be sure to route the air lines vertically from the jet to a manifold that is located above the maximum normal water line of the spa. Gravity will aid the removal of any water that may have accumulated in the air line as vacuum is created within the venturii of the jet. Also make sure that the plumbing in the air system does not starve the air requirement of the jets when they are all aspirating at the same time.
Balboa Water Group
2
2
Therapy Sequencer
Use a jet that has an individual water connection that accepts 3/4" tubing or flex PVC. The tubing may in some cases be preferred because it can be disassembled. The tubing or PVC is then routed as directly as possible to a 4 or 5 port manifold ,depending on the number of jets connected to each valve. (A 4 port manifold can be made into a 5 port by adapting one of the unused through ports to accept the plumbing from the jet.) The 2" inlet to the manifold is then reduced to accept the 1” sequencing valve. Important: Using a manifold with a 2" inlet provides a large I.D. within the manifold that helps to reduce friction loss and back pressure which in turn enhances flow and helps to produce the maximum amount of therapy at the jet. See Figures 1 and 2.
Suggestion 2. Select the proper pump.
The Balboa Therapy Sequencer is intended to operate with a 2 hp or larger pump. The pump selected should deliver a minimum of 140 to 150 gpm @ 15 to 18 psi. This will provide enough flow to aspirate all the jets in the system. (20 full size jets or 32 euro jets)
Suggestion 3. Layout the jet pattern and plan the plumbing
schematic in your spa to take advantage of all the selectable sequencing programs.
Design the jet layout so that each valve supplies no more than five full size jets or eight euro jets. Think about how you will plumb these jet groupings for the best mechanical as well as hydraulic efficiency. Plan the jet layout so that each valve supplies an equal number of jets. The plumbing scheme shown in Figure 1 works well. Start by building the valve/manifold assembly as shown in Figure 2. Be sure to orient the valves so that the flow arrows on the valves point toward the jets. Position the valve/manifold assembly and then systematically connect each jet to the outlet ports of the manifold. If you are using 8 euro jets per valve, use two 4-port manifolds plumbed together to provide additional ports for the additional jets. Important: If debris from the manufacturing process is in the plumbing of the system, blow it out with compressed air before installing the valves. This will avoid the possibility of clogging the valves during the water test
Next, assign numbers to each valve. If you have arranged the jet groupings in horizontal rows, (the best configuration) the top row should be supplied by valve number 1. Valves 2, 3, and 4 should follow below the top row in numerical order with valve number 4 supplying the bottom row. Adhere the number stickers supplied with the Therapy Sequencer to each valve and to the end of the power cable for each valve. This will aid you in connecting the valves electrically to the Therapy Sequencer in the proper order and assure that the jet zones are controlled to produce the best therapy patterns. To help you understand how the valves will be sequenced, consult the valve-sequencing chart shown in Figure
3. The chart shows 9 selectable sequencing programs, each program providing a different sequencing order.
Balboa Water Group
3
3
Therapy Sequencer
Loading...
+ 7 hidden pages