Balboa Water Group ML700 User Manual

Page 1
EL/GL Series - Mach 3
ML700 User Guide
F1
TL
F2
Mode/Prog
F1
F2
TL
WarmTime
Cool
WarmTime
Mode/Prog Jets 2
Cool
Light
Jets 1
Blower
Jets 2
Light
Jets 1
Note regarding EL and GL systems: Mach 3 EL and GL systems function identically, but conform to different International requirements. This user guide will refer to EL systems for the sake of simplicity, but the information given applies to both EL and GL products.
900854
YXcYfX$`ejkild\ekj%Zfd
Page 2
Page 3
EL/GL SERIES (Mach 3) CONTROL WITH ML700 PANEL
The ML700 panel can be used with the EL8000, EL5000, EL2000 and EL1000 systems. This user guide lists all features that are available. Your spa may not respond as described in this document as specific operation varies by system and equipment used. If your spa is not fully equipped, the panel buttons on your spa control may not be laid out as shown. Functions not accessible by this panel may be accessible by a larger panel such as the ML900. Example: The ML700 panel can be used with all EL8000 systems equipped with three pumps, but pump 3 cannot be controlled with this panel unless the system does not have a blower and an additional Jets button is added to the panel in its place. In other cases, pump 3 can be controlled with an optional auxiliary panel.
Table of Contents
EL/GL SERIES (Mach 3) CONTROL ..... 1
Initial Start-up ..................... 1
Icon Legend ...................... 1
Time ............................ 2
Setting the Time ................... 2
Temp Set ........................ 2
Warm/Cool ....................... 2
Mode/Prog . ....................... 2
Standby Mode ..................... 2
Jets 1 ........................... 2
Jets 2 ........................... 3
Blower .......................... 3
Invert ........................... 3
Preset Filter Cycles ................. 3
Optional Filter Cycle Programming ..... 3
Light ............................ 4
The pump responsible for heating and filtration (pump 1 low on non-circ systems, or the circ pump on circ systems) will be referred to simply as the pump.
Timeouts refer to a preset length of time that a function is programmed to operate before shutting off automatically. Certain conditions (filters or freeze) can cause a function to operate longer, while faults can cause a function to operate for a shorter length of time. The system keeps track of timeouts regardless of other conditions occurring.
In multi-button sequences, if buttons are pressed too quickly in sequence, they may not register.
Freeze Protection .................. 4
Locking the Panel .................. 4
Locking the Set Temperature .......... 4
Clean-up Cycle .................... 4
Circ Pump ........................ 4
Ozone ........................... 4
Displaying Information About Your Spa . . 5
User Preferences ................... 5
Editing User Preferences ............. 5
Diagnostic Messages .............. 6-7
Periodic Reminder Messages .......... 8
GFCI Protection .................... 8
GFCI Trip Test Procedure ............ 8
Optional Auxiliary Panels ............ 9
Basic Installation Guidelines ......... 10
CSA Compliance . . . . . . . . . . . . . . . . . . 10
Initial Start-up
When your spa is first actuated, it will go into Priming mode (after displaying some configuration information).
Please see the M-7 Installation Instruction Manual for complete instructions on Power-up and Pump Priming.
Icon Legend
Heat Icon - Indicates different stages of heating.
Jets Icon - Spins fast on high speed; spins slow on low speed.
Blower Icon - Biggest in highest speed; smallest in lowest speed.
The Priming mode will last for up to 4 minutes and then the spa will begin to heat and maintain the water temperature in the Standard mode. You can exit Priming mode early by pressing “Warm” or “Cool.”
Fiber-Optic Light Icon - Spins when the wheel is on; stands still when wheel is off.
Light Icon - On dim, the LCD will show the center circle plus one quarter of the light beams. Half of the light beams will show on medium brightness, and all of the light beams will show on bright.
Page 1
Page 4
Time
When time hasn’t been programmed, the “ ” icon flashes. To set the time, press “Time” then “Mode/Prog.” Use the “Warm” and “Cool” buttons to adjust time. See previous page for more detailed instructions. (Time
settings on EL1000 and some EL2000 systems are not preserved in the event of power loss; time will have to be reprogrammed upon each power up.)
If your spa has an optional pH/ORP sensor (not available on EL1000 and some EL2000 systems), pressing “Time” twice will display the current pH level; pressing it three times will display the current ORP.
Setting the Time
Once the spa has been properly connected the first time (every power up on the EL1000 and some EL2000 systems), notice the “ appearing on the screen.
TimeTime
Press Then
Select
the hour by pressing
Press
Mode/ProgMode/Prog
Select
minutes by pressing
Press
Mode/ProgMode/Prog
TimeTime
Press
to enter.
to exit the time setting procedure and enter the optional filter cycle programming. (Exits programming on EL1000 and some EL2000 systems.)
to exit programming.
Mode/ProgMode/Prog
WarmWarm
WarmWarm
Or
Or
(Each press changes the time by 1 minute)
CoolCool
(Each press changes the time by 1 minute)
CoolCool
” icon
Temp Set (80°F - 104°F / 26.0°C - 40.0°C)
The last measured temperature is constantly displayed on the LCD. Your spa’s set temperature range may vary from range shown above depending on your manufacturer’s settings.
Note that the last measured spa temperature displayed is current only when the pump has been running for at least 1minute.
Warm/Cool
Press the “Warm” or “Cool” button once to display the set temperature. Each time either button is pressed again, the set temperature will increase or decrease depending on which button is pressed. After three seconds, the LCD will automatically display the last measured spa temperature.
Mode/Prog
This button is used to switch between Standard, Economy, and Sleep modes. Press “Mode/Prog” to enter mode programming, press “Cool” to cycle through to desired mode (LCD flashes until confirmed), then press “Mode/Prog” to confirm selection.
Standard mode maintains the desired temperature. Note that the last measured spa temperature displayed is current only when the pump has been running for at least 1 minute. The “ mode is changed.
Economy mode heats the spa to set temperature only during filter cycles. The “ until mode is changed.
” icon will display until the
” icon will display
Pressing “Jets 1” while in Economy mode puts the spa in Standard-In-Economy mode, which operates the same as Standard Mode, then reverts to Economy Mode automatically after 1 hour. Both the “ and “
” icons display in this mode. During this
time, a press of the “Mode/Prog” button will revert to Economy Mode immediately.
Sleep mode heats the spa to within 20°F (11°C) of the set temperature only during filter cycles. The “
” icon
will display until mode is changed.
Standby Mode
Pressing “Warm” or “Cool” then “Jets 2” will turn off all spa functions temporarily. This is helpful when changing a filter. Pressing any button resets the spa. On some systems the “Jets 1” button will control the pump in Standby Mode (“Drain Mode”). In this case, press any other button to exit. System will revert to previous mode after 1 hour.
Jets 1
Press the “Jets 1” button once to turn pump 1 on or off, and to shift between low and high speeds if equipped. If left running, the pump will turn off after a timeout period. The pump 1 low speed timeout on some systems may be as long as 4 hours.
On non-circ systems, the low speed of pump 1 runs when the blower or any other pump is on. It may also activate for at least 1 minute every 30 minutes to detect the spa temperature (polling) and then to heat to the set temperature if needed, depending upon mode. When the low speed turns on automatically, it cannot be deactivated from the panel; however, the high speed may be started.
Page 2
Page 5
Jets 2 (optional on some systems)
Press the “Jets 2” button once to turn pump 2 on or off, and to shift between low and high speeds if it is a two-speed pump. If left running, the pump will turn off after a timeout period.
Blower
1-speed operation: on/off; 2-speed operation: med/hi/off; or 3-speed operation: lo/med/hi/off. If left on, the blower will automatically turn off after a timeout period.
Note: If your system does not have a “Blower” button, and is labeled as ”Jets 3” instead, please see page 9 “Jets 3”.
vary from system to system. To program, press “Warm” or “Cool,” then “Jets 1.” Press “Warm” or “Cool” to select the filter duration. Press “Jets 1” to select the number of filter cycles. The display will show “ and “night” cycles); “ cycle only). Press “Warm” or “Cool” to adjust, then press “Jets 1” to exit the programming mode. For continuous filtration, use “
Note: EL1000 and some EL2000 systems are capable of being programmed by time rather than by duration (see Preset Filter Cycles section). On EL2000 and EL1000 systems with duration programming only, the spa powers up at 12:54, thus the first filter cycles begins 6 minutes later at 1:00. If you would like your spa to begin filtering at another time, you may change the clock to align with your preferred filter time, rather than the actual time of day.
” (day cycle only); or “ ” (“night”
” and “ ”.
” (both “day”
Invert
Press the “Warm” or “Cool” button, then “Blower” to change the numbers in the display to read upside down. Repeat sequence to return the display to its normal right-side-up display.
Note: If your system does not have a “Blower” button, use ”Jets 3” instead.
Preset Filter Cycles
On all systems, the pump and the ozone generator will run during filtration. At the start of each filter cycle, the blower will run briefly on its highest speed to purge the air channels. The lowest speed of any other pumps and the mister will also run briefly. On some circ systems, pump 1 may also run for the duration of the filter.
(The following is specific to all systems that are programmed according time)
There are two filter cycles per day. The start/end times of each cycle are programmable. To program, set time as instructed above, then press “Mode/Prog” to advance to the next setting (or to exit after the last setting). Default filter cycles can vary from system to system. A common default is 8:00 AM to 10:00 AM and 8:00 PM to 10:00 PM. Press “Time” then “Mode/Prog” to step through the filter settings to see how they are currently set.
Each filter cycle automatically operates the pump for the
F1
duration of the filter cycle. The filter 1 “ light when filter 1 is running. The filter 2 “ will light when filter 2 is running.
(The following is specific to EL2000 and EL1000 systems that are programmed according to duration rather than time)
The first filter cycle (“day”) begins 6 minutes after the spa is powered up. The second filter cycle (“night”) begins 12 hours later. Filter duration is programmable for
”-“ ”). The default filter duration can
1-12 hours (
” icon will
F2
” icon
Optional Filter Cycle Programming
You are not required to set filter cycles; however, it is an option available to you. To change the filter cycle settings:
Press “Time” “Mode/Prog” “Mode/Prog” “Mode/Prog” within 3 seconds. You will see the “PROGRAM,” “FILTER 1” and “START TIME” icons appear on the display.
Press “Warm” or “Cool” to choose the filter start time hour. Enter the hour by pressing “Mode/Prog”. Press “Warm” or “Cool” to choose the filter start time minutes. Each press changes the start time by 5minutes.
Enter the minutes by pressing “Mode/Prog.”
Press “Mode/Prog” to see the “PROGRAM,” “FILTER 1” and “END TIME” icons. Adjust the time as done above.
Press “Mode/Prog” to see the “PROGRAM,” “FILTER 2” and “START TIME” icons. Proceed as above.
Press “Mode/Prog” to see “PROGRAM,” “FILTER 2” and “END TIME” icons. Adjust the time as done above.
Pressing “Mode/Prog” will enter the new filter cycle times into the system and display the current water temperature.
Pressing “Time” at any time during this programming sequence will save the values entered up to that point and exit programming.
If you would like to select continuous filtration, set the filter 1 start and end times to be the exact same time. In this case, the filter 2 start time only controls when the second purge happens. Filter 2 end time will be unavailable.
Page 3
Page 6
Light
Some systems are equipped with both a spa light and a fiber optic light; however, only one can be accessed by this panel. (Larger panels may be purchased so that both the spa light and fiber optic light can be utilized.) Depending upon how your spa is equipped and configured, the “Light” button will operate in one of three ways:
1) Press the “Light” button to turn the spa light on and off, and to shift between dim and bright settings if your light is dimmable. On dim, the LCD will show center circle plus one quarter of the light beams. Half of the light beams will show on medium brightness, and all of the light beams will show on bright.
2) If a fiber-optic light with wheel is installed, press the “Light” button once to start the light and wheel, press it again to stop the wheel, and then again to turn the light off. The fiber icon stands still when the fiber optic light is on by itself, and rotates when the color wheel is also on.
3) If a fiber-optic light without a separate wheel stop is installed, press the “Light” button to turn it on and off.
Again, both a spa light and a fiber optic light may be used simultaneously on the EL8000 and EL5000 systems with a different panel.
If any light is left on, it will automatically turn off after a factory programmed time period.
Note: If your spa has additional functions not listed here, please refer to the section Optional Auxiliary Panels as listed in the Table of Contents.
Freeze Protection
Locking the Set Temperature
Press “Warm” or “Cool” then “Time,” “Jets 1,” and “Warm” within 3 seconds to activate the lock. The
TL
TL “ is locked.
On some systems, locking the set temperature also locks out Mode changes.
To unlock the set temperature, press “Warm” or “Cool” then “Time,” “Jets 1” and “Cool.”
” light will light when the set temperature
Clean-up Cycle (optional)
When a pump or blower is turned on by a button press, a clean-up cycle begins 30 minutes after the pump or blower is turned off or times out. The pump and the ozone generator will run for one to four hours, depending on the system (on some systems, you can change this setting; see User Preferences section.)
Circ Pump (optional)
If your system is equipped with a circ pump, it may be configured to work in one of three different ways:
1) The circ pump operates continuously (24 hours) with the exception of turning off for 30 minutes at a time when the water temperature reaches 3°F (1.5°C) above the set temperature (most likely to happen in very hot climates).
2) The circ pump stays on continuously, regardless of water temperature.
3) The circ pump will come on when the system is checking temperature (polling), during filter cycles, during freeze conditions, or when another pump is on.
If the temperature sensors within the heater detect a low enough temperature, then the pump(s) and the blower automatically activate to provide freeze protection. The pump(s) and blower will run either continuously or periodically depending on conditions.
In colder climates, an optional additional freeze sensor may be added to protect against freeze conditions that may not be sensed by the standard sensors. Auxiliary freeze sensor protection acts similarly except with the temperature thresholds determined by the switch. See
your dealer for details.
Locking the Panel
Press “Time” “Jets 1” then “Warm” within 3 seconds.
PL
When locked, the PL “ are frozen except the “Time” button. To unlock the
panel, press “Time” “Jets 1” then “Cool.”
Page 4
” light will light. All buttons
Ozone (optional)
On most systems, the ozone generator (if installed) runs during filter cycles (except when pump 1 is operating at high speed on a non-circ system) and during clean-up cycles. On some systems, the ozone generator operates whenever the pump runs.
If your system is configured with the optional ozone suppress feature, the ozone generator will turn off for 1 hour any time a function button (Jets 1, Jets 2, Blower, etc.) is pressed.
Page 7
Displaying Information About Your Spa
There are several pieces of information about your spa that can be called up from the panel, but are only needed in special cases.
To access this information, press “Warm” or “Cool” then “Jets 1”, then “Light”. (Each press must be within 3 seconds of the previous press.) Then press “Temp” until you see “ the SSID (a series of 3 numbers, such as 100 133 10, which indicates the precise revision of the software in your spa), followed by the Mach software version number (such as 2.1), followed by “ spa’s network ID number (consisting of both letters and digits displayed in 5 steps).
If you need to see this series of numbers again, and “ “Jets1”again.
When done, press the “Light” button (more than once if necessary) until you see the normal temperature display.
” is once again on the display, just press
” on the display. Press “Jets 1” to see
” and then your
User Preferences
There are several aspects of spa operation that you can customize using the User Preferences submenu.
Press “Warm” or “Cool” then “Jets 1”, then “Light”. (Each press must be within 3 seconds of the previous press.) At this point, if “ press “Temp” until you see “ press “Jets 1” to enter the User Preferences submenu.
Once in the User Preferences submenu, press “Warm” or “Cool” to cycle between these settings:
– Suppress Reminders When set to “ on the panel. When set to “ displayed on the panel periodically.
– Temperature in Celsius When set to “ the panel in degrees Celsius. When set to “ temperatures are displayed in Fahrenheit.
” is not showing on the display,
” on the display. Then
”, reminders are never displayed
”, reminders are
”, temperatures are displayed on
”,
– Dolphin II Address When set to “ setting for a Dolphin I, or for a Dolphin II which is set for no address (which is the Dolphin II factory default). When set to “ number is the address (see your Dolphin II manual for details).
”, no addressing is used. Use this
” through “ ”, the
Editing User Preferences
View the setting.
The left two characters (before the decimal point) tell you what setting you’re viewing or editing, the right most character (after the decimal point) tells you the value of that setting (for example, “
If the value is flashing, you’re editing it. If the value is not flashing, you’re just viewing it.
Press “Jets 1” to switch editing of the value on (flashing) or off (not flashing).
Once you’re editing the value (it’s flashing), use the “Warm” or “Cool” buttons to change the value to the one you want.
After you change the value, you must press “Jets 1” again to stop the flashing before the change will register, and before you can view or edit another setting.
If you don’t interact with the menu for more than 30 seconds, it may time out.
If you press “Light” to back out of the menu, or pause long enough for it to time out, while a value was flashing, the changes you were making to that setting are not remembered. But changes you previously made to other settings will be in effect.
Any User Preferences that you change will stay in effect “forever” or until you change them again (unless the spa’s “persistent memory” is reset by a service technician), and will override the factory defaults for those settings.
” for Yes or “ ” for No).
– 24-hour Time Display When set to “ (military) format (00:00 is midnight, 23:00 is one hour before midnight). When set to “ is displayed in 12-hour (am/pm) format (12:00 is midnight, 11:00 pm is one hour before midnight).
– Clean-up Cycle Duration (some systems only) When set to “ When set to “ indicates how many hours each Clean-up Cycle will run.
”, time is displayed in 24-hour
”, ti me
”, Clean-up Cycles are disabled. ” through “ ”, the number
Page 5
Page 8
Diagnostic Messages
Message Meaning
No message on display. Power has been cut off to the spa.
“Overheat” - The spa has shut down. On some systems, an alarm may sound. One of the sensors has detected 118°F (approximately
47.8°C) at the heater.
“Overheat” - The spa has shut down. One of the sensors has detected that the spa water is 110°F (approximately 43.3°C).
“Ice” - Potential freeze condition detected.
Spa is shut down. The sensor that is plugged into the Sensor “A” jack is not working.
Action Required
The control panel will be disabled until power returns. Time of day will be preserved for 30 days with a battery back-up on EL8000 and EL5000 systems. EL1000 and some EL2000 systems reset the time of day on each power-up. Spa settings are preserved on all systems.
DO NOT ENTER THE WATER. Remove the spa cover and allow water to cool. Once the heater has cooled, reset by pushing any button. If spa does not reset, shut off the power to the spa and call your dealer or service organization.
DO NOT ENTER THE WATER. Remove the spa cover and allow water to cool. At 107°F (approximately 41.7°C), the spa should automatically reset. If spa does not reset, shut off the power to the spa and call your dealer or service organization.
No action required. The pumps and the blower will automatically activate regardless of spa status.
If the problem persists, contact your dealer or service organization. (May appear temporarily in an overheat situation and disappear when the heater cools.)
Spa is shut down. The sensor that is plugged into the Sensor “B” jack is not working.
Sensors are out of balance. If this is alternating with the temperature, it may just be a temporary condition. If the display shows only this message (periodically blinking), the spa is shut down.
1
A substantial difference between the temperature sensors was detected. This could indicate a flow problem.
Persistent low flow problems. (Displays on the fifth occurrence of the “
” message within 24 hours.) Heater is shut down, but other spa functions continue to run normally.
Inadequate water detected in heater.
Inadequate water detected in heater. (Displays on third occurrence of “ shut down.
1
” message.) Spa is
If the problem persists, contact your dealer or service organization. (May appear temporarily in an overheat situation and disappear when the heater cools.)
If the problem persists, contact your dealer or service organization.
Check water level in spa. Refill if necessary. If the water level is okay, make sure the pumps have been primed. Press any button to reset.
Follow action required for “
” message. Heating capacity of the spa will not reset automatically; you may press any button to reset.
Check water level in spa. Refill if necessary. If the water level is okay, make sure the pumps have been primed. Press any button to reset.
Follow action required for “
” message. Spa will not
automatically reset; you may press any button to reset.
When your spa is first actuated, it will go into Priming mode.
See the M-7 Installation Instruction Manual for complete instructions on Power-up and Pump Priming. The Priming mode will last for up to 4 minutes and then the spa will begin to heat and maintain the water temperature in the Standard mode.
1
On some systems even when spa is shut down, some equipment may occasionally turn on to continue monitoring temperature or if
freeze protection is needed.
Page 6
Page 9
Diagnostic Messages (continued)
Message Meaning
or
Temperature unknown.
Temperature not current in Economy or Sleep mode.
Standby Mode has been activated by pressing a button combination on the user panel.
pH is low.
pH is high.
Sanitizer is low.
Sanitizer is high.
The pump is on during Standby Mode to assist in draining the spa.
Action Required
After the pump has been running for 1 minute, the temperature will be displayed.
In Economy or Sleep mode, the pump may be off for hours outside a filter. If you wish to see the current spa temperature, either switch to Standard mode or turn Jets 1 on for at least 1 minute.
Press any button, except “Jets 1”, to leave Standby Mode and return to normal operation.
Add pH increaser according to manufacturer’s instructions.
Add pH reducer according to manufacturer’s instructions.
Add sanitizer according to manufacturer’s instructions.
Remove spa cover and allow sanitizer to dissipate.
Press “Jets 1” to turn off the pump when water has drained (or power off the spa.)
Hardware failure.
Hardware failure.
Firmware install problem.
Configuration error. Spa cannot start up.
Spa could not trip GFCI.
A pump appears to be stuck on, causing the water temperature to creep up, possibly to hazardous levels.
A pump appears to have been stuck on the last time spa was powered.
Contact your dealer or service organization.
Contact your dealer or service organization if message appears on more than one power up.
Contact your dealer or service organization if message appears on more than one power up.
Contact your dealer or service organization.
Contact your dealer or service organization. Continued operation may be unsafe.
POWER DOWN SPA IMMEDIATELY. DO NOT ENTER THE WATER. Contact your dealer or service organization.
POWER DOWN SPA IMMEDIATELY. DO NOT ENTER THE WATER. Contact your dealer or service organization.
Page 7
Page 10
Periodic Reminder Messages (Press the “Mode” button to reset a displayed reminder.*)
Message ** Frequency *** Action Required
Every 7 days Test and adjust pH chemical levels per manufacturer’s instructions.
Every 7 days Test and adjust sanitizer chemical levels per manufacturer’s instructions.
Every 30 days Remove, clean, and reinstall filter per manufacturer’s instructions.
Every 30 days Test & reset GFCI per manufacturer’s instructions.
Every 90 days Drain and refill spa per manufacturer’s instructions.
Every 180 days Clean and condition cover per manufacturer’s instructions.
Every 180 days Clean and condition wood per manufacturer’s instructions.
Every 365 days Install new filter.
As needed Install new Mineral cartridge.
* User can suppress all reminders in User Preferences.
** All of these Periodic Messages can be disabled individually by the spa manufacturer.
*** Any of these frequencies may be changed by the spa manufacturer.
Note: The GFCI section does not apply on EL systems used outside the United States.
This GFCI section does not apply to GL Systems.
GFCI Protection
Your spa may be equipped with a GFCI Protection feature. If your spa does have this feature enabled, the GFCI Trip Test must occur to allow proper spa function.
Within 1 to 7 days after startup, the spa will trip the GFCI to test it. (The number of days is factory programmed.) The GFCI must be reset once it has been tripped. After passing the GFCI Trip Test, subsequent GFCI trips will indicate a ground fault or other unsafe condition requiring the power to the spa to be shut off.
Warning: The Owner should test and reset the GFCI on a regular basis to verify its function.
GFCI Trip Test Procedure
The installer can cause the GFCI Trip Test to occur sooner by initiating it with the following button sequence.
Press “Warm”, then “Jets 1”, then “Light.” (Each press must be within 3 seconds of the previous press.) Press the “Warm” button repeatedly until “ Press “Jets 1” to select it. Press the “Warm” button until
” is displayed. Press “Jets 1” to initiate the GFCI
“ Trip Test.
The GFCI should trip within several seconds and the spa should shut down. If it does not, shut down the power and manually verify that a GFCI breaker is installed and that the circuit and spa are wired correctly. Verify the function of the GFCI with its own test button. Restore power to the spa and repeat the GFCI Trip Test.
Once the GFCI is tripped by the test, reset the GFCI and the spa will operate normally from that point. You can verify a successful test by navigating to the “ as described above, pressing “Jets 1” and then pressing the “Warm” button until you see “ signifies GFCI Status - Passed.
” is displayed.
” item
”. The code
Page 8
The system will exit this menu in 30 seconds if no buttons are pressed.
Page 11
Optional Auxiliary Panels
Note: Below is a partial list of optional auxiliary panels and their basic functions.
Please contact your local dealer for a complete list of options that will work with your spa.
BlowerJets 1Jets 1 Jets 2 LightLight
BlowerJets 1Jets 1 Jets 2
Jets 1 Jets 2Jets 1 Jets 2
Jets 3, Jets 4 (optional on some systems)
Press the “Jets 3” button once to turn pump 3 on or off, and to shift between low and high speeds if it is a two-speed pump. If left running, the pump will turn off after a timeout period. “Jets 4” operates the same way as “Jets 3”.
Jets 5, Jets 6 (optional on some systems)
Press the “Jets 5” button once to turn pump 5 on or off. If left running, the pump will turn off after a timeout period. “Jets 6” operates the same way as “Jets 5”.
Jets 1Jets 1
Jets 2Jets 2
BlowerBlower
Fiber (optional on some systems)
If a fiber-optic light with wheel is installed, press the “Fiber” button once to start the light and wheel, press it again to stop the wheel, and then again to turn the light off. The fiber icon stands still when the fiber-optic light is on by itself, and rotates when the color wheel is also on.
Both spa light and fiber-optic light can be used simultaneously on systems that have both. If either light is left on, it will automatically turn off after a timeout period (on some systems this timeout can be as long as 4hours.)
Mister (optional)
Press the “Mister” button to turn the Mister on and off. If left on, the mister will automatically turn off after 15 m inutes.
Option (optional)
Press the “Option” button to turn optional equipment (such as TV or Stereo) on and off (with no timeout).
TV Lift (optional)
Press the “TV Lift” button to raise and lower the TV Lift device. There is no timeout for this feature.
Use the “Light” button if your fiber-optic system is on/off only (no separate wheel stop).
Stir (optional on some systems)
Press the “Stir” button after adding new chemicals into the spa. This will turn all pumps on at high-speed for 5 minutes to thoroughly mix in the chemicals.
Page 9
Page 12
Warning! Qualified technician required for service and installation.
Basic Installation and Configuration Guidelines for Mach 3 EL-Series Spa Controllers.
Use minimum 6AWG copper conductors only. Torque field connections between 21 and 23 in lbs. Readily accessible disconnecting means to be provided at
time of installation. Permanently connected. Connect only to a circuit protected by a Class A Ground Fault
Circuit Interrupter (GFCI) mounted at least 5’ (1.52M) from the inside walls of the spa/hot tub and in line of sight from the equipment compartment.
CSA enclosure: Type 2
Typical field connections for main power.
FOR W-WIRES
WHITE AC (120 V)
J23 J19 J28 J43 J42 J48
Refer to Wiring Diagram inside the cover of the control enclosure.
Refer to Installation and Safety Instructions provided by the spa manufacturer.
GREEN
WHITE
BLACK
RED
FROM GFCI
FOR W-WIRES RED AC (240 V)
J53 J54 J55 J25 J26
Warning: People with infectious diseases should not use a
spa or hot tub.
Warning: To avoid injury, exercise care when entering or
exiting the spa or hot tub.
Warning: Do not use a spa or hot tub immediately following
strenuous exercise
Warning: Prolonged immersion in a spa or hot tub may be
injurious to your health
Caution: Maintain water chemistry in accordance with the
Manufacturers instructions.
Caution: The equipment and controls shall be located not
less than 1.5 meters horizontally from the spa or hot tub.
Warning! GFCI Protection.
The Owner should test and reset the GFCI on a regular basis to verify its function.
CSA Compliance/Conformité Caution:
• Test the ground fault circuit interrupter before each use of the spa.
• Read the instruction manual.
• Adequate drainage must be provided if the equipment is to be installed in a pit.
• For use only within an enclosure rated CSA Enclosure 3.
• Connect only to a circuit protected by a Class A ground fault circuit interrupter.
• To ensure continued protection against shock hazard, use only identical replacement parts when servicing.
• Install a suitably rated suction guard to match the maximum flow rate marked.
Warning:
• Water temperature in excess of 38°C may be injurious to your health.
• Disconnect the electrical power before servicing.
Attention:
• Toujours verifier l’efficacite du disjoncteur differentiel avant d’utiliser differentiel avant d’utiliser le bain.
• Lire la notice technique.
• Lorsque l’appareillage est installe dans une fosse, on doit assurer un drainage adequat.
• Employer uniquement a l’interieur d’une cloture CSA Enclosure 3.
• Connecter uniquement a un circuit protege par un disjoncteur differentiel de Class A.
• Afin d’assurer une protection permanente contre le danger de shock electrique, lors de l’entretien employer seulement des pieces de rechange identiques.
• Les prises d’aspiration doivent etre equipees de grilles convenant au debit maximal indique.
Avertissement:
• Des temperatures de l’eau superieures a 38°C peuvent presenter un danger pour la sante.
• Deconnecter du circuit d’alimentation electrique avante l’entretien.
Warning/Advertissement:
• Disconnect the electric power before servicing. Keep access door closed.
• Deconnecter du circuit d’alimentation electrique avant l’entretien. Garder la porte fermer.
Warning! Shock Hazard! No User Serviceable Parts.
Do not attempt service of this control system. Contact your dealer or service organization for assistance. Follow all owner’s manual power connection instructions. Installation must be performed by a licensed electrician and all grounding connections must be properly installed.
P/N 40520-99_C 04/26/2007
Loading...