M-Bus AMR Interface E350
User Manual
Page 1 from 6
E111306819090
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
General
Upgradable for future communication needs: flexible remote communication modules without breaking
approval seal. The new series of modules for domestic use puts promises into practice, paving the way not
only for multi-energy applications but also for new services in personal energy management.
This specification details the operation and the electrical requirements for connection of an AMR module
with M-Bus interface to the L+G E350 (ZxF series 100) meter.
Compatible meters
ZCF110/120 single phase meter
ZMF110/120 multiphase meter
ZFF110/120 multiphase meter
The owner of the AMR modules is responsible that all persons engaged on work
with the modules:
• Are competent and qualified in accordance with national regulations (see ISSA
"Guideline for Assessing the Competence of Electrically Skilled Persons").
• Have read and understood the relevant sections of the user manual.
• Strictly observe the safety regulations (according to the following section) and
the instructions in the individual chapters.
Functions
The AMR interface contains the following functions:
Bi-directional communications: an integrated M-Bus (2 wires, passive) interface provides a simple
means of connecting multi-energy meters. This makes multi-energy applications an affordable
proposition for domestic use. Transmission protocol: IEC 62056-21
Rate input for tariff switching via external control inputs
Pulse output (with pulse rate change)
Internal communication interface for the transfer billing data between the meter and AMR module
(every 10 seconds).
For details of the communications protocol, refer to the software interface specification (IEC
62056-21 and OBIS Codes).
Phase connections to one phase (230VAC)
Safety Notes
The owner of the modules is also responsible for:
• The protection of persons.
• The prevention of material damage.
• The training of personnel.
The following safety regulations must be observed at all times:
• Devices which have fallen down should not be installed, even if no damage is apparent, and should
be returned for testing to an authorised service centre (internal damage possible).
• Modules must never be cleaned with running water or high pressure devices. Water can cause
short-circuits or damage el. components.

Page 2 from 6
E111306819090
M-Bus AMR Interface E350
User Manual
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Strictly observe the safety regulations!
Remove the utility seals on the terminal cover and
the AMR module cover.
Remove the terminal cover (1).
Remove the AMR module (2).
Insert the AMR module carefully at the place
provided in the meter. Ensure the connector pins are
not bent when the module is pushed down.
Tighten and seal the 2 screws of the AMR module.
The connections are marked on the faceplate.
Installation Hints
The installation must be done in a way, that even in the case of cable break no dangerous voltages
are applied to touchable parts of the module. Generally, meters are delivered with the communication
modules installed. The fitting of a meter with a communication module is, therefore, an exception and
can be necessary e.g. when a module needs to be replaced.
Fit the AMR module in the meter as follows:

M-Bus AMR Interface E350
User Manual
Page 3 from 6
E111306819090
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Example for 2400 baud, 8N1: set the jumpers 1 and 4
Without jumper: 2 seconds
With jumper: 15 seconds (for readout via GPRS)
Rate Input
The module provides a single optically isolated rate input.
Maximum voltage: 230VAC (-20% / +15%) / 2mA
Function: no voltage on the rate input: T1 (register 1.8.1 active), default
with voltage on the rate input: T2 (register 1.8.2 active)
Pulse Output
The pulse output circuit appears as an open-collector from an opto-isolator.
Maximum voltage: 265VAC/DC
Maximum reading rate: 1ms
Communication Parameter
Some jumper blocks are used for setting the communication parameter.
Note: set the jumper before switch-on.
Jumper Block “Config A”
Jumper block “Config A” (left site) is used for setting the baud rate and the data format for the M-Bus
interface:
Default (without jumpers): 9600 baud, 7E1
Set the jumper for activation:
Jumper Block “Config B”
Jumper 1 is used for setting the timeout for acknowledge (according to specification for IEC 62056-21):

Page 4 from 6
E111306819090
M-Bus AMR Interface E350
User Manual
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
1/1: without jumpers: without pulse rate change (see meter setup)
minimum pulse length: 2ms
1/10: pulse rate 1/10; pulse length 20ms
1/20: pulse rate 1/10; pulse length 40ms
1/40: pulse rate 1/10; pulse length 80ms
Jumper 3 and/or 4 is used for setting the pulse rate for the pulse output:
LED Displays
Two LED’s display the current operating status of the module and give information about the data transfer.
Power: on: AMR module is supplied with power
flashed: communication via M-Bus interface
Error: on: communication error between AMR module and meter
off: no errors
Communication
The AMR port is conforming to IEC 62056-21 with fixed baud rate. For reading data the meter-ID
(device address) can be used (e.g. /?<meter-ID>!);
Explanations of massage contents (see IEC 62056-21):
Start character: / (forward oblique, code 2F
End character: ! (exclamation mark, code 21
Completion character: CR (carriage return, code 0D
Hex
Hex
)
)
) and LF (line feed, Code 0A
Hex
); enter key
Hex
Length of telegrams (data readout): 745 bytes max.
Example for communication path:
Sign-on sequence: /!? CR LF without meter-ID
or /?12345678! CR LF if the meter-ID := 12345678
Answer: /LGZz Ident CR LF z := baud rate identification
Sign-on acknowledgement: ACK 0z0 CR LF
Data readout (billing list): F.F(00)
C.1.0(12345678)
0.0(12345678 )
C.1.1(94858005)
1.8.0(0000750.3*kWh)
1.8.1(0000000.0*kWh)
1.8.2(0000750.3*kWh)
2.8.0(0000002.8*kWh)
32.7(233*V)
52.7(233*V)
72.7(233*V)
C.5.0(3A)
…
!

M-Bus AMR Interface E350
User Manual
Page 5 from 6
E111306819090
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Polycarbonate housing with terminals for using with Landis+Gyr E350
meters (L+G ZxF domestic meters)
IP52 (according to IEC 60529)
165mm x 90mm x 33mm (W x H x D)
230VAC (-20% / +15%) / 50Hz
connection spring for one phase: Live (L1) and Neutral (N) from meter
-45°C to +65°C (operational)
-45°C to +90°C (storage temperature)
2 LED’s: green: Power
red: Error
M-Bus (2 wires, passive) according to EN 13757-2 (physical layer)
2400, 4800 or 9600 baud; default: 9600 baud (fixed baud rate)
7E1, 8N1, 8E1; default: 7E1
IEC 62056-21 (conform to VDEW2+) with fixed baud rate (OBIS
Codes)
Max. voltage: 230VAC (-20% / +15%)
max. current: 2mA
Wipe, according to DIN 42864 (S0 output)
max. voltage: 265VAC/DC
max. current: 50mA
min. voltage: 5VDC
Technical data:
Dimensions

Page 6 from 6
E111306819090
M-Bus AMR Interface E350
User Manual
Baer Energie- & Messtechnik GmbH Siemensstr. 3 D-90766 Fürth Phone +49 911 970590 Fax +49 911 9705950
Phase (Live) 230VAC (-20% / +15%) / 50Hz
Description (according to VDEW)
Terminal assignment
Power connection via connection spring:
Terminal block:
Baer Energie- & Messtechnik GmbH
Siemensstr. 3
D-90766 Fürth
Germany
Phone: +49 (0)911 970590
Fax: +49 (0)911 9705950
Internet: www.baer-gmbh.com
Subject to change without notice! Version 1.13